Sei sulla pagina 1di 15

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/311934317

Chloride Contamination of the Water/Steam Cycle in Power Plants Part I:


Evidence from a Case Which Could Not Be Explained in Terms of Currently
Familiar Sources

Article · February 2012

CITATIONS READS

0 2,036

2 authors, including:

Emmanuel Kobina Quagraine


SaskPower
29 PUBLICATIONS   381 CITATIONS   

SEE PROFILE

Some of the authors of this publication are also working on these related projects:

Biological Activated Carbon process for removing Organics from high Quality Water View project

Remediation of Naphthenic Acid Contaminated Waters View project

All content following this page was uploaded by Emmanuel Kobina Quagraine on 05 May 2018.

The user has requested enhancement of the downloaded file.


PPCHEM Chloride Contamination of the Water/Steam Cycle in Power Plants – Part I

Chloride Contamination of the Water/Steam Cycle in Power Plants


Part I: Evidence from a Case Which Could Not Be Explained in
Terms of Currently Familiar Sources

Emmanuel K. Quagraine and Jonathan P. Ruffini

ABSTRACT
This is the first of a three-part publication series on the findings from investigations performed at the Shand Power
Station of SaskPower to determine a hitherto unfamiliar source(s) of chloride contamination to the water/steam circuit.
For this plant, which is usually on automatic grid control (AGC), unit ramping is common and there is some reason to
associate this with the initiation of the chloride ingress. The present paper presents a systematic approach to examin-
ing the various familiar sources currently known to plant operators, chemists and the like as potential culprits and pro-
vides the bases for eliminating these as responsible agents in this case. Based on routine plant operating data and
purposeful intermittent grab sample analyses as well as numerical analysis of chloride cycling in the boiler, these well-
known potential causative factors, which include condenser tube water leaks, make-up chloride, halo-organics from
the water treatment plant, and contaminated ammonia feed sources, could not be found to individually or cumulatively
account for the magnitude of chloride contamination observed in this plant. The extent of the chloride cycling required
too frequent blowdowns from the boiler, and a cost analysis of the implications from such frequent blowdowns is also
Author's Copy

presented as one of the incentives that drove the search for the root cause of such a level of contamination. There
were some indications that surplus condensate from the hotwell to the boiler make-up storage tanks was a significant
chloride origin, but this could not account for the level of contamination, and the source seems to be distinctly differ-
ent from the traditionally known condenser tube water leaks. Furthermore, there were some indications that ammonia
injection was associated with the chloride crises, although there was ample evidence to eliminate this as the source.
These associations formed the basis for further investigations, the findings of which will be reported as Part II and Part
III of this series.

INTRODUCTION
Chloride is a well-known corrosive inorganic ion, which 10 µg · kg–1 to 50 µg · kg–1 chloride to low-alloy steel
can potentially cause or contribute to equipment break- reactor pressure vessels resulted in acceleration of stress
down, e.g. boiler tube failures from acid chloride attacks corrosion cracking (SCC) crack growth rates in all investi-
and steam turbine failures from chloride stress corrosion gated materials by at least one order of magnitude [3].
of turbine blades [1–5]. It is specifically noted to contribute Even for steam turbine blade steels of sufficient alloy (e.g.
to the following [6]: high Cr) content, which demonstrate resistance to pH (or
CO2)-induced corrosion, a higher chloride content in the
(a) Corrosion fatigue, stress corrosion cracking (SCC), water resulted in higher corrosion rates [7]. Especially in
and pitting in low-pressure (LP) turbines; locations where water flow adjacent to the tubes is dis-
rupted and excessive deposits are bound to occur,
(b) Corrosion, hydrogen damage, and pitting in boilers;
chloride is a typical example of an acidic boiler contami-
and
nant that may concentrate up to dangerous levels to
(c) Synergistic effects on drum boiler waterwall corrosion cause hydrogen damage [5].
in the presence of oxygen and copper oxide.
There are various known sources of chloride ingress into
For instance, it has been reported that in oxygenated, the water/steam cycle, which include the following: make-
high-temperature water (T= 288 °C and a dissolved up water contamination [6,8], feedwater contamination
oxygen (DO) content of 8 mg · kg–1), the addition of from sources such as condenser tube leaks [6,9] and/or

© 2012 by Waesseri GmbH. All rights reserved.

98 PowerPlant Chemistry 2012, 14(2)


Chloride Contamination of the Water/Steam Cycle in Power Plants – Part I PPCHEM

leaks from condensate pump seal cooling water for the guidelines) based on higher sulphate contamination and
condensate pumps [10], leakages from condensate not chloride. Higher sulphate to chloride ratios in the
polishers [4,8], and via contaminated chemical injections water/steam cycle could sometimes also occur as a result
[9]. According to Bursik [11], heteroatom-containing of sulphate ingress from the make-up treatment system.
organics, of which trihalomethanes (THMs) are part, are Since January 2009, however, the basis for the blowdown
the most dangerous contaminants in make-up water for from the boiler drum at Shand Power Station has changed
utility and industrial plant cycles. About 90 % of THMs from sulphate based to chloride based, as the ratio of
have been noted to pass through water treatment plants chloride to sulphate was consistently higher in the boiler
of a nuclear plant [8], and this has partially been impli- drum. Figure 1 shows the relation between unit load/LP
cated in an "acid"-chloride boiler leak due the breakdown exhaust pressure with the boiler chloride concentration for
of the organochlorides that escaped the make-up water periods preceding when the chloride issues in the boiler
treatment plant [8]. THMs can also enter the water/steam drum seem to have become serious or begun and imme-
cycle through other routes. For example, the accidental diately thereafter. From the figure, it is tempting to point to
introduction of trichloroethane into the condensate of a the preceding unit ramping as a significant contributor to
once-through boiler plant through an oxygen supply line or initiator of the chloride ingress into the water/steam
which had previously been degreased with 1,1,1- cycle. Prior to this occurrence, the unit since the start-up
trichloroethane (and not blown dry afterwards) was conditions on November 9, 2008 had operated without the
reported [12]. The gradual decomposition of the contami- need for boiler blowdown due to water chemistry, and the
nant at different places along the feedwater and steam chloride (and sulphate) concentrations in the boiler drum
path was observed by the measurement of acid conduc- had remained essentially constant.
tivity, which was due mainly to chloride.
The impact of chloride ingress into the water/steam cycle
Condenser leaks are a major source of contaminants in can potentially be very damaging as alluded to in the intro-
the water/steam circuits and feeding of contaminated ductory section and could have a significant cost associa-
Author's Copy

condensate to vulnerable components (such as attemper- tion in terms of, for example, boiler tube and steam turbine
ator sprays, etc) can be detrimental [13]. For this reason, failures if not handled properly. Ignoring the impact of
condensate polishing units are recommended to avoid chloride (and for that matter cycle chemistry) in keeping a
such problems [10]. However, chloride leakages from con- unit in operation is therefore totally irresponsible and not
densate polishers are also known to occur [4]. an option; any unit operated under such conditions is
bound to spiral to complete destruction, with its conse-
This paper is the first of a three-part series reporting the quential billions of dollars in losses. Under conditions of
findings from investigations performed at the Shand moderate ingress of impurities, however, boiler blowdown
Power Station of SaskPower to identify the root cause of is one of the recommended options to keep a unit in oper-
chloride contamination of the water/steam cycle experi- ation whilst making sure the cycle chemistry (e.g. chloride
enced in the plant, which appeared quite illusive initially. levels in the boiler) is within acceptable limits that mini-
This current paper focuses on the systematic steps taken mize the risk of deposition and corrosion in the
by this plant to ascertain whether any of the commonly water/steam cycles and thus protect both the boiler and
known routes of chloride contamination were responsible turbine [6]. There are, however, also some drawbacks
for the contamination. The objective of the paper is to associated with boiler blowdowns, especially if they occur
convince its audience that there are some situations too frequently.
where the popularly known routes such as the traditional
condenser tube water leak, make-up contamination, Although the financial cost associated with efficiency
chemical contamination, etc (as tempting as they may be reduction (i.e. heat rate effect) from continuous blowdown
as potential sources) cannot be logically justified. This of the boiler (CBD), on its own and for a coal-fired power
gives room to search for alternative sources or routes as plant unit such as this one, is only moderate, there are
the actual root cause(s). other costs associated with CBD which are more signifi-
cant. For example, estimated fuel costs associated with
chloride-based CBD for the year 2010 and for January 1 to
April 10, 2011, when the chloride contamination was of
STATEMENT OF THE PROBLEM
significant proportions, were only $5,826 and $2,078
With high sulphate to chloride ratios (typically ranging respectively for this coal-fired unit (i.e. at a fuel cost of
between (6–7):1) in the re-circulating water at this station, $1.395 per GJ), which translates to about $14,993 and
condenser leaks typically result in the same sulphate to $5,348 respectively for an equivalent natural gas-fired unit
chloride ratio in the condensate and in the feedwater. (at a fuel cost of $3.590 per GJ). However, the frequent
Likewise, any weepy condenser water leak into the hotwell CBD gave rise to more significant costs in terms of
is expected to follow the same trend and hence the plant increased frequent maintenance requirements to replace
would typically blow down from the boiler drum (with EPRI the motor-operated blowdown valve, and the associated

PowerPlant Chemistry 2012, 14(2) 99


PPCHEM Chloride Contamination of the Water/Steam Cycle in Power Plants – Part I

(a)
350 140

300 120

LP Exhaust Pressure [kPa x 10]


250 100

Concentration [µg · kg –1 ]
Unit Load [MW]

200 80

MW generated, left axis

150 Boiler SO4, right axis 60


LP exhaust, right axis
Boiler Cl, right axis
100 40

50 20

0 0
13-Nov 14-Nov 15-Nov 16-Nov 17-Nov 18-Nov 19-Nov 20-Nov 21-Nov 22-Nov 23-Nov 24-Nov
Date in 2008

(b)
Author's Copy

350 120

300
100

LP Exhaust Pressure [kPa x 10]


250

Concentration [µg · kg –1 ]
80
Unit Load [MW]

200

60
MW generated, left axis
150
Boiler SO4, right axis
LP exhaust, right axis 40
100 Boiler Cl, right axis

20
50

0 0
15-Jan 16-Jan 17-Jan 18-Jan 19-Jan 20-Jan 21-Jan 22-Jan 23-Jan 24-Jan
Date in 2009

Figure 1:
Unit load and low pressure (LP) exhaust pressure versus chloride and sulphate concentrations in the boiler drum
for periods preceding the chloride contamination (i.e. in November 2008) (top) and in the period when the issue
started (January 2009).

piping and headers. In addition, it created safety concerns replacement during the crises period (January 2009 to
due to the wear down of this equipment and the potential April 2011), costing a total amount of $45,390 to date; an
for unexpected and sudden steam leakages. To illustrate, additional cost of about $29,362 is also anticipated during
although the CBD motor-operated valve and the header the major overhaul in 2012 to replace the header and
and connecting piping were replaced in 2005/2006, the some sections of the connecting piping again. As this
frequent chloride-based CBD led to their premature maintenance work requires unit outages to complete,

100 PowerPlant Chemistry 2012, 14(2)


Chloride Contamination of the Water/Steam Cycle in Power Plants – Part I PPCHEM

there are huge cost implications from the viewpoint of loss Responses from consulting with colleagues through the
of generation. Based on a total duration of approximately FOMIS platform indicated that the most common root
45 to 54 days recorded (and/or estimated) from the plant cause of chloride contamination in boiler drums is due to
SAP maintenance records to complete these jobs, as condenser tube leaks, even if only small leaks occur [9].
much as approximately $18,400,000 to $22,100,000 in Contaminated ammonia injected into feedwater for pH
lost generation is possible due to these repairs (using a control was also noted but as a less common possibility. It
fuel compensated electricity cost of $55.90 per MWh). was further noted that this latter potential source could be
eliminated by verifying that the supplier had made no
As most of the repairs (in this case) were done during process changes and by testing samples. Some specific
scheduled maintenance outages, when other required experience shared included water/steam cycle chloride
maintenance work was also completed, the estimated contamination from a leak at the base of a condensate
loss of generation cost above would, arguably, not have to pump that was introducing stagnant water. In a different
be exclusively attributed to the frequent CBD-related FOMIS report [14], high chlorides (occasionally up to
repairs. A counterargument would be that the associated 150 µg · kg–1) in the boiler drum with sodium levels only at
cost in lost generation could even be more than the esti- 1.2 µg · kg–1 had been experienced and it was considered
mates above if these had to be done unplanned as a result that this was likely to be associated with high chloride
of forced outages, in which case other factors such as concentrations in the caustic regenerant used for the con-
parts delivery etc could play a significant role by extending densate polisher, which was being fouled with iron and
the duration of the outages. In any case, the above cost was suspected to be the source of the contaminant. A
analysis illustrates that there are huge financial implica- membrane grade caustic was indicated to have a typical
tions, directly or indirectly, from using boiler blowdown as chloride level of 100 mg · kg–1, whilst a diaphragm grade
a corrective action to address such water chemistry caustic can have levels as high as 10 000 mg · kg–1 (i.e.
excursions, especially under conditions where the ingress 1 %) [14]. (The cause of the iron fouling of the resin had
of contaminants leads to too frequent blowdowns. also been determined by others to be due to high dis-
Author's Copy

Furthermore, it has to be realized that CBD is only a reac- solved iron in the caustic regenerant.) EPRI's cycle chem-
tive measure and does not address the root cause of the istry guidelines document gives condenser leakage and
chloride contamination. It was also not going to be sus- condensate polishers (but not ammonia feed systems) as
tainable, especially as the chloride contamination contin- possible causes of chloride excursions and includes
ued to increase, and would subsequently have resulted in make-up demineralizers as another source [6].
an increasing frequency of blowdowns with time. With the
condenser earmarked to be replaced soon, it was tempt- The following is a discussion of the step-by-step
ing to falsely rely on that as a hopeful solution. However, approach used to evaluate the various potential sources
replacing the condenser without knowing the mechanism of water/steam cycle chloride contamination presented
or means by which chloride is selectively entering the above and the reasons why we believe they were not the
water/steam cycle (even if associated with the condenser) main culprits responsible for the contamination experi-
may not be the right corrective action, as it does not enced by this plant that led to increasingly frequent blow-
address the root cause if this is unknown and has not downs from the boiler to keep it in operation.
been dealt with (properly) during the tube replacement
process. It was therefore crucial to identify the source of
this contamination and apply the necessary and more
effective corrective action. MATERIALS AND METHODS
Plant Design and Operating Conditions
Different sources of potential chloride contamination were
considered as suspects and were investigated: the aqua- Shand Power Station of SaskPower, a 305 MW coal (lig-
nite)-fired single unit power plant, has followed zero liquid
ammonia injection system for pH control in the
discharge (ZLD) requirements since commission in 1992.
water/steam cycle, halo-organics from the boiler make-up
water, condenser water leakage and, lastly, direct chloride
contamination of the make-up storage tanks from the hot
Cooling Water System
condensate draining (HCD) system and/or the plant's
closed circuit cooling water (CCCW) for plant equipment Ever since the early stages of operation, the plant has
such as boiler feed pumps, soot-blowers, and pulverizers. drawn mainly on a blend of secondary treated sewage
The CCCW and HCD systems are tied to the make-up water (after passage through constructed wetlands) and
storage tanks and hence contamination was a real possi- surface water as make-up water for re-circulating water in
bility with valve failures in the former or inadvertent trans- the cooling tower (CT) although snow melts and rains
fer from the latter without prior knowledge of the water gathered in a yard drainage system contribute a small por-
quality. tion. The proportions of the blend vary significantly

PowerPlant Chemistry 2012, 14(2) 101


PPCHEM Chloride Contamination of the Water/Steam Cycle in Power Plants – Part I

throughout the year, but are close to 100 % surface water The Water/Steam Circuit
between November and April and variable fractions of sur-
A schematic of the condensate make-up system and the
face and secondary treated sewage during the months of
boiler water/steam system, which depicts a typical drum-
May to October. During this latter period, which is the lim-
type boiler, together with the condenser cooling re-circu-
ited operating period of the constructed wetland, an
lating water system at the Shand Power Station is shown
approximately equivalent total volume from each of the
in Figure 2. Some chemical treatment programs in these
two sources (~50 % each) is received at the station for
systems which are relevant to this discussion have also
mainly cooling. Two 50 % re-circulating water pumps sup-
been indicated as possible sources of chloride contamina-
ply water through a 2-pass, Cu-Ni (90:10 in the condens-
tion to the water/steam cycle. The designed condensate
ing zone and 70:30 in the air cooling zone) condenser at a
flow is 198 kg · s–1 and the normal boiler make-up is
designed total rate of 7 700 L · s–1 with a water velocity of
2.46 kg · s–1. The firing boiler water volume is 216 400 L.
2.4 m · s–1 through tubes and a ⌬T across the condenser
The chemical treatment program for the water/steam
of 12.3 °C for the maximum design heat rate of the plant.
cycle is all-volatile oxidizing (AVT(O)). Ammonia (28 %) is
The designed hot (inlet) water temperature to the cooling
added for pH control at a typical rate of 2 115 kg per year
tower (i.e. the outlet water temperature from the con-
or only 5.1 mL · min–1, but it is injected in diluted form (with
denser) is 42.3 °C. The average flow during the investiga-
demineralized water) into the water/steam cycle.
tion and used in the calculations in this paper was about
7 500 L · s–1.
Water/Steam Cycle Chemistry and Make-up Water
An induced draft counter flow cooling tower (open re-cir-
Quality Monitoring
culating system) is used for heat rejection. There are two
towers: a main tower of precast concrete construction Apart from typical on-line continuous monitoring of
with 7 cells, where water is sprayed and falls through parameters such as sodium, pH, conductivity (specific
ceramic fill, and an auxiliary tower of 2 cells made of a and/or cation), dissolved oxygen (DO), and silica at the
Author's Copy

fibre glass structure and polyvinyl chloride (PVC) fill. In applicable recommended sampling locations such as the
normal operation, all cells in the former are in service, boiler/steam drum, after the condensate extraction pump
whilst the two cells in the latter are used only when (CEP), and at the economizer inlet or the outlet of the last
required under high temperature and humidity conditions. high-pressure (HP) heater #6, daily grab samples and test-

Steam lost

Steam/condensate
return
Steam turbine

H2SO4 Circulating water


(cooling tower) Air
Cooling water Feedwater
ingress High pressure
Bleach Water heater #6
Condensate Steam
Condenser
extraction boiler
hotwell
pump
NH3
Make-up
Surplus

Hot NH3 NH3


condensate
drain tank Blowdown

Closed
Low level High level Ammonia
circuit
condensate condensate tank
cooling
tank tank
water

Water Demineralized
treatment storage
plant tank

Figure 2:
A schematic of the condensate make-up system and the boiler water/steam system together with the condenser cooling re-circulating
water system at the Shand Power Station.

102 PowerPlant Chemistry 2012, 14(2)


Chloride Contamination of the Water/Steam Cycle in Power Plants – Part I PPCHEM

ing are typically performed to ensure the integrity and reli- The injected diluted ammonia, apart from delivering
ability of this on-line instrumentation and for the appropri- directly to the pipeline after the condensate extraction
ate remedial actions. For this power plant, the most critical pumps, is also partly directed through the LL tanks and HL
parameter for early detection of condenser leaks is tanks for eventual discharge into the hotwell (Figure 2).
sodium at the CEP outlet, which other parameters are Elimination of ammonia contamination as a major contrib-
used to confirm. utor to the chloride-based boiler blowdown is discussed
in a separate section (see below) and the explanations
In keeping with EPRI's guidelines [6,15], apart from some given are applicable irrespective of the injection route.
start-up conditions when silica is an issue, most of the Slippages from the demineralizing bed are possible, but
requirements to blow down from the boiler/steam drum this is an easy source to eliminate or confirm as the quality
are based on sulphate or chloride. For these ions, the from the beds is monitored on a routine basis. The relative
facility has two Dionex-IC instruments: the IC-DX-2000 for amount of the various parameters would give a clue as to
measuring these ions from grab sampling and the IC-DX- whether this is a major source of the chloride ingress.
800 as an on-line instrumentation. The latter is currently Furthermore, such slippages are quite intermittent and are
programmed to gather the spectrum at 30 min intervals not usually persistent enough to account for the constant
from three sampling lines in the sequence: boiler drum, chloride cycling in the boiler drum.
high level (HL) tank and demineralized tank. Thus, each of
these samples is recorded approximately every half an To eliminate the HCD tank as the source, this tank was
hour on a continuous basis. There is the capability to isolated from the LL tanks and the condensate water con-
include other sampling lines, but we typically focus on tent put to waste. During the period that the tank was iso-
these three. Although it should be possible to integrate lated, no obvious improvement was observed with the
these readings into our on-line data-logging system, this chloride cycling. The CCCW system is normally isolated
has not yet been done and hence the information is from the condensate tanks (LL and HL), but some previ-
accessed only from a localized computer attached to the ous experience had indicated the possibility of an isolation
Author's Copy

IC. The IC-DX-2000 measurements on grab samples are valve failure that could allow the CCCW water, which was
at the moment performed less frequently (i.e. about 1 to 2 of substantially poorer quality, to be back feeding into the
times per week) with the sole aim of checking the accu- LL tank. At least on one occasion (January 13, 2011), the
racy and the reliability of the on-line measurements. In CCCW was found to be of significantly higher chloride to
instances when the IC-DX-800 is non-functional, more sulphate concentration ratio (11.9:1). To eliminate this
regular measurements are taken, typically once a day. It is potential source (and in fact the HCD tank too at the same
also operated more frequently during start-ups and up-set time), the LL tanks were isolated from the HL tanks that
conditions. day (11:30 pm) so that the demineralized water was
directly delivered to the HL tank. The LL tank was kept
isolated for about 3 months, but no significant improve-
ment was seen with respect to the chloride cycling (see
RESULTS AND DISCUSSION
Figure 3). As shown in the figure, the boiler blowdowns
Make-up Sources before and during the LL tank isolation continued to be
based on chloride and were at a consistent frequency of
Chlorides from the Make-up Dosing Tanks For this
every 3 to 5 days. Furthermore, apart from some periods
plant, there are at least 5 possible ways that the make-up
during which a condenser leak occurred (i.e. February 21,
dosing tanks and subsequently the water/steam cycle
2011), the sulphate concentrations in the boiler drum were
could be contaminated with chloride (see Figure 2):
typically significantly less than the chloride concentra-
(a) contaminated ammonia injection into the low level (LL) tions.
and high level (HL) condensate tanks;
Surplus from the hotwell to the make-up dosing tanks can
(b) slippages from the demineralizing beds in the water
be tricky to both identify and eliminate as this is difficult to
treatment plant (WTP);
monitor and control. However, such a source is only an
(c) contaminated water pumped from the hot condensate indirect source with its actual roots in the condenser,
drain (HCD) tank to the LL tank without prior water either as a condenser water leak, which has been dis-
quality checks; cussed as an unlikely major source of the experienced
chloride cycling, or as gaseous chlorine compound
(d) failure of isolating valves, to causing back feed from
ingress, which is discussed later in a separate paper.
the plant's closed circuit cooling water (CCCW) used
Furthermore, such contamination of the make-up water
for cooling plant equipment (such as boiler feed
(HL) would only be intermittent (and not continuous) and
pumps, soot-blowers, and pulverizers); and
as the HL tank is more regularly monitored for chloride
(e) surplus from the hotwell to the make-up feed tanks (and sulphate), it would be noticed. For example, outside
(i.e. HL tanks). the LL tank isolation period, some exceptionally higher

PowerPlant Chemistry 2012, 14(2) 103


PPCHEM Chloride Contamination of the Water/Steam Cycle in Power Plants – Part I

350 4.0

3.5
300

MW generated, left axis 3.0


Condenser leak
Cl & SO4 Concentration [µg · kg –1 ]

250 Cl concentration, left axis

Blowdown Rate [kg · s –1]


SO4 concentration, left axis
2.5
Boiler CBD, right axis
Unit Load [MW]

200
Start of LL Carbon beds in parallel
2.0
tank isolation
150
1.5

100
1.0

50
0.5

0 0
1-Jan 8-Jan 15-Jan 22-Jan 29-Jan 5-Feb 12-Feb 19-Feb 26-Feb 5-Mar 12-Mar 19-Mar 26-Mar 2-Apr 9-Apr
Date in 2011

Figure 3:
Unit load versus chloride and sulphate concentrations in the boiler drum for periods preceding (January 1 to January 13,
Author's Copy

2011) and during (January 14 to April 8, 2011) the low level (LL) tank isolation.

chloride contents (11.7± 3.0 µg · kg–1) were observed in As all five listed sources end up in the HL tanks (and chlo-
the HL tank for December 3 and 4, 2010, as compared to ride levels are routinely measured from these tanks) before
the sulphate concentration (9.7±1.0 µg · kg–1) even though injection into the hotwell as make-up, a simple mathemat-
the demineralized tanks that fed the HL tanks contained ical calculation can also be performed to estimate the
only 2.5±1.2 µg · kg–1 chloride but higher sulphate contribution of these sources (as composite) to the boiler
(4.5±0.9 µg · kg–1). Such high chloride concentrations in drum cycling, provided the make-up rate is known.
the HL can significantly impact on the chloride cycling (i.e. According to this calculation (Method 1 of Appendix A), it
~11.5 µg · kg–1 Cl–1 increase per day in the boiler drum), could take about 28 days for the chloride ingress of
but the source is unlikely to be from the water treatment 4 µg · kg–1 (the highest recorded during the LL tank iso-
plant, leaving the HCD, CCCW, and hotwell surplus as lation) to result in boiler blowdown based on EPRI's
likely culprits. Since later investigations (see above) by guidelines of ~110 µg · kg–1 under the typical operating
isolating the LL tanks eliminated the HCD and CCCW as pressures in this plant for action level 1 response. It was
the dominant culprits for the persistent chloride cycling therefore concluded that potential contamination of the
(Figure 3), the hotwell surplus remained the most likely make-up water was not responsible for the frequent chlo-
source of the HL tank chloride contamination and subse- ride-based blowdown (for instance, once every 3–5 days
quently the water/steam cycle chloride contamination. In experienced at its peak).
support of the hotwell as the likely culprit is the intermit-
tent nature of the HL tank contamination. The average The conclusion above based on mathematical estimation
chloride concentration in the HL tanks the following day is further supported by grab sample measurements of the
(December 5, 2010) was only 4.3±1.1 µg · kg–1 whilst the water quality in the HL tanks as compared to that from
sulphate was higher at 17.3±3.9 µg · kg–1, indicating that post CEP and HP heater #6. With the low typical make-up
the source was probably the demineralized water (i.e. rate, MR = 2.46 kg · s–1, as compared to the condensate
1.0±0.1 µg · kg–1 Cl–1 and 8.5±2.8 µg · kg–1 SO42–) that fed return, R, of 198 kg · s–1, contaminant concentrations in
the HL tank. The intermittent significantly higher chloride the make-up (MX) cannot exceed the feedwater concen-
(than sulphate) levels also found in the HL tanks during the tration (FX) of this contaminant, which mathematically
chloride crises are therefore attributed to surplus conden- speaking is the make-up flow rate (MR) over the total
sate from the hotwell when it was contaminated with chlo- feedwater flow rate (FR) fraction of this concentration, i.e.
ride. The likely source of chloride contamination of the
MR
condensate water in the hotwell is discussed in detail in a FX = –––– · MX (1)
separate paper of this series. FR

104 PowerPlant Chemistry 2012, 14(2)


Chloride Contamination of the Water/Steam Cycle in Power Plants – Part I PPCHEM

Within the period of the LL tank isolation from the HL tanks treated make-up, and various limits, ranging from 100 to
(Figure 3), specifically from January 13 – March 7, 2011, 300 µg · L–1 as carbon, have been arbitrarily set by organi-
grab sample measurements of chloride and sulphate were zations such as EPRI, VGB and Eskom for make-up water
purposely conducted with the aim of troubleshooting the to the water/steam cycle [11,16]. Bursik however argues
source of the chloride issues, and their measurements in that it is almost impossible to give generally applicable nor-
the HL tank (make-up supply) were respectively mal target values as organic compounds that enter the
0.3±0.7 µg · kg–1 and 6.3±1.5 µg · kg–1. In fact, the chlo- plant cycle are different in many ways. He draws attention
rides, for all practical purposes, were non-detectable to the fact that it is the presence of heteroatoms (e.g. halo-
within this period except on February 16, 2011, when only gens, sulphur, and phosphorus) in the organics (measured
a small value of 2 µg · kg–1 was recorded as an average in as TOC) that should be of major concern. Thus, whereas
the two HL tanks which are tied together as make-up. 100 µg · L–1 (EPRI's target for make-up TOC [15]) in the
However, chlorides of varying and higher amounts in either form of a heteroatom-free organic compound may be rela-
post CEP and/or post HP heater #6 were observed. This tively harmless, it can be harmful in the form of, for exam-
indicates different sources of chloride ingress, and these ple, chloroform (CHCl3) [11].
are discussed in separate papers (Parts II and/or III) of this
series of chloride-contamination investigations. For Assuming a total decomposition of the organic com-
instance, for the February 16, 2011 sampling, with a rela- pound(s) and neglecting losses due to deaeration or blow-
tively higher sulphate concentration of 6 µg · kg–1 (than the down, a measured carbon content of 100 µg · L–1 (TOC) in
2 µg · kg–1 chloride) in the HL tank, the chloride and sul- the make-up when the organic compound is CHCl3
phate after both the CEP and the HP heater #6 were (994 µg · L–1) would translate to a chloride concentration of
7 µg · kg–1 and 0 µg · kg–1 respectively. Thus, although the 11 µg · L–1 in the boiler feedwater for a plant that operates
sulphate (and for that matter also the chloride) in the make- with similar make-up (2.46 kg · s–1) and steam flows
up was to be diluted to the extent of not being detectable (198 kg · s–1) as this plant. And with the boiler operating at
in the feedwater (i.e. < 0.03 µg · kg–1 by calculations), both the water volume and conditions as in this plant, such
Author's Copy

appreciable chloride concentrations were measurable in a level of chloride in the feedwater could lead to an
the feedwater. Unquestionably, the persistent chloride in increase in chloride concentration in the boiler water of
the feedwater must be coming from sources other than the ~37 µg · kg–1 per hour (see Appendix A, method 1, for how
make-up. In fact, the results for that day may also be used this was calculated). In practice, such a situation will call
to support the elimination of the ammonia injection system for continuous blowdown (CBD) all the time to keep within
as a significant cause of the chloride issue as that should the cycle chemistry operating limits set by recognized
have translated into a higher chloride concentration at the organizations such as EPRI (e.g. [6]). In a nuclear power
downstream sampling spot (HP heater #6). However, there plant with "once-through" boilers and seawater-cooled
were at least two occasions (February 28 and March 2, condensers that experienced on-load corrosion boiler tube
2011) when with no detectable chloride in the HL tank leaks from halide sources [8], THMs in the make-up water
make-up water or the CEP water, 4.2 and 2.0 µg · kg–1 Cl–1 were identified as a significant source of chloride and bro-
were respectively measured in the post HP heater #6 sam- mide ions in the boiler feedwater (contributing
ples. This arguably could be coming from the ammonia ~0.3 µg · kg–1 halide in the feedwater). The measured chlo-
injection; however, it is also possible that it came from the rine-containing THMs in their make-up water were
condenser in the form of some Cl-containing compound 22 µg · kg–1 CHCl3, 20 µg · kg–1 CHCl2Br and 13 µg · kg–1
(e.g. HOCl, haloacetic acids, THM or chloroamines) which CHClBr2. For the operating conditions of the power station
could be converted to chloride after the CEP. This second under discussion in this paper and the assumptions made
idea forms part of the working hypothesis of Parts II and III above, such make-up THM levels will translate to
of this series of water/steam cycle investigations, which 0.37 µg · kg–1 chloride in the feedwater and would lead to a
will be published in separate papers. chloride increase of 1.2 µg · kg–1 per hour. This level of
ingress, if it pertained to the power station under discus-
Halo-organic Sources from WTP THMs can decom- sion, would be high enough to account for the chloride
pose in the water/steam cycle to form chlorides [12]. A high contamination encountered as this would require blow-
proportion of THMs has been observed to escape the down intervals of approximately 3–4 days due to chlorides.
make-up water treatment plant [8], and they can also enter
the water/steam cycle through other routes [12]. Bursik, in At this power plant, however, the total THMs in the make-
his article entitled "Carbon Is Not Equal to Carbon," puts up water were found to be less than the detection limit of
emphasis on organics as a more frequent cause of cycle 2 µg · kg–1 [17]. Assuming a total decomposition of the
chemistry issues and lists them even above the well- THMs, neglecting losses due to deaeration or blowdown,
known causes of component failures such as flow-acceler- and assuming that the THMs in the make-up are essentially
ated corrosion (FAC), corrosion fatigue, stress corrosion composed of CHCl3 (which has the greatest number of Cl
cracking (SCC) and hydrogen damage [11]. Total organic atoms), then under the worst case scenario (i.e. = limit of
carbon (TOC) is the common measure for organics in detection), a maximum chloride concentration of only

PowerPlant Chemistry 2012, 14(2) 105


PPCHEM Chloride Contamination of the Water/Steam Cycle in Power Plants – Part I

~0.02 µg · kg–1 in the feedwater is expected from this (b) Beds in parallel operation
source. This translates to an increase of only ~1.8 µg · kg–1 (March 3–23, 2011):
per day (see calculation method 1, Appendix A) in chloride 23.4±20.7 µg · kg–1 Cl–1, 2.19±17.7 µg · kg–1 SO42–,
levels in the boiler water. For such a level of chloride and 11.9±49.9 µg · kg–1 Na+;
ingress, ~46 to 63 days would be the required time interval
(c) Beds in series after parallel operation
between chloride-based blowdown using EPRI's action
(March 24 – April 8, 2011):
level 1 requirement [6] if the chloride concentration prior to
14.6±37.6 µg · kg–1 Cl–1, 0.9±10.0 µg · kg–1 SO42–, and
the ingress or at the end of each blowdown is kept within 0
11.9±33.2 µg · kg–1 Na+.
to 30 µg · kg–1, as an example. Apart from THMs,
haloacetic acids (HAAs) in the boiler make-up water,
The minor differences (in the light of the significant stan-
though not often mentioned, can also contribute chloride
dard deviations) observed during this change in operation
to the water/steam circuit. Previously [17], 1.6 µg · kg–1
of the carbon beds could not account for the switch from
CCl3COOH, 0.8 µg · kg–1 CHCl2COOH, and < 0.5 µg · kg–1
sulphate-based blowdown to chloride-based blowdown
CHBrClCOOH were measured in the make-up water of this
observed in this plant.
plant [17]. Taking the worst case scenario, the maximum
chloride concentration expected in the feedwater from
both THM and HAAs sources will be ~0.04 µg · kg–1 and will Condenser Tube Water Leak When discussing the
cause a daily increase of ~3.3 µg · kg–1 Cl– in the boiler events with colleagues within the plant and within the cor-
water (i.e. a blowdown requirement every 25–34 days to poration, or when consulting through the FOMIS platform,
keep within EPRI's guidelines for "normal" operation). With the first suspect for the chloride contamination in the boiler
a significantly more frequent chloride-based boiler blow- drum was condenser tube water leak(s) [9]. However, with
down than experienced (typically 7–10-day and in some a significantly high sulphate to chloride ratio of (~6–7):1 in
worse situations 3–5-day intervals between blowdowns) the re-circulating cooling water, any condenser tube water
with this scenario, THMs and HAAs from the WTP (though leak from the water box should somehow reflect this rela-
Author's Copy

jointly fairly significant) were not regarded as the main tive ratio also in the water/steam cycle even if only small
source or root cause of the observed chloride ingress. leaks occur. Sodium, for example, is typically more than
Furthermore, the estimations made above are quite con- twice the concentration of chloride in the cooling water
servative, as some THMs will certainly be removed by the system; hence any such potential water leak, however
deaerator. THM removal of between 30 and 60 % has been small, should also reflect the relative amounts of these
reported [18]. However, due to some operational changes parameters in the water/steam cycle. Figure 4 shows chlo-
made in the WTP just prior to the water/steam cycle chlo- ride and sulphate concentration changes in the boiler
ride issues, this source was also investigated as a potential together with sodium concentration in the condensate
source. return for a period directly preceding one occasion of unit
outage for condenser tube leak repairs. As illustrated in the
On December 4, 2008, a decision was made to switch the figure, the first indication of a condenser leak in this plant is
operation of the carbon beds (which are upstream of the typically from the sodium levels in the CEP discharge
mixed bed in the boiler make-up treatment train) from par- water. With respect to the boiler chloride and sulphate, the
allel operation to series operation [17,19], and as the chlo- sulphate to chloride ratio prior to the first indication of the
ride contamination issue started quite soon after this condenser tube leak averaged 0.13±0.02 and increased to
operational change (January 19, 2009), this was consid- 0.30±0.12 from the first period of indication of the con-
ered as a potential source. With the isolation of the LL tank denser tube leak to when it became more obvious, at
(see above), the two beds which had been running in which point the ratio escalated to 1.53. With a CBD of
series for over 2 years were switched back to parallel about 3.5 L · s–1 after this obvious indication of the con-
operation and maintained so between March 2 to March denser tube leak, the sulphate to chloride ratio continued
23, 2011. The water/steam cycle was monitored atten- to increase to ~3.3 (approximately 12 h after) and to ~4.7
tively with particular reference to any significant drop in (just before the outage to fix the leak). The increasing SO42–
chloride increases as compared to periods prior to and to Cl– ratio reflects the increasing amount of the relatively
after the switch (see Figure 3). Based on some daily grab higher sulphate cooling water leak into the hotwell. As can
samples, the average daily changes in chloride, sulphate be seen from Figure 4, the sudden increase in CEP Na+
and sodium in the boiler (excluding periods when the indicating the condenser leak coincides reasonably with
boiler was being blown down or during start-up & shut- the increase of the SO42–/Cl– ratio in the boiler drum. There
down conditions) were as follows: are therefore many clear indications in this plant's opera-
tion that distinguish a condenser tube water leak from the
(a) Beds in series before switching to parallel observed chloride-specific ingress, which had been
(February 3 – March 1, 2011): persisting since January 2009 and resulted in frequent
28.1±18.1 µg · kg–1 Cl–1, 0.8±3.0 µg · kg–1 SO42–, and boiler drum blowdown. It is noteworthy that the Feb 21,
14.4±40.4 µg · kg–1 Na+; 2011 condenser tube leak outage occurred when the LL

106 PowerPlant Chemistry 2012, 14(2)


Chloride Contamination of the Water/Steam Cycle in Power Plants – Part I PPCHEM

350 10

9
300
8
MW generated
Cl and SO4 Concentration [µg · kg –1 ]

250 Cl boiler 7
SO4 boiler

CBD Rate [kg · s –1]


CEP Na [µg · kg –1 ]
6
Unit Load [MW]

200 Na (CEP)
Boiler CBD
5
Indication of more obvious leak
SO4/Cl ratio
150
4

100 3
1st indication of
condenser leak 2
50
1

0 0
19-Feb 19-Feb 19-Feb 19-Feb 19-Feb 20-Feb 20-Feb 20-Feb 20-Feb
0:00 4:48 9:36 14:24 19:12 0:00 4:48 9:36 14:24
Date, Time in 2011

Figure 4:
Author's Copy

Unit load versus CEP sodium and boiler chloride and sulphate concentrations, and continuous blowdown (CBD) rate for
periods directly preceding (February 19, 2011, 00:00 to February 20, 05:00 am) and during a condenser leak episode
(after February 20, 2011, 05:00 am).

tanks were isolated from the HL tanks (the make-up supply of ammonia from different suppliers were dosed at different
tank). periods and attention was paid to the cycle chemistry, but
we could not confirm that the chloride ingress was due to
Condensate Pump Leak Chloride ingress into the contaminated ammonia. Although we have ion chromatog-
water/steam cycle from leakages via condensate pump(s) raphy (Dionex IC-DX-2000) to perform chloride analysis at
has been experienced by others, either as a leak at the low ppb levels, concerns about column damage from
base of the pump introducing stagnant water [9] or as ammonia, even in diluted solutions where the chloride lev-
leaks from condensate pump seal cooling water for the els were likely to be detected, made this prohibitive.
pump [10]. This was pursued, but there was no indication Furthermore, as the use of none of the different batches
that this was the likely source of the persistent chloride (including a supply from a previous source prior to the
ingress. chloride issue) alleviated the issue, there was not much
reason to pursue the analysis. An alternative approach was
NH3 Chemical Injection Contaminated ammonia sought to evaluate whether the cause of the chloride-
injected into the feedwater for pH control has also been based boiler drum blowdown was due to the ammonia
noted as a possibility, though it is less common [9]. This injection. From the suppliers' technical data sheet informa-
was perhaps the most confusing source to eliminate. It had tion, a maximum chloride amount of 1 mg · kg–1 can be
been initially noted that by switching the ammonia injection expected in any of the 28–30 % aqua ammonia dosed into
from one of the two ammonia dosing tanks to the other, the boiler. With a typical ammonia injection rate of only
some improvements were made in the boiler drum chem- ~5.1 mL · min–1, the expected increase in the boiler water
istry. However, a consistent switch from one tank to the chloride concentration from this injection source will be
other could not confirm this. Having changed vendors for only ~12 µg · kg–1 for an entire year of continuous operation
the supply of ammonia and with indiscriminate ammonia (see Appendix A, method 1, for the calculation). It was
dosing from the various supplies, the ammonia injection therefore concluded that the ammonia injection was not
was considered a suspect for the chloride ingress. responsible for the chloride-based blowdown. However,
Furthermore, our laboratory staff had noticed a higher the observation of a likely association of the problem with
requirement to dose more ammonia for pH control. With all ammonia injection will be discussed in more detail in sepa-
this in mind, the first step taken was to empty and clean rate papers as Parts II and Parts III of this series of chlo-
both ammonia dosing tanks (in stages). Different batches ride-contamination investigations.

PowerPlant Chemistry 2012, 14(2) 107


PPCHEM Chloride Contamination of the Water/Steam Cycle in Power Plants – Part I

CONCLUSIONS ACKNOWLEDGEMENT
Chloride is a well-known corrosive inorganic ion, which We would like to express our gratitude to all the fellow
can potentially cause or contribute to equipment break- chemists at SaskPower for the helpful discussions. To the
down, e.g. boiler tube and steam turbines failures. The Shand Power Station laboratory, operational and mainte-
power plant unit discussed in this report was affected by nance staff, thanks for being part of the team in this effort
elevated chloride levels in the water/steam circuit, result- to identify the root cause of the chloride contamination. To
ing in more than normal continuous blowdown of the Blair Mowchenko (production specialist), Kevin Guillemin
boiler to keep it in operation. The paper enumerates pop- (production supervisor), Kevin Scobie (plant manager) and
ularly known sources of chloride ingress into the the others, we say thanks for all the fruitful discussions
water/steam cycle and provides the bases on which these and thought-provoking ideas. Special thanks also go to
were eliminated as root causes of the chloride crises. Dwayne Selensky and Jackie Lam of the Chemical
These sources include the following: make-up water con- Laboratory Division and Mahnaz Missaghi of the
tamination, feedwater contamination from sources such Metallurgy Laboratory Division of the Chemical Services
as condenser tube water leaks and/or leaks from conden- Laboratory for the Operation Support Group of
sate pump seal cooling water for the condensate pumps, SaskPower for performing laboratory analyses which were
leakages from condensate polishers or via contaminated instrumental in the general understanding of the issues
chemical injections. discussed in this paper. Lastly, we want to thank Rico
Tomsha for the excellent schematic drawing.

APPENDIX
Author's Copy

Determining the Cycling Rate in the Boiler and Specified Contaminant (X) Based Blowdown Frequency
Requirements

Nomenclature
B blowdown
–1
BR kg · s blowdown flow rate
BV L firing boiler volume (drum, waterwalls, headers, etc)
–1
BWX µg · kg contaminant concentration in the boiler water
–1
BX µg · kg contaminant concentration in the blowdown
–1
COC s cycle of concentration
F feedwater
–1
FR kg · s feedwater rate
–1
FX µg · kg contaminant concentration in the feedwater
–1
L kg · s steam losses
M make-up
–1
MR L·s make-up flow rate
–1
MX µg · kg contaminant concentration in the make-up
–1 –1
RX µg · kg · s rate of increase of the contaminant concentration in the boiler water
t s time
T s cycle duration
TBD d time required for the next blowdown
–1
TBWX µg · kg target concentration of the contaminant in the boiler water
X contaminant
W kg mass of water in a condensate return vessel

108 PowerPlant Chemistry 2012, 14(2)


Chloride Contamination of the Water/Steam Cycle in Power Plants – Part I PPCHEM

In water/steam cycle operation, there is generally an accu- only under conditions when the boiler is being blown
mulation of contaminants in the boiler and accumulation down and hence is inapplicable for in-between blowdown
of condensate (pure water) in the condensate return sys- conditions. For in-between blowdown conditions, the
tem; in the absence of blowdown, the contaminant level in boiler serves as a sink to continuously increase the con-
the boiler will rise rapidly [20]. When operating within stan- centration. Cycles of concentration, if used here, would
dard guidelines (such as those specified by EPRI as fol- likewise increase with time. Thus, modification of Eq. (1) is
lowed for the operation of this unit), carryover of contami- required in predicting the cycling in the boiler under the in-
nants such as chloride in the steam is negligible or is between blowdown conditions and this is addressed
assumed to be negligible [6]; the boiler therefore acts as a below using different approaches.
"sink" to accumulate ingress of such contaminants in-
between blowdowns. Therefore, occasionally, there is the
need to blow down some content of the boiler water,
Method 1A
which is replaced with fresh make-up to dilute the content
of the remaining soluble contaminants in the boiler to This method can be used when the concentration of the
within standard operational requirements. There are two contaminant or parameter in the make-up or the feedwa-
main reasons for blowing down from the boiler: intermit- ter and their respective flow rates are known. Based on
tent removal of suspended solid particles, where the take- mass balance and treating the boiler as the main "sink" for
off is usually located at the bottom of the boiler drum, and the ingress of the contaminant, an increasing amount of
the continuous blowdown (CBD) of soluble contaminants the contaminant is expected with time. The rate of
from locations of the highest dissolved solids in the boiler increase of the contaminant (X) concentration in the boiler,
drum [21]. As can be seen in the name, CBD is the contin- RX, can therefore be calculated simply (in make-up terms
uous removal of water from the boiler, but this can be for instance) as follows:
done automatically or manually, both of which is based on
the operating water quality criteria for blowing down [21]. (2)
Author's Copy

(The automatic blowdown system continuously monitors


the boiler water, adjusts the rate of blowdown, and main- The time required (in days) for the next blowdown can be
tains the specific conductance of the boiler water at the calculated using
desired level.) In this article, reference to CBD means the
latter and the CBD control valves are adjusted "manually" (3)
from the control room according to laboratory grab sam-
ple test results to meet the specifications by EPRI to main- It is noteworthy that Eq. (2) can similarly be expressed in
tain good water/steam cycle chemistry. Thus, the CBD feedwater terms (i.e. by replacing the make-up concentra-
operation for this unit can be said to be operated intermit- tion and flow with the feedwater concentration and flow,
tently instead of continuously. respectively).

For a water/steam cycle where some of the boiler water is


being blown down, the term cycles of concentration, COC
Method 1B
(used more commonly for cooling towers), is used to refer
to the number of times the minerals in the feedwater have Following Spencer et al.'s boiler model [20], the state of
been concentrated in the boiler by its operation [22]. COC the water/steam system is described by 2 variables only,
can be defined both in terms of the relative flows and the namely the mass of water in a condensate return vessel,
relative concentrations of the contaminant (X) in the feed- W, and the contaminant concentration in the boiler, BWX.
water and the blowdown water as expressed in Eq. (1) [22]. The infinitesimal change in these variables with time (by
expressing the flows in terms of the usual measurable
(1) terms of volume/time instead of mass terms as by
Spencer et al. [20]) can be expressed in the following
Some properties required of X to make the equation valid differential equations:
include zero or minimal carryover and high solubility in
water. Chloride, for example, exhibits these characteris- (4)
tics, especially when maintained below the maximum level
permissible as in recognized operating guidelines by and
organizations such as EPRI. Thus, for example, make-up
water with a chloride concentration of 5 µg · kg–1 and or
boiler water with a concentration of 30 µg · kg–1 is said to
have boiler water at 6 cycles of concentration. However,
and without getting into technical details, the definition of (5)
COC itself as in Eq. (1) suggests that the term is applicable

PowerPlant Chemistry 2012, 14(2) 109


PPCHEM Chloride Contamination of the Water/Steam Cycle in Power Plants – Part I

0 ≤ t ≤ T, where t is time and T is the duration of a cycle. REFERENCES


[1] Sakai, Y., Thermal Power and Nuclear Power 1999,
We focus on Eq. (5) as the relevant equation for this paper
50(7), 778.
and solve the differential Eq. (5) as follows:
[2] Daniels, D. G., Power 2009, 153(6), 56.
(6)
[3] Ritter, S., Seifert, H.-P., PowerPlant Chemistry 2004,
6(12), 748.
In the absence of blowdown, as presented for Method 1A
[4] Cutler, F. M., PowerPlant Chemistry 2001, 3(5), 283.
above, the integral equation simplifies to
[5] Dooley, R. B., Bursik, A., PowerPlant Chemistry
(7) 2010, 12(2), 122.
[6] Cycle Chemistry Guidelines for Fossil Plants: All-
This yields Eq. (8) as the solution: Volatile Treatment: Revision 1, 2002. Electric Power
Research Institute, Palo Alto, CA, U.S.A., 1004187.
(8)
[7] Zhang, H.-F., Niu, L.-B., Oishi, S., Takaku, H.,
Shiokawa, K., Yamashita, M., Sakai, Y., PowerPlant
It has to be noted that Eq. (8) is the same as Eq. (2), Chemistry 2006, 8(9), 558.
although different approaches were used to derive the
[8] Hutchison, G. W., Garbett, K., Drew, N. J.,
expression. Furthermore, the make-up terms can be sub-
PowerPlant Chemistry 2006, 8(4), 234.
stituted with feedwater terms to obtain the same result.
[9] Steinberg R., FOMIS Report # 25829 (for Request
F10-11-021 submitted by Stock R.; Shand Power
Method 2 Station/SaskPower), 2010.
Author's Copy

In the situation in which the parameter or contaminant of [10] Kutty, P. C. M., Dalvi, A. G. I., Al-Jerfaley, T. H.,
interest can be measured accurately in the feedwater, a Evaluation of Steam Chemistry in Al-Jubail Desalina-
modified method of the COC approach can be used to tion and Power Plants, 1992. Saline Water Con-
determine a time-dependent concentration cycling version Corporation, Al-Jubail, Saudi Arabia, SWCC
expression in the boiler for the ingress in the feedwater. (RDC)-21. Available at
This is determined from the measurement of the BWX at http://www.swcc.gov.sa/files/assets/Research/Tech
times t1 and t2 to obtain concentrations BWX,1 and BWX,2 nical%20Papers/Chemstry/EVALUATION%20OF%2
(= ⌬BWX) as well as the feedwater concentration FX. The 0STEAM%20CHEMISTRY%20IN%20AL-JUBAILDE
COC is expressed per unit time (e.g. per second COC) as SALINATION%20AND%20P.pdf.
follows:
[11] Bursik, A., PowerPlant Chemistry 2008, 10(12), 708.
(9) [12] Daucik, K., PowerPlant Chemistry 2006, 8(1), 10.
[13] Chemical Guidelines for Water/Steam Cycle of Fossil
Thus, an increase in the boiler drum concentration from Fired Units, 1997. The Union of the Electricity
any particular time can be determined by multiplying the Industry (EURELECTRIC), Brussels, Belgium,
projected time by the COC and by the feedwater concen- 02004Ren9766. Available at
tration (assuming it is constant). In cases where the con- www.eurelectric.org/Download/Download.aspx?Do
taminant concentration in the feedwater is unsteady (vari- cumentID=11637.
able), a weighted average of the feedwater concentrations
[14] Gibson, B., FOMIS Report # 14597 (for Request F96-
within the specified time intervals would have to be used
05-005 submitted by FOMIS/Scientech Inc), 1996.
in Eq. (9) to determine the time-dependent COC. Similarly,
a weighted average would have to be used in determining [15] Guidelines for Makeup Water Treatment, 2010.
the increase in the boiler drum concentration of the con- Electric Power Research Institute, Palo Alto, CA,
taminant if the feedwater concentration is variable. U.S.A., 1019635.
[16] Maughan, E. V., Staudt, U., PowerPlant Chemistry
Knowing the rate of increase of the contaminant in the
2006, 8(4), 224.
boiler, the time required for the next blowdown can be pre-
dicted as in Eq. (9) above. [17] Quagraine, E. K., Hill, K. D., Omorogbe, F.,
PowerPlant Chemistry 2010, 12(1), 22.
[18] Knowles, G., The Occurrence of Organic Halides in
Make-up Water, Part II – The Fate of Chloroform in

110 PowerPlant Chemistry 2012, 14(2)


Chloride Contamination of the Water/Steam Cycle in Power Plants – Part I PPCHEM

Steam/Water Circuits, 1980. CEGB North Western Jonathan P. Ruffini (B.Eng., Chemical Engineering, E.I.T.
Region Stockport, UK. (Engineer in Training)) started his engineering career at
SaskPower as an intern in 2010. After graduating from
[19] Quagraine, E. K., Proc., International Water Confer-
McMaster University, Canada, in 2008, Jonathan Ruffini
ence, 2011 (Orlando, FL, U.S.A.). Engineers' Society
did several different jobs before starting as an engineering
of Western Pennsylvania, Pittsburgh, PA, U.S.A.,
intern at the Shand Power Station, where he progressed
Paper #11-69.
to a chemical engineering position within SaskPower a
[20] Spencer, J. L., Connick, B. J., Filippi, A. J., Chemical year later with the Clean Coal Project. He had written one
Engineering Communications 1986, 47(4–6), 329. paper on the sequestration of carbon dioxide from a coal-
fired power plant before graduating.
[21] Handbook of Industrial Water Treatment, Chapter 13:
Boiler Blowdown Control. GE Power & Water, Power
& Process Technologies. Available at
http://www.gewater.com/handbook/boiler_water_sy
CONTACT
stems/ch_13_blowdowncontrol.jsp.
Emmanuel K. Quagraine
[22] Unified Facilities Criteria (UFC). Industrial Water
Shand Power Station
Treatment Operation & Maintenance, 2005. U.S.
P. O. Box 1310
Department of Defence, Washington, DC, U.S.A.
Estevan, SK, S4A 2K9
U.S.A., UFC 3-240-13FN, Chapter 3. Available at
Canada
http://www.wbdg.org/ccb/DOD/UFC/ufc_3_240_13f
n.pdf.
E-mail: equagraine@saskpower.com
Author's Copy

THE AUTHORS
Emmanuel K. Quagraine (B.S., Chemistry and Diploma in
Education, M.S., Analytical Chemistry, University of Cape
Coast, Ghana, Ph.D., Analytical Chemistry/Bio-inorganic
Chemistry, University of Saskatchewan, Canada) started
his career as an assistant lecturer at the University of
Cape Coast in 1993 and later became a lecturer and a
senior lecturer at the same university. Since April 2006, he
has been the supervisor of the Chemistry Laboratory and
Environmental Affairs for the Shand Power Station,
SaskPower. Emmanuel Quagraine previously also worked
as a sessional instructor at the University of
Saskatchewan and as an instructional associate at
Brandon University, Manitoba, Canada. He has various
post-doctoral experience including working with the
University of Saskatchewan, the National Water Research
Institute, and the WateResearch Corporation, all in
Saskatoon, SK, Canada, and with the Chemistry
Department of the University of Michigan, Ann Arbor,
Michigan, U.S.A. He has presented many papers at local,
national and international conferences and has authored
or co-authored several published articles in peer-reviewed
journals. He is currently a member of the American Water
Works Association (AWWA) and the Association of the
Chemical Profession of Ontario, Canada.

PowerPlant Chemistry 2012, 14(2) 111

View publication stats

Potrebbero piacerti anche