Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Introduction All coupons were made by a recog- rangement was such that the deforma-
The strength of a fillet weld is de- nized steel fabricator from CSA G40.12 tion measured included only a negligible
pendent upon the direction of the steel plate,4 which has a specified yield contribution from the plate itself. The
applied load with respect to, say, the stress of 44 ksi and a minimum tensile location of the gauges is shown in Fig. 2.
longitudinal axis of the weld." Most of strength of 62 ksi. The welds were made The specimens were loaded in ten-
the reported experimental studies have using AWS E60XX electrodes.1 In every sion in a 440,000 lb capacity electro-
been directed toward strength proper- case the cross-sectional area of the mechanical testing machine. Generally,
ties only, however, and little attention connected parts was proportioned to readings were taken at 5 kip increments
has been paid to deformation 9 ' 10 . As assure weld failure before rupture of in the lower ranges and at 2.5 kip
with most engineering materials, an the plates. At the same time, the thick- increments as the response became
increase in fillet weld strength could be ness of the parts was limited by the weld noticeably inelastic. As the ultimate
expected to be accompanied by a size, in conformance with present load was approached, the increment
decrease in deformation capacity. This building codes.2 A schematic drawing was further reduced. Deformation read-
reduced ductility can be of considerable of the coupons is shown in Fig. 1A for ings were taken until the ultimate load
importance and could influence a longitudinal welds and in Fig. IB for was reached and then the gages were
designer to orient fillet welds in one inclined weld coupons. The dimensions removed as loading continued to failure.
direction in preference to another. In shown are nominal and in all cases
addition, an evaluation of the complete actual dimensions were taken, including Test Results
load response curve would be useful in weld leg size. The results of the coupon tests are
assessing the validity of present design The welds were made as uniform as presented in Figs. 3 through 6 in the
methods for fillet welded connections, possible by having all welding done by form of load vs. deformation plots.
most of which assume an elastic weld the same operator, using electrodes all (The solid lines in these illustrations
response.8 from the same lot and having the start relate to the theoretical expressions
In the course of an investigation into and finish of all welds sawn free. The developed below). The mean values and
the behavior of eccentrically loaded five coupons of the longitudinal weld standard deviations of the ultimate
fillet weld groups, basic information group (8 = zero deg) were fabricated load and maximum deformation for
with respect to the load-deformation individually while the coupons of the each group are given in Table 1. As
response of fillet welds was developed.3 other groups were obtained by sawing expected, all specimens failed in the
The results of this portion of the study six 1 in. wide strips from a single as- fillet welds. Further details of the
are reported herein. sembly. failure modes, etc. are available else-
where.3
Test Program Test Procedure
Description of Tests Two 0.001 in. dial gauges were Theoretical Analysis
A series of 23 tests were conducted on
fastened to each specimen in order to It has been shown5 that the load-
\i in. fillet welds in order to establish measure the weld deformation. The deformation response for mechanical
the load-deformation response for ele- gauges were mounted on steel brackets fasteners can be expressed by the
mental lengths of fillet weld. The 23 soldered to the specimen and the ar- following relationship:
coupons were grouped in four cate-
gories. Group 1, with five coupons,
had the weld axis parallel to the direction
^ 1/4 fr-
of the applied load. Groups 2-4 had I
1
six coupons each with the welds in- 1 I 1 1/4
1 1
clined at angles of 30, 60, and 90 deg, _ ^
respectively, to the direction of the
applied load. k-
JL
/2
L. J. BUTLER is Engineer, Lundrigans iZ 3 T I i 3 1/2
Ltd., St. John's, Newfoundland, and G. L.
KULAK is Associate Professor of Civil
T
Engineering, University of Alberta, Ed- Fig. 1—Schematic representation of coupons. A (left)—longitudinal weld coupons;
monton, Canada. B (right)—inclined weld coupons
12
Fig. 2—Location of dial gauges • •• * • • •
• • • • —• i • • V -r •
R =Rult(l -e-*<y (1) • • • • *
where R = fastener load at any given
deformation; Ruit = ultimate load at-
tainable by fastener; A = shearing,
bending, and bearing deformation of
fastener and local bearing deformation LOAD
of the connected plates; p., X = re- kip / i n .
gression coefficients; e = base of natu-
ral logarithms. The constants Ruu, p.
and X are determined for the particular
fastener under investigation.
It should be possible to use this same
expression for welds. However, unlike
a mechanical fastener such as a high-
strength bolt, the direction of the 1/4in. fillet welds
applied load must be taken into account. 9 = 0 degrees
The 23 coupons which made up the
test series represent only a small sample
and the curve-fitting was limited there-
fore to a trial-and-error procedure. In 0
addition to fitting an individual curve, 0 0.02 0.04 0.06 0.08 0.10 0.12
the equation developed must be a D E F O R M A T I O N , inches
general expression valid for any angle
of applied load. After trial, the following Fig. 3—Load (kips/in.) v. deformation (0=0 deg.)—^in. fillet welds
expressions were chosen for the variables
in eq (1). These have been developed Amax = 0.225 (6 + 5) -0 - 47 (3) coupons where the discrepancy i s
specifically for }4 in. fillet welds made about 9%. From Table 1 it can be
using E60XX electrodes. The angle 6 p. = 75 e°"lue (4) noted that the mean ultimate load of this
is that between the direction of the X = 0.4 eom6$ (5) group does not follow the progression
applied load and the longitudinal axis of the other groups. Equation (3) is
of the weld. A plot of eq (2) is given in Fig. 7. The plotted in Fig. 8. The maximum de-
ultimate loads as calculated from this formations as calculated from this
10 +6 expression are within 2 % of the mean expression are in good agreement with
Ruit — (2)
0.92 + 0.0603(9 test data except for the 60 deg group the test data.
16 IO
/•
7 •
14
/ •
*/• / * •• • •
12
/•
1 •
10
6 -•
4 - m
r
1/4 in. fillet welds 1/4 in. fillet welds 1/4 in (illel welds
f
8 - 30 degrees 8 = 6 0 degrees 8 -• 90 degrees
:
0.02 0.04 0.06 0.08 0 0.02 0.04 0.06 0.08 0 0.02 0.04 0.06 0.08
DEFORMATION,inches DEFORMATION, inches DEFORMATION, inches
Fig. 4—Load (kips/in.) vs. deformation Fig. 5—Load (kips/in.) vs. deformation Fig. 6—Load (kips/in.) vs. deformation
(-9=30 deg)—VJin. fillet welds (-9=60 deg)—'/ 4 in. fillet welds (-9=90 deg)—'Ain. fillet welds
232-s I M A Y 1971
the coupons in which the welds run
Table 1—Test Results and Predicted Values parallel to the load, virtually the same
. Ultimate load, . Maximum d sformation, Predicted values — test configuration as prescribed by
kips/in. in Ultimate Maximum AWS, these tests give an ultimate
Group Std. Std. load, deformation, strength of 61.6 ksi. This is only 2.7%
9, deg Mean deviation Mean deviation kips/in. in. greater than the minimum specified
0 10.9 0.67 0.101 0.008 10.9 0.105 value of 60 ksi. It can be expected then
30 14.6 0.03 0.049 0.011 14.6 0.042 that the strength of fillet welds made
60 14.1 0.51 0.031 0.004 15.4 0.031 using other lots of E60XX electrodes
90 15.5 0.95 0.026 0.002 15.7 0.026 will be the same or greater than the
values reported herein while the ulti-
mate deformations will be the same or
Equation (1) can now be used with that any detail using welds inclined at less than these reported values.
the substitutions given by eqs (2)-(5). about 30 deg or more to the load will The most common electrodes in use
The results are shown against the basic be much less ductile than it would have today are probably AWS E60XX and
test data in Figs. 3 to 6. Agreement been otherwise. E70XX. Since these electrodes have
between the theoretical and actual load- It is clear from Figs. 3 to 6 that, like specified ultimate elongations which
deformation responses is excellent for high-strength bolts,12 there is no well- are nearly the same,1 the results of the
the two extreme cases (6 = zero and defined yield point for fillet welds tests reported herein could be applied
90 deg) and adequate for the two inter- acting in shear. Any arbitrary definition to connections using E70XX electrodes
mediate angles tested. of yield, such as use of an offset method, by a proper consideration of the in-
gives neither consistent nor meaningful crease in electrode strength. Further-
Discussion values as the angle of load changes. more, it has been shown7 that the
Furthermore, it appears that the total strength of welds made using electrodes
The increase in strength of the fillet
response cannot be idealized by any of grades E60XX and E70XX is not
welds tested in this program was ap-
of the conventional representations like appreciably affected by the grade of
proximately 44% as the angle of load
elastic or elastic-perfectly plastic. To base metal involved. It shou'd be
changed from zero degrees (longitu-
satisfactorily describe the load-defor- possible, therefore, to use the results
dinal weld) to 90 deg (transverse weld).
mation behavior of fillet welds acting of this study for all steels commonly
Although this represents a substantial
in shear, equations such as those given used in conjunction with these two
increase, the decrease in deformation
in this paper are necessary. electrodes.
capacity was also substantial. Welds
In using the results of the tests re- Within the common range of struc-
oriented parallel to the direction of the
ported in this study for other cases, a tural weld sizes, it has been shown that
load were nearly four times as ductile as
number of variables arise which should the throat stress for fillet welds is inde-
those oriented transversely to the load.
be examined. These include basic pendent of weld leg size.6 Deformation
The shape of the load-deformation
electrode strength, use of other elec- could likewise be expected to be inde-
diagram was also more favorable in the
trodes, use of other base metals, and pendent of weld leg size s'nce shear area
ductile case—that is, a considerable
changes in weld leg size. is a direct function of the leg dimension.
portion of the curve was in the region
where only small increments in load The electrodes used in these tests
produced relatively large increases in represent E60XX electrodes of sub- Conclusions
deformation. It should be recognized stantially minimum strength. Using The conclusions that may be drawn
as a result of this study are as follows:
1. The strength and ductility of
IO
0.12
15 - / - " - " ~ -
0.10
14 - /{ 0.08
/ \ 10+9
ult -0.47
•ult / ' " ' 0.92 + 0.06039 ax • 0.225(0+5
13 A max
kips/in.
inches o.06
12
- /
0.04
11
I 8, degrees 0 30 60 90
0.02
8, degrees 0 30 60 90
RU|T, kips/in. 10.9 14.6 15.4 15.7 A m a x ,inches 0.105 0.042 0.031 0.026
i i i i i i i i _i i i i_
0 30 60 90 0 30 60 90
Fig. 7—Ultimate load vs. weld angle Fig. 8—Maximum deformation vs. weld angle
^ goto
* In this study, plastic strain range (Aep) was stress-strain relationship could accurately be detectable within the accuracy of the laboratory
approximated by subtracting twice the static yield obtained from the load-strain fatigue data gathered measurements from the early life load records. In
strain (e e ), determined from a monotonic stress- during testing. This is due to the bending mode of addition, the monotonic stress-strain curves of this
strain curve, from the applied total strain range loading, which causes a non-uniform stress distri- material agrees well with the wrought Zircaloy
(Aer), a measured quantity. Use was made of the bution. This approach was considered valid be- cyclic stress-strain curves reported by O'Donnell
monotonic stress-strain curve because no cyclic cause no cyclic hardening or softening was and Langer.*
234-s I MAY 1 9 7 1