03/22/2020

Supplier

Sl.no Description TG BMS Engineer


Make: Honeywell Make: Johnson Control Make: Siemens
Contact: Mr.Ignatus Contact: Mr.Ciju Prakasam Contact: Mr. Mohammed Yahya

During tender, they will cost based During tender, they will cost based During tender, they will cost based on
1 DDC Selection
on assumptions only on assumptions only assumptions only

2 Capacity of DDC Maxiumum upto 600 points Permissble points 128 points Maxiumum upto 250 points

3 Approximate points per DDC 200 to 300 points 60 to 65 points 50 to 100 points

High rise building - Average distance for each points varies Analogue points - 75 to 100m
4 30 to 40 m 25 to 30m 50 to 60m
between (excluding FCU's, Thermostat quantities) Digital Points - 125 to 150m

Wide spread building like warehouse, Malls etc., - Average


5 distance for each points varies between 60 to 70m 50 to 60m 100 to 150m
(excluding FCU's, Thermostat quantities)

6 FCU's - 3 speed fan, 3 wires per points. 5 to 8m


FCU loop - 20m
Consider 6 runs of wires with 8 mtr Consider 8 core wires with 10 mtr Thermostat-15m
average average Control Valve - 10
FCU (Speed) - 5 to 7m
7 Thermostat 8 to 10m

BMS - Cabling Avearge Working Page:1


03/22/2020

Average based Average based Average to be


Points Total Unit Total
Sl.No Description on site i/p on Supplier considered by TG Unit Unit labour Total Labour Remarks
(in nos) quantity Rate Material
(in meters) (in meters) (in meters)

Cabling

1 Equipment Points (Excluidng FCUs & Thermostat) Pts

Analogue points - 75 40 - m - - 25% of Total Points


Digital points - 125 60 - m - - 75% of Total Points
2 FCU Units
FCU to FCU Looping - 20 12 - m - -
FCU Controller to Control Valve - 10 10 - m - -
FCU Speed Control (Low/Medium/High) - 7 7 - m - -
3 Thermostat Units
Thermostat cabling - 15 10 - m - -
If IBMS, looping cable shall be
4 DDC Looping Cable m -
part of Structured cabling.
Total for Cabling - - -
Containment

Assuming Main branch circuits


1 GI Conduit (considered 1conduit/3points) - 15 - m - -
are routed in Trunking

2 PVC Conduits - 15 - m - -
3 Kopex Conduit (considered 1conduit/3points) - 1.5 - m - -
Total for Containment - - -

TG- BMS - Cabling Containment 2of3


03/22/2020

Average Average
Points Total Unit Total Points Total Unit Total
Sl.No Description length Unit length Unit Remarks
(in nos) quantity Rate Material (in nos) quantity Rate Material
(in meters) (in meters)

Cabling Estimation Site

1 Equipment Points (Excluidng FCUs & Thermostat) 6,263 Pts 2,445 Pts

Analogue points - m - 611 120 73,320 m 1.70 124,644


Digital points 6,263 15 91,800 m 2.70 247,860 1,834 120 220,080 m 1.70 374,136
2 FCU Units Units
FCU to FCU Looping - - m - - - m -
FCU Controller to Control Valve - - m - - - m -
FCU Speed Control (Low/Medium/High) - - m - - - m -
3 Thermostat Units Units
Thermostat cabling - - m - - - m -
DDC Looping Cable (considered for 1no DDC/40
4 157.00 150 23,550 m 3 70,650 18.00 m
points)
Total for Cabling 115,350 318,510 293,400 498,780
Cables per DDC 735 16,300

TG-2516 Mankhool BMS - Cabling Containment 3of3