STT 3000 Smart Temperature Transmitter 34-TT-03-07

August 2014
Series STT170
STT171, STT173, STT17H, STT17F, STT17C Specification and
Model Selection Guide

OVERVIEW
The Honeywell STT170 series of programmable temperature transmitters provides cost effective solutions for temperature
monitoring applications. Compared to direct-wired temperature sensor monitoring points, the STT170 series of transmitters
delivers increased accuracy, safety and reliability while also reducing wiring costs. These transmitters automatically linearize
the temperature output signal bounded by the upper range value and lower range value established by the user. In addition, the
user can program high or low limit alarms to activate in the case of sensor failure.

STT171 FEATURES
 Analog 4-20 mA output
 RTD or Ohm input
 DIN form B headmount
 NAMUR NE43 sensor error response
 Configurable using STT17C configuration tool and PC

STT173 FEATURES
 Analog 4-20 mA output
 RTD, T/C, Ohm or mV input
 DIN form B headmount
 NAMUR NE43 sensor error response
 Configurable using STT17C configuration tool and PC
 Galvanic isolation

STT17H FEATURES
 HART™/4-20 mA output
 RTD, T/C, Ohm or mV input
 Single or dual (difference or average) sensor input
 DIN form B headmount
 HART Multidrop capable
 NAMUR NE43 sensor error response
 Configurable using STT17C configuration tool and PC or HART field communicator
 Galvanic isolation

STT17F FEATURES
 FOUNDATION™ fieldbus protocol
 RTD, T/C, Ohm or mV input
 Single or dual (difference, average or redundant) sensor input
 DIN form B headmount
 Function blocks: 2 analogue, 1 PID
 FISCO certified
 Basic or LAS capability
 Galvanic isolation
HART is a registered trademark of the HART Communication Foundation.
FOUNDATION is a registered trademark of the Fieldbus Foundation.
Dimensions (all models)

Wiring

STT171 STT173
Input:
Input: RTD, 2-wire RTD, 3-wire RTD, 4-wire TC, internal CJC

RTD, 2-wire RTD, 3-wire Resistance, 2-wire Resistance, 3-wire

TC, external CJC mV Resistance, 2-wire Resistance, 3-wire

Output:
2-wire installation

Resistance, 4-wire

Output:
2-wire installation
Wiring

STT17H STT17F
Input:
Input:
RTD, 2-wire RTD, 3-wire RTD, 4-wire TC, internal CJC 2X
RTD, 2-wire RTD, 3-wire RTD, 4-wire RTD, 2-wire

TC, external CJC mV Resistance, 2-wire Resistance, 3-wire

2X
RTD, 2- / 3-wire Resistance, 2-wire Resistance, 3-wire Resistance, 4-wire

TC, difference TC, difference


RTD, difference or average or average
Resistance, 4-wire or average with internal CJC with external CJC

2X
resistance, TC, 2-wire TC, 3-wire
2- / 3-wire TC, internal CJC external CJC external CJC

mV, difference
or average Output: 2-wire installation

2x TC, 2x TC,
internal CJC 2-wire CJC mV 2x mV

Potmeter Two 3-wire


Potmeter, 3-wire cabel compensation potmeters Connections with
two sensors can
be configured for
2 measurements,
difference, average,
or redundancy
STT17C Configuration tool
The STT17C configures the STT171, STT173 and STT17H. The intuitive graphical user interface of the STT17C virtually
eliminates the need for operator training after installation on a PC. The STT17C includes all software and transmitter interface
hardware necessary to configure the STT171, STT173 and STT17H in non-hazardous work environments.

WARNING: The STT17C is not approved for use in Hazardous work environments.

System Requirements:
Windows® 98SE, ME, 2000 and XP with the following recommendations:
Memory: 16 MB
Display resolution: 800 x 600
Hard disk space: 12 MB

Windows is a registered trademark of Microsoft Corporation


STT171-BS Specifications

o o
Temperature Effects per 1.0 C (1.8 F)
Sensor Basic Accuracy* Rated Range Change in Ambient Temperature***
o o
Type Fixed % of Span C F Standards Minimum Span** Fixed % of Span
o o o o o o
Pt100 0.3 C (0.54 F) ± 0.1 -200 to 850 -328 to 1562 IEC60751 25 C (45 F) 0.01 C (0.018 F) ±0.01
o o o o o o
Ni100 0.3 C (0.54 F) ± 0.1 -60 to 250 -76 to 482 DIN 43760 25 C (45 F) 0.01 C (0.018 F) ±0.01
 0.2  ± 0.1 0 to 10000  30  20 m ±0.01
*whichever is greater; Total Reference Accuracy = Basic Accuracy
**or 50% of upper range value, whichever is greater
*** reference temperature 24oC

OPERATING CONDITIONS APPROVALS


o o
Ambient temperature, rated……….………-40 to 85 C (-40 to 185 F) Observed Authority requirements: Standard:
Humidity………………………………………0 to 95% RH (non-cond.) EMC 2004/108/EC
Vibration…………………………………...…Max 4g over 25 to 100Hz Emmission and immunity ……… EN 61326
ATEX 94/9/EC…………………………………… EN 50014, EN 50020,
ELECTRICAL INPUT SPECIFICATIONS EN 50281-1-1 and EN 50284
Supply voltage………………………………8 to 30 VDC FM, ASCN……………………………………….. 3600, 3611, 3610
Power supply voltage effect……………….≤ 0.005% of span per VDC CSA, CAN / CSA…………………………………. C22.2 No. 157, E60079-11,
Warm-up time…………………………..…. 5 min UL 913
Response time (programmable)…………… 0.33 to 60 sec Ex / I.S. approval:
o o
KEMA 06 ATEX 0042 X…………………………… II 1 GD, T80 C…T105 C
CURRENT OUTPUT SPECIFICATIONS EEx ia IIC T4...T6
o
Signal output range…………………………4 to 20 mA Max. amb. Temperature for T4……………………85 C
o
Update time………………………………… 135 msec Max. amb. Temperature for T6……………………60 C
Load resistance………....……...……………≤(V supply - 8) / 0.023 A Applicable in zone………………………………. 0, 1, 2, 20, 21 or 22
0 to 870  FM, applicable in……………………………………IS, CL I, DIV 1, Grp. A-D, T4…T6
AEx ia IIC
ALARM LEVELS NI, CL I, DIV 2, Grp. A-D, T4…T6
Programmable…………………..…………… 3.5 to 4 mA downscale Entity, FM Installation Drawing No…………… 50016324
20 to 23 mA upscale CSA, applicable in………………………………. IS, CL I, DIV 1, Grp. A-D, T4…T6
NAMUR NE43 Upscale……………….……23 mA Ex ia IIC, AEx ia IIC
3.5 mA
NAMUR NE43 Downscale………………..… Entity, Installation Drawing No……………………50016326

Ex / I.S. data:
Ui (max)…………………………………………… 30 VDC
Ii (max)………………………………………………120 mADC
Pi (max)………………………………………………0.84 W
Li (max)…………………………………………… 10 H
Ci (max)…………………………………………… 1.0 nF

Uo (max)……………………………………………27 VDC
Io (max)…………………………………………… 7 mADC
Po (max)……………………………………………45 m W
Lo (max)……………………………………………35 mH
Co (max)……………………………………………90 nF
STT173-BS Specifications
STT17H-BS Specifications
STT17H-BN Specification
STT17F-BS Specifications

o o
Temperature Effects per 1.0 C (1.8 F)
Sensor Basic Accuracy* Rated Range Change in Ambient Temperature**
o o
Type Fixed % of reading C F Standards Fixed % of reading
o o o o
Pt100 0.2 C (0.36 F) ± 0.1 -200 to +850 -328 to +1562 IEC60751 0.01 C (0.018 F) ±0.01
o o o o
Pt1000 0.2 C (0.36 F) ± 0.1 -200 to +850 -328 to +1562 IEC60751 0.01 C (0.018 F) ±0.01
o o o o
Ni100 0.3 C (0.54 F) ± 0.1 -60 to +250 -76 to +482 DIN 43760 0.01 C (0.018 F) ±0.01
o o o o
Cu10 1.3 C (2.3 F) ± 0.1 -50 to +200 -58 to +392 = 0.00427 0.02 C (0.036 F) ±0.01
o o o o
B 1 C (1.8 F) ± 0.1 +400 to +1820 +752 to +3308 IEC584 0.2 C (0.36 F) ±0.01
o o o o
E 0.5 C (0.9 F) ± 0.1 -100 to +1000 -148 to +1832 IEC584 0.05 C (0.09 F) ±0.01
o o o o
J 0.5 C (0.9 F) ± 0.1 -100 to +1200 -148 to +2192 IEC584 0.05 C (0.09 F) ±0.01
o o o o
K 0.5 C (0.9 F) ± 0.1 -180 to +1372 -192 to +2502 IEC584 0.05 C (0.09 F) ±0.01
o o o o
L 0.5 C (0.9 F) ± 0.1 -200 to +900 -328 to +1652 DIN 43710 0.05 C (0.09 F) ±0.01
o o o o
N 0.5 C (0.9 F) ± 0.1 -180 to +1300 -292 to +2372 IEC584 0.05 C (0.09 F) ±0.01
o o o o
R 1 C (1.8 F) ± 0.1 -50 to +1760 -58 to +3200 IEC584 0.2 C (0.36 F) ±0.01
o o o o
S 1 C (1.8 F) ± 0.1 -50 to +1760 -58 to +3200 IEC584 0.2 C (0.36 F) ±0.01
o o o o
T 0.5 C (0.9 F) ± 0.1 -200 to +400 -328 to +752 IEC584 0.05 C (0.09 F) ±0.01
o o o o
U 0.5 C (0.9 F) ± 0.1 -200 to +600 -328 to +1112 DIN 43710 0.05 C (0.09 F) ±0.01
o o o o
W3 1 C (1.8 F) ± 0.1 0 to +2300 +32 to +4172 ASTM E988-90 0.2 C (0.36 F) ±0.01
o o o o
W5 1 C (1.8 F) ± 0.1 0 to +2300 +32 to +4172 ASTM E988-90 0.2 C (0.36 F) ±0.01
 0.05  ± 0.1 0 to 10000  2 m ±0.01
mV 10 V ± 0.1 -800 to 800 mV 0.2 V ±0.01
*whichever is greater; Total Reference Accuracy = Basic Accuracy + CJ Accuracy (T/C only)
** reference temperature 24oC

OPERATING CONDITIONS APPROVALS


o o
Ambient temperature, rated…………...………-40 to 85 C (-40 to 185 F) Observed Authority requirements: Standard:
Humidity…………………………………………0 to 95% RH (non-cond.) EMC 2004/108/EC
Vibration…………………………………...……Max 4g over 25 to 100Hz Emmission and immunity EN 61326
Cold junction accuracy………......……………±0.5oC ATEX 94/9/EC……………………………EN 50014, EN 50020,
EN 50281-1-1, EN 50284,
ELECTRICAL INPUT SPECIFICATIONS and IEC 60079-27 (FISCO)
Supply Voltage…………………………………9 to 30 VDC FM, ASCN…………………………………3600, 3611, 3610
In FISCO installations………………………9 to 17.5 VDC CSA, CAN / CSA…………………………C22.2 No. 142, No. 157
Consumption……………………………………< 11 mA CAN / CSA………………………………… E60079-0, E60079-11,
Warm-up time…………………………..………30 sec E60079-15, UL913, UL1604
Response time (programmable)……………… 1 to 60 sec
Galvanic isolation………………………………1500 VAC Ex / I.S. approval:
o o
Update time………………………………….. < 400 msec KEMA 06 ATEX 0046……………..…… II 1 GD, T65 C…T105 C
Execution time, PID controller………………. < 200 msec EEx ia IIC T4…T6
Execution time, analogue input………………< 50 msec Ex II 2(1) GD, T65oC…T105oC
EEx ib [ia] IIC T4…T6
OUTPUT SPECIFICATIONS Applicable in zone………………………… 0, 1, 2, 20, 21 or 22
FoundationTM Fieldbus connection: FM, applicable in…………………………IS, CL I, DIV 1, Grp. A-D, T4…T6
TM
Foundation Fieldbus version…………….. ITK 4.6 AEx ia IIC
TM
Foundation F. capability……………………Basic or LAS NI, CL I, DIV 2, Grp. A-D, T4…T6
TM
Foundation F. function blocks……………. 2 analogue and 1 PID Entity, FM Installation Drawing No………50016325
CSA, applicable in……………………… IS, CL I, DIV 1, Grp. A-D, T4…T6
Ex ia IIC, AEx ia IIC
CL I, DIV 2, Grp. A-D, T4…T6
Entity, CSA Installation Drawing No……50016325

Ex / I.S. data: Ex / I.S. data:


Class I, Zone 0, EEx ia IIC, Entity/FISCO Class I, Zone 1, EEx ib IIC, Entity/FISCO
IS, Class I, Division 1, Group A, B, C, D, Entity/FISCO IS, Class I, Division 2, Group A, B, C, D, Entity/FISCO
Barrier where Barrier where Suitable for Suitable for Unit Barrier where Po < 5.32 W FISCO segment coupler
Unit Po < 0.84 W Po < 1.3 W FISCO systems FISCO systems Ui 30 VDC 17.5 VDC
Ui 30 VDC 30 VDC 17.5 VDC 15 VDC Ii 250 mADC All
Ii 120 mADC 300 mADC 250 mADC 900 mADC Pi 5.32 W All
Pi 0.84 W 1.3 W 2.0 W 5.32 W Li 1 H 1 H
Li 1 H 1 H 1 H 1 H Ci 2.0 nF 2.0 nF
o o
Ci 2.0 nF 2.0 nF 2.0 nF 2.0 nF T1…T4 Tamb. < 85 C Tamb. < 85 C
o o o o o o
T1…T4 Tamb. < 85 C Tamb. < 75 C Tamb. < 85 C Tamb. < 85 C T5 Tamb. < 75 C Tamb. < 75 C
o o o o o o
T5 Tamb. < 70 C Tamb. < 65 C Tamb. < 60 C Tamb. < 60 C T6 Tamb. < 60 C Tamb. < 60 C
o o o o
T6 Tamb. < 60 C Tamb. < 45 C Tamb. < 45 C Tamb. < 45 C
STT17F-BN Specifications

o o
Temperature Effects per 1.0 C (1.8 F)
Sensor Basic Accuracy* Rated Range Change in Ambient Temperature**
o o
Type Fixed % of reading C F Standards Fixed % of reading
o o o o
Pt100 0.2 C (0.36 F) ± 0.1 -200 to +850 -328 to +1562 IEC60751 0.01 C (0.018 F) ±0.01
o o o o
Pt1000 0.2 C (0.36 F) ± 0.1 -200 to +850 -328 to +1562 IEC60751 0.01 C (0.018 F) ±0.01
o o o o
Ni100 0.3 C (0.54 F) ± 0.1 -60 to +250 -76 to +482 DIN 43760 0.01 C (0.018 F) ±0.01
o o o o
Cu10 1.3 C (2.3 F) ± 0.1 -50 to +200 -58 to +392 = 0.00427 0.02 C (0.036 F) ±0.01
o o o o
B 1 C (1.8 F) ± 0.1 +400 to +1820 +752 to +3308 IEC584 0.2 C (0.36 F) ±0.01
o o o o
E 0.5 C (0.9 F) ± 0.1 -100 to +1000 -148 to +1832 IEC584 0.05 C (0.09 F) ±0.01
o o o o
J 0.5 C (0.9 F) ± 0.1 -100 to +1200 -148 to +2192 IEC584 0.05 C (0.09 F) ±0.01
o o o o
K 0.5 C (0.9 F) ± 0.1 -180 to +1372 -192 to +2502 IEC584 0.05 C (0.09 F) ±0.01
o o o o
L 0.5 C (0.9 F) ± 0.1 -200 to +900 -328 to +1652 DIN 43710 0.05 C (0.09 F) ±0.01
o o o o
N 0.5 C (0.9 F) ± 0.1 -180 to +1300 -292 to +2372 IEC584 0.05 C (0.09 F) ±0.01
o o o o
R 1 C (1.8 F) ± 0.1 -50 to +1760 -58 to +3200 IEC584 0.2 C (0.36 F) ±0.01
o o o o
S 1 C (1.8 F) ± 0.1 -50 to +1760 -58 to +3200 IEC584 0.2 C (0.36 F) ±0.01
o o o o
T 0.5 C (0.9 F) ± 0.1 -200 to +400 -328 to +752 IEC584 0.05 C (0.09 F) ±0.01
o o o o
U 0.5 C (0.9 F) ± 0.1 -200 to +600 -328 to +1112 DIN 43710 0.05 C (0.09 F) ±0.01
o o o o
W3 1 C (1.8 F) ± 0.1 0 to +2300 +32 to +4172 ASTM E988-90 0.2 C (0.36 F) ±0.01
o o o o
W5 1 C (1.8 F) ± 0.1 0 to +2300 +32 to +4172 ASTM E988-90 0.2 C (0.36 F) ±0.01
 0.05  ± 0.1 0 to 10000  2 m ±0.01
mV 10 V ± 0.1 -800 to 800 mV 0.2 V ±0.01
*whichever is greater; Total Reference Accuracy = Basic Accuracy + CJ Accuracy (T/C only)
** reference temperature 24oC

OPERATING CONDITIONS APPROVALS


o o
Ambient temperature, rated…………...………-40 to 85 C (-40 to 185 F) Observed Authority requirements: Standard:
Humidity…………………………………………0 to 95% RH (non-cond.) EMC 2004/108/EC
Vibration…………………………………...……Max 4g over 25 to 100Hz Emmission and immunity EN 61326
o
Cold junction accuracy………......……………±0.5 C ATEX 94/9/EC……………………………EN 60079-0, EN 60079-15
o
Reference temperature……………………… 20 to 28 C FM, ASCN…………………………………3600, 3611
CSA, CAN / CSA…………………………C22.2 No. 142, No. 213
ELECTRICAL INPUT SPECIFICATIONS CAN / CSA…………………………………E60079-0, E60079-15,
Supply Voltage…………………………………9 to 32 VDC UL1604
Consumption……………………………………< 11 mA Ex / I.S. approval:
Warm-up time…………………………..………30 sec KEMA 06 ATEX 0045 X……………..… II 3 G
Response time (programmable)………………1 to 60 sec EEx nA [L] IIC T4…T6
Galvanic isolation………………………………1500 VAC Applicable in zone………………………… 2
Update time………………………………….. < 400 msec FM, applicable in…………………………NI, CL I, DIV 2, Grp. A-D, T4…T6
Execution time, PID controller……………….< 200 msec FNICO
Execution time, analogue input………………< 50 msec Entity, FM Installation Drawing No………50016325
CSA, applicable in……………………… CL I, DIV 2, Grp. A-D, T4…T6
OUTPUT SPECIFICATIONS CL I, Zone 2,
FoundationTM Fieldbus connection: Ex nA IIC, AEx nA IIC
TM
Foundation Fieldbus version…………….. ITK 4.6 Entity, CSA, Installation Drawing No……50016325
TM o
Foundation F. capability……………………Basic or LAS Max. amb. Temperature for T4…………85 C
TM o
Foundation F. function blocks……………. 2 analogue and 1 PID Max. amb. Temperature for T6…………60 C

Vmax………………………………………32V
Li……………………………………………1 H
Ci……………………………………………2.0 nF
STT171 Custom Configuration Data Sheet

Customer P.O. Number __________________________________________________________


Line Item _____________________________________________________________________
Model Number ________________________________________________________________
Tag Number (max 15 char) _______________________________________________________
Honeywell Sales Order Number ___________________________________________________

Sensor Type:
□ Pt100
□ Ni100
□ Ohms

Output Values:
4 mA Value: 20 mA Value: Response time:
o o
□ __________ C □ __________ C _______ (0.33 – 60 sec)
o o
□ __________ F □ __________ F
□ __________ Ohms □ __________ Ohms

Output Limits:
□ Span (4 to 20 mA)
□ Max (3.5 to 23 mA)
□ Specify Low ______ mA, High _____ mA
□ NAMUR NE 43 (3.8 to 20.5 mA)

Sensor Error Action:


□ Off
□ Specify _____ mA
□ NAMUR NE 43 upscale (23 mA)
□ NAMUR NE 43 downscale (3.5 mA)
STT173 Custom Configuration Data Sheet

Customer P.O. Number __________________________________________________________


Line Item _____________________________________________________________________
Model Number ________________________________________________________________
Tag Number (max 15 char) _______________________________________________________
Honeywell Sales Order Number ___________________________________________________

Sensor Type:

□ Pt100 □ Type B T/C Cold Junction Compensation:


□ Ni100 □ Type E T/C □ Internal
□ Type J T/C □ External / Pt100
Wiring: □ Type K T/C □ External / Ni100
□ 2-wire □ Type L T/C
□ 3-wire □ Type N T/C
□ 4-wire □ Type R T/C
□ Type S T/C
□ Ohms □ Type T T/C
□ mV □ Type U T/C
□ Type W3 T/C
□ Type W5 T/C

Output Values:
4 mA Value: 20 mA Value: Response time:
o o
□ __________ C □ __________ C _______ (1 – 60 sec)
o o
□ __________ F □ __________
□ __________ mV □ __________ mV
□ __________ Ohms □ __________ Ohms

Output Limits:
□ Span (4 to 20 mA)
□ Max (3.5 to 23 mA)
□ Specify Low ______ mA, High _____ mA
□ NAMUR NE 43 (3.8 to 20.5 mA)

Sensor Error Action:


□ Off
□ Specify _____ mA
□ NAMUR NE 43 upscale (23 mA)
□ NAMUR NE 43 downscale (3.5 mA)
STT17H Custom Configuration Data Sheet

Customer P.O. Number __________________________________________________________


Line Item _____________________________________________________________________
Model Number ________________________________________________________________
Tag Number (max 15 char) _______________________________________________________
Honeywell Sales Order Number ___________________________________________________

Sensor Input:
□ Single Sensor
□ Duplex Sensor (Average)
□ Duplex Sensor (Differential)

Sensor Type:

□ Pt100 □ Type B T/C Cold Junction Compensation:


□ Ni100 □ Type E T/C □ Internal
□ Type J T/C □ External / Pt100
Wiring: □ Type K T/C □ External / Ni100
□ 2-wire □ Type L T/C
□ 3-wire □ Type N T/C
□ 4-wire □ Type R T/C
□ Type S T/C
□ Ohms □ Type T T/C
□ mV □ Type U T/C
□ Type W3 T/C
□ Type W5 T/C

Output Values:
4 mA Value: 20 mA Value: Response time:
o o
□ __________ C □ __________ C _______ (1 – 60 sec)
o o
□ __________ F □ __________
□ __________ mV □ __________ mV
□ __________ Ohms □ __________ Ohms

Output Limits:
□ Span (4 to 20 mA)
□ Max (3.5 to 23 mA)
□ Specify Low ______ mA, High _____ mA
□ NAMUR NE 43 (3.8 to 20.5 mA)

Sensor Error Action:


□ Off
□ Specify _____ mA
□ NAMUR NE 43 upscale (23 mA)
□ NAMUR NE 43 downscale (3.5 mA)
STTF Custom Configuration Data Sheet

Customer P.O. Number __________________________________________________________


Line Item _____________________________________________________________________
Model Number ________________________________________________________________
Tag Number (max 15 char) _______________________________________________________
Honeywell Sales Order Number ___________________________________________________

TRANSDUCER BLOCK PARAMETERS

Temperature Units Sensor Input


o
□ C □ Single Sensor
o
□ F □ Duplex Sensor (Average)
□ mV □ Duplex Sensor (Differential #1 - #2)
□ Ohms

Sensor Type (Sensor 1, Sensor 2)::

□ Pt100 □ Type B T/C Cold Junction Compensation:


□ Ni100 □ Type E T/C □ Internal
□ Pt500 □ Type J T/C □ External / Pt100 2-w
□ Ni100 □ Type L T/C □ External / Ni100 3-w
□ Cu10 □ Type N T/C
□ Type R T/C
Wiring: □ Type S T/C
□ 2-wire □ Type T T/C
□ 3-wire □ Type U T/C
□ 4-wire □ Type W3 T/C
□ Type W5 T/C
□ Ohms
□ mV

Sensor Error Detection:


Sensor #1
□ Lead breakage and short circuit detection disable
□ Lead breakage and short circuit enable
□ Lead breakage detection enable, short circuit detection disable
□ Lead breakage detection disable, short circuit detection enable

Sensor #2
□ Lead breakage and short circuit detection disable
□ Lead breakage and short circuit enable
□ Lead breakage detection enable, short circuit detection disable
□ Lead breakage detection disable, short circuit detection enable
Model Selection Guide (34-44-16-07)
Model Selection Guides are subject to change and are inserted into the specifications as guidance only.
Prior to specifying or ordering a model check for the latest revision Model Selection Guides which are published at:
http://hpsweb.honeywell.com/Cultures/en-US/Products/Instrumentation/ProductModelSelectionGuides/default.htm

34-44-16U-07
Issue 13
Page 1 of 2

STT 3000 Temperature Transmitter Model Selection


Series STT170 Guide

Instructions
 Choose Availability column based on Key Number.
 A dot ( ) denotes unrestricted availability.
 Select the desired Key Number based on the
desired communications protocol.
 Select options and approvals from Tables.

Key Number I II III IV V VI, options


STT17_ - __ - _ - ___ - ___ - ___ - __,__

Key Number
Description Selection Availability
4-20mA Output, RTD input STT171
4-20mA Output, universal input STT173
HART Protocol, 4-20mA output STT17H
Digital output, Foundation Fieldbus protocol STT17F
Configuration tool for STT171, 173 and 17H STT17C

Table I - Safety Approvals


Approval
Approval Type Location or Classification
Body
None No approval body certifications included 00     
Intrinsically Safe Class I, Div. 1, Groups A,B,C,D, T4
ENTITY Class I, Zone 0/1; AEx ia IIC, T4
Non-Incendive Class I, Div. 2, Groups A,B,C,D, T4
Intrinsically Safe Class I, Div. 2, Groups A,B,C,D, T4
FM,
ENTITY Class I, Zone 0/1; Ex ia IIC, T4
BS    
CSA,
Non-Incendive Class I, Div. 2, Groups A,B,C,D, T4
ATEX
* Intrinsically Safe Ex II 1 GD, EEx ia IIC, T4..T6
Zone 0/1 Ex II 2 (1) GD, T4..T6
Non-Incendive Class I, Div. 2, Groups A,B,C,D, T4
Zone 2 Ex II 3 G, EEx nA [L] T4..T6
BN  
When installed in Field Mount Enclosure Table IV, E _ _, or T _ _
Intrinsically Safe Class I, Div. 1, Groups A,B,C,D, T4
FM
ENTITY Class I, Zone 0/1; AEx ia IIC, T4 1G e e e e
Approval
Non-Incendive Class I, Div. 2, Groups A,B,C,D, T4
Intrinsically Safe Class I, Div. 2, Groups A,B,C,D, T4
CSA ENTITY Class I, Zone 0/1; Ex ia IIC, T4 2G e e e e
Non-Incendive Class I, Div. 2, Groups A,B,C,D, T4
* Intrinsically Safe Ex II 1 GD, EEx ia IIC, T4..T6
3S e e e
Zone 0/1 Ex II 2 (1) GD, T4..T6
ATEX
Non-Incendive Class I, Div. 2, Groups A,B,C,D, T4 3N e
Zone 2 Ex II 3 G, EEx nA [L] T4..T6

* Ex II GD or II 2 (1) GD allows for installation in potentially explosive atmospheres caused by the presence of combustible dusts
only when mounted in a m etal enclosure of form B according to DIN 43729 (Head-Mount enclosure) that provides a degree of
protection of at least IP 6X in accordance with EN 60529, that is suitable for the application and is correctly installed.

TABLE II - No Option
No Option 0     
TABLE III - Configuration & Certificates
Configuration
None - Factory Default Configuration Supplied 0__     
Custom Transmitter Configuration with Printed Report ** T__    
Calibration Custom Transmitter Calibration with Printed Report ** C__   
Optional
No Option _0_     
Certificates
No Certificate of Conformance/Origin __0    
Certificate of Conformance/Origin __R    
Model Selection Guide, (34-44-16-07) cont.

Availability
STT17 _
Selection 1 3 H F C
TABLE IV - Transmitter Housing and Integral Meters (Reference EN0I-6032 for details)
No Housing Supplied 0__     
Housing Field Aluminum with Beige Epoxy Coating E__ d d d d
Mount 316 Stainless Steel T__ d d d d
Head Mt Type 4X housing - Beige C__ g g g g
Cable/ Not Applicable - No Housing Supplied _0_     
Conduit 1/2" NPT Cable/ Conduit Entry _N_    
Entry M20 x 1.5 Cable/ Conduit Entry _M_    
Integral No Integral Meter Supplied __0     
Meter E.U. Meter for Field Mount Housing __E h h h

TABLE V - Optional Equipment


No mounting bracket 0_ _     
Carbon steel pipe mounting bracket for 2" pipe M_ _ e e e e
Mounting Stainless Steel mounting bracket for 2" pipe S_ _ e e e e
Spring loading mounting set L_ _ f f f f
DIN rail mounting clip (top hat or G rail) D_ _ f f f f
No adaptors required _0_     
M20 adaptors 1 adaptor for M20 x 1.5 wiring entry _1_    
2 adaptors for M20 x 1.5 wiring entry _2_    
3/4"NPT adaptors 1 adaptor for 3/4"NPT wiring entry _3_    
Lightning
No lightning protection supplied __0     
Protection
Externally Mountable to Field Mount Housing __L    
Internal lightning protection __S    
TABLE VI - Additional Features
No Selection 00     
Optional Extended
Warranty
Additional Warranty - 1 year W1    
Customer
316 SS Wired-on Customer I.D. Tag (4 lines, 28 chars. TG    
per line, customer specified information) b
Tagging
316 SS Wired-on Customer I.D. Tag (blank) TB    
STT171 Version; English, French, German Language M1 
Operator's Manual
STT173 Version; English, French, German Language M3 
STT17H Version; English, French, German Language MH 
STT17F Version; English, French, German Language MF 
RESTRICTIONS
Restriction Available Only With Not Available With
Letters Table Selection Table Selection
b VI Select only one option from this group
d IV _N _
e IV E _ _, or T _ _
f IV 0_ _
g IV _0E
I 00
h
IV E _ _, or T _ _

ACCESSORIES Part Number


DIN rail clip 50017850-001    
** If Custom Configuration option "T" or the Custom Calibration option "C" is ordered, the configuration or calibration
information required must me be entered as a note on the order. Any of the following elements can be included, based on the
selected model number:
(STT171, STT173, STT17H) Tag Number, CJC, Sensor Type, Sensor Wiring, Temperature Units, URV/LRV, Output Range, Output
Limits, Sensor Error Action, Response Time.
(STT17F) Tag Number, Sensor Type, URV/LRV, Burnout- High or Low, Response Time

Ordering Example: STT17H-BN-0-000-EN0-000-00


Sales and Service
For application assistance, current specifications, pricing, or name of the nearest Authorized Distributor, contact one
of the offices below.

ASIA PACIFIC EMEA AMERICA’S


Honeywell Process Solutions, Honeywell Process Solutions, Honeywell Process Solutions,
(TAC) hfs-tac- Phone: + 80012026455 or Phone: (TAC) 1-800-423-9883 or
support@honeywell.com +44 (0)1344 656000 215/641-3610
(Sales) 1-800-343-0228
Australia
Honeywell Limited Email: (Sales)
Phone: +(61) 7-3846 1255 FP-Sales-Apps@Honeywell.com Email: (Sales)
FAX: +(61) 7-3840 6481
or FP-Sales-Apps@Honeywell.com
Toll Free 1300-36-39-36
Toll Free Fax: (TAC) or
1300-36-04-70 hfs-tac-support@honeywell.com (TAC)
China – PRC - Shanghai hfs-tac-support@honeywell.com
Honeywell China Inc.
Phone: (86-21) 5257-4568
Fax: (86-21) 6237-2826

Singapore
Honeywell Pte Ltd.
Phone: +(65) 6580 3278
Fax: +(65) 6445-3033

South Korea
Honeywell Korea Co Ltd
Phone: +(822) 799 6114
Fax: +(822) 792 9015
For more information
To learn more about Temperature Transmitters,
visit www.honeywellprocess.com
Or contact your Honeywell Account Manager

Process Solutions
Honeywell
1250 W Sam Houston Pkwy S
Houston, TX 77042

Honeywell Control Systems Ltd


Honeywell House, Skimped Hill Lane
Bracknell, England, RG12 1EB

Shanghai City Centre, 100 Jungi Road


Shanghai, China 20061
34-TT-03-07
August 2014
www.honeywellprocess.com 2014 Honeywell International Inc.