1. Scope of the Delivery


This document contains release notes for the major release of S1 Agile V1.4.1 (Build 012 – 18.9.10.0).

2. Purpose of the Release


The purpose of this installer is to incorporate enhancements and defect fixes on S1 Agile 1.4 (Official Internal
Release). It also includes the changes related to Hotfix 1 for S1 Agile 1.3.1 (Last Official Release). The
enhancements and the defects fixed on this release are listed in MaFS Document.

Enhancements:
 5834 - GE re-branding on MiCOM S1 Agile Backend Access Tool v1.3 (Not part of S1 Agile)
 5828 - Concurrent Protocol implementation with DNP3oE and IEC 61850 for P40 Agile
 5826 - Installation and Uninstallation Issues on S1 Agile 1.4 - B007
 5825 - Fault Locator Issues on V1.0 (S1 Agile 1.4 - B007)
 5816 - MAC address filtering for REB Configurator
 5770 - GS-01408169 Can S1 be packaged?
 5844 - Rename REB Configurator as Redundant Ethernet Configurator
 5843 - Fault Locator Issues on V1.0 (S1 Agile 1.4.1 - B011)
 5842 - Fault Locator Issues on V1.0 (S1 Agile 1.4.1 - B009)

Bug fixes: (Mingle)


 5835 - MiCOM S1 Agile is crashing, when we load corrupted DNP Files
 5829 - USB Flag setting to ignore HW Serial Number in earlier versions of Windows 10.
 5795 - Settings file comparison failing to detect changed settings
 5794 - P40 Agile text editor doesn’t allow downloading languages apart from language 1 to Px4x relays
 5412 - When a PSL file is saved as group 4, it comes back up as group 0 when attempting to Save as
 5247 - "Copy" button doesn't copy anything
 4891 - The Psl editor cannot send the big psl to the P141 relay

Confidential Page 1 of 20
 4679 - Help button in New Default Scheme window is not working

Confidential Page 2 of 20
The following defects are also included in this release as a part of Hotfix 1 on S1 Agile 1.3.1.

 5797 - If Root LD name is edited, the modification is not seen in all placed when SCL is exported
 5796 - IED configurator fails to save the MAC address in the subscription menu
 5777 - Schema error while exporting CID from IED configurator

3. Intended End user:


GE and all stakeholders associated with Px40 relays.

4. Release Details

Phase of Type of Release


Project Code 68700/25 Date 10-09-2018
Release (Initial / Incremental / Defect fix)

Project Name S1 Agile V1.4.1 Development Incremental


Validation of
Release ID - Incremental
S1 Agile Tool

5. Package Contents

 Source  Unit Test Plan/  System Test Plan/  Others – Installer for
 SRS  HLD/LLD
Code Test Report System Test Record 32 and 64-Bit platforms
DLL, EXE,
HTML, PDF,
File
DOC, TXT,  Others (Specify): None
Format
CHM and
Images

Confidential Page 3 of 20
6. SW Environment
Operating System: Microsoft Windows 7, 8.1 and 10
Platform: 32Bit/64 Bit

7. References
 Marketing and Functional Specification for S1 Agile 1.4.1 Project
 GE Rebranding Guideline document.

8. Directory Structure
Source (SVN): http://svn.gs.ec.ge.com/sasprod/spd-s1-agile-dev/dev , Rev 310 (Build 012 - 18.9.10.0)
Files: MiCOM S1 Agile Installer B012.zip (MiCOM S1 Agile Installer B012.exe,
ReleaseNotes_S1AgileV1.4.1_B012.docx & MiCOM_S1_Agile_Installer_B012.iss)
Installer Path: GE Box – https://ge.ent.box.com/folder/50890317248
Installation Path: <Program Files>\GE\MiCOM S1 Agile

9. Deliverables Details
Change Description
Deliverable Versi
SN Description (Defect ID / MR ID Remarks
(File Name) on
etc.)
MiCOM S1 Agile Installer Setup files used to install
1 1.4.1 Refer MaFS Document None.
B012.exe the tool.
Recorded Setup file for
MiCOM_S1_Agile_Installer_B012.i
2 Silent-mode installation (IT 1.4.1 Mingle Card 5770 None.
ss
Support)
ReleaseNotes_S1AgileV1.4.1_B0
3 Information for the release - - None.
12.docx

Confidential Page 4 of 20
Confidential Page 5 of 20
10. List of Known Defects
SN Deliverable Defe Defect Description Defect Severi Remarks
ct ID Type ty
- - - - - - -

11. List of Open Items, issues and limitations of the release:

SN Issue/Limitation Description Remarks

This is due to GE re-branding is performed on registry,


program files and data folders. Also, S1 Agile 1.3.1 or
S1 Agile 1.3.1 or older versions needs to
older versions cannot be directly upgraded to S1 Agile
1 be uninstalled manually, prior to
1.4 or newer versions, due to the re-branding updates.
installing S1 Agile 1.4 or newer versions.
However, S1 Agile 1.4 version can be upgraded to S1
Agile 1.4.1.
By default, certificate (UK Grid Solutions
2 Ltd) needs to be added as trusted
publisher.
During the incomplete installation (either
aborted by user or administrative
It’s an improvement and observed in S1 Agile 1.3.1 as
3 privilege issues), the finish window is not
well.
closing, after reverting the partially
installed tools.
These tools are from Reason and may need updates
Sometimes, the uninstallation is struck at
4 related to re-branding changes in registry/deployment
RPV Support Tool or MU320 configurator. features.
5 Fault locator has technical limitations and

Confidential Page 6 of 20
SN Issue/Limitation Description Remarks

are clearly explained in user manual.


Refer the Fault Locator help document
for more information.

Confidential Page 7 of 20
12. Installation requirements
Requirements

Operating System: Microsoft Windows 7, 8.1 and 10


Pre-Installation:
(1) Uninstall the existing MiCOM S1 Agile 1.3.1 and Hot fix 1 for V1.3.1 manually and Make sure the files are totally
removed from Installation Folder (...\Alstom Grid\Micom S1 Agile), if any. While performing 1.4.1 installation, the
setup will abort the installer, if the previous version is detected as 1.3.1 or older.
For S1 Agile 1.3.1 or older versions, the installation will be aborted with following message: S1 Agile 1.3.1 or
older version is already installed on the system.\nPlease uninstall it and run setup again.
(2) If S1 Agile 1.4 version is installed, the user can repair the installation with this version of S1 Agile Installer 1.4.1.
Post Installation: Manual restart is necessary to complete the installtion.

Installation
a. Make sure the requirements are satisfied.
b. Uninstall the previous version of S1 Agile, if any. This is a recommended step, refer Pre-Installation for more
information.
c. Run the installer (MiCOM S1 Agile Installer B012.exe) with admin privileges.
Note: Right click the SETUP and run the same as administrator.
d. Trust the publisher “UK Grid Solutions Limited” to proceed further.
e. Select the Language for installtion from Chinese (Simplified), English (US), French (Standard), German, Italian, Polish,
Portuguese (Brazilian), Russian and Spanish.

Confidential Page 8 of 20
Confidential Page 9 of 20
f. Click “Next” in the welcome window.

g. Accept the Terms of Agreement and click “Next” in the License/information window.

Confidential Page 10 of 20
h. Select the Mode of installation from this window.
a. Express Mode: Default programs, features and language (English) will be installed.
b. Custom Mode: User can select additional languages and is recommended for advanced users.
Note: If the express mode of installtion is selected, the installation directly goto Review Window (Step m).

i. Provide User and Organization name in the next window and click “Next”.

Confidential Page 11 of 20
j. Click “Next” in the Installer Path window, if you are fine with default path i.e ...\GE\MiCOM S1 Agile, Else browse the
path by clicking “Change”.

k. Select the tools and Language from the options window.

Confidential Page 12 of 20
Confidential Page 13 of 20
l. User Group setup window appears with current user details.
a. Add/Remove users to “MiCOM S1 Agile Users” group, if necessary.
b. This can also be managed through “Local Users and Group” in future.

m. Click “Next” on the review window, if you are fine with changes of installation. Note: If the express mode of installtion
is selected, the installation directly goto Finish Window (Step p) and Installation may take a 10-15 minutes.

Confidential Page 14 of 20
n. Create shortcut using Additional Options window.

o. Migrate all the existing System (*.agsys) and Datamodels from Alstom Folders (..\Documents\AG S1 Agile and
..\ProgramData\Alstom Grid\MiCOM S1 Agile\DataModels), if S1 Agile 1.3.1 or older version is uninstalled.
Note: This step is disabled, if there are no System (*.agsys) and Datamodels exist in Alstom Folders.

Confidential Page 15 of 20
p. Close the setup by clicking “Finish”.

q. Verify that the new version of S1 Agile or its associated tools is present in the Installation Folder, after the restart.
Note: Manual restart is necessary to complete the installation.

Silent Mode Installation (For IT)


To support IT to install the S1 Agile in silent mode or background, the ISS file is created and attched in the
deliverables.
a. Open the Command Prompt with administrator priveleges.
b. Issue the command <“Setup.exe” /s /f1Setup.iss> in command prompt as follows:

Command Prompt>“MiCOM S1 Agile Installer B012.exe” /s /f1MiCOM_S1_Agile_Installer_B012.iss

Note 1: Pre-Installation requirements are applicable this mode of installation as well.


Note 2: Provide full path for both EXE and ISS Files in the above command.
Note 3: There should be no space left in between /f1 and path of *.iss file.
Note 4. After successful installation, user need to perform a manual restart of PC to ensure proper functionality of
S1 Agile.

Confidential Page 16 of 20
Uninstallation
a. Run the installer (MiCOM S1 Agile Installer B012.exe) with admin privileges.
b. Select “Remove” to uninstall the feature and click “Next” to proceed with re-installation.
Note: Uninstallation may take a 10-15 Minutes.
c. Verify that the files are totally removed from Installation Folder: ...\GE\MiCOM S1 Agile
d. Close the window.

Maintenance or Upgrade
(Only applicable to S1 Agile 1.4 onwards)
a. Run the installer (MiCOM S1 Agile Installer B012.exe) with admin privileges.
b. Select either “Repair” or “Modify” from the next window.
a. Modify: Customize the installation by adding or removing the features and click “Next” on the review window, if
you are fine with changes of installation.
b. Repair: Re-install all the features and whole installation and click “Next” to proceed with re-installation.
Note: Repairing may take a 10-15 MInutes.

c. Close the window by clicking “Finish”.

Confidential Page 17 of 20
d. Verify that the new version of S1 Agile or its associated tools is present in the Installation Folder.
Note: Manual restart is necessary to complete the installation.

Troubleshooting
a. Perform Clean installation of S1 Agile 1.4 or newer by uninstalling older versions of S1 Agile 1.3.1 or older.
b. For S1 Agile 1.3.1 or older, manually delete the files from Installation Folder (...\Alstom Grid\ MiCOM S1 Agile OR ...\GE\
MiCOM S1 Agile), if any failure occurs, before the next attempt.
c. Any issues in installation, uninstallation and repairing, may be due to privileges. So, make sure the SETUP was run with
admin privileges.
d. If either installation or uninstllation fails, kill the following process and clean the Installation Folder (...\Alstom Grid\
MiCOM S1 Agile OR ...\GE\ MiCOM S1 Agile).
a. MiCOM S1 Agile Installer BXXX (Description: Neo)
b. Setup.exe (Description: Neo)
c. ISBEW64 (Description: Installshield (R) 64 Bit Setup Engine)
d. Any MSI Installer (msiexec.exe)
e. From S1 Agile 1.4 onwards, upgrade is compatible with S1 Agile 1.4.1 or newer versions. This is not possible with S1
Agile 1.3.1 or older versions.

Contact:
Mail: Contact.centre@ge.com

Confidential Page 18 of 20
Website: www.gegridsolutions.com
Call: +44 1785 250070

Confidential Page 19 of 20
13. Details of internal reviews

Internal Reviewer Kajahusain A Peer Reviewer Haresh Joshi

Date 10-09-2018 Date 10-09-2018


Link for review Link for review
- -
report report
Remarks None Remarks None

14. Approvals (Not Applicable as Interim Release)


Project Quality
Functional
Tech Lead Kajahusain A Haresh Joshi Analyst / Release -
Lead Coordinator

Signature - Signature - -

Date 10-09-2018 Date 10-09-2018 Date -


Link for review
- - -
report
Remarks None Remarks None Remarks -

Confidential Page 20 of 20

Potrebbero piacerti anche