Sei sulla pagina 1di 16

GPMM Tomasz Komalski 2009

Indoor Switches
OEM Presentation

© ABB Group
April 29, 2009 | Slide 1
Indoor Switches
Complete offer
ADNN

NAL / NALF VersaRupter C3 / C4

OJON

Airswitch

SFG SHS2
OWIII

© ABB Group
April 29, 2009 | Slide 2
Indoor Switches
SFG & SHS2 Basic Technical Data

SHS2 SFG
Dimensions [mm]
Pole distance 230 210
SFG Top Unit
Width* 360 375 375, 500
Height 650 383 604
Depth* 705 818 983
Enclosure material Stainless steel Epoxy cast resin
Inspection window NO YES, 2
Insulating medium SF6 SF6
SF6 gas pressure 125 kPa 140 kPa
Operating mechanism
operating slots 2 1 or 2
types 1 spring or 2 springs 1 spring or 2 springs
motor operation 1 spring only available on both
Switchgear dimensions [mm]
CB unit 750 750
Switch units 375/500 375/500
* without operating mechanism

© ABB Group
April 29, 2009 | Slide 3
Indoor Switches
SFG & SHS2 Basic Technical Data

SHS2 SFG
Rated voltage 24kV 12kV 17,5kV 24kV
Rated current 630A 800A 800A 630A
Rated short time withstand current 20kA 25kA 20kA 20kA
Rated short circuit duration 1s 2s 3s 3s
Electrical endurance Class E3* Class E3*
Mechanical endurance Class M1*(1000op.) Class M2*(5000 op.)
Making current 31,5/40kA 62,5kA 50kA 50kA
Internal arc current inside the switch 20kA 20 kA
* according to CEI EN 60265-1/2000-02

© ABB Group
April 29, 2009 | Slide 4
Indoor Switches
SFG Supply concept

SFG: Switch Disconnector with spring


device
Top Unit: Switch Disconnector and spring
device with top metal frame and
LV compartment. Bushing unit as
an option.
Accessories: Pressure gauge or indicator, gas
valve, earthing switch; EF or EM,
fuse holder base and tripping
mechanism, key interlocking
system , voltage indicator, manual
or motor operation, position
indicator, etc.

© ABB Group
April 29, 2009 | Slide 5
Indoor Switches
SHS2 Supply concept

SHS2: Switch Disconnector with spring


device
Kit: Switch Disconnector/Isolator
and spring device complete with
all components needed for
typical units completion:
earthing switch, fuse holder
frame, door lock.
Accessories: Pressure gauge, key
interlocking system, voltage
indicator, manual or motor
operation, auxiliary contacts,
etc.

© ABB Group
April 29, 2009 | Slide 6
Indoor Switches
SFG&SHS2 Main Product Differences

SFG: Epoxy cast resin enclosure (similar


to Schneider’s)
Visible isolation with inspection
windows to see the switch position
25kA at 12kV
800A breaking current at 12kV and
17,5kV
SHS2: Stainless steel enclosure
Switch itself provides earthed metallic
segregation between compartments

© ABB Group
April 29, 2009 | Slide 7
Indoor Switches
SFG&SHS2 Main Product Advantages

Compact 3 positions indoor disconnectors: Line-Open-Earth


Suitable for metal-enclosed distribution switchgears
Earthing switch with full making capacity
Motorized operative mechanism on switch disconnectors
Safety: Made to highest IEC standards, non corrosive leak
proof enclosure, inspection windows (SFG), earthed metallic
segregation (SHS2), integrated voltage indicator, interlocking
device, gas gauge, etc.
Economy: A life span of minimum 30 years, sealed for life, low
maintenance costs
Reliability: Stringent testing of each unit, extremely durable and
reliable actuator, worldwide use, etc.
Smart integration: Modular construction, compact size, easy
installation, one switch - many applications

© ABB Group
April 29, 2009 | Slide 8
Indoor Switches
AM/NAL/C4 Basic Technical Data
AM NAL
Rated voltage 24kV 12kV 17,5kV 24kV 36kV
Rated current 630A 1250A 1250A 1250A 1000A
Rated short time withstand current 16kA 31,5kA 31,5kA 31,5kA 25kA
Rated short circuit duration 1s 1s 1s 1s 2s
Electrical endurance Class E1* Class E1* Class E3* Class E1* Class E3*
Mechanical endurance Class M1*(1000op.) Class M1*(2000op.)
Making current 40kA 67kA 50kA 50kA 50kA
Pole distance [mm] 300 150/170/210 170 170/235/270 360
Rated frequency 50/60Hz 50/60 Hz
Max. rated current with fuses (IEC 420/IEC 62271-105) 125 125 80 40
Power frequency withstand voltage 50 Hz 1 min. [kV]
to earth and between poles 50 42 45 55 80
across isolating distance 60 42 60 70 88
Impulse withstand voltage 1 ,2/50 us [kV]
to earth and between poles 125 75 95 125 170
across isolating distance 145 85 110 145 195
* according to CEI EN 60265-1/2000-02

C4
Rated voltage 12kV 17,5kV 24kV
Rated current 1250A 630A 630A
Rated short time withstand current 25kA 20kA 16kA
Rated short circuit duration 3s 3s 3s
Electrical endurance Class E1* Class E1* Class E1*
Mechanical endurance Class M1*(2000op.)
Making current 63kA 50kA 40kA
Pole distance [mm] 125/150/210 150/210/275
Rated frequency 50/60 Hz
Max. rated current with fuses (IEC 420/IEC 62271-105) 63 40 40
Power frequency withstand voltage 50 Hz 1 min. [kV]
to earth and between poles 28 38 50
across isolating distance 32 45 60
Impulse withstand voltage 1 ,2/50 us [kV]
to earth and between poles 75 95 125
across isolating distance 85 110 145
* according to CEI EN 60265-1/2000-02

© ABB Group
April 29, 2009 | Slide 9
Indoor Switches
AM/NAL/C4 Main Product Differences

AM: rotary type NAL/VersaRupter: hinged type C4: rod type (wall mounted)
Metallic separation between 31.5kA (1s) up to 24kV, 25 kA Up to 25kA (3s) withstand
busbar and line areas (2s) at 36 kV withstand current current
Available as rotary isolator Up to 36 kV and 1250 A Up to 24 kV and 1250 A
Integrated front panel breaking current breaking current
16kA at 24kV Class E3 for selected voltages Class E1
Up to 24 kV and 630 A ANSI/CSA/IEC tested
breaking current 100 breaking operations tested
Class E1 at 630A

© ABB Group
April 29, 2009 | Slide 10
Indoor Switches
AM/NAL/C4 Main Product Advantages

Metallic separation between busbar and line areas


(rotary type)
Direct wall mounting without supports (hinged type)
Arc quenching by means of air blast
Visible insulation break
Sturdy structure and resin insulators with large clearance
Automatic tripping performed by fuses
Wide range of application with easy installation, service
and limited maintenance
Integrated and free standing earthing switches with and
without making capacity

© ABB Group
April 29, 2009 | Slide 11
Indoor Switches
AM/NAL/C4 Supply concept

Switch Disconnector with spring device and set of


accessories: earthing switch, fuse holder frame, door
lock, auxiliary contacts, mechanical interlocking, motor
drives, fuse tripping, operating mechanism, etc.
Technical support for adaptation in panel and
transformer kiosk

© ABB Group
April 29, 2009 | Slide 12
Indoor Switches
Load break switches compare to breakers…

LBS LBS+CL Fuses CB


nominal voltage 12-40,5kV 12-40,5kV 12-40,5kV
nominal current 1250A limited by fuses 2500A
breaking current <10xIn >10xIn (by fuses) >10xIn
breaking time 30-100 ms 4-300 ms 55-75 ms
max.making current 67 kA 67 kA 80 kA
withstand current 31,5 kA (1s) 31,5 kA (1s) 31,5 kA (3s)
number of operations el/mech 100/2000 100/2000 >5000
operating mech. spring spring spring/magnetic
price 600$ 1000$ 4000$
price for 50 kA no 1000$ >10000$
visual break yes (except SHS2) yes (except SHS2) only for withdr. version
protection function no yes by fuses yes with relay on board
maintenance free no no yes

© ABB Group
April 29, 2009 | Slide 13
Indoor Switches
NAL product modifications…

material
changed (PC)

© ABB Group
April 29, 2009 | Slide 14
Indoor Switches
VersaRupter(ANSI) product modifications…

© ABB Group
April 29, 2009 | Slide 15
© ABB Group
April 29, 2009 | Slide 16

Potrebbero piacerti anche