00813-0100-4015

English
Rev. AB

Model 3095FT
Flow Transmitter

Model 3095FT

Pressure-159
Model 3095FT Flow Transmitter

MODEL 3095FT FEATURES AND BENEFITS:


• Measurement of differential pressure, static
pressure, and process temperature in a single,
compact package
• Greater billing accuracy through industry-
leading ±0.075% differential and absolute
pressure measurement accuracy
• Reduced maintenance, easier installation, and
lower installed cost due to fewer pipe
penetrations
• Reduced calibration with highly stable sensor
design

3095-001AB
Greater meter flexibility with 100:1 rangeability
• Low power design that allows remote
installation with optional solar power system
FIGURE 1. Model 3095FT Flow Transmitter with
RTD Assembly.

The Model 3095FT Flow Transmitter is the world’s • Chart recorders have high maintenance costs,
Model 3095FT

most compact electronic flow measurement (EFM) including recommended monthly calibration,
device. Developed in conjunction with the Gas and replacement pens and charts.
Research Institute, the multivariable Model 3095FT • Charts must be integrated to calculate
is a high-performance extension of the Rosemount® flow volumes.
pressure family. In one package, this transmitter
measures differential pressure, absolute pressure, • Chart recorders are prone to losing data
and process temperature, as well as calculates flow. or recording inaccurate data—ink runs dry,
The three process variables along with the painted charts, vibration effects, and errors
calculated flow are available at all times in response due to moisture, temperature, drift, and
to a single request. mechanical wear.
• Integration is slow and cumbersome.
Model 3095FT communications occur on a two-wire
Billing, accounting, and auditing may take
system using the digital HART® (Highway
weeks, and inaccurate or late data may result
Addressable Remote Transducer) protocol, which is
in prohibitive penalties.
based on the Bell 202 Frequency Shift Keying (FSK)
standard. The Model 3095FT performs flow
With the Model 3095FT, chart recorders can now be
calculations and relevant data storage in nonvolatile
replaced with state-of-the-art measurement
memory per applicable American Gas Association
technology with minimal disruption to your business
(A.G.A.), American Petroleum Institute (API), and
methods. The Model 3095FT can be installed in
Gas Processors Association (GPA) orifice meter and
many types of flow monitoring and custody transfer
electronic flow measurement standards.
applications, ranging from monitoring flow at
remote locations, to a comprehensive system that
provides instantaneous flow, DP, AP, and PT via the
NEW SOLUTIONS FOR digital HART protocol signal.
GAS FLOW MEASUREMENT Advantages with the Model 3095FT include superior
Traditionally, mechanical chart recorders have been accuracy, thereby eliminating penalties and
installed in low-volume flow metering applications. reducing unaccounted-for natural gas, high
However, chart recorders do not provide the reliability, low maintenance, and no integration fees,
timeliness or accuracy needed to compete in today’s all resulting in lower long-term operating costs.
gas industry. Following are some of the problems
associated with chart recorders:
© 1995, 1996, 1997, 1998 Rosemount Inc.
May be protected by one or more of the following U.S. Pat. Nos. 4,370,890;
4,612,812; 4,791,352; 4,798,089; 4,798,089; 4,818,994; 4,833,922; 4,866,435;
4,926,340; 5,028,746; Des. 358,782. MEXICO PATENTADO NO. 154961.
Other U.S. and Foreign Patents Issued and Pending.
Pressure-160
Pressure-160
Rosemount Inc.

Model 3095FT with Model 3095FB Multivariable™Transmitter


HART Protocol with Modbus™ RTU Protocol

Introduced in 1994, the Model 3095FT Flow Transmitter New in 1996, the Model 3095FB Multivariable Transmitter
provides a field-proven solution for natural gas flow with Modbus Protocol provides a low cost measurement
monitoring and custody transfer applications. solution for monitoring natural gas flow.
• Accurately measures differential pressure, absolute • Accurately measures differential pressure, absolute
pressure, and process temperature (or gage) pressure, and process temperature
• Digital HART protocol communications • Provides RTUs (Remote Terminal Units) or flow
computers with real-time process variable information
• Performs flow calculations per American Gas
Association (A.G.A.), American Petroleum Institute • Transmission speed is configurable from 1200 to
(API), and Gas Processors Association (GPA) orifice 9600 baud
meter and electronic flow measurement standards • Easily integrates into existing SCADA applications
• User-configurable data logging that exceeds API • Capable of multidroping up to 32 transmitters on
MPMS Chapter 21.1 requirements the same RS-485 bus
• Most cost-effective EFM replacement for mechanical • For additional information, see Pressure-145
chart recorders

Model 3095FT
SYSTEM INTEGRATION
The Model 3095FT communicates via HART
protocol, which uses the Bell 202 Frequency Shift
Keying (FSK) technique. Communication is
accomplished by superimposing a high-frequency
signal on top of the fixed output signal. Because all
communication uses HART, the Model 3095FT does
not provide a 4–20 mA output signal.
The Model 3095FT meets the needs of a stand-alone
gas flow measurement instrument. The integration
of multivariable measurement, advanced flow
calculations, and audit trail capabilities into one
cost-effective, compact package make the Model
3095FT the ideal choice for orifice plate gas flow
measurement installations.

3095-DATAA22B
Remote communication is possible using cellular
phone, RF radio, satellite, and land-line
communications. In addition, Rosemount Inc. can
offer or recommend a variety of protocol converters
to convert HART into industry standard, or
proprietary protocols for integration into an existing FIGURE 2. Model 3095FT Single Site Metering Installation.
SCADA system. For more information on how the
Model 3095FT can be used to meet your telemetry
system requirements, contact your local Rosemount
Sales Engineer.

Pressure-161
161
Model 3095FT Flow Transmitter

MODEL 3095FT (1) The Model 3095FT sensor operating limits may limit the pressure
SOFTWARE FUNCTIONALITY and temperature range.

Flow Calculation and Data Logging


The Model 3095FT is preprogrammed with orifice
meter flow computation algorithms to meet the
requirements of the natural gas industry. The flow
calculations are performed according to 1992 A.G.A.
Report No. 3/API MPMS Chapter 14.3, with A.G.A.
Report No. 8/API MPMS Chapter 14.2 for the
compressibility factor. The Model 3095FT can be
configured for either flange tap or pipe tap

3095-30950005
installations, and automatically performs the
corresponding AGA calculations.
The Model 3095FT fast update and computation
frequencies contribute to its high overall flow FIGURE 3. Logged Variables Screen.
accuracy. Sensor updates occur nine times per
second and flow calculations update once per second.
Gross versus Detail Characterization Detail characterization covers all pressure,
The Model 3095FT calculates the gas temperature, and gas composition ranges for
compressibility factor using either gross or detail which A.G.A. computes compressibility factors.
characterization methods. Gross characterization is Table 1 identifies the acceptable ranges for both
a simplified method that is acceptable for a narrow of these characterization methods.
Model 3095FT

range of pressure, temperature, and gas Data Logging


composition. One significant advantage for the Model 3095FT is
its advanced logging capabilities. The Model 3095FT
sensor averages flow data continuously, and the
TABLE 1. Acceptable Ranges: Gross vs. Detail averaged data is then logged into the nonvolatile
Characterization Methods. memory as part of the Model 3095FT audit trail.
Gross Detail The Model 3095FT creates three types of logs:
Variable
Method Method
• Daily Logs
(1)
Pressure 0–1200 psia 0–20,000 psia (1) • Variable Logs
Temperature 32 to 130 °F (1) –200 to 400 °F (1) • Event Logs
Specific Gravity 0.554–0.9 0.07–1.52 When the seven API required variables are logged,
Heating Value 477–1200 0–1800 the Model 3095FT maintains at least 50 days of
BTU/SCF BTU/SCF daily logs for user-selected process variables and
Mole % Methane 45.0–100 0–100 calculated values. The variable log records the same
Mole % Nitrogen 0–50.0 0–100 data as the daily log according to a user-selected
Mole % CO2 0–30.0 0–100 time duration (between 1-99 minutes). The event log
Mole % Ethane 0–10.0 0–100
provides a record of alarms, configuration changes,
and significant occurrences that could affect the flow
Mole % Propane 0–4.0 0–12
calculation.
Mole % Butanes 0–1.0 0–6
Mole % Pentanes 0–0.3 0–4
Figure 3 illustrates the 19 parameters available for
logging by both the daily and variable log. Any or all
Mole % Hexanes Plus 0–0.2 0–Dew Point
of the parameters listed may be selected. Figure 4
Mole % Helium 0–0.2 0–3.0 illustrates an actual variable log configured to log
Mole % Hydrogen 0–10.0 0–100 the seven API required variables at 60-minute
Mole % CO 0–3.0 0–3.0 intervals.
Mole % Argon 0 0–1.0 To meet existing billing system requirements, the
Mole % Oxygen 0 0–21.0 Model 3095FT can calculate and log static pressure
Mole % Water 0–0.05 0–Dew Point as absolute or gage, based on upstream or
Mole % H2S 0–0.02 0–100 downstream tap locations. However, flow is always
calculated using the upstream absolute pressure
NOTE
Reference conditions are 14.73 psia and 60 °F for Gross Method. measurement for greatest accuracy.
In total, the Model 3095FT provides the user with a
complete audit trail, which exceeds current API
Pressure-162
Pressure-162 MPMS Chapter 21.1 standards for electronic flow
measurement systems.
Rosemount Inc.

Report Date: 96/10/17 15:43:44

Model 3095FT Data View V1.18 (1032)


Archived VariableLog: 96/07/01 00:00:00 - 96/10/17 15:42:29 (92 Records)

Total Total Total Average Average Average


DATE TIME FLOW FLOW TIME ENERGY DP SP PT SEQUENCE
94/08/04 17:00:00 347.01 SCF 01:00:00 351944 BTU 124.94 InH2O 13.91 psi 83.47 DegC 1
94/08/04 18:00:00 347.64 SCF 01:00:00 352583 BTU 124.94 InH2O 13.95 psi 83.47 DegC 2
94/08/04 19:00:00 348.12 SCF 01:00:00 353070 BTU 124.93 InH2O 13.98 psi 83.48 DegC 3
94/08/04 20:00:00 348.40 SCF 01:00:00 353354 BTU 124.94 InH2O 14.00 psi 83.48 DegC 4
94/08/04 21:00:00 348.80 SCF 01:00:00 353760 BTU 124.94 InH2O 14.03 psi 83.52 DegC 5
94/08/04 22:00:00 349.09 SCF 01:00:00 354054 BTU 124.94 InH2O 14.05 psi 83.49 DegC 6
94/08/04 23:00:00 349.30 SCF 01:00:00 354267 BTU 124.94 InH2O 14.06 psi 83.43 DegC 7
94/08/05 00:00:00 349.56 SCF 01:00:00 354531 BTU 124.94 InH2O 14.08 psi 83.45 DegC 8
94/08/05 01:00:00 349.69 SCF 01:00:00 354663 BTU 124.94 InH2O 14.09 psi 83.48 DegC 9
94/08/05 02:00:00 349.58 SCF 01:00:00 354551 BTU 124.94 InH2O 14.08 psi 83.50 DegC 10
94/08/05 03:00:00 349.83 SCF 01:00:00 354805 BTU 124.94 InH2O 14.10 psi 83.52 DegC 11
94/08/05 04:00:00 349.71 SCF 01:00:00 354683 BTU 124.94 InH2O 14.09 psi 83.53 DegC 12
94/08/05 05:00:00 349.81 SCF 01:00:00 354784 BTU 124.95 InH2O 14.10 psi 83.53 DegC 13
94/08/05 06:00:00 349.71 SCF 01:00:00 354683 BTU 124.94 InH2O 14.09 psi 83.55 DegC 14
94/08/05 07:00:00 349.71 SCF 01:00:00 354683 BTU 124.95 InH2O 14.09 psi 83.55 DegC 15
94/08/05 08:00:00 349.93 SCF 01:00:00 354906 BTU 124.95 InH2O 14.10 psi 83.53 DegC 16
94/08/05 09:00:00 349.85 SCF 01:00:00 354825 BTU 124.95 InH2O 14.10 psi 83.54 DegC 17
94/08/05 10:00:00 349.91 SCF 01:00:00 354886 BTU 124.95 InH2O 14.10 psi 83.54 DegC 18
94/08/05 11:00:00 349.72 SCF 01:00:00 354693 BTU 124.95 InH2O 14.09 psi 83.54 DegC 19
94/08/05 12:00:00 349.68 SCF 01:00:00 354652 BTU 124.95 InH2O 14.09 psi 83.53 DegC 20

FIGURE 4. Variable Log Example with Required API Variables.

Analysis of the log file is a critical part of gas flow The Model 3095FT system includes two types of
measurement. Model 3095FT log files can be saved transmitter security to prevent unauthorized or

Model 3095FT
as an ASCII file or as a comma separated value file. accidental changes to the configuration. Mounted on
This information can then be printed as a text file or the electronics board is a transmitter security
retrieved using a spread sheet program. switch, which when enabled, prevents changes to the
transmitter configuration.
Model 3095FT logged data can also be imported into
Flow-Cal,™ an editing and graphing software In addition, the Model 3095FT User Interface
package developed by Coastal Flow Measurement Software provides three levels of password security:
Inc. This software provides edit, recalculation, and System Administrator (one password), Maintenance
sophisticated graphing capabilities. For further (three passwords), and Operation (six passwords).
information concerning this software package,
contact Coastal Flow.
USER INTERFACE
Configuration and Security
The Model 3095FT has extensive configuration SOFTWARE PACKAGES
capabilities, including gas properties, gas The Model 3095FT User Interface Software is a
composition, calculation methods, flow parameters, separate software package that allows easy
LCD display, and multiple audit trails. Figure 5 configuration of the Model 3095FT Flow
illustrates the Model 3095FT flow parameters Transmitter and retrieval of audit trail data. This
configuration screen. tool serves as a communications interface to the
Model 3095FT.
For best performance of the User Interface Software,
the following computer hardware and software is
recommended:
• DOS-based 386 computer or above
• 4 MB RAM minimum
3095-30950001

• Windows 3.1, Windows for Workgroups 3.11,


or Windows 95
• DOS 3.1 or higher
• Mouse or other pointing device
FIGURE 5. Flow Parameters Configuration Screen. • 2 MB of free hard disk space

Pressure-163
163
Model 3095FT Flow Transmitter

LCD METER PROVEN TECHNOLOGY


The optional Model 3095FT LCD meter, shown in The Model 3095FT benefits from the proven
Figure 6, provides local display of process variables, capacitance cell technology featured in our Model
calculated variables, and transmitter diagnostic 3051C Differential Pressure Transmitter and the
messages. patented piezoresistive silicon sensor of the Model
3051C Absolute Pressure Transmitter. The digital
During normal operation, the display changes
technology employed in the Model 3095FT ensures
every three seconds to display user-selected
maximum accuracy and rangeability and remote
parameters.The LCD meter uses two displays to
data communications capability.
indicate a parameter’s value, engineering unit,
and parameter name: The extensive use of application-specific integrated
Parameter Value circuits (ASICs) and surface-mount electronic
technology significantly reduces the size and weight
of the transmitter. This flow transmitter actually
performs the same measurement and computing
40.203 40.203 functions of other electronic flow measurement
IN_H2O DP devices over 10 times its size and weight.
Figure 7 shows a functional block diagram of the
Model 3095FT Flow Transmitter. Its functionality is
Engineering Unit Parameter Name divided between the sensor module and the
electronics module. The sensor module performs all
Each display lasts three seconds, with a brief blank
tasks related to measuring and correcting the
display before the LCD meter shows the next
process variables, while the electronics module
parameter. The LCD scrolls through the entire list of
performs the flow calculation, data logging, and
selected parameters before repeating the displays.
output functions.
Model 3095FT

Any of the following variables may be selected for


the LCD display:
Flow Rate Heating Value MULTIVARIABLE SENSOR MODULE
Differential Pressure Mole Percent CO2 The advanced sensor module of the Model 3095FT
Totalized Flow Today Mole Percent N2 measures three process variables simultaneously.
Totalized Flow Yesterday Orifice Bore at 68 °F The multivariable module incorporates a high-
Static Pressure Date and Time accuracy capacitance sensor for differential
Process Temperature Specific Gravity pressure, a high-accuracy piezoresistive sensor for
Energy Flow Rate Totalized Energy Today
absolute pressure, and a four-wire RTD input for
Totalized Energy Yesterday
process temperature measurement. In addition, the
The LCD meter also automatically displays any sensor electronics convert the process variables
alarm conditions that might occur during operation. directly into digital format for further correction and
compensation within the sensor module.

Differential Pressure
In the differential pressure sensor, process pressure
is transmitted through the isolating diaphragm and
Meter Assembly fill fluid to the sensing diaphragm in the center of
the capacitance cell. Capacitor plates on both sides
Meter of the sensing diaphragm detect its position. The
Cover
differential capacitance between the sensing
diaphragm and the capacitor plates is directly
proportional to process pressure.
3051-3031C05C

Meter
Connection

FIGURE 6. LCD Meter Exploded View.

Pressure-164
Pressure-164
Rosemount Inc.

SENSOR MODULE ELECTRONICS MODULE


Analog-to-Digital
Signal Conversion

Sensor Output Non-Volatile Memory


Microprocessor Microprocessor • Transmitter
Module and Memory • Damping Configuration
Temperature • Correction • Diagnostics • Range Values
Coefficients • Communication • Logging
• Module Info. • Rerange
• Sensor • Flow Calculation
Linearization
• Diagnostics RAM

HART
Communications
Piezoresistive Capacitive
AP Sensor DP Sensor

H L
RTD
Input Pressure Pressure Personal

3095-0181A
Computer

FIGURE 7. Model 3095FT Flow Transmitter Block Diagram.

Model 3095FT
Absolute Pressure
The absolute pressure sensor is fabricated utilizing a The Model 3095FT can accept a signal from any
processing method called chemical vapor deposition 100-ohm platinum RTD that conforms to IEC-751
(CVD). This technique, which is superior to other Class B. The Model 3095FT Flow Transmitter can be
technologies that are vulnerable to drift over time, supplied with an optional Rosemount Series 68 or 78
isolates the sensing element from the silicon RTD temperature sensor. For further information on
substrate to achieve high accuracy and repeatability. Rosemount temperature sensors and accessory
hardware, contact your Fisher-Rosemount Sales
The absolute sensor consists of a Wheatstone bridge
Engineer.
circuit made from polysilicon resistors deposited on
a silicon substrate. The absolute pressure sensor is
hydraulically connected to the high pressure side of
Digital Compensation
the transmitter. Process pressure is transmitted The Model 3095FT uses a dedicated micro-processor,
through the fill fluid to the sensing element, creating located inside the sensor module, to linearize and
a very small deflection of the silicon substrate. The correct the raw sensor outputs. To ensure premium
resulting strain on the substrate changes the bridge performance, this sensor microprocessor uses the
resistance in proportion to the pressure applied. absolute (or gage) pressure measurement to
compensate for zero line pressure effects and an
Process Temperature internal temperature measurement to compensate
for thermal effects.
Process temperature is measured using an input
connection on the sensor module for a standard
resistance temperature device (RTD). Rosemount
Inc. offers a special shielded cable with connector
for connecting the RTD input to the Model 3095FT
(see ordering information for details).

Pressure-165
165
Model 3095FT Flow Transmitter

Certification Label

Housing

Terminal Block

Cover O-ring
Electronics Board
Cover

Real-Time Clock Battery

Nameplate

Module O-ring
Model 3095FT

Sensor Module
Housing Locking Screw

Process Flange O-ring

RTD Connector
Drain/Vent Valve

Coplanar Flange

Flange Adapter O-ring

Optional
Flange Adapters
3095-3095B08A.EPS

Bolts

FIGURE 8. Exploded View of Model 3095FT.

Pressure-166
166
Rosemount Inc.

5.0 4.20
(127) (107)
½–14 NPT Conduit 4.09 Certification
4.3 Label
(110) Connection (104)
Meter Cover (Two Places)
(Optional) 2.15
(55)
0.75 (19)
0.75 (19) Clearance for
Clearance for Cover Removal
Cover Removal

Transmitter Transmitter
7.07
Circuitry Connections
(180)
This Side This Side
8.17
Nameplate (208)

Drain/Vent
Valve Housing
Rotation
Set Screw

6.4
(163)

3095-3095G05B, H05A

Model 3095FT
½–14 NPT on optional mounting adapters.
Adapters can be rotated to give connection ¼–18 NPT on Coplanar flange
centers of 2.00 (51), 2.125 (54), or 2.25 (57). for pressure connection without
the use of mounting adapters
NOTE
Dimensions are in inches (millimeters).

FIGURE 9. Dimensional Drawings of Model 3095FT.

PANEL MOUNTING PIPE MOUNTING


2.82 4.3
(72) (110

7.07
(180)

1.10 (28)

6.15
(156)
2.81
3095-3095J04B , K04A, L04B

(71)

6.25
3.54 (159)
(90)
4.73
(120)
NOTE
Dimensions are in inches (millimeters).

FIGURE 10. Mounting Configurations for Model 3095FT.

Pressure-167
167
Model 3095FT Flow Transmitter

MODEL 3095FT SPECIFICATIONS Failure Mode Alarm


If self-diagnostics detect a gross transmitter failure,
Functional Specifications the HART output registers an alarm with each
Service message.
Natural gas. Hazardous Locations Certifications
Differential Sensor Factory Mutual (FM) Approvals
Ranges A Explosion Proof for Class I, Division 1, Groups
Code 2: 0–2.5 to 0–250 inH2O (0–0.62 to 0–62.2 kPa). B, C, and D. Dust-Ignition Proof for Class II,
Code 3: 0–10 to 0–830 inH2O (0–2.48 to 0–206 kPa). Division 1, Groups E, F, and G. Suitable for
Limits Class III, Division 1, indoor and outdoor
Code 2: –250 to 250 inH2O (–62.2 to 62.2 kPa). (NEMA 4X) hazardous locations. Factory
Code 3: –830 to 830 inH2O (–206 to 206 kPa). Sealed. Provides non-incendive RTD
connections for Class I, Division 2, Groups A,
Absolute Sensor B, C, and D. Install per Rosemount drawing
Ranges 03095-1025.
Code 3: 0–8 to 0–800 psia (0–55.16 to 0–5515.8 kPa). Canadian Standards Association (CSA)
Code 4: 0–36.26 to 0–3,626 psia (0–250 to Approvals
0–25000 kPa). C Explosion Proof for Class I, Division 1, Groups
Limits B, C, and D. Dust-Ignition Proof for Class II,
Code 3: 0.5 to 800 psia (3.4 to 5515.8 kPa). Division 1, Groups E, F, and G. Suitable for
Code 4: 0.5 to 3,626 psia (3.4 to 25000 kPa). Class III, Division 1, indoor and outdoor
Output hazardous locations, CSA enclosure Type 4X.
Factory Sealed. Provides non-incendive RTD
Two-wire fixed 9.5 mA with digital HART protocol
connection for Class I, Division 2, Groups A, B,
superimposed on current signal.
Model 3095FT

C, and D. Approved for Class I, Division 2,


Power Supply Groups A, B, C, and D. Install in accordance
External power supply required. Transmitter with Rosemount Drawing 03095-1024.
operates on terminal voltage of 7.5–35 V dc with a ISSeP/CENELEC Flameproof Certification
constant average operating current of 9.5 mA. H EEx d IIC T6 (Tamb = 40 °C).
Load Limitations EEx d IIC T5 (Tamb = 70 °C).
Maximum loop resistance is determined by the IP 65.
voltage level of the external power supply, as Over Pressure Limit
described by: 0 psia to two times the absolute pressure sensor
range with a maximum of 3,626 psia.
Power Supply Voltage – 7.5
Max. Loop Resistance ≤ ------------------------------------------------------------------- Static Pressure Limit
0.014
1964
Operates within specifications between static line
pressures of 0.5 psia and the URL of the absolute
Load (Ohms)

pressure sensor.
Temperature Limits
Process:
Operating Region –40 to 185 °F (–40 to 85 °C).
250

0 Ambient:
7.5 11.0 35 –40 to 185 °F (–40 to 85 °C).
Power Supply Voltage
Storage:
Communication requires a minimum loop resistance of 250 ohms.
–50 to 212 °F (–46 to 100 °C).
Zero Suppression Humidity Limits
Can be set anywhere within the sensor limits as long 0–100% relative humidity.
as the span is greater than or equal to the minimum LCD Meter
span, the lower range value does not exceed the Optional dual-row, 11-digit, alphanumeric, scrolling
lower range limit, and the upper range value does liquid crystal display.
not exceed the upper range limit.
LCD Meter Temperature Limits
NOTE Operating: –13 to 185 °F (–25 to 85 °C).
Flow calculations will cease with negative DP readings. Storage: –40 to 185 °F (–40 to 85 °C).

Pressure-168
Pressure-168
Rosemount Inc.

Turn-on Time Ambient Temperature Effect per 50 °F (28 °C)


Process variables will be within specifications less ±(0.05% URL + 0.125% of span) spans from 1:1 to 30:1.
than 60 seconds after power is applied to ±(0.06% URL – 0.175% of span) spans from 30:1 to
transmitter. 100:1.
Damping Stability
Response to step input change can be user-selectable ±0.1% of URL for 12 months.
from 0 to 15 seconds for one time constant. This is in Process Temperature (RTD)
addition to sensor response time of 0.2 seconds. Specification for process temperature is for the
Real-Time Clock Accuracy transmitter portion only. Sensor errors caused by
±2 minutes per month at reference conditions. the RTD are not included. The transmitter is
compatible with any PT100 RTD conforming to
Performance Specifications IEC 751 Class B, which has a nominal resistance
of 100 ohms at 0 °C and ∝ = 0.00385. Examples of
(Zero-based spans, reference conditions, silicone oil compatible RTDs include the Rosemount Series 68
fill, 316 SST isolating diaphragms, and digital trim and 78 RTD Temperature Sensors.
values equal to the span end points.)
Range
Differential Pressure –40 to 185 °F (–40 to 85 °C).
Range 2
Accuracy
0–2.5 to 0–250 inH2O (0–0.62 to 0–62.2 kPa)
(including Linearity, Hysteresis, Repeatability)
(100:1 rangeability is allowed).
±1.0 °F (0.56 °C).
Range 3
Ambient Temperature Effects
0–10 to 0–830 inH2O (0–2.48 to 0–206 kPa)
±0.72 °F (0.40 °C) per 50 °F (28 °C).
(83:1 rangeability is allowed).
Stability
Reference Accuracy

Model 3095FT
±1.0 °F (0.56 °C) for 12 months.
(including Linearity, Hysteresis, Repeatability)
±0.075% of span for spans from 1:1 to 10:1 of URL.
Physical Specifications
For spans less than 10:1 rangedown, Electrical Connections
½–14 NPT, M20 3 1.5 (CM20), PG-13.5.
Accuracy = 0.025 + 0.005  ------------ % of Span
URL
 Span Process Connections
Transmitter: ¼–18 NPT on 2 1/8 -in. centers.
Ambient Temperature Effect per 50 °F (28 °C) RTD: RTD dependent (see ordering information).
±(0.025% URL + 0.125% span) spans from 1:1 to 30:1.
±(0.035% URL – 0.175% span) spans from 30:1 to Process Wetted Parts
100:1. Isolating Diaphragms
Static Pressure Effects 316L SST or Hastelloy C-276.®
Zero error = ±0.10% of URL per 1,000 psi (6894 kPa). Drain/Vent Valves
Span error = ±0.20% of reading per 1,000 psi 316 SST or Hastelloy C.®
(6894 kPa). Flanges
Stability Plated carbon steel, 316 SST, or Hastelloy C.
±0.1% of URL for 12 months. Wetted O-rings
Absolute Pressure Glass-Filled TFE.
Range 3 (absolute) Non-Wetted Parts
0–8 to 0–800 psi (0–55.16 to 0–5515.8 kPa) Electronics Housing
(100:1 rangeability is allowed). Low copper aluminum.
Range 4 (absolute) Bolts
0–36.26 to 0–3,626 psi (0–250 to 0–25000 kPa) Plated carbon steel per ASTM A449, Grade 5;
(100:1 rangeability is allowed). or austenitic 316 SST.
Reference Accuracy Fill Fluid
(including Linearity, Hysteresis, Repeatability) Silicone oil.
±0.075% of span for spans from 1:1 to 6:1 of URL.
Paint
For spans less than 6:1 rangedown, Polyurethane.
Accuracy = 0.03 + 0.0075  ------------ % of span
URL O-rings
 Span Buna-N.

Pressure-169
169
Model 3095FT Flow Transmitter

Weight ACCESSORIES
Component Weight in lb (kg) Model 3095FT User Interface Software Packages
Model 3095FT Transmitter 6.0 (2.7) The User Interface software package is available
LCD Meter 0.5 (0.2) with or without the HART modem and connecting
SST Mounting Bracket 1.0 (0.4) cables. All configurations are packaged separately.
12 ft (3.66 m) RTD Shielded Cable 0.5 (0.2)
12 ft (3.66 m) RTD Armored Cable 1.1 (0.5) Part No. 03095-5100-0001: Windows User Interface
24 ft (7.32 m) RTD Shielded Cable 1.0 (0.4) Software–Single PC License, HART Modem, and
24 ft (7.32 m) RTD Armored Cable 2.2 (1.0) Cables.
Part No. 03095-5110-0001: Windows User Interface
Software–Single PC License.
OPTIONS Part No. 03095-5110-0003: Windows User Interface
Standard Configuration Software– Site License.
Unless otherwise specified, the transmitter is Part No. 03095-5105-0001: HART Modem and
shipped as follows: Cables.
Engineering units: Remote Power Supply Options
Differential inH2O (Range 2) The Model 3095FT can be powered from a solar
Absolute/Gage psi (all ranges) panel/battery system. Although other systems can
Output: Digital HART protocol signal be used if they meet the power requirements of the
Flange type: Specified model code option 3095FT, Rosemount can supply the following
Flange material: Specified model code option systems:
O-ring material: Specified model code option
A/ ASP5127: Base System: powers one 3095FT
Drain/vent: Specified model code option
(5W solar panel, 7Ah battery).
Flow Configuration
Model 3095FT

Parameters: Factory default B/ ASP201234: Radio-Ready system: powers 1–4


Software tag: (Blank) 3095FT with RF telemetry
(20W solar panel, 34Ah battery).
Software tag (8 characters maximum) is left blank
unless specified. C/ ASP51234: Base system, field upgradeable to
Radio-Ready: powers one 3095FT
Custom Configuration (Option Code C1)
(5W solar panel, 34Ah battery).
If Option Code C1 is ordered, the customer specifies
the following information for the Model 3095FT in D/ ASP20M: Upgrade to Radio-Ready—upgrades C
addition to the standard configuration parameters. to B Radio-Ready
(20W solar panel).
Configuration Data Sheet 00806-0100-4015
Gas composition parameters, contract hour, Any of these power supplies can be supplied with
log parameters, LCD display parameters, meter run an optional external BNC connector to allow
configuration parameters, low flow cut-off, communication without opening the cabinet or
passwords, static pressure tap location, static the transmitter.
pressure measurement, damping, descriptor,
message, and upper and lower trim points for each For more information on 3095FT power supply
process variable. options, contact your Rosemount Sales Engineer.

Tagging
Three customer tagging options are available:
Rosemount and the Rosemount logotype are registered trademarks of
1. Standard SST tag is wired to the transmitter. Rosemount Inc.
Tag character height is 0.125 in. (3,18 mm), Coplanar and Multivariable are trademarks of Rosemount Inc.
85 characters maximum. HART is a registered trademark of the HART Communication Foundation.
Modbus is a trademark of Modicon, Inc.
2. Tag may be permanently stamped on transmitter Hastelloy C and Hastelloy C-276 are registered trademarks of Cabot Corp.
nameplate upon request. Tag character height is Windows is a registered trademark of Microsoft Corp.
Flow-Cal is a trademark of Coastal Flow Measurement, Inc.
0.0625 in. (1,59 mm), 65 characters maximum.
3. Tag may be stored in transmitter memory. Cover photo: 3095-002AB

Software tag (8 characters maximum) is left blank


unless specified.

Pressure-170
Pressure-170
Rosemount Inc.

ORDERING INFORMATION
Model Product Description
3095F Flow Transmitter
Code Output
H Digital HART Protocol Signal
Code Differential Pressure Range
2 0–2.5 to 0–250 inH2O (0–0.62 to 0–62.2 kPa)
3 0–10 to 0–830 inH2O (0–2,48 to 0–206 kPa)
Code Absolute/Gage Pressure Ranges
3 0–8 to 0–800 psia (0–55.16 to 0–5515.8 kPa)
4 0–36.26 to 0–3,626 psia (0–250 to 0–25000 kPa)
Code Isolator Material Fill Fluid
A 316L SST Silicone
B(1) Hastelloy C-276 Silicone
Code Flange Style, Material
A Coplanar, CS
B Coplanar, SST
C Coplanar, Hastelloy C
0 None (Required for Option Code S5)
Code Drain/Vent Material
A SST
C Hastelloy C
0 None (Required for Option Code S5)
Code O-ring
1 Glass-filled TFE

Model 3095FT
Code Process Temperature Input (RTD ordered separately)
0 Fixed Process Temperature (no cable)
1 RTD Input with 12 ft (3.66 m) of Shielded Cable (Intended for use with conduit.)
2 RTD Input with 24 ft (7.32 m) of Shielded Cable (Intended for use with conduit.)
3 RTD Input with 12 ft (3.66 m) of Armored, Shielded Cable
4 RTD Input with 24 ft (7.32 m) of Armored, Shielded Cable
7 RTD Input with 75 ft (22.86 m) of Shielded Cable (Intended for use with conduit)
8 RTD Input with 75 ft (22.86 m) of Armored, Shielded Cable
Code Transmitter Housing Material Conduit Entry Size
A Polyurethane-covered Aluminum ½–14 NPT
B Polyurethane-covered Aluminum M20 3 1.5 (CM20)
C Polyurethane-covered Aluminum PG 13.5
D Polyurethane-covered Aluminum G½
J SST ½–14 NPT
K SST M20 3 1.5 (CM20)
L SST PG 13.5
Code Terminal Block
A Standard
B With Integral Transient Protection
Code Meter
0 None
1 LCD Meter for Flow Units, Aluminum Housing
Code Bracket
0 None (Required for Option Code S5)
1 Coplanar SST Flange Bracket for 2-in. Pipe or Panel Mount, SST Bolts
Code Bolts
0 CS bolts
1 Austenitic 316 SST Bolts
N None (Required for Option Code S5)
Code Approvals
0 None
A Factory Mutual (FM) Explosion-Proof Approval
C Canadian Standards Association (CSA) Explosion-Proof Approval
H ISSeP/CENELEC Flameproof Certification

Pressure-171
171
Model 3095FT Flow Transmitter

Code Engineered Measurement Solution (EMS)

A { Averaging Method: Flow Dependent Time-weighted Formulaic Averaging


Compressibility Factor: A.G.A. Report No. 8 /API MPMS Chapter 14.2
Code Options
S5 Assembly with Model 305 Integral Manifold (requires integral manifold model number - see Pressure-79)
C1 Custom Configuration

{
Plated CS
DF Flange Adapters — Adapter Type Determined by Selected Flange Material: SST
Hastelloy C
Typical Model Number 3095F H 2 3 A B A 1 1 A B 1 1 0 A A

(1) Meets NACE material recommendations per MR 01–75.

Optional Model 305 Integral Manifolds for Natural Gas/Metering Platform


Model 3095FT Flow Transmitter and Model 305BC6 • Designed to integrally mount to Rosemount Coplanar
Integral Manifold are fully assembled, calibrated, and pressure transmitters
seal tested by the factory.
• Factory assembled, seal tested, and calibrated
This five-valve manifold is used with differential
• Reduced engineering, purchasing, shipping,
pressure transmitters. It provides two blocking valves,
assembly, and testing costs
two equalizing valves, and one vent valve.
• Factory assembled, seal tested, and calibrated
The two equalizing-valve design ensures bubble-tight
shut off at the equalizer-valve position. This • Patented Pressure-Core Stem Seal system eliminates
eliminates any uncertainty in the accuracy of the valve stem maintenance requirements. Backed up
differential signal. Test ports are provided for with a 3-year leak-free warranty
Model 3095FT

simplified in-process calibration capability.


• Fewer process seals ease environmental compliance
For additional Model 305 information, refer to and reduce risks
Pressure-79.
• Carbide Ball Hard Seal eliminates seal galling to
ensure thousands of leak-free cycles
• All designs (316 SS) meet NACE Material
Recommendations per MR 01-75
• ½–14 NPT process connections
• Compatible with the standard Coplanar flange
mounting bracket
305_HI-980073BB

30535C2A

Rosemount Inc. Fisher-Rosemount Limited Fisher-Rosemount


8200 Market Boulevard Heath Place Singapore Pte Ltd.
Chanhassen, MN 55317 USA Bognor Regis 1 Pandan Crescent
Tel 1-800-999-9307 West Sussex PO22 9SH Singapore 128461
Telex 4310012 England Tel (65) 777-8211
Fax (612) 949-7001 INT
Tel 44 (1243) 863 121 Fax (65) 777-0947
ED
PR

IN
© 1998 Rosemount, Inc. U. S. A. Fax 44 (1243) 867 5541 Tlx RS 61117 FRSPL
http://www.rosemount.com

¢00813-0100-4015• ¤
00813-0100-4015 Rev. AB 11/98
Pressure-172

Potrebbero piacerti anche