Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Contents:
1.
1. Protection
2. Selective coordination
3. Power factor considerations
4. Voltage considerations
5. Conclusions
<="" ins="" data-adsbygoogle-status="done" style="text-size-adjust: none;
outline: none; -webkit-tap-highlight-color: rgba(0, 0, 0, 0); box-sizing: border-
box; height: 250px; width: 300px; display: block;">
1. Protection
The function of system protection may be defined as the detection and prompt
isolation of the affected portion of the system when a short circuit or other
abnormality occurs that might cause damage to, or adversely affect, the
operation of any portion of the system or the load that it supplies.
1. phase-overcurrent and
2. ground-fault.
At the present state of the art, phase-overcurrent conditions are detected on the
basis of their magnitudes. Response time is dependent upon the particular
overcurrent time-current characteristic (TCC) curve.
Series-connected ratings should be based on tests and are only valid for the
specific circuit breaker types listed in the test reports.
Selection of appropriate trip unit functions and their settings to provide protection
and coordination is the next consideration.
The amount of time delay provided by the long-time delay characteristics should
be selected to be no higher than necessary to override transient overcurrents
associated with the energizing of load equipment and to coordinate with
downstream protection devices.
Rule #2
Take advantage of the adjustable instantaneous trip characteristic on
MCCBs and LVPCBs. Set the instantaneous trip no higher than necessary to
avoid nuisance tripping. Be sure that instantaneous trip settings do not exceed
the maximum available short-circuit current at the location of the circuit breaker
in the system.
Rule #3
Provide ground-fault protection in accordance with the NEC, where
required. Ground-fault current settings should be set to minimize hazard to
personnel and damage to equipment.
Go back to contents ↑
Moving toward the load, on many feeder circuits sufficient impedance exists in
the distribution system to appreciably lower the available short-circuit current at
the next load-side level circuit breaker.
If the available short-circuit current at this circuit breaker is less than the
instantaneous trip setting of the feeder circuit breaker, then selectivity is
achieved (see Figure 5 below).
That signal restrains circuit breakers farther to the line-side from reacting until
they time out according to their settings. Because it does not receive such a
restraining signal from a load-side circuit breaker, the circuit breaker nearest
the fault continues to trip with minimum delay.
Go back to contents ↑
3. Power factor considerations
Test circuits with lagging power factors no greater than in Table 1 are used
to establish interrupting ratings.
10 000 or less 50 15 20
10 001 – 20 000 30 15 20
Over 20 000 20 15 20
(a) UL 489
(b) ANSI C37.50
These multiplying factors adjust the short-circuit current to a value equal to the
maximum transient offset in the initial half-cycle of short-circuit current flow
using the relation in Elements of Power System Analysis, as follows:
where
t is time and is 0 when voltage is applied,
α is the electrical angle after t = 0 at which point the circuit is closed,
θ is the power angle and equals tan–1(ωL / R),
Z is √(R2 +(ωL)2)
By making the simplifying assumption that the circuit is closed at a time t = 0
when the instantaneous voltage is zero, the following multiplier is derived:
where
Example
Go back to contents ↑
4. Voltage considerations
The most common industrial and commercial utilization voltage by far is the
solidly grounded 480Y/277 V system. Yet, a number of 600 V and 480 V delta
systems are in service of both ungrounded and corner-grounded configurations.
With two faults to ground, voltage across the interrupting pole is at some value
between phase voltage and line voltage. Again, the magnitude of the fault
depends on the prospective current and the value of the impedances to ground
at the respective faults.
Ta
ble 3 – Single-pole short-circuit test values for MCCBs
These test values are the minimum required for certification to UL 489. They
are not marked ratings and are printed here to aid the system designer who
may need them for single-phase short-circuit analysis. Single-pole circuit
breakers are tested at values equal to their interrupting ratings.
Table test values are the minimum required for certification to UL 489. They are
not marked ratings and are printed here to aid the system designer who may
need them for single-phase short-circuit analysis. Single-pole circuit breakers
are tested at values equal to their
interrupting ratings.
Table 4 is provided as a guide for applying the appropriate voltage rating of the
MCCB to each system.
480Y/277 Solid • • • •
480 Ungrounded • •
600Y/347 Solid • •
600 Ungrounded •
(a) Codes and standards allow 480 V rated MCCBs in these applications. Some
manufacturers provide MCCBs specially rated for the corner-grounded delta
system to satisfy user preference. These ratings may also be applied to
resistance-grounded wye systems. LVPCBs are also an option.
Go back to contents ↑
5. Conclusions