This edition of OnBoard provides a
summary of the requirements for
installing plasterboard in external ceilings.
External ceilings include alfresco areas,
carports, balconies and breezeways with
plasterboard installed horizontally or
sloping downwards away from the main
dwelling.
External ceilings are subject to harsher The plasterboard and plaster Framing
conditions than internal ceilings, compounds must not be subjected Ceiling framing at maximum
and therefore they need additional to any direct water, long periods of 450mm framing centres.
protection from the weather. The high humidity, sea spray or damp Provide additional framing
following installation requirements are conditions. around the perimeter by
designed to control the occurrence of The plasterboard and plaster inserting trimmers between
common external ceiling faults, such as: compounds must be installed after the ceiling frames or install steel
Condensation on the plasterboard roof covering has been completely angle. [Refer to Figures 1 and 2]
installed and sealed.
Condensation on framing or roofing
and dripping down on to the Minimum 100mm clearance from
plasterboard external ceiling lining to lower edge
of verandah beam or masonry lintel,
Water penetrating the paint system
otherwise provide protection against
Distortion of joints
wind blown rain. [Refer to Figures 3, Insert trimmers between ceiling frames for
Plasterboard sagging 4, 5, 6 and 7] perimeter sheet support. Fix plasterboard to
trimmers at 300mm max centres.
Mould growth
Installation requirements for FIGURE 1
Fastener popping External Trimmer
external ceilings
Minimum conditions to use Use either 10mm SpanShield,
plasterboard in external ceilings 13mm MastaShield,
The plasterboard substrate must be 10mm or 13mm SoundShield,
designed for the appropriate loading 13mm or 16mm FireShield.
conditions including wind loading. For improved water resistance use
The cavity above the plasterboard either 13mm WaterShield, 13mm
ceiling must have cross ventilation. or 16mm TruRock. Install angle for perimeter sheet support. Fix
plasterboard to angle at 300mm max centres.
Fix angle to verandah beam at 600mm max
Sarking and thermal insulation must centres and 100mm from ends.
be used to improve temperature
FIGURE 2
control, reduce wind pressure and Perimeter Angle
control condensation.
ONBOARD Technical Newsletter
Trimmeraround
Trimmer around
Insulation Trimmeraround
Trimmer aroundperimeter
perimeter perimeter
perimeter
Ceilingbatten
Ceiling batten
Edgemoulding
Edge moulding
100mmmin
100mm minclearance
clearance
Verandahbeam
Verandah beam
FIGURE 66
FIGURE
Withedge
With edgemoulding
mouldingon
onbattens
battens