NOTES FOR ELECTRICAL WORKS:
SCHEDULE OF LOADS
MACTAN ECONOMIC ZONE
LAPU-LAPU CITY, 6015, CEBU
TEL. (032) 340-1568/342-8375
OF AND FOR OTHERPROJECTS OR BUILDINGS, WHETHER EXECUTED PARTLY OR IN WHOLE, WITHOUT THE WRITTEN CONSENT OF ARCHITECT/ENGINEER OR AUTHOR OF SAID DOCUMENTS.

1.ALL ELECTRICAL WORKS AND INSTALLATION HEREIN SHALL CONFORM WITH THE LATEST
INTELLECTUAL PROPERTY OF ARCHITECT/ENGINEER. IT SHALL BE UNLAWFUL FOR ANY REASON TO DUPLICATE OR TO MAKE COPIES OF SAID DOCUMENTS FOR USE IN THE REPETITION

APPROVED EDITION OF THE ELECTRICAL CODE, RULES AND REGULATIONS OF THE LOCAL
AND NATIONAL AUTHORITIES CONCERNED IN THE ENFORCEMENT OF ELECTRICAL LAWS AND OFFICE OF BUILDING OFFICIAL
ORDINANCES.
CIRCUIT CIRCUIT
DESCRIPTIONS COUNT WATTS VOLTS AMPERS REMARKS
REPUBLIC ACT 9266 - ALL DRAWINGS AND SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS DULY SIGNED, STAMPED OR SEALED, AS INSTRUMENTS OF SERVICE, ARE THE

2. ADEQUATE AND EFFECTIVE GROUND SHALL BE PROVIDED TO


ALL METALLIC CONDUITS, CABINETS, ENCLOSURES AND
NUMBER BREAKER
RECOMMENDING APPROVAL:
EQUIPMENTS BY MEANS OF COPPER CLAD GROUNDING RODS.
HEAD, ELECTRICAL SECTION DATE
3.NO BRANCH CIRCUIT SHALL HAVE A LOAD OF MORE THAN 80% OF ITS RATING. 23W. LED APPROVED:
01 11 253 220 1.15 15 A. 2-2.0MM SQ. THW
LIGHTING OUTLET
4.ELECTRICAL SERVICE REQUIREMENTS SHALL BE 220 VOLTS, 3-PHASE, 60 HERTZ.
23W. LED
5.ALL SINGLE PHASE LOADS SHALL BE SO CONNECTED TO EFFECT A BALANCED THREE 02 11 253 220 1.15 15 A. 2-2.0MM SQ. THW
PHASE SYSTEM. LIGHTING OUTLET

180W. x 2 GANG
6.ALL MATERIALS TO BE USED SHALL BE NEW AND APPROVED TYPE FOR BOTH PURPOSE 03 03 1,080 220 4.91 20 A. 2-3.50MM SQ. THW
AND LOCATION INTENDED. ALL WIRES SHALL BE INSULATED FOR 600 VOLTS TYPE THW. OR CONVENIENCE OUTLET
TW. AND SHALL BE INSIDE RIGID UPVC PIPES FOR EMBEDDED PIPE. EMT/IMC FOR EXPOSE
PIPES. CIRCUIT BREAKER PANEL BOARD SHALL BE STANDARD FACTORY PRODUCTS. ALL 180W. x 2 GANG BUILDING OFFICIAL DATE
04 03 1,080 220 4.91 20 A. 2-3.50MM SQ. THW
CIRCUIT BREAKERS SHALL BE BOLT-ON TYPE. CONVENIENCE OUTLET
7.WORKMANSHIP SHALL BE EQUAL TO THE BEST STANDARD PRACTICE RECOGNIZED AND
ADOPTED FOR THIS TRADE.

8.ALL ELECTRICAL WORKS AND INSTALLATION HEREIN SHALL BE DONE UNDER THE DIRECT CIRCUIT COMPUTATION:
SUPERVISION OF A DULY LICENSED ELECTRICAL ENGINEER OR HIS REPRESENTATIVE. CIRCUIT NO. 3 CIRCUIT NO. 4
CIRCUIT NO. 1 CONVENIENCE OUTLET CONVENIENCE OUTLET
LIGHTING LOAD 180W x 2 GANG x 3 PCS. = 2,160 W. 180W x 2 GANG x 3 PCS. = 2,160 W.
LED23Wx11 PCS. = 253 W I: 2,160/220 = 9.82 A. I: 2,160/220 = 9.82 A.
I: 322/220= 1.15 A. USE: USE:
USE: 2 PCS.-3.5 MM2 TW COPPER WIRE 2 PCS.-3.5 MM2 TW COPPER WIRE
#06 MMØ TWISTED
2 PCS.-2.0 MM2 TW COPPER WIRE 1 PC. - 15MM ø CONDUIT PIPE 1 PC. - 15MM ø CONDUIT PIPE
ALLUM. SERVICE DROP
SERVICE ENTRANCE COMPUTATION: 1 PC. - 15MM ø CONDUIT PIPE
1 PC. - 15 A. TRIP BREAKER
1 PC. - 20 A. TRIP BREAKER 1 PC. - 20 A. TRIP BREAKER
CABLE 220 V. 1Ø 6 Hp

LIGHTING LOAD - 322 W.


CONVENIENCE OUTLET - 1,080 W.
CIRCUIT NO. 1
LIGHTING LOAD
M
CONVENIENCE OUTLET- 1,080 W.
LED23Wx11 PCS. = 253 W
P= 2,482 W. SERVICE ENTRANCE:
I: 322/220= 1.15 A.
I: 2,482/220= 11.28 A. 2-8 MM² THW CU.
USE:
USE:
2 PCS.-22 MM2 TW COPPER WIRE
1 PC. - 15MM ø CONDUIT PIPE
1 PC. - 60 A. TRIP BREAKER
2 PCS.-2.0 MM2 TW COPPER WIRE
1 PC. - 15MM ø CONDUIT PIPE
1 PC. - 15 A. TRIP BREAKER
LEGEND OF SYMBOLS
23W. LED
LIGHTING OUTLET 60 AMP.

180W
2 GANG OUTLETS 1 15 A.

3 GANG SWITCH
LIGHTING 20 A. 2
3 20 A. POWER

2 GANG SWITCH POWER


M
M METER
GROUND

PANEL BOARD

SWITCH LINE

LIGHTING CIRCUIT LINE

POWER CIRCUIT LINE 02 SINGLE LINE DIAGRAM


E01/E01 SCALE = NOT DRAWN TO SCALE

EXHAUST FAN
01 ELECTRICAL LAYOUT PLAN
E01/E01 SCALE = 1:150 MILLIMETERS

PROJECT TITLE: PREPARED BY : CHECKED BY : PRC NO.: SEAL APPROVED BY : SHEET SET
VALIDITY: E 01
V. M. JHEK BUILDERS
SOONG ROAD, BRGY. POB.
BACUAG, SURIGAO DEL NORTE
CONSTRUCTION OF CONTRACTOR MAINTENANCE CANTEEN PTR NO.:
-E01
RAMIL D. ABARCA
ISSUED DT.: RYUJI EUTANI OF SHEET NO.
PROJECT LOCATION: BARANGAY TAGANITO, CLAVER, SURIGAO DEL NORTE
MASTER ELECTRICIAN PROFESSIONAL ELECTRICAL ENGINEER
ISSUED AT:
ADMINISTRATION MANAGER