Type EQA 99 is a pressure reducing regulator for air or gas, suitable for

multiple applications due to its wide range of inlet pressures which go up to


25 bar and outlet pressures of between 0,0175 bar and 4 bar. Its maximum
flow for natural gas is 5.250 m³/hora.
The 99 regulator is equipped with protection against excesses in regulated
outlet pressure through a manual reset system (shut off device).
These units are specially suitable for those cases in which it is not convenient
to have venting systems installed in order to provide relief safety.
The valve’s body may be threaded or flanged 2” S-150. This type of valves is
commanded through a pilot, which uses the flow as its principle of operation
to cover all ranges of outlet pressures. Two types of pilots are manufactured,
which are interchangeable:
- For low pressures (type. 6351-B) from 0,017 bar up to 0,5 bar.
- For high pressures (type. 6351-S) from 0,5 bar up to 4 bar.
In some cases of high inlet pressures a second stage pilot is incorporated in
order to obtain optimal outlet pressures.

TECHNICAL DATA
End connections: Threated 2” NPT/ 2” flanged S-150
Operation temperature: -20ºC to 60ºC (-10ºF to 140ºF)
Aprox weight: 37 Kg (82,1 Lbs)

MATERIALS
Main body: Carbon steel
Seat orifice: Brass
Diaphragm: Nitrile
Valve disk: Nitrile or Teflon

OUTLET PRESSURE ADJUSTMENT


Turn screw (A) clockwise in order to increase outlet pressures,
and in the opposite direction to decrease it. Screw (B) shall not
be used unless there exist oscillations in outlet pressure when
the valve is operating. Ask for instructions to manufacturer
in order to do this.

Pressure Regulator

99-17
B

A
CAPACITY CHART | Sp. Gravity 0,6 | Ø 1-1/8" Orifice GENERAL DIMENSIONS
Ø 314
Natural Gas Capacity in Nm³/hour
Inlet Outlet Pressure (bar)
Pressure
(bar) 0.017 0.035 0.07 0.14 0.2 0.3 0.35 0.4 0.5 0.55 0.65 0.7
0.07 98
0.14 147 137 119
0.21 175 175 168

260
Ø ½”
0.28 196 196 175 168
0.35 235 235 217 196 175
0.42 256 256 256 235 196 175
0.49 294 277 277 256 235 196 186

210
0.56 315 315 294 277 256 235 217 186
0.63 336 336 336 315 294 277 235 217 196
0.70 357 375 354 336 315 294 277 256 235 196
1.05 473 473 473 473 473 462 434 434 396 396 375 258
153 (Threated) 180 245
1.40 613 613 613 613 613 613 592 553 532 515 494 473
1.75 693 693 693 693 693 693 693 693 693 651 651 634 254 (Flanged)
2.10 770 770 770 770 770 770 770 770 770 770 770 770
2.45 872 872 872 872 872 872 872 872 872 872 872 872
2.80 931 931 931 931 931 931 931 931 931 931 931 931
3.50 1127 1127 1127 1127 1127 1127 1127 1127 1127 1127 1127 1127 INSTALLATION
4.20 1288 1288 1288 1288 1288 1288 1288 1288 1288 1288 1288 1288
5.25 1544 1544 1544 1544 1544 1544 1544 1544 1544 1544 1544 1544
7.00 1960 1960 1960 1960 1960 1960 1960 1960 1960 1960 1960 1960
Generally, the diaphragm box is installed horizontally and the pilot
8.75 2419 2419 2419 2419 2419 2419 2419 2419 2419 2419 2419 2419 downwards, but it can be modified according to the specific
10.50 2835 2835 2835 2835 2835 2835 2835 2835 2835 2835 2835 2835 requeriments. The positions of the body can be varied due to the
12.00 3171 3171 3171 3171 3171 3171 3171 3171 3171 3171 3171 3171
14.00 3567 3567 3567 3567 3567 3567 3567 3567 3567 3567 3567 3567 junction rotation. In this case, the pilot feeding pipe shall be connected
16.00 4064 4064 4064 4064 4064 4064 4064 4064 4064 4064 4064 4064 again. Flow must be checked to follow the direction indicated by the
17.50 4361 4361 4361 4361 4361 4361 4361 4361 4361 4361 4361 4361
21.00 5250 5250 5250 5250 5250 5250 5250 5250 5250 5250 5250 5250
arrow on the body. This type of regulator is provided with two 1/2”
threaded connections, located in the lower box of the diaphragm. One of
Inlet Outlet Pressure (bar)
Pressure them shall be chosen and the other blocked with the cap provided
(bar) 1 1.4 1.75 2.1 2.5 2.8 3.1 3.5 4.2 5.25 7
(important). It shall be connected downstream through a Ø 1/2” pipe
1.40 354
1.75 490 396 and ball valve with a distance of between 400 y 600 mm. from the
2.10 672 553 413 regulator, as can be seen in the installation diagram.
2.45 791 693 592 434
2.80 931 872 753 634 473
3.50 1127 1127 1029 931 830 694 515
4.20 1288 1288 1288 1229 1148 991 889 753
5.25 1544 1544 1544 1544 1544 1467 1348 1229 991
7.00 1960 1960 1960 1960 1960 1960 1960 1960 1743 1463
A
8.75 2419 2419 2419 2419 2419 2419 2419 2419 2419 2181 1586
10.50 2835 2835 2835 2835 2835 2835 2835 2835 2835 2835 2377
12.00 3171 3171 3171 3171 3171 3171 3171 3171 3171 3171 3073
14.00 3567 3567 3567 3567 3567 3567 3567 3567 3567 3567 3567
16.00 4064 4064 4064 4064 4064 4064 4064 4064 4064 4064 4064
17.50 4361 4361 4361 4361 4361 4361 4361 4361 4361 4361 4361
21.00 5250 5250 5250 5250 5250 5250 5250 5250 5250 5250 5250
Note: Please consult us about appopiate flows and orifices for higher inlet pressures (up to 28 Bar).
diseño: www.oryana.com.ar
400 to 600 mm

CAPACITY FORMULA C

Capacity according to orifice - Natural Gas (d=0,6)

Orifices K FACTOR Capacity formula in [m³/Hora]


Ø 3/8" 0.16
Ø 1/2" 0.27
Ø 5/8" 0.41 Capacity = K x QT
Ø 3/4" 0.48 Control line
Ø ½” B
Ø 7/8" 0.6 K = Constant according to orifice. (See chart)
Ø 1-1/8" 1 QT = Capacity according to Ip and Op determined in Ø 1-1/8” orifice figure.
99-17-02 / Abril 2013

EQA S.A.I.C. DISTRIBUIDOR | DISTRIBUTOR


26 de abril 3836 - ITUZAINGO (1714) - Pcia. de Buenos Aires
Tel. (54 11) 4481-9950 y rotativas / Fax.(54 11) 4481-9288
e-mail: eqa@eqa.com.ar - web site: www.eqa.com.ar