HVAC CALCULATIONS
FOR
SWITCHGEAR BUILDING – SABKHA 113
SHAYBAH
PREPARED BY:
OCTOBER 2012
________________________________________________________________________________________________________
1.0 HVAC DESIGN DATA
CONDITION 2
SAES-K-001 100 73 50
Sect. 4.2.1.5
Switchgear Room 75 50
Mechanical Room 75 50
Battery Room 72 50
________________________________________________________________________________________________________
(k) (R)
(t)
(FROM OUTDOOR TO INDOOR) BTU-in ft2-°F-hr
mm (in)
°F-ft2-hr BTU
Outside Surface Resistance - - 0.250
Notes:
a.) Values were obtained from ASHRAE Fundamentals 2001 (IP) Edition, Chapter 29 Table 22.
b.) The roof layer details are taken from Architectural drawings.
Solving for Roof U - VALUE:
Resistance = t/k
U - VALUE = 1 / Total Resistance = 1 / 22.353
2
U - VALUE = 0.045 BTU / hr-ft -°F
SAES-N-004, Para. 4.4: “The overall heat transmission coefficient (U-factor) of insulated roofs, walls,
partitions or floors shall not exceed 0.568 W/(m² °K) or (0.10 Btu/h ft² °F)”. Therefore, calculated Roof U-
factor of 0.054 Btu / hr-ft2-°F is within limit.
________________________________________________________________________________________________________
Inside Vertical Surface Resistance - - 0.680
Notes:
a.) Values were obtained from ASHRAE Fundamentals 2001 (IP) Edition, Chapter 29 Table 22.
b.) The wall layer details are taken from Architectural drawing.
Solving for Wall U - VALUE:
Resistance = t/k
U - VALUE = 1 / Total Resistance = 1 / 13.731
2
U - VALUE = 0.073 BTU / hr-ft -°F
SAES-N-004, Para. 4.4: “The overall heat transmission coefficient (U-factor) of insulated roofs, walls,
partitions or floors shall not exceed 0.568 W/(m² °K) or (0.10 Btu/h ft² °F)”. Therefore, calculated Wall
U-factor of 0.088 Btu / hr-ft2-°F is within limit.
Total
Lighting Ballast
Room Lighting
SI No. Room Name Quantity Fixtures, Factor
No. Wattage
watts 20%
watts
33 2 x 36 1.2 2851
1 Switchgear Room -
1 2 x 36 1.2 96
8 2 x 36 1.2 691
2 Mechanical Room -
1 2 x 36 1.2 96
4 2 x 36 1.2 346
3 Battery Room -
1 2 x 36 1.2 96
NOTE: The lighting wattages are taken from Electrical lighting layout drawings.
________________________________________________________________________________________________________
Total
Zone
Room Name Area, ft2 Quantity Wattages/Unit Watts
No.
Tabulation 1
SI Wattages /
Equipment Description Tag No. Qty Total Watts
No. Unit
TOTAL 45032
________________________________________________________________________________________________________
Heat Loss in Watts
Circuit Breaker Relaying & Vertical Total Heat
Panel Number Cross Bus
Qty. 1200 Amps Breaker Control Bus Loss (watts)
101 1 675 330 410 288 1703
102 1 675 330 410 288 1703
103 1 675 330 410 288 1703
104 1 675 330 410 288 1703
105 1 675 330 410 288 1703
TOTAL 8515
________________________________________________________________________________________________________
________________________________________________________________________________________________________
2.3 RATES OF HEAT GAINS FROM OCCUPANTS
The rates of heat gain from occupants of conditioned spaces are in accordance with ASHRAE
Fundamentals Handbook, 2009 Edition Chapter 29 Table 1. The rates of heat gain for this facility
used on the calculation are as follows:
Type of Activity : Seated, very light works
2.4NUMBER OF OCCUPANTS
Number of Occupants
Number of
Zone Room Area, in Accordance with
Room Name Occupants
No. No. ft² ASHRAE
Layout Used
Std. 62
1 Switchgear Room - 2079 0 - 0
________________________________________________________________________________________________________
Outdoor Air Outdoor
Zone Area, No. of
Room Name Quantity Requirements, Air Used,
No. ft² Persons
CFM CFM
TOTAL 1953
b. In accordance with SAES-K-001, Section 4.4.11.2(a), the minimum amount of outside air shall equal
the greater than 5% of supply air plus all exhaust air.
Based on cooling load calculation:
3.1 The designed cooling loads for the whole system are as follows:
________________________________________________________________________________________________________
Temperature Leaving Dry Bulb : 56.00 °F
Temperature Leaving Wet Bulb : 55.47 °F
Total Cooling Required with Outside Air : 28.50 Tons
Total Heating Required with Outside Air : 63,973 (18.7 kW
The selection of air-cooled condensing units is in accordance with SAES-K-001, Section 4.2.1.7. The
summer design dry bulb temperature at 1% exceedance and the following shall be used:
a. The summer dry bulb temperature at 1% exceedance + 10 °F for facilities within Plant areas.
b. The summer dry bulb temperature at 1% exceedance + 5 °F for facilities located in areas other
than plant areas.
________________________________________________________________________________________________________
________________________________________________________________________________________________________
________________________________________________________________________________________________________
________________________________________________________________________________________________________
________________________________________________________________________________________________________