April 2008
Comfortable energy efficient
kitchen ventilation starts here.
Accurex specializes in ventilation comfort—for restaurants and other food service establishments. Our many top
performing kitchen ventilation products reflect the industry’s latest technological advances and will provide you with a
fully integrated ventilation system that results in a positive, balanced building where customers and employees prefer
to dine and work.
Our state-of-the-art, computer-aided product selection program (CAPS) helps you select and configure products
for your system, view real-time drawings and create AutoCAD files quickly. You’ll also like the friendly, responsive
customer service we provide. Your Accurex representative is just a phone call or e-mail away, and is always
well prepared to help you design a ventilation system that reduces future energy and operating costs.
[]
Selection Chart
Table of Contents
[]
Untempered Make-Up Air Units
XKSFB and XKSFD models are UL Listed XKSFD and XKSFB models are ETL Listed.
for electrical (UL US 705) File no. E40001.
[]
Untempered
Model Overview
Accurex’s untempered make-up air units are specifically designed to provide industry leading performance
and durability for restaurant and other food service applications. Untempered make-up air units are available
in belt drive (XKSFB) and direct drive (XKSFD) arrangements, for maximum performance and flexibility.
Eight available blower sizes provide airflow capacities up to 9,800 cfm (16,650 m³/hr) and static pressure
capabilities up to 2.0 in. wg (497 Pa).
Accurex untempered make-up air units incorporate an industry first hinged design. The hinged design
minimizes installation time, while maximizes access to fan and motor assemblies. Accurex’s untempered
make-up air units feature:
• XKSFB and XKSFD sizes are certified to UL 705
• All blower sizes are tested in our accredited laboratory to ensure accurate fan performance
• Casing is constructed of G90 galvanized steel
XKSFD - 70 - H05
[]
Untempered
Model Comparison
XKSFB. XKSFD.
XKSFB / XKSFD
Model XKSFB (belt drive) and XKSFD (direct drive)
supplies untempered make-up air where
needed. Choose from a downturned or extended
weatherhood. Both are designed to provide
compliance to NFPA 96 when used with a
combination package. Horizontal and downblast
discharge arrangements are available. Airflow ranges
from 800 to 9,800 cfm (1,359 to 16,650 m³/hr).
[]
Untempered
Options and Accessories
XKSFB. XKSFD.
Accessories
Speed Controller – Available on the XKSFD, the Weatherhood – With a combination package, a
speed controller provides an economical means of downturn weatherhood provides a minimum of 36
system balancing. inches of vertical separation between supply and
exhaust air streams and the extended weatherhood
Special Coatings – Permatector™ coating is available provides 10 feet of horizontal separation between supply
for a durable, long lasting finish. Decorative coatings and exhaust streams. Both configurations are designed
are also available in a variety of colors to match existing to satisfy NFPA 96, simplifying the installation while
building fixtures. Consult your Accurex representative meeting codes.
for coating selections.
Supply Voltages – Multiple voltages in single and
Discharge Blower Arrangements – Multiple three phase are available to conveniently match
discharge arrangements are available to meet job- building power.
specific requirements.
Roof Curbs – Prefabricated roof curbs are available
Intake Dampers – Powered or gravity dampers prevent to reduce installation time and costs by ensuring
unintended air transfer between the outside and space. compatibility between the fan and the roof opening.
All curbs are lined with fiberglass insulation to prevent
Unit Mounted Control Center – Factory mounted condensation and to reduce sound levels. Combination
supply fan starter, overloads, and a Class II transformer packages allow an exhaust fan and make-up air fan
for a secondary voltage in the unit. to be mounted on a common curb, with weatherhood
options complying with NFPA 96 Standards. See the
roof curb section in this catalog for more information.
NEMA-3R Remote Starter Control Panel – Provides
power to the supply and exhaust fans through either a
single-point connection or multiple power connections.
Starters, disconnects, Class II transformers, and fusing
is provided for each voltage source.
• Multiple supply voltages
• Wide range of horsepower
• Disconnect switch(es)
• Control transformer for low voltage remote switching
• Terminal strips
• Fuse blocks
• Electronic motor overload protection
[]
Untempered
Combination Packages
XKSFB. XKSFD. 10 ft.
Combination Packages
With either ten feet of horizontal separation or three Accurex combination packages are specifically
feet of vertical separation, Accurex has a combination designed to comply with NFPA 96, which states:
package for your requirements. The Accurex • Exhaust duct must terminate at least 24 in. above
combination package simplifies installation and the roof deck.
reduces field labor costs. This pre-engineered design • Fan discharge must terminate at least 40 in. above
offers the benefit of only one roof penetration for both the roof deck.
supply and exhaust ducts, while ensuring complete • There must be at least 10 ft. of horizontal or 3 ft.
compatibility and interface between the supply fan, of vertical separation between the intake and
exhaust fan, curb and combination extension. exhaust discharge.
Note: Consult local codes and the authority having jurisdiction if there are questions concerning the use of this
product.
Standard Arrangements
Models XKSFB and XKSFD have a compact
design that is available in both downblast
discharge (arrangement DB) and horizontal
discharge (arrangement HZ). Installations may
be as stand alone supply fans as pictured at
right or as combination packages with exhaust
and supply fans on a common curb.
Arrangement
3 ft. DB Arrangement HZ
[]
[]
Direct Gas-Fired Units
XDG and XDGK models shall be ETL Listed to ANSI Z83.4 and CAN 3.7.
XDGX shall be ETL Listed to ANSI Z83.4-1999, CSA 3.7-M99 (for 100% outdoor air) or ANSI Z83.18-
2000 (for recirculation).
[ 10 ]
Direct Gas-Fired
Model Overview
Accurex direct gas-fired heaters provide tempered make-up air to restaurant and other food service facilities.
Accurex direct gas-fired heaters use an ultra-efficient line burner to reduce energy costs, while maintaining
tight temperature control. The line burners are constructed of durable stainless steel mixing plates and cast
aluminum manifolds for years of reliable performance. Three models of direct gas-fired make-up air units
are available to serve a variety heating and cooling applications. Seven available blower sizes provide airflow
capacities up to 15,000 cfm (25,485 m³/hr) and static pressure capabilities up to 2.0 in. wg (497 Pa).
A wide range of direct gas-fired line burners, with capacities up to 2,000,000 BTU/hr, provide efficient heating
in any climate. Direct-gas-fired heater housings incorporate a flexible design, and are constructed of durable
G90 galvanized steel suitable for indoor and outdoor installations. Accurex’s direct gas-fired heaters are
available with a wide range of construction and control accessories for maximum flexibility and performance.
Accurex’s direct gas-fired make-up air units feature:
• High-quality cast aluminum burners with stainless steel mixing plates and Maxitrol electronic modulation
burner control
• Variable volume ventilation capabilities provide energy savings, increased equipment life and enhance
employee comfort
• All Accurex direct gas-fired heaters are certified to the ANSI Z83.4 safety standard
• All blower sizes are tested in our accredited laboratory to ensure accurate fan performance
[ 11 ]
Direct Gas-Fired
Model Comparison
XDGK. XDG. XDGX.
XDGK
Model XDGK is designed to be the most
economical, compact, and simple approach to
100% outdoor air kitchen applications. Airflow voumes
range from 1,500 to 8,500 cfm (2,548 to 14,442 m³/hr)
with heating capacities up to 800,000 BTU/hr.
XDG
Model XDG sets the standard for an efficient
approach to 100% outdoor air applications. Airflow
volumes range from 800 to 15,000 cfm (1,359
to 25,485 m³/hr) with heating capacities up to
1,600,000 BTU/hr.
Cooling options:
• Evaporative cooling up to 12,000 cfm (20,388 m³/hr)
XDGX
Model XDGX is a highly configurable, 100% efficient
direct gas-fired heating and ventilating unit. It’s
modular design provides the most configuration
flexibility and expanded heating and airflow
capacities, which is designed for providing make-up
air to commercial and industrial facilities. In addition
to 100% outdoor air operation, variable volume
airflow options are available. Airflow volumes range from
800 to 15,000 cfm (1,359 to 25,485 m³/hr) with heating
capacities up to 2,000,000 BTU/hr.
Cooling options:
• Evaporative cooling up to 15,000 cfm (25,485 m³/hr)
• Chilled water or direct expansion (DX) cooling up to 11,000 cfm (18,689 m³/hr)
• Evaporative cooling options are available for combination heating and cooling requirements.
[ 12 ]
Direct Gas-Fired
Standard Construction Features
XDGK.
Durable Construction – Designed for maximum Access Panels – Large access panels are provided for
weather resistance, XDGX housings are constructed easy inspection and maintenance of motors, drives, fan
of heavy-gauge G90 galvanized steel. Lifting lugs are wheels, filters, and heater controls.
standard. XDGX only.
Factory Wired and Tested – All
Direct Gas-Fired System – Accurex’s direct gas-fired units are tested prior to shipment.
make-up air units feature: Units are checked for proper
• High-quality cast operation of the gas train, electrical
aluminum burners components and airflow.
with stainless steel
mixing plates, for rust- Weatherhood – A filtered
free operation weatherhood with G90
• Maxitrol electronic galvanized steel construction
modulation is standard. The filtered
burner control weatherhood includes aluminum
mesh filters mounted in the
• 25:1 turn down ratio intake, eliminating the need for
an additional filter section.
Control Center – The control center includes the
following standard components: Discharge Temperature Control – Control of discharge
• Magnetic motor starter air temperature is accomplished with a standard factory
• Control transformer installed sensor located at the fan discharge. A Maxitrol
14 system modulates the gas valve to provide the
• Disconnect switch desired discharge temperature.
Premium grade control components are selected for
reliable operation. All electrical components are UL Fiberglass Insulation – Standard 1-inch foil-faced
Listed, Recognized or Classified and factory prewired fiberglass insulation is used to line the housing,
for single point power connection. preventing condensation and forming an acoustical
barrier.
Reliable Fan Performance/Durable Construction –
Air performance ratings Inlet Air Sensor – An on/off type duct stat automatically
from Accurex’s accredited energizes the gas system when the inlet air temperature
test chamber ensure falls below the desired setting.
accurate data.
Double-width, double inlet,
forward-curved wheels for
high-efficiency and low
sound levels are constructed of heavy-gauge steel.
Wheels are statically and dynamically balanced
to ensure vibration-free operation. The entire fan
and motor assembly is mounted on vibration
isolators to minimize noise transmission
into the building. Adjustable motor sheaves
are standard.
Designed for maximum weather resistance, XDGK
housings are constructed of heavy-gauge G90
galvanized steel. Lifting lugs are standard.
[ 13 ]
Direct Gas-Fired
Standard Construction Features
XDG. XDGX.
Durable Construction – Designed for maximum Vibration Isolators – The entire fan and motor
weather resistance, XDGX and XDG housings are assembly is mounted on vibration isolators to
constructed of heavy-gauge G90 galvanized steel. minimize noise transmission into the building.
Lifting lugs are standard. XDGX only.
Reliable Fan Performance – Air performance
ratings from Accurex’s test chamber ensure
Direct Gas-Fired System – Accurex’s direct gas-fired accurate data.
make-up air units feature:
Double-width, double inlet,
• High-quality cast forward-curved wheels for
aluminum burners high-efficiency and low sound
with stainless steel levels are constructed of
mixing plates heavy-gauge steel. Wheels
• Maxitrol electronic are statically and dynamically
modulation balanced to ensure vibration-free operation.
burner control
• 25:1 turn down ratio
Access Panels – Large access panels are provided for
easy inspection and maintenance of motors, drives, fan
Control Center – The control center includes the wheels, filters, and heater controls.
following standard components:
• Magnetic motor starter Factory Wired and Tested – All units are tested prior
• Control transformer to shipment. Units are checked for proper operation
• Disconnect switch of the gas train, electrical
components and airflow.
Premium grade control components are selected for
reliable operation. All
electrical components are
UL Listed, Recognized
or Classified and factory
prewired for single point
power connection.
[ 14 ]
Direct Gas-Fired
Options and Accessories
XDGK. XDG. XDGX.
Weatherhoods
Weatherhoods with standard G90 galvanized steel construction are available.
[ 15 ]
Direct Gas-Fired
Options and Accessories
XDGK. XDG. XDGX.
Special Coatings – Permatector™ coating is available Exhaust Fan Starter(s) – Exhaust fan starters are
for a durable, long lasting finish. Decorative coatings available factory mounted and wired. Exhaust fan
are also available in a variety of colors to match existing starters allow for an electrical interlock between the
building fixtures. Consult your Accurex representative for supply and exhaust fan(s).
coating selections. Freeze Protection – Electronic freeze protection is
Roof Curbs – Factory provided roof curbs are available available to automatically shut down the supply fan
to ensure compatibility between the make-up air unit when the discharge temperature is below the adjustable
and roof curb. Standard construction is G90 galvanized set point for an extended amount of time. This prevents
steel. See the roof curbs section in this catalog for the unit from discharging non-tempered air into the
more information. building and freezing pipes and other temperature
Duct Adapter – Duct adapter is available with factory sensitive items.
supplied roof curbs. The duct adapter allows for easy Inlet Air Sensor (Heat) – The heating inlet air sensor
alignment of the supply duct connection. will automatically turn the heat on and off based on the
V-Bank Filter Section – V-bank filter sections are outdoor air temperature.
available with 2-inch washable aluminum mesh or 2-inch Service Receptacle – A 115 volt GFCI outlet is
30% efficient disposable filters. mounted externally in a NEMA-3R box for the
Weatherhoods – Three weatherhoods are available: convenience of service personnel. A separate 115 volt
birdscreen, filtered, and louvered. Standard construction power source is required.
is G90 galvanized steel. Auxiliary Contacts – Normally open and normally
Motorized Dampers – Intake or discharge dampers are closed contacts are available for supply fan status and
available to prevent backdrafts when the supply fan is supply fan interlocks.
not in operation. Intake dampers are factory mounted Air Filter Gauge – Indicates when filters become
and wired. Discharge dampers ship loose for field dirty. An indicator light may be wall/beam mounted or
mounting in the supply air duct. provided with a remote control panel.
Fiberglass Insulation – One inch fiberglass insulation is Propane Gas – A propane heater may be provided in
available to line the housing to prevent the formation of lieu of natural gas.
condensation and to form an acoustical barrier. Gas Pressure Regulator – Required if building
Double Wall Construction – An interior metal liner is gas line pressure exceeds the maximum inlet gas
available to isolate the 1-inch fiberglass insulation from pressure of the make-up air unit. Ships separately for
the airstream. field installation.
[ 16 ]
Direct Gas-Fired
Options and Accessories
XDG. XDGX.
Temperature Controls
Discharge DDC Interface – Discharge
Temperature The discharge Temperature
Control – temperature can be Control with Room
Control of controlled by a DDC Override – The room
discharge air signal. The DDC override option,
temperature is options provides a factory installed available with the
accomplished interface, allowing easy integration Maxitrol 14 system,
with a factory installed sensor into your building management boosts the discharge temperature
located at the fan discharge. A system. The discharge temperature when the space temperature is too
Maxitrol 14 system modulates the can be controlled using a 2-10 VDC cool. Discharge sensor is factory
gas valve to provide the desired or 4-20 mA signal. installed. Room sensor may be
discharge temperature. wall/beam mounted or included on
a remote control panel.
Discharge Options
Cooling Options
Cooling Coils – Chilled water or direct expansion (DX) cooling is available (XDGX
only). The cooling section includes the cooling coil, sloped stainless steel drain pan
and insulated double wall construction. Drain and coil connections are stubbed
through the wall for convenience.
For proper coil sizing, contact your local Accurex representative. Four-row and six-
row chilled water or DX coils are available with airflow capacities up to 11,000 cfm
(18,689 m³/hr).
Cooling coil sections are installed upstream of the fan section for a draw through
arrangement and provide a streamlined transition to adjacent sections. DX coils
require remote condensing units.
[ 17 ]
Direct Gas-Fired
Options and Accessories
XDGK. XDG. XDGX.
[ 18 ]
Direct Gas-Fired
Installation
XDGK. XDG.
Combination Packages
Kitchen Combination Package
The Accurex combination package simplifies
installation (model XDG only) and reduces field
labor costs. The pre-engineered design ensures
that the supply fan, exhaust fan, curb, and
combination extension components interface
properly for kitchen ventilation applications.
Equally important, Accurex combination packages
are specifically designed to comply with NFPA 96.
Combination Package - Arrangement DBC
NFPA 96 states:
• Exhaust duct must terminate at least 24 inches Note: Consult local codes and the authority having jurisdiction
above the roof deck if there are questions concerning the use of this product.
• Fan discharge must be at least 40 inches
above the roof deck
• Air intake shall have a horizontal separation of
10 feet from the exhaust discharge
[ 19 ]
Direct Gas-Fired
Installation
XDGX.
Variable Volume
The variable volume Airflow Control Strategies – Accurex offers four
option is recommended methods of controlling the make-up air volume.
when a building’s All three vary the fan speed for maximum energy
exhaust volume will savings.
vary. The make-up air • Variable frequency drive controlled by cooking load
volume will track with
the exhaust volume, • Variable frequency drive controlled by a 2-10 VDC
providing only the or 4-20 mA signal
necessary amount of make-up air. • 2-speed motor controlled manually with a
The system monitors the cooking operation and remote switch
adjusts the exhaust, supply and rooftop unit fans on Burner Bypass Damper – The variable volume
demand so when the cooking load is reduced, the option includes a patented burner bypass damper,
fans operate at a reduced level. This reduces the which maintains the pressure drop across the burner
amount of energy used to run the fans and temper air. as air volumes change. This assures that complete
The variable volume option saves energy by reducing and proper combustion occurs. The bypass damper
both electric and gas consumption, whenever make- is self-adjusting, designed for minimal maintenance,
up air requirements are less than the maximum. and requires no controls.
Outside Air
Supply Air
[ 21 ]
Indirect Gas-Fired Units
XIG and XIGX models are ETL and cETL Listed to ANSI Z83.8-2002 and CGA 2.6.
Indirect gas-fired units are Listed to UL1995.
Both are harmonized standards between USA and Canada.
[ 22 ]
Indirect Gas-Fired
Model Overview
Accurex indirect gas-fired heaters provide tempered make-up air to restaurants and other food service facilities.
Accurex indirect gas-fired heaters use an 80% efficient tubular style heat exchanger for high performance and tight
temperature control. Accurex’s heat exchanger design features horizontally firing burners and power venting with
post purge cycle, which together provide flexibility, maximum heat exchanger life, and make stainless steel burners
unnecessary and drip pans obsolete. Two models of indirect gas-fired make-up air units are available to serve a
variety heating and cooling applications. Seven available blower sizes provide airflow capacities up to 15,000 cfm
(25,485 m³/hr) and static pressure capabilities up to 2.0 in. wg (497 Pa).
A wide range of indirect gas-fired heaters, with capacities up to 1,200,000 BTU/hr, provide efficient heating in
any climate. Indirect gas-fired heater housings incorporate a flexible design, and are constructed of durable G90
galvanized steel suitable for indoor or outdoor installations. Accurex indirect gas-fired heaters are available with a
wide range of construction and control accessories for maximum flexibility and performance.
• All Accurex indirect gas-fired heaters are certified to the ANSI Z83.8 safety standard
• All blower sizes are tested in our accredited laboratory to ensure accurate fan performance
• Up to 8:1 staged turndown and 4:1 modulating turndown per furnace
[ 23 ]
Indirect Gas-Fired
Model Comparison
XIG. XIGX.
XIG
Model XIG features a unique indirect furnace that
includes an integrated downturned plenum. This
eliminates the need for an additional section to
achieve a downblast discharge.
Model XIG is ideally suited for make-up air
applications where a direct gas-fired system is
not appropriate. The XIG is a single-piece housing
offering simplicity in an economical design for
indoor or outdoor applications. These units come
standard with vibration isolators, downturn plenum,
furnace control, and optional accessories are
available including special coatings, freeze protection, and motorized dampers.
Airflow volumes range from 800 to 7,000 cfm (1,359 to 11,893 m³/hr) with heating capacities up to 400,000
BTU/hr (input).
Cooling options:
• Evaporative cooling up to 7,000 cfm (11,893 m³/hr)
XIGX
Model XIGX expands on the XIG model with a
modular design that offers broad configuration
flexibility and higher capacities.
Model XIGX is ideally suited for indirect gas-fired
make-up air applications where a direct gas-fired
system is not appropriate. The XIGX has a modular
design for broad configuration flexibility. In addition
to 100% outdoor air operation, variable volume
airflow options are available.
Airflow volumes range from 800 to 15,000 cfm
(1,359 to 25,485 m³/hr) with heating capacities up
to 1,200,000 BTU/hr (input).
Cooling options:
• Evaporative cooling up to 14,000 cfm (23,786 m³/hr)
• Chilled water or DX cooling up to 11,000 cfm (18,689 m³/hr)
[ 24 ]
Indirect Gas-Fired
Standard Construction Features
XIG. XIGX.
Indirect Gas-Fired Furnaces – Accurex’s indirect gas- Integrated Downturn Plenum – Accurex’s unique
fired make-up air units feature: indirect furnace design includes an integrated
• Power vented with post purge cycle downturned plenum, eliminating the need for an
additional section to achieve a downblast discharge.
• ETL Listed to ANSI standard Z83.8 and CGA 2.6 (Model XIG only)
• 80% thermal efficiency
• Gas control options include up to 8:1 staged Durable Construction – Designed for maximum
turndown and up to 4:1 modulating turndown weather resistance, XIG housings are constructed of
• Aluminized steel or stainless steel heat exchanger heavy-gauge G90 galvanized steel. Insulated double
wall construction and lifting lugs are standard.
• Direct spark ignition system
• Easy access burner controls Reliable Fan Performance – Air
• Insulated double wall construction performance ratings from Accurex’s
accredited test chamber ensure
Control Center – The accurate data.
control center includes Double-width, double inlet
the following standard forward-curved wheels for high-
components: efficiency and low sound levels
• Magnetic motor are constructed of heavy-gauge
starter with solid state steel. Wheels are statically and
overload protection dynamically balanced to ensure
vibration-free operation.
• Control transformer
with fusing
Access Panels – Large access panels are provided for
• Disconnect switch easy inspection and maintenance of motors, drives, fan
• Separately fused motor wheels, filters, and heater controls.
• Distribution terminal strip
Premium grade control components are selected to Factory Wired and Tested – All units
provide you with years of reliable operation. are tested prior to shipment to ensure
All electrical components are UL Listed, Accurex’s high level of quality. Units
Recognized or Classified and factory prewired are checked for proper fan, furnace
for single point power connection. and controls operation.
[ 25 ]
Indirect Gas-Fired
Installation
XIG. XIGX.
Installation
Downblast or Horizontal Discharge
Model XIGX is available in either downblast (arrangement DB) or
horizontal (arrangement HZ) discharge. Accurex’s furnace design
features an integrated downturned plenum, eliminating the need
for an additional section to achieve a downblast discharge.
Indoor air is used for combustion. Outdoor air is used for combustion. Outdoor air is used for combustion.
Combustion by-products vent Combustion by-products vent Combustion by-products vent
outdoors through a vent line. outdoors through a vent line. outdoors through a vent line. Only
Requires one opening for each line. one opening is needed.
[ 26 ]
Indirect Gas-Fired
Options and Accessories
XIG. XIGX.
Cooling Options
Evaporative Cooling – Adding evaporative cooling may simply be done by adding
an evaporative cooling section. The evaporative cooling section includes a galvanized
steel housing with a louvered intake, 2-inch aluminum mesh filters and a stainless steel
evaporative cooling module. The evaporative cooling media is Munters CELdek or
GLASdek and has a depth of 12 inches for 90% cooling effectiveness.
The entire section mounts directly to the front of the unit, eliminating transition or
ductwork by others. Drain and overflow are conveniently tapped through the side of the
cooling section. The supply line connection is field located where convenient. Freeze
protection, automatic drain & fill, and the Water Wizard™ are available.
Airflow capacities for evaporative cooling is up to 14,000 cfm (23,786 m³/hr). The
evaporative cooling section for the housing size 32 ships separately.
Cooling Coils – Chilled water or direct expansion (DX) cooling is available with the
model XIGX. The cooling section includes the cooling coil, sloped stainless steel drain
pan and insulated double wall construction. Drain and coil connections are stubbed
through the wall for convenience.
For proper coil sizing, contact your local Accurex representative. Four-row and six-
row chilled water or DX coils are available with airflow capacities up to 11,000 cfm
(18,689 m³/hr).
Cooling coil sections are installed upstream of the fan section for a draw through
arrangement and provide a streamlined transition to adjacent XIGX sections. DX coils
require remote condensing units.
[ 27 ]
Indirect Gas-Fired
Options and Accessories
XIG. XIGX.
Furnace Control
Choose from staged or modulating furnace control.
Temperature Control
Discharge Temperature Control – Discharge Temperature Control
Model XIG and XIGX controls with Room Override – The
heat output based on discharge room override option enables
temperature. A factory mounted a make-up air unit to boost its
discharge temperature sensor feeds heat output when the space
information back to the unit control temperature is cooler than desired.
center. The furnace(s) either stage or When the space temperature is
modulate the heat output to satisfy satisfied, the XIG and XIGX will
the discharge temperature set point. control heat output based on the
The set point is easily field adjustable normal discharge temperature
with a dial located in the furnace control center. For set point. When the space is too cool, the discharge
make-up air applications, single-stage furnace control is temperature will be elevated, typically by 20°F (-7°C),
not recommended. until the override thermostat is satisfied. Room sensor
may be wall/beam mounted or included on a remote
control panel.
[ 28 ]
Indirect Gas-Fired
Options and Accessories
XIG. XIGX.
Weatherhoods
Weatherhoods with standard G90 galvanized steel construction are available.
[ 29 ]
Indirect Gas-Fired
Options and Accessories
XIG. XIGX.
Air Filter Gauge – Indicates when filters become Special Coatings – Permatector™ powder coating
dirty. An indicator light may be wall/beam mounted or is available if a painted look is desired. Decorative
provided with a remote control panel. baked enamel coatings are also available in a variety of
Motorized Dampers – Intake or discharge dampers colors to match existing building fixtures. Consult your
are available to prevent backdrafts when the fan is Accurex representative for coating selections.
not in operation. Intake dampers are factory mounted Fiberglass Insulation – Fiberglass insulation is
and wired. used to line the housing to prevent the formation of
Exhaust Fan Starter(s) – Up to 2 exhaust fan starters condensation and to form an acoustical barrier.
may be added to the control center. 2-Speed Motor – A 1⁄3 reduction 2-speed motor
Inlet Air Sensor – An on/off type duct stat is available, provided that the temperature rise at
automatically de-energizes the gas system and maximum output is within acceptable limits for
interrupts the flow of gas to the burners when the inlet both speeds.
air temperature is above the desired setting. Variable Frequency Drive – A variable frequency drive
115 Volt Service Receptacle – A 115 volt GFCI is available to automatically vary the fan speed.
outlet is mounted externally in a NEMA-3R box for the Propane Gas – A propane heater may be provided in
convenience of field service personnel. A separate 115 lieu of natural gas.
volt power source is required.
Duct Adapter – Duct adapter is available with factory
Roof Curbs – Factory provided roof curbs are supplied curbs and allows an easy method for
available to ensure compatibility between the make-up connecting ductwork to curb.
air unit and roof curb. Standard construction is G90
Double Wall Construction – An interior metal liner is
galvanized steel. See the roof curbs section in this
available to isolate insulation from the airstream. One
catalog for more information.
inch thick insulation is included with this option.
Equipment Supports – Factory provided equipment
Gas Pressure Regulator – Required if building gas
supports may be required in addition to a roof
line pressure exceeds the maximum inlet gas pressure
curb, depending on the specified unit configuration.
of 14 in. wg.
Standard construction is G90 galvanized steel.
Weatherhood – A galvanized steel weatherhood with
Freezestat – An on/off type discharge duct stat
birdscreen is standard on 100% outdoor air units. A
(with a timer) prevents the discharge of cold air into
louvered intake is optional.
the building when the furnace(s) is not providing
adequate tempering.
[ 30 ]
Indirect Gas-Fired
Options and Accessories
XIG. XIGX.
XIG XIGX
Cooling Options
Evaporative Optional Optional
Chilled Water — Optional
Direct Expansion (DX) — Optional
Furnace Control
Staged Control Optional Optional
Modulation Control Optional Optional
Temperature Controls
Discharge Temperature Control Optional Optional
Discharge Temperature Control w/ Room Override Optional Optional
DDC Interface — Optional
Intake Options
Birdscreen Optional Optional
Filtered — Optional
Louvered Optional Optional
Remote Control Panels
XFCC Optional Optional
Kitchen Style Optional Optional
Accessories
Air Filter Gauge Optional Optional
Motorized Dampers Optional Optional
Exhaust Fan Starter(s) Optional Optional
Inlet Air Sensor Optional Optional
115 Volt Service Receptacle Optional Optional
Roof Curbs Optional Optional
Equipment Supports — Optional
Freezestat Optional Optional
Special Coatings Optional Optional
Fiberglass Insulation Optional Optional
2-Speed Motor — Optional
Variable Frequency Drive (VFD) — Optional
Propane Gas Optional Optional
Duct Adapter Optional Optional
Double Wall Construction — Optional
Gas Pressure Regulator — Optional
Weatherhood Optional Optional
Aluminum or Stainless Steel Heat Exchanger Optional Optional
[ 31 ]
Modular Supply Units
[ 32 ]
Modular Supply
Model Overview
Accurex’s non-gas-fired units are designed to provide fresh make-up air to restaurants and other food service
facilities where natural or propane gas is either not available or not desired for heating. The Accurex model XMSX
utilizes coil heating and/or cooling tempering options for high performance operation. Seven available blower sizes
provide airflow capacities up to 15,000 cfm (25,485 m³/hr) and static pressure capabilities up to 2.0 in. wg (497 Pa).
All blower sizes are tested in our accredited laboratory to ensure accurate fan performance.
Electric heating coils with SCR control, hot water, and/or steam heating, provide efficient heating in any climate when
gas-fired equipment is not an option. Chilled water, direct expansion, and evaporative coolers provide cooling when
required. XMSX housings incorporate a flexible design, and are constructed of durable G90 galvanized steel suitable
for indoor or outdoor installations. Accurex XMSX make-up air units are available with a wide range of construction
and control accessories for maximum flexibility and performance.
Model
XMSX - Modular Supply Non-Gas-Fired
Housing Size
Models ending in X indicate modular construction
12 — 32
Blower Quantity Blower Size
1, 2 or 3 08 — 36
[ 33 ]
Modular Supply
Standard Construction Features
XMSX.
Model XMSX is ideally suited for make-up air applications where hot water, steam or electric heat is desired. The
XMSX has a modular design for broad configuration flexibility. In addition to 100% outdoor air operation, recirculation
and variable volume airflow options are available.
Airflow volumes range from 800 to 15,000 cfm (1,359 to 25,485 m³/hr). These units feature belt driven, double-
width, forward-curved fans, vibration isolation, intake filters, and a variety of heating and cooling options.
Heating options: Cooling options:
• No heat up to 15,000 cfm (25,485 m³/hr) • Evaporative cooling up to 45,000 cfm (76,455 m³/hr)
• Hot water up to 15,000 cfm (25,485 m³/hr) • Chilled water or DX cooling up to 11,000 cfm (18,689 m³/hr)
• Steam up to 15,000 cfm (25,485 m³/hr)
• Electric heat up to 15,000 cfm (25,485 m³/hr)
Reliable Fan Performance – Air performance ratings Vibration Isolators – The entire fan
from Accurex’s accredited and motor assembly is mounted on
test chamber ensure accurate vibration isolators to minimize noise
data. Double-width, double inlet transmission to the building.
forward-curved wheels for high- Durable Construction – Designed for maximum
efficiency and low sound levels weather resistance, XMSX housings are constructed
are constructed of heavy-gauge of heavy-gauge G90 galvanized steel. Lifting lugs
steel. Wheels are balanced to are standard.
ensure vibration-free operation.
Shafts – Shafts are precision turned, ground and
Control Center (Optional) – The control center polished steel sized so that the first critical speed is at
includes the following standard components: least 25% over the maximum operating speed.
• Magnetic motor starter with solid state overload Bearings – Shafts rotate in permanently lubricated,
protection heavy-duty ball bearings. Bearings are selected for a
• Control transformer minimum average (L10) life in excess of 100,000 hours
with fusing at maximum operation speeds.
• Disconnect switch Access Panels – Large access panels are provided for
• Individual motor fusing easy inspection and maintenance of motors, drives, fan
wheels, filters, and heater controls.
• Distribution terminal
strip Factory Wired and Tested – All units are tested prior
to shipment. Units are checked for proper fan and
Premium grade control components are selected for controls operation.
reliable operation. All electrical components are UL
Listed, recognized or classified and factory prewired for
single point power connection.
[ 34 ]
Modular Supply
Options and Accessories
XMSX.
Heating Options
Hot water, steam and electric heating options are available with the model XMSX. The heating section consists of
the heating coil factory installed in a pre-engineered coil housing.
For proper coil sizing, contact your local representative. All heating options are available with airflow capacities up to
15,000 cfm (25,485 m³/hr).
Cooling Options
Cooling Coils – Chilled water or direct expansion (DX) cooling is available with the
model XMSX. The cooling section includes the cooling coil, sloped stainless steel
drain pan and insulated double wall construction. Drain and coil connections are
stubbed through the wall for convenience.
For proper coil sizing, contact your local representative. Four-row and six-row
chilled water or DX coils are available with airflow capacities up to 11,000 cfm
(18,689 m³/hr).
Cooling coil sections are installed upstream of the fan section for a draw through
arrangement and provide a streamlined transition to adjacent XMSX sections. DX
coils require remote condensing units.
[ 35 ]
Modular Supply
Options and Accessories
XMSX.
Air Filter Gauge – The air filter gauge indicates when Freezestat – An on/off type discharge duct stat (with a
filters become dirty. An indicator light may be wall/beam timer) prevents the discharge of cold air into the building
mounted or provided with a remote control panel. when the unit is not providing adequate tempering.
Motorized Dampers – Intake or discharge dampers Equipment Supports – Factory provided equipment
are available to prevent backdrafts when the fan is supports may be required in addition to a roof curb,
not in operation. Intake dampers are factory mounted depending on the specified unit configuration. Standard
and wired. construction is G90 galvanized steel.
Exhaust Fan Starter(s) – Exhaust fan starters may be Special Coatings – Permatector™ powder coating is
added to the control center. available if a painted look is desired. Decorative baked
enamel coatings are also available in a variety of colors
Inlet Air Sensor – An on/off type duct stat automatically to match existing building fixtures. Consult your Accurex
de-energizes the gas system and interrupts the flow representative for coating selections.
of gas to the burners when the inlet air temperature is
above the desired setting. Fiberglass Insulation – Fiberglass insulation is
used to line the housing to prevent the formation of
115 Volt GFCI Service Receptacle – A 115 volt GFCI condensation and to form an acoustical barrier.
outlet is mounted externally in a NEMA-3R box for the
convenience of field service personnel. A separate 115 Weatherhood – A galvanized steel weatherhood with
volt power source is required. birdscreen is available. A DRIFdek mist eliminator is an
optional weatherhood accessory.
Roof Curbs – Factory provided roof curbs are available
to ensure compatibility between make-up air unit and Duct Adapter – Duct adapter is available with factory
roof curb. Standard construction is G90 galvanized supplied curbs and allows an easy method for
steel. See the roof curbs section in this catalog for more connecting ductwork to curb.
information.
Double Wall Construction – An interior metal liner is
2-Speed Motor – A 1⁄3 reduction 2-speed motor is available to isolate insulation from the airstream. One
available. Consult the factory for 1⁄2 reduction 2-speed inch thick insulation is included with this option.
motor availability.
Variable Frequency Drive – A variable frequency drive
Smoke Detector – Photoelectric smoke detector is is available to automatically very the fan speed.
available for duct mounting.
[ 36 ]
Modular Supply
Installation
XMSX.
Arrangements
Arrangement HZ
[ 37 ]
Packaged Rooftop Units
[ 38 ]
Packaged Rooftop
Model Overview
The restaurant industry is ever growing, ever changing, and more competitive than ever. Owners today are acutely
aware that restaurant comfort is becoming more important for both their customers and their employees. Humidity
and temperature swings upset customers, affect employee productivity and morale, damage buildings, reduce the
life of décor, and destroy perishable food products such as baked goods. Traditional kitchen design used a dedicated
make-up air unit, and one or more small rooftop units with limited outside air capabilities to achieve ventilation
requirements, delivering marginal comfort. A superior alternative is Accurex’s packaged rooftops, which offer the
opportunity to introduce 50‑100% outside air into a unit that heats, cools and dehumidifies, yielding a safe and
comfortable environment for diners and employees.
XVPR - 210 - 20 A - 40 I - A
Model Electrical
XVPR - Packaged Unit With Cooling A - 208V, 3-Phase, 60 Hz
and Heating B - 230V, 3-Phase, 60 Hz
C - 460V, 3-Phase, 60 Hz
Cabinet Size Heating Type
1, 2 or 3 I - Indirect Gas-Fired Heat
Series Number J - Indirect Gas-Fired Heat With Temperator
T - Temperator Only
10 - (e.g. Version 1.0) X - None or Heat Pump
Nominal Cooling Capacity in Tons Nominal Heat Input in MBH/10
Cooling Type When Heating Type = I, J, D, W, S
A - Packaged Air Cooled With Reheat Nominal Heat Input in kW/10
B - Packaged Air Cooled With No Reheat
When Heating Type = E, T
X - None
[ 39 ]
Packaged Rooftop
Standard Construction Features
XVPR.
Casing – The casing is a 2-inch thick double-wall with Indirect Gas Furnace – Consists of a stainless steel
expanded polyurethane foam insulation. Foam insulation heat exchanger with modulating control valve and a 4:1
will not slough and creates very rigid, durable panels. turn down ratio.
More importantly, the foam will not absorb water or R-22 Scroll Compressors – Multiple compressor units
support mold growth. Cabinet includes hinged, toolless have two independent refrigeration circuits, providing
panels to provide quick and easy access to components. efficient cooling and up to four stages of control.
Hinged access protects both the access panels and the Compressors are protected by high/low-pressure
roof material during service. switches and include a five-year parts warranty.
Thermal Break Panels – Casing panels are 2-inch thick Control System – To handle the demands of 100%
thermal break construction. outside air and humidity control, the XVPR is provided
Pullout Intake Hood – Intake ships flush to the unit to with a powerful DDC system. The system offers flexible
reduce shipping and storage footprint, and minimizes the sequences, open protocol communications (BACnet,
risk of damage during unit installation. LonTalk, Modbus), internet connectivity, and a standard
Dampers – Galvanized steel frame and blades, supplied unit mounted display (LCD) with keypad.
with direct-coupled electric actuators. Electrical Panel – Unique electrical panel design allows
Air Filtration – 2-, 4- or 6-inch pleated media filters are an operator to adjust controls without disabling the
located in the mixed air chamber upstream of the cooling disconnect. All high-voltage components are housed
coil. Standard filters include a MERV 8 rating. within the panel creating a safer environment when
servicing the unit.
Cooling Coil – 6-row intertwined DX slab coil ensures
moisture removal for superior humidity control. Coil Supply Air – Supply air can exit the unit vertically
capacity is controlled via thermostatic expansion valves. downward through the floor or horizontally outward
Both coil faces are easily accessible for cleaning. through the side of the unit. Special curbs or curb
adaptors are not required for horizontal discharge.
Direct Drive Fans with VFDs – The XVPR’s direct
drive supply fans eliminate the maintenance, downtime,
noise, and vibration associated with typical belt-driven
systems. The fan wheel is a high performance composite
radial plug fan with backward-curved blades. Variable
frequency drives, standard on the XVPR, allow for easy
on-site air balancing, variable supply volume operation,
and customized control sequences.
[ 40 ]
Packaged Rooftop
Options and Accessories
XVPR.
[ 41 ]
Roof Curbs
[ 42 ]
Roof Curbs
Model Overview
Accurex offers prefabricated roof curbs, which reduce installation time and costs by ensuring compatibility between
the unit, curb and roof opening. A wide variety of roof curbs are available, including: flanged, straight-sided, canted,
pitched, and ridged. Extensions are also available and can provide an accessible mounting location for dampers.
The Model Number Code is designed to completely identify the roof curb. The correct code letters must be
specified to designate configurations and size.
GPI R - 34 - 24 - G 12 GPI P - 30 x 42 - 22 x 34 - A 12
Nominal Material (Roof Type) *Optional Damper Curb
Curb Size P-Pitched Tray Size Height (in.)
A-Aluminum
(Unit curb cap) G-Galvanized R-Ridged Nominal Material
Curb Size A-Aluminum
(Roof Type) *Optional Damper Curb (Unit curb cap) G-Galvanized
P-Pitched Tray Size Height (in.)
R-Ridged
[ 43 ]
Roof Curbs
Model Comparison
Equipment Supports and Curb Extensions
Roof Type/
Roof Curb Description Model and Service
Application
Welded, straight-sided construction
Flat, insulated with rigid fiberglass insulation and 2 inch GPI - Galvanized 12 in. high, with
or non-insulated mounting flange. or without damper tray,
roof decks These curbs are designed for roof decks square sizes for stock fans
that are covered with 2 to 6 inches of
insulation. Models GPI and GPIP are
standard with fully welded construction,
Flat, pitched or wood nailer, 1-inch insulation and 2-inch
flashing flange. Model GPI is for use on GPI - Aluminum or galvanized,
ridged, insulated
flat roofs and GPIP for pitched roofs. other heights, non-stock
or non-insulated
Models are available in heights of 12 to square and rectangular sizes
roof decks
24 inches.
Adapters
Equipment Supports
[ 44 ]
[ 45 ]
[ 46 ]
Performance
XKFSB
48-51
XKFSD
48-51
XDGK
52
XDG
53-54
XDGX
54-55
XIG
56-57
XIGX
58-59
XMSX
60-61
XVPR
62
Untempered
Performance and Dimensional Data
XKSFB. XKSFD.
XKSFB-109-H15-01
Total Static Pressure (in. wg)
CFM OV
0.125 0.250 0.375 0.500 0.750 1.000 1.250 1.500 2.000
RPM 593 678 762 842 987 1118 1236
1,300 1,413
BHP 0.15 0.19 0.23 0.27 0.35 0.43 0.52
RPM 691 764 833 902 1032 1153 1265 1371 1561
1,600 1,739
BHP 0.26 0.30 0.35 0.40 0.50 0.60 0.69 0.80 1.02
RPM 793 859 918 976 1091 1201 1303 1404 1588
1,900 2,065
BHP 0.41 0.47 0.52 0.58 0.70 0.82 0.93 1.04 1.28
RPM 899 956 1011 1061 1161 1261 1356 1448
2,200 2,391
BHP 0.61 0.68 0.74 0.80 0.94 1.08 1.22 1.35
XKSFB-110-H15-01
Total Static Pressure (in. wg)
CFM OV
0.125 0.250 0.375 0.500 0.750 1.000 1.250 1.500 2.000
RPM 741 781 834 885 977 1066 1153 1234 1392
2,400 2,123
BHP 0.54 0.59 0.65 0.72 0.85 0.98 1.12 1.27 1.57
RPM 839 871 913 958 1046 1124 1202 1279 1423
2,750 2,433
BHP 0.80 0.85 0.91 0.99 1.14 1.29 1.44 1.60 1.93
RPM 940 967 996 1036 1118 1192 1262 1330
3,100 2,743
BHP 1.13 1.18 1.24 1.32 1.50 1.67 1.84 2.01
RPM 1041 1064 1089 1119 1191 1264
3,450 3,053
BHP 1.55 1.60 1.66 1.73 1.92 2.12
XKSFB-112-H15-01
Total Static Pressure (in. wg)
CFM OV
0.125 0.250 0.375 0.500 0.750 1.000 1.250 1.500 2.000
RPM 507 561 617 671 768 860 941 1014
2,700 1,731
BHP 0.40 0.47 0.55 0.63 0.78 0.94 1.09 1.24
RPM 596 641 687 733 821 902 979 1052 1183
3,300 2,115
BHP 0.68 0.77 0.87 0.96 1.15 1.33 1.52 1.72 2.09
RPM 691 729 766 804 881 956 1027 1093 1221
3,900 2,500
BHP 1.09 1.19 1.30 1.41 1.63 1.86 2.08 2.28 2.76
RPM 787 817 852 884 951 1017 1082 1146
4,500 2,885
BHP 1.64 1.74 1.87 2.00 2.25 2.51 2.77 3.03
XKSFB-115-H25-01
Total Static Pressure (in. wg)
CFM OV
0.125 0.250 0.375 0.500 0.750 1.000 1.250 1.500 2.000
RPM 524 567 608 1.31 722 790 856 915 1031
4,700 2,146
BHP 1.02 1.16 1.31 1.45 1.74 2.03 2.34 2.63 3.29
RPM 589 628 665 700 768 832 891 950 1056
5,400 2,465
BHP 1.49 1.66 1.83 1.99 2.32 2.65 2.98 3.33 4.01
RPM 656 691 724 757 819 877 934 988 1090
6,100 2,785
BHP 2.10 2.29 2.47 2.66 3.04 3.40 3.79 4.16 4.94
RPM 723 755 786 815 872 928 979 1031
6,800 3,105
BHP 2.86 3.07 3.28 3.48 3.91 4.33 4.72 5.15
XKSFB-118-H25-01
Total Static Pressure (in. wg)
CFM OV
0.125 0.250 0.375 0.500 0.750 1.000 1.250 1.500 2.000
RPM 438 473 510 544 608 667 723 776
6,500 2,145
BHP 1.26 1.42 1.60 1.78 2.13 2.47 2.83 3.20
RPM 495 526 557 588 646 702 754 802 897
7,500 2,475
BHP 1.87 2.06 2.26 2.46 2.86 3.27 3.66 4.05 4.92
RPM 554 580 607 636 690 740 790 835 922
8,500 2,805
BHP 2.66 2.87 3.09 3.32 3.79 4.22 4.69 5.14 6.04
RPM 614 637 661 685 735 783 827 872 954
9,500 3,135
BHP 3.67 3.86 4.13 4.37 4.90 5.41 5.90 6.43 7.43
Power rating (BHP) does not include drive losses. Performance ratings do not include the effects of appurtenances in the airstream.
[ 48 ]
Untempered
Performance and Dimensional Data
XKSFB. XKSFD.
B
Housing
A B C D
Size
H05 18.4 31.6 20.0 19.4
H08 18.4 31.8 36.9 19.4
C
H15 25.3 71.1 31.9 39.5
H25 34.0 81.4 40.3 47.4
All dimensions in inches.
XKSFD-70-H05-01
CFM/Static Pressure (in. wg)
RPM AMPS Watts
0.000 0.100 0.125 0.250 0.375 0.500 0.625 0.750 1.000
1,600 3.77 405 813 783 776 741 707 671 637 603 527
XKSFD-80-H08-01
CFM/Static Pressure (in. wg)
RPM AMPS Watts
0.000 0.100 0.125 0.250 0.375 0.500 0.625 0.750 1.000
1,610 8.32 830 1672 1617 1604 1542 1484 1427 1367 1306 1171
XKSFD-90-H08-01
CFM/Static Pressure (in. wg)
RPM AMPS Watts
0.000 0.100 0.125 0.250 0.375 0.500 0.625 0.750 1.000
1,100 7.8 735 2249 2175 2156 2044 1900 1701 1424 1114
Power rating (BHP) does not include drive losses. Performance ratings do not include the effects of appurtenances in the airstream.
[ 49 ]
Untempered
Performance and Dimensional Data
XKSFB. XKSFD.
B Housing
A B C D
Size
H05 14.5 171.1 20.0 21.3
H08 14.5 165.8 36.9 21.3
C
H15 22.3 145.3 31.9 40.8
H25 29.5 152.5 40.3 52.3
All dimensions in inches.
D
[ 50 ]
Untempered
Performance and Dimensional Data
XKSFB. XKSFD.
B*
36 in. min.
40 in. min.
Top of curb
Weatherhood
w/Filters
* Maximum dimensions
(dependent on XRUB fan)
Housing
A* B* C*
Size
H05 25.0 50.0 70.1
H08 35.4 52.9 82.5
H15 42.9 55.0 131.8
H25 58.8 66.1 164.3
All dimensions in inches.
A*
Top of C*
XRUB fan
B*
40 in. min.
Top of curb
Adjustable Legs
10 ft. min.
[ 51 ]
Direct Gas-Fired
Performance and Dimensional Data
XDGK.
Housing
A B C Width
Size
Housing 15
Housing 25
[ 52 ]
Direct Gas-Fired
Performance and Dimensional Data
XDG.
Housing 10
Total Static Pressure (in. wg) Maximum
Model CFM
0.75 1.00 1.25 1.50 1.75 2.00 MBH
RPM 1109 1216 1311 1399
800 120
BHP 0.26 0.31 0.35 0.40
RPM 1228 1325 1415 1500 1579
XDG-108 1,000 150
BHP 0.41 0.47 0.53 0.59 0.65
RPM 1347 1445 1530
1,200 180
BHP 0.59 0.68 0.75
RPM 1014 1140 1255 1361 1460
1,500 225
BHP 0.45 0.54 0.63 0.73 0.84
RPM 1102 1210 1312 1411 1504
XDG-109 1,950 295
BHP 0.73 0.86 0.97 1.1 1.2
RPM 1216 1306 1397 1484
2,400 365
BHP 1.1 1.3 1.4 1.6
RPM 912 1013 1110 1199
2,000 305
BHP 0.59 0.71 .084 .096
RPM 995 1082 1166 1247 1325
XDG-110 2,500 380
BHP 0.93 1.1 1.2 1.4 1.5
RPM 1097 1172 1244 1315 1386
3,000 400
BHP 1.4 1.6 1.7 1.9 2.1
Housing 20
Housing 30
Total Static Pressure (in. wg) Maximum
Model CFM
0.75 1.00 1.25 1.50 1.75 2.00 MBH
RPM 609 668 724 777
6,500 990
BHP 2.1 2.5 2.8 3.2
RPM 668 721 772 819 864 910
XDG-118 8,000 1220
BHP 3.3 3.7 4.2 4.6 5.0 5.5
RPM 736 783 827 872 914
9,500 1450
BHP 4.9 5.4 5.9 6.4 6.9
RPM 590 634 678 723 765 803
10,000 1525
BHP 4.0 4.5 5.0 5.6 6.1 6.6
RPM 672 711 748 784 820 855
XDG-120 12,500 1600
BHP 6.9 7.5 8.1 8.7 9.3 10.0
RPM 763 795 829 861 892 921
15,000 1600
BHP 10.9 11.6 12.3 13.1 13.8 14.5
Note: The air performance data shown does not include internal static pressure losses due to items such as filters, dampers, and coils. For
exact air performance data based on specific unit configuration, contact your local Accurex representative.
[ 53 ]
Direct Gas-Fired
Performance and Dimensional Data
XDG. XDGX.
XDG Dimensions
Combination Package
A max.
Stand Alone
A B C Housing
Max MBH
Size
H10 400
H20 800
D H30 1600
Housing A
B* C D Width
Size Filtered Louvered Birdscreen*
H10 31.8 27.5 26.3 27.8 78.3 33.8 28
H20 34.8 30.3 32.3 30.3 86.3 33.8 37
H30 65.3 33.3 28.3 33 101.8 42.5 48
All dimensions in inches.
*The birdscreen weatherhood requires an additional filter section. The additional filter section is optional with the filtered or louvered weatherhood.
XDGX Dimensions
Weatherhood Louvered V-Bank Cooling Burner Fan
w/ Birdscreen Intake Filters Coil
A AAA B C D E
AA
Housing C
A AA AAA B D E F Width
Size Low High
H12 29.9 31.5 13.8 21.5 30 50.4 37.6 42.5 39 33.6
H22 45.6 47.1 16.9 24 30 69.4 52.3 52.2 44.9 44.1
H32 47.3 48.7 16.9 25.8 98 52.5 66 48.7 53.1
[ 54 ]
Direct Gas-Fired
Performance and Dimensional Data
XDGX.
Housing 12
Housing 32
Housing
Max MBH
Size
H12 400
H22 1200
H32 2000
[ 55 ]
Indirect Gas-Fired
Performance and Dimensional Data
XIG.
Blower Size
MBH Housing
108 109 110 112 115
75 10 x x
100 10 x x
125 10 x x
150 10 x x
175 10 x x x
200 20 x x x
225 20 x x x
250 20 x x x x
300 20 x x x
325 30 x x x
350 30 x x x
400 30 x x x
Note: The air performance data shown does not include internal static pressure losses due to items such as filters, dampers and furnaces. For exact air performance
data based on specific unit configuration, contact your local Accurex representative.
[ 56 ]
Indirect Gas-Fired
Performance and Dimensional Data
XIG.
Arrangement HZ and DB
B A
Housing
Max MBH
Size
H10 175
36 in. H20 300
H30 400
A**
10 ft.
min
56 in.**
** Arrangement DBC dimensions are based on the largest compatible XRUB fan. For specific dimensions, contact your local Accurex representative.
All dimensions in inches.
[ 57 ]
Indirect Gas-Fired
Performance and Dimensional Data
XIGX.
Housing 12
Blower Total Static Pressure (in. wg) Max MBH
CFM
Size 0.50 0.75 1.00 1.25 1.50 1.75 (Input)
RPM 993 1109 1216 1311 1399 -
800 100
BHP 0.21 0.26 0.31 0.35 0.40 -
108
RPM 1238 1347 1445 1530 - -
1,200 150
BHP 0.51 0.59 0.68 0.75 - -
RPM 880 1014 1140 1255 1361 1460
1,500 200
BHP 0.36 0.45 0.54 0.63 0.73 0.84
109
RPM 1154 1244 1329 1419 1503 1587
2,500 250
BHP 1.1 1.2 1.4 1.6 1.7 1.9
RPM 906 995 1082 1166 1247 1325
2,500 250
BHP 0.79 0.93 1.1 1.2 1.4 1.5
110
RPM 1131 1202 1275 1340 1401 1464
3,500 250
BHP 1.8 2.0 2.2 2.4 2.6 2.8
Housing 22
Blower Total Static Pressure (in. wg) Max MBH
CFM
Size 0.50 0.75 1.00 1.25 1.50 1.75 (Input)
RPM 662 761 853 934 1009 -
2,600 350
BHP 0.58 0.72 0.86 1.0 1.2 -
112
RPM 871 939 1006 1073 1137 1197
4,400 600
BHP 1.8 2.1 2.4 2.6 2.9 3.1
RPM 671 741 808 871 931 986
5,000 600
BHP 1.7 2.0 2.3 2.6 2.9 3.2
115
RPM 833 889 943 994 1044 1093
7,000 600
BHP 3.7 4.2 4.6 5.0 5.5 5.9
Housing 32
Blower Total Static Pressure (in. wg) Max MBH
CFM
Size 0.50 0.75 1.00 1.25 1.50 1.75 (Input)
RPM 566 627 685 738 790 839
7,000 1,050
BHP 2.1 2.5 2.8 3.2 3.6 4.0
118
RPM 712 759 805 849 891 933
10,000 1,200
BHP 5.0 5.5 6.1 6.6 7.1 7.7
RPM 542 590 634 678 723 765
10,000 1,200
BHP 3.6 4.0 4.5 5.0 5.6 6.1
120
RPM 731 763 795 829 861 892
15,000 1,200
BHP 10.2 10.9 11.6 12.3 13.1 13.8
Note: The air performance data shown does not include internal static pressure losses due to items such as filters, dampers and furnaces. For exact air performance
data based on specific unit configuration, contact your local Accurex representative.
[ 58 ]
Indirect Gas-Fired
Performance and Dimensional Data
XIGX.
A AAA B C D E
AA
Housing C Furnace
A AA AAA B D E F Width
Size Low High Size
H12 29.9 31.5 13.8 21.5 30.0 50.4 42.5 100-250 33.2 39 44.6
150-300 44.6
33.2
H22 45.6 47.1 16.9 24.0 30.0 69.4 52.2 350-400 44.9 53.9
500-600 66.4 44.6
350-400 33.2
H32 47.3 48.7 16.9 25.8 98.0 66 500-800 66.4 48.7 52.2
1050-1200 99.6
[ 59 ]
Modular Supply
Performance and Dimensional Data
XMSX.
Housing Size 12
Total Static Pressure (in. wg)
Model CFM
0.50 0.75 1.00 1.25 1.50 1.75
RPM 993 1109 1216 1311 1399
800
BHP 0.21 0.26 0.31 0.35 0.40
XMSX-108
RPM 1238 1347 1445 1530
1,200
BHP 0.51 0.59 0.68 0.75
RPM 880 1014 1140 1255 1361 1460
1,500
BHP 0.36 0.45 0.54 0.63 0.73 0.84
XMSX-109
RPM 1154 1244 1329 1419 1503 1587
2,500
BHP 1.1 1.2 1.4 1.6 1.7 1.9
RPM 906 995 1082 1166 1247 1325
2,500
BHP 0.79 0.93 1.1 1.2 1.4 1.5
XMSX-110
RPM 1131 1202 1275 1340 1401 1464
3,500
BHP 1.8 2.0 2.2 2.4 2.6 2.8
Housing Size 22
Total Static Pressure (in. wg)
Model CFM
0.50 0.75 1.00 1.25 1.50 1.75
RPM 662 761 853 934 1009
2,600
BHP .58 .72 .86 1.0 1.2
RPM 756 839 920 993 1065 1133
XMSX-112 3,500
BHP 1.0 1.3 1.5 1.7 1.9 2.1
RPM 871 939 1006 1073 1137 1197
4,400
BHP 1.8 2.1 2.4 2.6 2.9 3.1
RPM 671 741 808 871 931 986
5,000
BHP 1.7 2.0 2.3 2.6 2.9 3.2
RPM 749 812 870 929 982 1035
XMSX-115 6,000
BHP 2.6 2.9 3.3 3.7 4.0 4.4
RPM 833 889 943 994 1044 1093
7,000
BHP 3.7 4.2 4.6 5.0 5.5 5.9
Housing Size 32
Total Static Pressure (in. wg)
Model CFM
0.50 0.75 1.00 1.25 1.50 1.75
RPM 566 627 685 738 790 839
7,000
BHP 2.1 2.5 2.8 3.2 3.6 4.0
RPM 636 690 740 790 836 880
XMSX-118 8,500
BHP 3.3 3.8 4.2 4.7 5.1 5.6
RPM 712 759 805 849 891 933
10,000
BHP 5.0 5.5 6.1 6.6 7.1 7.7
RPM 542 590 634 678 723 765
10,000
BHP 3.6 4.0 4.5 5.0 5.6 6.1
RPM 633 672 711 748 784 820
XMSX-120 12,500
BHP 6.3 6.9 7.5 8.1 8.7 9.3
RPM 731 763 795 829 861 892
15,000
BHP 10.2 10.9 11.6 12.3 13.1 13.8
Note: The air performance data shown does not include internal static pressure losses due to items such as filters, dampers and coils.
For exact air performance data based on specific unit configuration, contact your local Accurex representative.
[ 60 ]
Modular Supply
Performance and Dimensional Data
XMSX.
A AAA B C D E
AA
Housing D
A AA AAA B C E F Width
Size Low High
H12 29.9 31.5 13.8 21.5 30 50.4 42.5 39.0 33.6
43.9
H22 45.6 47.1 16.9 24.0 30 69.4 52.2 44.9 44.1
H32 47.3 48.7 16.9 25.8 48.0 98.0 66.0 48.7 53.1
Housing
Max kW
Size
H12 70
H22 140
H32 220
[ 61 ]
Packaged Rooftop
Performance and Dimensional Data
XVPR.
Size XVPR-110 XVPR-210 XVPR-310
A 56 63.25 84
B 34 34 34
C 48 60.25 67
D 110 120 130
All dimensions in inches.
B C D
Rows 6 6 6 6 6 6 6 6 6 6 6 6 6 6
Coil Area (ft²) 3.8 5.6 6.6 6.8 8.0 9.6 10.8 12.8 14.4 13.5 16.5 18.2 20.0 21.9
Evaporative
Coil Min Face 200 213 229 221 244 250 250 235 261 223 227 247 263 274
Velocity (fpm)
Max Face 400 426 457 442 488 501 501 470 522 446 455 494 526 549
Velocity (fpm)
Coil Face 13.9 13.9 19.4 30.0 27.5 30.0 35.0 35.0 36.6 37.5 38.9 47.9 48.6 48.6
Area (ft²)
Condenser Fan Quantity 1 1 1 2 2 2 2 3 3 3 3 3 3 3
Circuit 1 5 8 10 5 5 8 8 10 12 10 12 14 15 20
Nominal Tons
Compressors
Circuit 2 — — — 5 8 8 10 10 13 10 13 16 20 20
Nominal Tons
Coil Area (ft²) 2.4 3.6 4.9 4.7 6.3 7.8 9.4 10.2 10.9 9.5 10.4 12.2 13.9 15.6
Hot Gas
Reheat Coil
Rows 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Gas Heat Max Input 125 150 150 250 300 400 400 400 400 600 700 800 800 800
Section (MBH)
Quantity 4 4 4 6 6 6 6 6 6 9 9 9 9 9
SA Filters
Size (in.) 20x20 20x20 20x20 16x25 16x25 16x25 16x25 16x25 16x25 24x20 24x20 24x20 24x20 24x20
kW 6.0 9.0 12.0 12.0 15.0 18.0 21.0 25.0 28.0 25.0 28.0 34.0 44.0 44.0
Supplemental
Electric Max temp. 29.6 27.8 29.6 29.6 28.5 27.8 28.8 30.0 27.6 30.9 27.6 28.0 31.0 23.0
rise (°F)
Heater
Min temp. 14.8 13.9 14.8 14.8 14.2 13.9 14.4 15.4 13.8 15.4 13.8 14.0 15.5 11.5
rise (°F)
[ 62 ]
[ 63 ]
Accurex, LLC
P.O. Box 410 • Schofield, WI 54476
Phone: 800.333.1400 • Fax: 715.241.6191
www.accurex-systems.com
A Greenheck Company