Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Interconnection Protection
April 5, 2005
D.M. Costyk
1
What’s down the road today??
2
Course Goals
3
Main Topics
• Equipment Operation Overview
• Basic Principles
• Issues
• SCADA
4
Equipment &
Operation
5
Breakers & Reclosers
6
Breakers
7
Breakers
8
Breakers
• Note
o Load Capability
o Interrupting Rating
o Fault Closing Rating
o Momentary rating
9
Reclosers
Key Points for DG
• Note
o Load Capability
o Interrupting Rating
o Fault Closing Rating
o Momentary Rating
10
Issue #3 Single Phase Recloser Timing Diagram Loadability
Sensitivity
Out of Synchronism
Approx Approx Approx Selectivity
100 100 100
cycles cycles cycles
Condition
Time of fault Locked Out
Open
Closed
Recloser
Status
Closed
1. Fault occurs
2. Recloser opens on “Fast” time delay curve
3. Recloser recloses with no intentional time delay (approximately 15 cycles)
4. Recloser opens on “Slow” time delay curve
5. Recloser recloses after set time delay. (20 seconds in this case)
6. Recloser opens again on “Slow” time delay curve.
7. Recloser recloses the final time after set time delay. (20 seconds in this case)
8. Recloser opens the final time on the “Slow” time delay curve.
9. Recloser locks out and stays open until manually closed.
12
Fuses
Key Points for DG
• Note
o Load Capability
o Interrupting Rating
o Fault Closing Rating
o Momentary Rating 13
DR Relays
3 U/O Voltage
1-U/O Frequency
13.2-4.8 Switch
Cutoff Switches
14
Relays
Key Points for DG
• Note
o Load Capability
o Adjustment Range
o Power Supply Voltage
15
Basic Relaying Principles
Loadability
Equipment must carry load
Sensitivity
The protecitve equipment must sense fault
conditions
Selectivity
Isolate the fault with the minimum amount of load
loss - - the device closest to the fault operates
Reliability
16
Basics
17
Synchronous Generator Fault Characteristics
• Subtransient reactance X” T”
• Transient reactance X’ T’
• Synchronous reactance
18
Synchronous Generator Faults Loadability
Sensitivity
Generator Short Circuit Current
Selectivity
It=(I''-I')*e-t/T"+(I'-I)*e-t/T'+I
Key points:
• Transient reactance is used for most relay studies
• The transient time constant falls in the range of most protective
equipment
• However for exended fault periods, the study is complicated by the
changing value of current - - relay and fuse characteristics assume a
19
steady value of current
Synchronous Generator Faults Loadability
Sensitivity
Selectivity
1 pu voltage
Characteristic is programmable on
modern inverters
Induction
• Similar to motor
22
Synchronous Generators in Parallel
V
Load
23
7,620v
15,240v
0v
V
7,620v Load
24
V
Load
26
The 29 Issues
27
29 Issues
Issue Issue
28
29 Issues Key to Relay Studies
Issue Issue
29
Prioritization of Key Relay Issues
1 Improper Coordination
(Sensitivity & Selectivity) 16 Isolate DR for Upstream Fault
5 Islanding 17 Close-in fault Causes Voltage Dip -
4 Transfer Trip Trips DR
28 Underfrequency Relaying 27 Upstream Single Phase Fault Causes Fuse
3 Reclosing out of Synchronism Blowing
21 Stability During Faults 29 Distribution Automation Studies
6 Equipment Overvoltage
18 Switchgear Ratings
2 Nuisance Fuse Blowing
30
Basics
31
Basics
(Relay Engineer’s DG Study Checklist)
General
1. A detailed drawing showing the proposed location of DR facilities
2. A one-line diagram showing the arrangement of the major equipment such as overhead
lines, underground cables, transformers , breakers, disconnects, arresters, C.T.’s, V.T.’s and
metering.
3. A list showing the voltage and normal day to day current ratings of each major electric line
and equipment component
System Protection
1. System protection one-line diagrams
2. A description of each proposed protection scheme
3. Periodic testing and maintenance plans for the system protective devices and interrupting
devices.
4. Protective device settings
Prime Mover
1. Type – gas turbine, spark ignition gas, diesel, photovoltaic, fuel cell, stirling, wind turbine,
and other – describe
2. Manufacturer and model
3. Nominal rating, and overload rating
4. Inertia constant
5. % governor droop, nominal 5%
33
Basics
Protection Engineer
• Determine if the additional fault current contribution from the DR subjects any
devices to fault current duty beyond its capability. I.e. interrupting, momentary,
and fault closing ratings
3200A
C A D
A
B 2900A 1300A
CB-1 3800A
Protection Zone
35
Issue 1 Fault Detection Sensitivity
One-Line
Scenario
Fault at point A as shown below.
• Fault is near the line protection device that has the least available fault current at
its location.
• The substation breaker will typically not be required to sense faults beyond this
device.
• Fault current contribution from DR reduces fault contribution from substation
• Protective device at substation takes longer to trip or does not trip until DR trips
Substation
First Sectionalizing
Breaker Device
Fault A
System Fault Current - Is
II
DR Fault Current - Idr
DR 36
Loadability
Sensitivity
Selectivity
Selectivity
Fault A = 2987 A
Distribution Circuit 2
37
Selectivity
10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7
1000 1000 1000 1000
70 70 70 70
50 1 50 50 1 50
40 40 40 40
30 Fault Description: 30 30 30
3LG Bus fault on:
20 Test 13.2 kV 20 20 20
Fault Z= 2.4 Ohm
2 2
S 10 1. Test CO-8 TD=2.000 10 S 10 1. Test CO-8 TD=2.000 10
E CTR=200.0 Tap=5.A No inst. TP=0.7611s E CTR=200.0 Tap=5.A No inst. TP=0.7611s
C 7 7 C 7 IfS+ IfDR = 2987.9A T= 1.68s 7
O IfDR +IfS= 2987.9A T = 1.68s O
N 5 5 N 5 5
D 4 4 D 4 2. Close 140 recl d ME-220-D TD=1.000 4
S 2. Close 140 recl d ME-220-D TD=1.000 S CTR= 1.0 Tap=1.A No inst.
3 CTR= 1.0 Tap=1.A No inst. 3 3 IfDR= 717.3A T= 1.69s 3
IfDR= 717.3A T= 1.69s
2 2 2 2
Fault Description:
3LG Bus fault on:
1 1 1 Test 13.2 kV 1
Fault Z= 2.4 Ohm
.7 .7 .7 .7
.5 .5 .5 .5
.4 .4 .4 .4
.3 .3 .3 .3
.2 .2 .2 .2
.1 .1 .1 .1
Fault I=2987.9 A
.01 .01 .01 .01
10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7
CURRENT (A) CURRENT (A)
38
Selectivity (notes Cont’d)
10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7
1000 1000 1000 1000
70 70 70 70
50 1 50 50 1 50
40 40 40 40
30 Fault Description: 30 30 30
3LG Bus fault on:
20 Test 13.2 kV 20 20 20
Fault Z= 2.4 Ohm
2 2
S 10 1. Test CO-8 TD=2.000 10 S 10 1. Test CO-8 TD=2.000 10
E CTR=200.0 Tap=5.A No inst. TP=0.7611s E CTR=200.0 Tap=5.A No inst. TP=0.7611s
C 7 7 C 7 IfS+ IfDR = 2987.9A T= 1.68s 7
O IfDR +IfS= 2987.9A T = 1.68s O
N 5 5 N 5 5
D 4 4 D 4 2. Close 140 recl d ME-220-D TD=1.000 4
S 2. Close 140 recl d ME-220-D TD=1.000 S CTR= 1.0 Tap=1.A No inst.
3 CTR= 1.0 Tap=1.A No inst. 3 3 IfDR= 717.3A T= 1.69s 3
IfDR= 717.3A T= 1.69s
2 2 2 2
Fault Description:
3LG Bus fault on:
1 1 1 Test 13.2 kV 1
Fault Z= 2.4 Ohm
.7 .7 .7 .7
.5 .5 .5 .5
.4 .4 .4 .4
.3 .3 .3 .3
.2 .2 .2 .2
.1 .1 .1 .1
Fault I=2987.9 A
.01 .01 .01 .01
10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7
CURRENT (A) CURRENT (A)
39
Loadability
Sensitivity
Nuisance Fuse Blowing Selectivity
Substation
Breaker
Recloser
CB-1
IfS IfDR
DR
40
Nuisance Fuse Blowing
10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7
1000 60000
50000
40000
500 30000
20000
3
250
10000
8000
100 6000
1. 140AD recl mid ME-220-D TD=1.000 5000
CTR= 1.0 Tap=1.A No inst.
4000
50 2. 140AA recl mid ME-220-A TD=1.000 3000
CTR= 1.0 Tap=1.A No inst.
2000
3. I2 80k 62 mid 165-62-80
25 Minimum melt.
1000
800
1
S 10 600 C
E 500 Y
C 400 C
O L
N 5 300 E
D S
S 200
6
2.5 0
H
100 Z
80
1 60
50
2 40
.5 30
20
.25
10
8
.1 6
5
4
.05 3
2
.025
1
.8
.01 .6
10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7
CURRENT (A)
800
700 694
673 679
616 623
600
DR Fault current
500 trip
497 If this point represents the DR and
in rectangle area system
(below 280 amperes) impedance to a branch point, you can
move toward the origin on a straight line
400 that will represent an increasing branch DR Fault
382 length or fault impedance. As you cross Current
the "inselectivity line" from this point, you
enter a region where the fuse should be
300 saved by the recloser fast curve.
283
200
42
Interrupting Ratings
Approximate Values
43
13.2 kV Radial Distribution System - Grounded Wye
Issue #18 Additional DR's Cause Interrupting Ratings to be Exceeded
Cable
Pole
24/32/40 Underground
MVA Cable
approx.1/2 mile
x
Circuit Breaker
Appro
Figure 1 New Distributed LOAD
Resource Generator
Problem:
1. Maximum system fault current at an existing DR is approximately 7000amps without fault current contribution from the new DR
2. Fuses are capable of interrupting 8000 amps symmetrical, however, it is often desireable to include a margin to accommodate
increased fault level in the future and also to conservatively cover inaccuracies in the fault calculations.
3. A 5 MVA DR is connected electrically near the existing load and contributes approximately 1000 additional amps to the fault
current available at the existing cable pole at the load.
4. Fault current at the existing load is now approximately 8000 amps. If fuses are standard cutout type that are rated at 8000 amps
symmetrical interrupting capability, then they may be subjected to more fault current than they are capable of interrupting.
Solution:
1. Replace the fuses with equipment that has a higher interrupting rating. Note that this problem can arise at any location. All
equipment should be surveyed to insure that it is not subjected to fault duty beyond its capability.
44
Island Detection
• P1547 section
4.4.1 Unintentional Islanding
For an unintentional island in which the DR energizes a
portion of the Area EPS through the PCC, the DR
interconnection system shall detect the island and cease
to energize the Area EPS within two seconds of the
formation of an island.7
• Transfer tripping
• Transfer Tripping pilot
45
Island Detection
• Islanding Problems
– Resynchronizing
– Voltage
– Safety
• P1547 section
• Transfer tripping
• Transfer Tripping pilot
46
P1547 Island Definitions
47
P1547 Island Requirements
4.4 Islanding
48
ISSUE # 4 - Installation of Transfer Trip Relaying
For systems where DR's are not permitted to operate as an island, transfer tripping from
the utility's breaker or recloser to the DR may be needed. The D.R generation is
automatically removed from the utility’s system when the utility’s breaker or recloser
opens.
Circuit Configuration: 13.2kV “Y” Multiground
Fault A
Substation
Circuit Breaker
V
VI
Substation
Circuit Breaker
V
VI
Local Load
Figure 3 Dispersed Generator
51
Synchronizing and Stability Problems
52
ISSUE # 3 - RECLOSING
Fault Type: Single phase to ground
Example #1: Single phase to ground fault causes three phase recloser to operate. Fault is
successfully cleared by recloser operation. DR is connected to system through delta transformer
and does not sense fault. DR stays on line. Recloser recloses and DR is out of sychronism.
53
Stability During Faults
Substation
Breaker
IfS IfDR
CB-1
DR
54
4.2.5 Loss of Synchronism
Loss of synchronism protection is not
required except as necessary to meet
clause 4.3.2.
4.3.2 Limitation of Flicker Induced
by the DR
The DR shall not create objectionable
flicker for other customers on the Area
EPS. 6
55
13.2 kV Radial Distribution System - Grounded Wye
Fault Causing loss of Synchronism
Underground
Cable
Cable Load
Pole Fault A
I IV
Three Phase to
Substation
ground
Circuit Breaker
Temporary Fault
V
Distributed Generator
•Three phase to ground fault causes voltages to fall to near zero at the generator.
•Because voltage is zero, the power output of the generator goes to near zero.
•For synchronous rotating machines the full torque from the prime mover continues to be applied to
the generator.
•See recloser timing diagram. DR is connected to the system through a delta-wye transformer and does not sense
the fault (Delta does not provide ground current). DR stays on line temporarily. When the recloser recloses, DR
could be out of synchronism with the system.
•Because of this applied torque and the lack of a counter torque cause by load, the rotor speed will increase.
2. DR must be removed prior to reclosing to prevent out of synchronism operation of the generator
56
Issue #3 Three Phase Recloser Timing Diagram
Approx
15 cycles 20 seconds 20 seconds
Recloser
Status
Closed
1. Fault occurs
2. Recloser opens on “Fast” time delay curve
3. Recloser recloses with no intentional time delay (approximately 15 cycles)
4. Recloser opens on “Slow” time delay curve
5. Recloser recloses after set time delay. (20 seconds in this case)
6. Recloser opens again on “Slow” time delay curve.
7. Recloser recloses the final time after set time delay. (20 seconds in this case)
8. Recloser opens the final time on the “Slow” time delay curve.
9. Recloser locks out and stays open until manually closed.
57
Issue #3 Single Phase Recloser Timing Diagram
Out of Synchronism
Approx Approx Approx
100 cycles 100 cycles 100 cycles
Condition
Time of fault Locked Out
Open
Closed
58
13.2 kV Radial Distribution System - Grounded Wye
Reclosing Out of Synchronism
Underground
Cable
3 Phase Recloser
Cable Load
Pole Fault A
II
I IV
Single Phase to ground
Substation
Temporary Fault
Circuit Breaker
V
Distributed Generator
2. DR must be removed prior to reclosing to prevent out of synchronism operation of the generator
59
13.2 kV Radial Distribution System - Grounded Wye
Reclosing Out of Synchronism
Solutions
Cable
Underground Pole Recloser Dead Line
Cable Sensing
Load
Fault A
Distributed Generator
Example 1: Three-Phase Recloser (continued)
Solutions: 1. Install dead line sensing at the recloser, which consists of three voltage transformers (VTs) connected wye. If
potential is present on any VT, automatic reclosing of the recloser is disabled. This will prevent reclosing of
the recloser if the DR is operating.
2. Another solution is to install transfer-tripping from the recloser to the DR(s). See Issue #4.
60
13.2 kV Radial Distribution System - Grounded Wye
Reclosing Out of Synchronism
3 Single Phase Reclosers
Underground
Cable
Cable X
Pole
Y
Z Fault A
I One-Line
Substation Representation
Circuit Breaker of Three Phases II IV
Single Phase to Ground
Temporary Fault
V Other Remote
Customer Load
Local Load
Single Phase 20kVA
Example 2: Three Single-Phase Reclosers
Synchronous Distributed Generator
Problems: 1. Recloser on Phase Z opens on fast curve “A” and may reclose before generator breaker opens. The generator
is less likely to trip as the distance or impedance between the fault and generator increases.
2. Recloser recloses prior to generator breaker opening which could result in non-synchronous operation. See
single phase recloser timing diagram.
Solution: 1. Install dead-line sensing at the recloser. This consists of 1 VT at the recloser. This prevents the recloser from
closing if the generator is in operation.
61
Case Studies
62
Issues : Fault Current from DR has
maximum desensitizing effect on
substation relay
Increased fault current level may be
above interrupting rating of
RECLOSER equipment
800a load 280a
Solution: Replace underated
1000a Trip
equipment, install current limiting
fuses, install reactors.
BREAKER SECTIONALIZER
80a load
160a Blow
Close to Substation
63
Issues : Fast reclosing may cause
out of synchronism condition
Island due to small circuit load
RECLOSER beyond recloser
800a load 280a Solution: Remove fast reclosing
1000a Trip Move recloser downstream.
BREAKER SECTIONALIZER
80a load
160a Blow
Downstream of Recloser
64
Issues : Single phase generator with
blown fuse
Island due to small circuit load
beyond fuses
RECLOSER
800a load 280a Solution: Move fuses downstream.
1000a Trip
BREAKER SECTIONALIZER
80a load
160a Blow
66
Loadability
Fault Currents vs Transformer Size Sensitivity
Selectivity
Line Length
Generator Size
Miles From Source
0.5 1 2 3 5 10
Tranformer size P.U. Imp 10 MVA P.U. Z 13.2kV amps
15 0.08 0.053 8201 5931 4645 3240 2488 1699 947
10 0.08 0.080 5468 4356 3620 2706 2160 1539 896
7.5 0.08 0.107 4101 3442 2965 2322 1909 1407 849
5 0.08 0.160 2734 2424 2178 1810 1548 1201 770
2.5 0.08 0.320 1367 1285 1212 1089 988 834 601
Fault A
System Fault Current - IfS
DR Fault Current -
67
Fault currents on Circuit Loadability
Sensitivity
6000 300 Selectivity
Fault Levels
Fault Current (Am ps)
5000 250
4000 200 Ift
3000 150 Ifs
2000 100 Ifg
1000 50
0 0
0 2 4 6 8 10 12
Line length (Miles)
Substation
First Sectionalizing
Breaker Device
Fault A
System Fault Current - Is
II
DR Fault Current - Idr
DR 68
Loadability
Sensitivity
Fault Currents on Circuit Selectivity
0 1 1.5 2 2.5 3 4 5 10
Zline 0.000 0.041 0.061 0.082 0.102 0.122 0.163 0.204 0.408
Gen On If 5418 3598 3081 2694 2393 2152 1792 1535 894
Ifs 5249 3486 2984 2609 2318 2085 1736 1487 866
Ifg 170 113 97 84 75 67 56 48 28
Gen Off If 5249 3523 3025 2651 2359 2125 1773 1521 890
69
Loadability
Sensitivity
Selectivity
Fault Levels
Substation Branch
Breaker Node
L1 L2
CB-1
IfS L3 IfDR
DR
70
Fault Levels Loadability
Sensitivity
Substation Branch
Selectivity
Breaker Node
L1 L2
CB-1
IfS L3 IfDR
DR
L1 0.5 1 2 3 5 8 10 ZL2 L2
ZL1 0.020 0.041 0.082 0.122 0.204 0.327 0.408
If 2651 2385 1994 1721 1362 1055 925 0.0204 0.50
Ifs 2524 2254 1857 1579 1215 903 771
Ifg 127 131 137 141 147 152 154
If 2650 2384 1993 1720 1361 1054 924 0.0408 1.00
Ifs 2524 2254 1857 1579 1215 903 771
Ifg 126 130 136 140 146 151 153
If 2649 2383 1992 1718 1359 1052 922 0.0817 2.00
Ifs 2525 2255 1858 1580 1216 903 771
Ifg 124 128 134 138 144 148 150
If 2647 2381 1990 1716 1357 1050 920 0.1225 3.00
Ifs 2525 2255 1858 1580 1216 904 771
Ifg 122 126 132 136 142 146 148
If 2644 2378 1987 1713 1354 1046 916 0.2042 5.00
Ifs 2526 2256 1859 1580 1216 904 772
Ifg 119 122 128 132 137 142 144
If 2638 2372 1980 1705 1346 1037 907 0.4083 10.00
Ifs 2528 2258 1860 1582 1217 905 772
Ifg 111 114 120 123 128 132 134
Fault current levels for various length of L1 and L2 and a single value of L3
To show multiple values of L3 requires multiple sheets
73