This section contains a full range of lightweight partition and wall
systems for use in new and existing buildings. They cover all applications,
from simple space division to high performance walls
Partitions
C04
Introduction
Partitions
British Gypsum offers a full range of lightweight
partition and wall systems. Our systems are
non-loadbearing and constructed using modern,
drylining techniques. British Gypsum metal
framed partitions and walls can be used in all
types of new and existing buildings, including
private and social housing, apartments,
Partitions
healthcare, educational facilities, recreational
and industrial properties.
C04
They cover all applications, from simple space
division, through to high performance walls
designed to meet the most demanding fire
resistance, sound insulation, impact and height
requirements.
When specifying partitions, a number of performance characteristics are normally used to determine the required solution.
Depending on the project or construction type, these performance parameters could be set by minimum regulatory
standards, or a client or customer requirement for buildings that offer the highest standards of performance and comfort.
Our quick-reference partition system guide, below, allows you to simply select the performance categories of interest and
identify the British Gypsum partitions systems that best satisfy your project requirements.
Duty Maximum
Fire rating height1
Partition
Acoustic performance
performance thickness System Page
Partitions
Medium -
30 - 120 75 - 211 34 - 63 47 - 57 8100 GypWall classic C04.S02.P02
Severe
C04
Heavy -
30 - 90 102 - 208 49 - 63 48 - 55 5700 GypWall staggered C04.S06.P02
Severe
Non-loadbearing timber
30 - 120 88 - 196 34 - 52 - - - C04.S11.P02
stud (internal partitions)
Non-loadbearing timber
60 - 90 141 - 293 56 - 63 48 - 53 - - C04.S11.P05
stud (separating walls)
1
Based on studs at 600mm centres
Additional information
Try out The White Book System Selector, an online tool designed to help find the ideal solutions for your
project needs. Additional information such as BIM data (Revit), NBS clauses, CAD drawings and other
associated items can be downloaded. Visit british-gypsum.com
Introduction
Acoustic performance
Table 1 — Sound insulation performance for residential specification
On-site Laboratory2
Approved Document E (England and Wales) Minimum solution Recommended solution
DnT,w + Ctr dB
(Rw + Ctr ) dB (Rw + Ctr ) dB
On-site Laboratory2
Partitions
Technical Standards Section 5 (Scotland) Minimum solution Recommended solution
DnT,w + Ctr dB
Rw dB Rw dB
C04
or conversion (traditional buildings1)
1
Definition of traditional buildings - A building or part of a building of a type constructed before or around 1919:
a) using construction techniques that were commonly in use before 1919; and
b) with permeable components, in a way that promotes the dissipation of moisture from the building fabric.
2
Minimum solutions provide little or no margin of safety to allow for reduction in performance due to flanking transmission. Recommended solutions have
greater potential to satisfy the requirements of Building regulations.
Table 2 – GypWall classic metal stud partition recommended maximum heights (mm) - based on a limiting deflection of L/240 at
200Pa. Applicable to non fire-rated or BS 476: Part 22 fire-rated constructions only (not applicable to EN 1364-1)
Stud Boarding 600mm 600mm 400mm 400mm 300mm 300mm
each side centres boxed centres boxed centres boxed
48 S 50 1 x 12.5mm 2500 2800 2900 3200 3100 3500
1 x 15mm 2800 3000 3100 3300 3300 3600
2 x 12.5mm 3400 3600 3600 3800 3800 4000
2 x 15mm 3700 3800 3900 4000 4000 4200
48 I 50 1 x 12.5mm 2900 - 3400 - 3700 -
1 x 15mm 3100 - 3500 - 3800 -
Partitions
In all GypWall classic systems, it is recommended that for heights between 4200mm and 8000mm, the Gypframe Deep Flange Floor & Ceiling Channel is
used. Gypframe Extra Deep Flange Floor & Ceiling Channel is used for heights above 8000mm. Additional consideration needs to be given if there is a deflection
head requirement.
Introduction
Table 2 (continued) – GypWall classic metal stud partition recommended maximum heights (mm) - based on a limiting
deflection of L/240 at 200Pa. Applicable to non fire-rated or BS 476: Part 22 fire-rated constructions only (not applicable to
EN 1364-1)
Stud Boarding 600mm 600mm 400mm 400mm 300mm 300mm
each side centres boxed centres boxed centres boxed
92 S 60 1 x 12.5mm 4700 5000 5200 5600 5600 6100
1 x 15mm 4900 5300 5400 5800 5800 6300
2 x 12.5mm 5800 6000 6100 6500 6500 6900
2 x 15mm 6000 6200 6300 6700 6600 7000
92 AS 50 1 x 12.5mm 4700 5100 5200 5700 5700 6200
Partitions
1 x 15mm 4900 5300 5400 5700 5800 6400
2 x 12.5mm 5800 6100 6200 6500 6500 6900
2 x 15mm 6000 6300 6400 6700 6700 7000
92 S 10 1 x 12.5mm 5300 5800 6000 6600 6500 7200
1 x 15mm 5500 6000 6100 6700 6600 7300
C04
2 x 12.5mm 6200 6600 6700 7200 7200 7700
2 x 15mm 6400 6800 6900 7400 7300 7800
92 I 90 1 x 12.5mm 6000 - 6800 - 7400 -
1 x 15mm 6200 - 6900 - 7500 -
2 x 12.5mm 6800 - 7400 - 7900 -
2 x 15mm 6900 - 7500 - 8000 -
146 S 50 1 x 12.5mm 6200 6800 6900 7600 7500 8300
1 x 15mm 6500 7000 7200 7800 7700 8400
2 x 12.5mm 7600 8000 8100 8600 8500 9100
2 x 15mm 7900 8200 8300 8800 8700 9300
146 AS 50 1 x 12.5mm 6600 7100 7300 8000 8000 8800
1 x 15mm 6800 7400 7600 8200 8200 8900
2 x 12.5mm 7800 8200 8400 8900 8900 9500
2 x 15mm 8100 8500 8600 9100 9100 9700
146 I 80 1 x 12.5mm 7900 - 8900 - 9700 -
1 x 15mm 8100 - 9000 - 9800 -
2 x 12.5mm 8800 - 9600 - 10400 -
2 x 15mm 9000 - 9800 - 10500 -
146 TI 90 1 x 12.5mm 8300 - 9400 - 10300 -
1 x 15mm 8400 - 9500 - 10400 -
2 x 12.5mm 9200 - 10100 - 10900 -
2 x 15mm 9400 - 10300 - 11100 -
In all GypWall classic systems, it is recommended that for heights between 4200mm and 8000mm, the Gypframe Deep Flange Floor & Ceiling Channel is
used. Gypframe Extra Deep Flange Floor & Ceiling Channel is used for heights above 8000mm. Additional consideration needs to be given if there is a deflection
head requirement.
To be read in conjunction with system specific details. Refer to relevant system sections
1 1a
1
3
5
5
Partitions
300mm
2
600mm
600mm
600mm
C04
2
300mm
6
7
2 2a
Centres
at 600mm
Centres
at
thereafter
600mm
thereafter
1479mm
1479mm
50mm
50mm
50mm
38mm
30mm
38mm
879mm
879mm
279mm
279mm
Service cut-outs - Gypframe ‘C’ and Gypframe ‘I’ Studs Service cut-outs - Gypframe AcouStuds
Introduction
To be read in conjunction with system specific details. Refer to relevant system sections
3 3a
Partitions
11
4
3 6
3
1
C04
2 7
6
4
10
Head and base Junction with masonry and stop end detail
To be read in conjunction with system specific details. Refer to relevant system sections
5 6
2 1
3
Partitions
7a 7b
2 2
1
1
4
3
3
‘T’ junction to optimise acoustic performance and reduce ‘T’ junction to optimise acoustic performance and reduce
flanking transmission flanking transmission
8 9
2 1
1
5
2
3
1 Gyproc plasterboard or Glasroc F specialist board 4 Gypframe GA5 Internal Fixing Angle
2 Gypframe 'C' Stud 5 Gypframe GA6 Splayed Angle
3 Isover insulation
Guidance must be sought from the relevant approval authority e.g. Building Control to establish if a cavity barrier is required (Approved Document B)
Introduction
To be read in conjunction with system specific details. Refer to relevant system sections
10 11
1
1
2
2
Partitions
Corner detail - single layer Corner detail - double layer
C04
12 13
16
mm
12 12
mm mm
2
3
1
1
4
14
Installing the screw into the side of the Gypframe Service Support Plate and the web of the Gypframe 'C' Stud will avoid creating excessive distortion to
the lining board.
To be read in conjunction with system specific details. Refer to relevant system sections
15
15mm 7 16 15mm 7
15mm 6 15mm 6
4 4
20mm 15mm 10
3
11
2
1 2
1
Partitions
Deflection head for 15mm downward movement Deflection head for 15mm downward movement
and 60 minutes fire resistance and up to 120 minutes fire resistance
Not suitable for 60 minutes single layer systems on 48mm studs to Not suitable for 48mm studs to BS EN 1364-1
C04
BS EN 1364-1
17 7 18
7
25mm 50mm
8 8
7
25mm 7 50mm
5 5
55mm
30mm
3
3
2
2
1
1
Deflection head for plus or minus 25mm movement Deflection head for 50mm downward movement
and 60 minutes fire resistance and 60 minutes fire resistance
19 20 7
7
25mm 9
50mm
9
7
25mm 7
50mm
5 5
30mm
3 55mm
3
2 2
1 1
Deflection head for plus or minus 25mm movement Deflection head for 50mm downward movement
and 60 minutes fire resistance and 60 minutes fire resistance
No fixings should be made through the boards into the flanges of the head channel. The arrow ( ) denotes the position of the uppermost board fixing,
which should be made into Gypframe GFS1 Fixing Strap (or stud nogging in construction detail 16). Continuous Gyproc FireStrip must be installed as shown to
maintain fire performance. Where there is a need for a deflection head in a 90 minute wall, the 120 minute solution can be used (refer to construction detail 16)
or alternatively, please contact the British Gypsum Technical Advice Centre for further guidance.
To minimise loss in acoustic performance refer to C02 S01 P10 Acoustic performance of head details.
Introduction
To be read in conjunction with system specific details. Refer to relevant system sections
21 2 22
5 7
2
9
5
8
15mm 6 15mm 6
15mm 15mm
3 3
15mm 10
15mm
Partitions
10
4
4
C04
1
1
Deflection head parallel to floor profile for 15mm downward Deflection head perpendicular to floor profile for 15mm downward
movement and up to 60 minutes fire resistance 1 movement and up to 60 minutes fire resistance
Not suitable for 60 minutes single layer systems on 48mm studs to Not suitable for 60 minutes single layer systems on 48mm studs to
BS EN 1364-1 BS EN 1364-1
23 24
12 12
13 13
1
1
4
4
11 11
14
No fixings should be made through the boards into the flanges of the head channel. The arrow ( ) denotes the position of the uppermost board fixing,
which should be made into Gypframe GFS1 Fixing Strap. Continuous Gyproc FireStrip must be installed as shown to maintain fire performance.
1
To minimise acoustic downgrade, install Isover insulation within the hollow rib void.
To be read in conjunction with system specific details. Refer to relevant system sections
25
Partitions
150mm
4
C04
1200mm 1200mm
Door frame (maximum 1200mm width) to satisfy BS 5234: Parts 1 & 2: 1992 - Light and Medium Duty (up to 35kg door)
1 Gyproc plasterboard or Glasroc F specialist board 5 Timber door frame and architrave
2 Gypframe 'C' Stud 6 Gypframe 'C' Stud to maintain stud module
3 Gypframe Floor & Ceiling Channel 7 Timber sub-frame
4 Gypframe Floor & Ceiling Channel cut and bent to form door head
Advice should be sought from the door manufacturer prior to the construction of these details.
Introduction
To be read in conjunction with system specific details. Refer to relevant system sections
26
150mm
Partitions
4
C04
3
2
300mm
1200mm 1200mm
150mm
Door frame (maximum 1200mm width) to satisfy BS 5234: Parts 1 & 2: 1992 - Heavy and Severe Duty (up to 60kg door)
1 Gyproc plasterboard or Glasroc F specialist board 5 Timber door frame and architrave
2 Gypframe 'C' Stud 6 Gypframe 'C' Stud to maintain stud module
3 Gypframe Floor & Ceiling Channel to sleeve studs 7 Gypframe Floor & Ceiling Channel cut and bent to extend up studs
4 Gypframe Floor & Ceiling Channel cut and bent to form door head
Advice should be sought from the door manufacturer prior to the construction of these details.
At the base, the channel is cut and bent to extend 300mm up the studs and fixed each side with two British Gypsum Wafer Head Drywall Screws. The
studs each side of the opening are sleeved full height of opening with Gypframe Floor & Ceiling Channel.
To be read in conjunction with system specific details. Refer to relevant system sections
27
8
7
Partitions
150mm
4
C04
2
300mm
150mm
Alternative door frame for fixed partition heads only (maximum 1200mm width) to satisfy
BS 5234: Parts 1 & 2: 1992 - Heavy and Severe Duty (up to 60kg door)
1 Gyproc plasterboard or Glasroc F specialist board 6 Gypframe 'C' Stud to maintain stud module
2 Gypframe 'C' Stud 7 Gypframe 'C' Studs fixed back to back with
British Gypsum Drywall Screws at 300mm centres staggered
3 Gypframe Floor & Ceiling Channel to sleeve studs
8 Plasterboard infill (same type as lining) cut to fit between studs
4 Gypframe Floor & Ceiling Channel cut and bent to form door head
9 Gypframe Floor & Ceiling Channel cut and bent to extend up studs
5 Timber door frame and architrave
Advice should be sought from the door manufacturer prior to the construction of these details.
At the base, the channel is cut and bent to extend 300mm up the studs and fixed each side with two British Gypsum Wafer Head Drywall Screws.
The studs each side of the opening are sleeved full height of opening with Gypframe Floor & Ceiling Channel.
The principle of this alternative detail is only suitable for GypWall classic, GypWall robust and GypWall extreme for fixed head situations only.
Introduction
To be read in conjunction with system specific details. Refer to relevant system sections
28
3
1
Partitions
150mm
4
C04
5
150mm
Openings 1201 - 3300mm wide, for example double doors or large windows
1 Gypframe 'C' Stud 6 Centre stud required for margin up to 600mm between openings
2 Stud sleeved to full opening height with Gypframe Floor & Ceiling Channel 7 Partition between openings, minimum 600mm for Gypframe 'C' Studs
3 Gypframe studs (appropriate to system) (minimum 300mm for Gypframe 'I' Studs)
4 Gypframe Extra Deep Flange Floor & Ceiling Channel 8 Maximum distance 2400mm (if exceeds 2400mm contact British Gypsum
Technical Advice Centre)
5 Gypframe stud insert
To be read in conjunction with system specific details. Refer to relevant system sections
29 30
Elevation
4
X
Y
Partitions
2
C04
2
Section X - X
1
Fire tested construction in which the damper is supported
3 by the partition (isometric view)
4 31
150mm
6
Section Y - Y
Opening for service penetrations in fire-rated partitions Opening up to 600mm wide for services
1 Gyproc plasterboard or Glasroc F specialist board 5 Damper (by others). Weight of damper should not exceed 57kg.
2 Gypframe 'C' Stud Size of damper should not exceed 1400 x 1200mm
3 Gypframe Floor & Ceiling Channel 6 Gypframe Folded Edge Standard Floor & Ceiling Channel cut and bent
to form opening head and cill
4 Penetration seal if required (refer to damper manufacturer for details)
Introduction
To be read in conjunction with system specific details. Refer to relevant system sections
32
Partitions
5
C04
2
33 34
2 6
7 7
Horizontal board joint - double layer Horizontal board joint - single layer
1 Inner layer of Gyproc plasterboard or Glasroc F specialist board 5 British Gypsum Drywall Screws
2 Outer layer of Gyproc plasterboard or Glasroc F specialist board 6 Gyproc plasterboard or Glasroc F specialist board
3 Gypframe GFS1 Fixing Strap 7 Gypframe 'C' Stud
4 Gypframe metal framing 8 Gypframe GFT1 Fixing T (alternatively use Gypframe GSF1 Fixing Strap)
GypWall extreme
Ultimate impact and abrasion resistant partition system
Partitions
The GypWall extreme family of partitions have Refer to C02. S01. P49
C04
surpassing all requirements of a full Severe Duty
Rating in accordance with BS 5234: Part 2: 1992. Refer to C01. S01. P07
Key benefits
— Provides performance beyond a Severe Duty
Rating from a lightweight, narrow-footprint
solution
— Heavy fixtures can be secured to a single layer
without the need for additional pattressing
— Reduced maintenance cycles due to a highly
impact and scratch resistant board surface
— Fully compatible with other British Gypsum
systems, meaning GypWall extreme can be
specified in areas of the building that really
need it
Handy hint
For areas of a building where extreme levels of duty are required
to only one side of the construction, for example a partition
between a corridor and a classroom, refer to C04. S04. P08
GypWall extreme / robust hybrid system performance tables.
1 2 3
One layer of board each side of One layer of board each side of One layer of board each side of
Gypframe 70 S 60 ‘C’ Studs at 600mm Gypframe 70 S 60 ‘C’ Studs at 600mm Gypframe 70 S 60 ‘C’ Studs at 600mm
centres. Linings as in table. centres. 25mm Isover Acoustic Partition centres. 50mm Isover Acoustic Partition
Roll (APR 1200) in the cavity. Roll (APR 1200) in the cavity.
Linings as in table. Linings as in table.
Partitions
4 5 6
C04
One layer of board each side of Two layers of board each side of Two layers of board each side of
Gypframe 70 S 60 ‘C’ Studs at 600mm Gypframe 70 AS 50 AcouStuds at Gypframe 70 AS 50 AcouStuds at
centres. 60mm Isover ULTIMATE™ Piano 600mm centres. Linings as in table. 600mm centres. 25mm Isover Acoustic
Plus in the cavity. Linings as in table. Partition Roll (APR 1200) in the cavity.
Linings as in table.
Detail Partition Inner board type ACTIVair Outer board ACTIVair Max. Sound Duty Approx. System
thickness mm technology type technology partition insulation rating weight reference
mm available1 mm available1 height2 Rw dB kg/m²
mm
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
These systems have an ACTIVair board option available, which improves indoor air quality. Alternatively, all systems can be skim finished
with ThistlePro PureFinish, which contains ACTIVair technology. Refer to C08. S02. P05 and C02. S01. P49 for further details.
2
The maximum heights quoted are limited by the fire state field of application or by limiting deflection of L/240 at 200 Pa, whichever is the more onerous.
3
The resistance to impact of Rigidur h is higher than the most severe criteria set out in BS 5234. British Gypsum has conducted a number of additional
structural performance and durability tests beyond Severe Duty to better reflect actual use in high traffic areas. Search for substantiation report on
british-gypsum.com and type in the reference number.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
Gypframe Deep Flange Floor & Ceiling Channel or Gypframe Extra Deep Flange Floor & Ceiling Channel should be used at base and at head
(subject to deflection criteria).
GypWall extreme
For details of when
to specify fire
70mm Gypframe ‘C’ Stud and Gypframe AcouStud resistance using BS
Refer to C02. S01. P05
Table 1b — Solutions to satisfy requirements of BS 476: Part 22: 1987
1 2 3
One layer of board each side of One layer of board each side of One layer of board each side of
Gypframe 70 S 60 ‘C’ Studs at 600mm Gypframe 70 S 60 ‘C’ Studs at 600mm Gypframe 70 S 60 ‘C’ Studs at 600mm
centres. Linings as in table. centres. 25mm Isover Acoustic Partition centres. 50mm Isover Acoustic Partition
Roll (APR 1200) in the cavity. Roll (APR 1200) in the cavity.
Linings as in table. Linings as in table.
Partitions
4 5 6
C04
One layer of board each side of Two layers of board each side of Two layers of board each side of
Gypframe 70 S 60 ‘C’ Studs at 600mm Gypframe 70 AS 50 AcouStuds at Gypframe 70 AS 50 AcouStuds at
centres. 60mm Isover ULTIMATE™ Piano 600mm centres. Linings as in table. 600mm centres. 25mm Isover Acoustic
Plus in the cavity. Linings as in table. Partition Roll (APR 1200) in the cavity.
Linings as in table.
Detail Partition Inner board type ACTIVair Outer board ACTIVair Max. Sound Duty Approx. System
thickness mm technology type technology partition insulation rating weight reference
mm available1 mm available1 height2 Rw dB kg/m²
mm
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
These systems have an ACTIVair board option available, which improves indoor air quality. Alternatively, all systems can be skim finished
with ThistlePro PureFinish, which contains ACTIVair technology. Refer to C08. S02. P05 and C02. S01. P49 for further details.
2
Based on a limiting deflection of L/240 at 200 Pa.
3
The resistance to impact of Rigidur h is higher than the most severe criteria set out in BS 5234. British Gypsum has conducted a number of additional
structural performance and durability tests beyond Severe Duty to better reflect actual use in high traffic areas. Search for substantiation report on
british-gypsum.com and type in the reference number.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
Gypframe Deep Flange Floor & Ceiling Channel or Gypframe Extra Deep Flange Floor & Ceiling Channel should be used at base and at head
(subject to deflection criteria).
Detail Partition Inner board type ACTIVair Outer board ACTIVair Max. Sound Duty Approx. System
thickness mm technology type technology partition insulation rating weight reference
C04
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
These systems have an ACTIVair board option available, which improves indoor air quality. Alternatively, all systems can be skim finished
with ThistlePro PureFinish, which contains ACTIVair technology. Refer to C08. S02. P05 and C02. S01. P49 for further details.
2
The maximum heights quoted are limited by the fire state field of application or by limiting deflection of L/240 at 200 Pa, whichever is the more onerous.
3
The resistance to impact of Rigidur h is higher than the most severe criteria set out in BS 5234. British Gypsum has conducted a number of additional
structural performance and durability tests beyond Severe Duty to better reflect actual use in high traffic areas. Search for substantiation report on
british-gypsum.com and type in the reference number.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
Gypframe Deep Flange Floor & Ceiling Channel or Gypframe Extra Deep Flange Floor & Ceiling Channel should be used at base and at head
(subject to deflection criteria).
GypWall extreme
For details of when
to specify fire
146mm Gypframe AcouStud resistance using BS
Refer to C02. S01. P05
Table 2b — Solutions to satisfy requirements of BS 476: Part 22: 1987
Partitions
Partition Roll (APR 1200) in the cavity.
Linings as in table.
Detail Partition Inner board type ACTIVair Outer board ACTIVair Max. Sound Duty Approx. System
thickness mm technology type technology partition insulation rating weight reference
C04
mm available mm available1 height2 Rw (Rw + Ctr ) kg/m²
mm dB
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
These systems have an ACTIVair board option available, which improves indoor air quality. Alternatively, all systems can be skim finished
with ThistlePro PureFinish, which contains ACTIVair technology. Refer to C08. S02. P05 and C02. S01. P49 for further details.
2
Based on a limiting deflection of L/240 at 200 Pa.
3
The resistance to impact of Rigidur h is higher than the most severe criteria set out in BS 5234. British Gypsum has conducted a number of additional
structural performance and durability tests beyond Severe Duty to better reflect actual use in high traffic areas. Search for substantiation report on
british-gypsum.com and type in the reference number.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
Gypframe Deep Flange Floor & Ceiling Channel or Gypframe Extra Deep Flange Floor & Ceiling Channel should be used at base and at head
(subject to deflection criteria).
1 2 3 4
One layer of board each side of One layer of board each side of One layer of board to side 1 and two One layer of board to side 1 and two
Gypframe 70 S 60 ‘C’ Studs at 600mm Gypframe 70 S 60 ‘C’ Studs at 600mm layers of board to side 2 of Gypframe layers of board to side 2 of Gypframe
centres. Linings as in table. centres. 50mm Isover Acoustic Partition 70 AS 50 AcouStuds at 600mm centres. 70 AS 50 AcouStuds at 600mm centres.
Roll (APR 1200) in the cavity. Linings as in table. 50mm Isover Acoustic Partition Roll
Linings as in table. (APR 1200) in the cavity.
Linings as in table.
Partitions
Detail Partition Board type and ACTIVair Board type and ACTIVair Max. Sound Duty Approx. System
thickness thickness (side 1) technology thickness (side 2) technology partition insulation rating weight reference
mm mm available mm available1 height2 Rw dB kg/m²
C04
mm
Gyproc WallBoard 15 -
3 115 Gyproc DuraLine 15 -
+ Rigidur h 12.5 4200 47 Severe3 40 X606A019
Gyproc SoundBloc 15 -
3 -
115 Gyproc DuraLine 15
+ Rigidur h 12.5 4200 49 Severe3 44 X606A021
Gyproc WallBoard 15 -
4 115 Gyproc DuraLine 15 -
+ Rigidur h 12.5 4200 52 Severe3 40 X606A020
Gyproc SoundBloc 15 -
4 -
115 Gyproc DuraLine 15
+ Rigidur h 12.5 4200 55 Severe3 44 X606A022
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
These systems have an ACTIVair board option available, which improves indoor air quality. Alternatively, all systems can be skim finished
with ThistlePro PureFinish, which contains ACTIVair technology. Refer to C08. S02. P05 and C02. S01. P49 for further details.
2
The maximum heights quoted are limited by the fire state field of application or by limiting deflection of L/240 at 200 Pa, whichever is the more onerous.
3
The resistance to impact of Rigidur h is higher than the most severe criteria set out in BS 5234. British Gypsum has conducted a number of additional
structural performance and durability tests beyond Severe Duty to better reflect actual use in high traffic areas. Search for substantiation report on
british-gypsum.com and type in the reference number.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
Gypframe Deep Flange Floor & Ceiling Channel or Gypframe Extra Deep Flange Floor & Ceiling Channel should be used at base and at head
(subject to deflection criteria).
GypWall extreme
For details of when
to specify fire
70mm Gypframe 'C' Stud and Gypframe AcouStud resistance using BS
Refer to C02. S01. P05
Table 3b - Solutions to satisfy requirements of BS 476: Part 22: 1987
1 2 3 4
One layer of board each side of One layer of board each side of One layer of board to side 1 and two One layer of board to side 1 and two
Gypframe 70 S 60 ‘C’ Studs at 600mm Gypframe 70 S 60 ‘C’ Studs at 600mm layers of board to side 2 of Gypframe layers of board to side 2 of Gypframe
centres. Linings as in table. centres. 50mm Isover Acoustic Partition 70 AS 50 AcouStuds at 600mm centres. 70 AS 50 AcouStuds at 600mm centres.
Roll (APR 1200) in the cavity. Linings as in table. 50mm Isover Acoustic Partition Roll
Linings as in table. (APR 1200) in the cavity.
Linings as in table.
Partitions
Detail Partition Board type and ACTIVair Board type and ACTIVair Max. Sound Duty Approx. System
thickness thickness (side 1) technology thickness (side 2) technology partition insulation rating weight reference
mm mm available mm available1 height2 Rw dB kg/m²
C04
mm
Gyproc WallBoard 15 -
3 115 Gyproc DuraLine 15 -
+ Rigidur h 12.5 4200 47 Severe3 40 X606A019
Gyproc SoundBloc 15 -
3 -
115 Gyproc DuraLine 15
+ Rigidur h 12.5 4200 49 Severe3 44 X606A021
Gyproc WallBoard 15 -
4 115 Gyproc DuraLine 15 -
+ Rigidur h 12.5 4200 52 Severe3 40 X606A020
Gyproc SoundBloc 15 -
4 -
115 Gyproc DuraLine 15
+ Rigidur h 12.5 4200 55 Severe3 44 X606A022
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
These systems have an ACTIVair board option available, which improves indoor air quality. Alternatively, all systems can be skim finished
with ThistlePro PureFinish, which contains ACTIVair technology. Refer to C08. S02. P05 and C02. S01. P49 for further details.
2
Based on a limiting deflection of L/240 at 200 Pa.
3
The resistance to impact of Rigidur h is higher than the most severe criteria set out in BS 5234. British Gypsum has conducted a number of additional
structural performance and durability tests beyond Severe Duty to better reflect actual use in high traffic areas. Search for substantiation report on
british-gypsum.com and type in the reference number.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
Gypframe Deep Flange Floor & Ceiling Channel or Gypframe Extra Deep Flange Floor & Ceiling Channel should be used at base and at head
(subject to deflection criteria).
Whilst our GypWall partition systems are non-loadbearing, they Control joints may be required in the partition to relieve stresses
are able to provide resistance to levels of horizontal uniformly induced by expansion and contraction of the structure. They should
distributed loads. coincide with movement joints within the surrounding structure.
Refer to C02. S01. P26 – Robustness. Refer to Partitions introduction C04. S01. P10 – construction
detail 12.
Planning – key factors
Deflection heads
GypWall extreme comprises Gypframe 'C' Studs installed at 600mm
centres within Gypframe Deep Flange Floor & Ceiling Channels. Partition head deflection designs may be necessary to
The position of services and heavy fixtures should be accommodate deflections in the supporting floor. Deflection heads
pre-determined and their installation planned into the frame may also be required to the underside of roof structures subjected
Partitions
Fixing floor and ceiling channels To minimise the loss of acoustic performance:
Gypframe Deep Flange Floor & Ceiling Channels must be securely Refer to C02. S01. P10 – Building acoustics.
fixed with a row of fixings at 600mm maximum centres. For 94mm
C04
channels and above, two rows of staggered fixings are required, For deflection head design:
each row at 600mm centres and each fixing 25mm in from the
Refer to Partitions introduction C04. S01. P11 – construction
flange. If the floor is uneven, a 38mm thick timber sole plate equal
details 15-22.
to the width of the channel should be used.
Services
If the concrete or screeded floor is new, consideration should be
given to the installation of a damp-proof membrane between the Penetrations
floor surface and the channel or sole plate. Penetrations of fire-resistant or sound-insulating constructions
for services need careful consideration to ensure that the
Splicing performance of the element is not downgraded. Consideration also
needs to be given to the services themselves so they do not act as
To extend studs, overlap by 600mm (minimum). Fix together using
the mechanism of fire spread or sound transmission.
British Gypsum Wafer Head Drywall Screws or steel pop rivets (two
to each flange), or by using the Gyproc Stud Interlocking Tool twice Refer to C02. S01. P32 – Service installations.
to each flange.
Electrical
Refer to Partitions introduction C04. S01. P07 – construction
The installation of electrical services should be carried out in
detail 1.
accordance with BS 7671. The cut-outs in the studs can be used for
routing electrical and other small services (Partitions introduction
Partition to structural steelwork junctions
C04. S01. P07 – construction detail 2). Switch boxes and socket
When designing the layout of rooms requiring separation by sound outlets can be supported from Gypframe 99 FC 50 Fixing Channel
insulating walls abutting structural steelwork, consideration should fixed horizontally between studs, or a high performance socket box
be given to the potential loss of sound insulation performance detail used where higher acoustic performance is required.
through the steelwork.
Refer to C02. S01. P10 – Building acoustics. Where Gypframe AcouStuds are used, services are routed through
50mm x 28mm ‘H’ shaped push-outs, at the same centres as shown
Door openings in Partitions introduction C04. S01. P07 – construction detail 2a
for conventional cut-outs. Cables should be protected by conduit,
The designer should consider the thickness tolerances of the or other suitable precautions taken to prevent abrasion when they
partition types in relation to the proposed door frame detail. pass through the metal frame. Service cut-outs should be aligned to
To satisfy BS 5234 requirements for Heavy and Severe Duty allow easy installation of service. If studs require cutting, cut from
partitions, door framing should be specified as shown in Partitions the same end of each stud to ensure cut-out alignment.
introduction C04. S01. P14 – construction details 26. The door
manufacturer should also be consulted in relation to the door detail. Independent support
If a plastered finish is specified, the thickness of the door or glazing When designing for the installation of services such as fire
frame must allow for the thickness of the plaster finish. dampers and associated ductwork through a GypWall partition,
consideration should be given to the size and weight of the
Cavity barriers damper - this will determine whether it can be supported directly
from the partition or needs to be independently supported from
Minimum 12.5mm Gyproc plasterboard screw-fixed into the web the structure.
of perimeter channels or vertical studs will provide a satisfactory
closure to flame or smoke. Refer to Partitions introduction C04. S01. P17 – construction
details 28-31.
Refer to C06. S07. P02 – Cavity barriers.
GypWall extreme
Fixtures Board finishing
Due to the inherent strength of Rigidur h, some fixtures can be For increased resistance to accidental damage, a skim coat of
made directly to the board – please see the Rigidur h for commercial ThistlePro DuraFinish plaster may be applied.
applications Product Data Sheet and the British Gypsum Site Book
Refer to the Rigidur h for commercial applications Product Data
for more information, available to download from
Sheet, available to download from british-gypsum.com
british-gypsum.com. Heavyweight fixtures (to BS 5234), such
as wash basins and wall cupboards, can be fixed using plywood
Tiling
secured with Gypframe Service Support Plates.
Tiles can be applied to the surface of lightweight partition systems.
Refer to C02. S01. P33 – Service installations.
Refer to C08. S04. P02 – Tiling
Access for maintenance
Construction details
Partitions
Gyproc Profilex Access Panels are available to provide access for
maintenance. Access panels must be fully compatible with drywall For standard GypWall construction details
construction and match the fire rating of the partition. Refer to Partitions introduction C04. S01. P07 – construction
details
Refer to profilex.co.uk for further information.
C04
Handy hint SpecSure®
— Rigidur h is available as a special order in All our systems are covered by SpecSure® when
sizes up to 2.5m x 6.0m, reducing the using genuine British Gypsum and Saint-Gobain
amount of tape and jointing required Isover products.
— The use of insulation within the partition
cavity to provide a higher acoustic
performance than may initially be
required, will help to future proof for
subsequent changes of room use
— Cut-outs in the Gypframe Studs can be
used to accommodate horizontal service
runs. Installers should be made aware of
this to avoid vertical misalignment of
cut-outs between adjacent studs
1 2
4 1
2
Partitions
2
C04
Head Base
3 4
1
1
1 Rigidur h 5 Bulk fill with Gyproc jointing materials (where gap exceeds 5mm)
2 Gypframe ‘C’ Stud 6 Skirting
3 Gypframe Deep Flange Floor & Ceiling Channel 7 Internal blockwork
4 Gyproc Sealant 8 DriLyner basic wall lining system
GypWall extreme
Gypframe metal components ( Refer to C10. S02. P02 for details)
Partitions
Gypframe Deep Flange Floor & Ceiling Channels Gypframe GA5 Internal Fixing Angle
(72 DC 60, 148 DC 60) Steel angle providing framing stability and
Floor and ceiling channels with deep flanges for board support.
C04
retaining the Gypframe studs at floor and ceiling
junctions for partitions 4200mm to 8000mm high.
Also used around openings and in deflection heads
(maximum 30mm deflection).
Gypframe Extra Deep Flange Floor & Ceiling Gypframe GA6 Splayed Angle
Channels (72 EDC 80, 148 EDC 80) Steel angle providing framing stability and
Floor and ceiling channels with extra deep flanges board support.
for retaining the Gypframe studs at floor and ceiling
junctions for partitions over 8000mm high. Also used
around openings and in deflection heads (maximum
50mm deflection).
1
Also available in a Moisture Resistant (mr) version. mr boards are specified in intermittent wet use areas.
than 0.8mm thick. greater (‘I’ stud 0.6mm thick and greater).
British Gypsum Wafer Head Drywall Screws British Gypsum Wafer Head Jack-Point Screws
Corrosion resistant self-tapping steel screws Corrosion resistant self-tapping steel screws for
C04
for fixing metal to metal framing less than fixing metal to metal framing 0.8mm thick
0.8mm thick (‘I’ studs less than 0.6mm thick). (‘I’ studs 0.6mm thick and greater).
Gyproc AquaBead
An easy to apply, water, activated adhesive corner
bead, for reinforcing external 90°C angles in taped
and jointed plasterboard constructions.
GypWall extreme
Finishing products ( Refer to C10. S06. P02 for details)
Partitions
common backgrounds including undercoat plasters
and plasterboard. For more information refer to
C02. S01. P49.
C04
Thistle SprayFinish ThistlePro Magnetic
To provide a plaster skim finish by spray or hand To provide a plaster skim finish that provides an
application, ideal for medium to large projects. attraction to magnets used to finish a wide range
of backgrounds, including undercoat plasters and
plasterboard.
Isover Acoustic Partition Roll (APR 1200) Isover ULTIMATE™ Piano Plus
Glass mineral wool for enhanced acoustic and Glass mineral wool for enhanced acoustic and fire
thermal performance. performance.
Gypframe Deep Flange or Extra Deep Flange Gypframe Studs are suitably fixed to The perimeter of the partition is then sealed
Floor & Ceiling Channels are suitably fixed abutments. on both sides with Gyproc Sealant.
to the floor and soffit.
C04
Gypframe studs are then friction fitted into Door openings are constructed to the Heavy M&E services can be located within the
the Gypframe Deep Flange Floor & Ceiling and Severe Duty detail. partition cavity.
Channels at required centres.
Isover insulation can also be added to Gyproc DuraLine, Gyproc SoundBloc or Rigidur h boards are then fixed as the outer
the partition cavity for increased acoustic Gyproc WallBoard plasterboards may be layer to all Gypframe framing members
performance. installed as either an inner layer, or as part with Rigidur Screws.
of the GypWall extreme / robust hybrid system
with British Gypsum Drywall Screws. It is recommended that Rigidur H
boards are pre-drilled and countersunk
screw locations for improved ease of
installation. For further information, refer to
the British Gypsum Good Practice Guide.
Additional information
For full installation details, refer to the
British Gypsum Site Book, available to
download from british-gypsum.com