Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
MODULE II
VOLTAGE REGULATION
1
03-03-2020
Regulation characteristics
Change in voltage regulation plotted w.r.t. change in power
factor, at constant load current.
Regulation positive for upf & lagging pf
Regulation negative for leading pf
Problem 1
A 3-phase, 4-pole, star-connected turbo-alternator has a
smooth cylindrical type rotor. The effective resistance &
synchronous reactance per phase are 0.15 ohm and 2.5 ohm.
Calculate the voltage regulation when delivering 250A at 6.6kV
and 0.6 pf lagging.
I = 150 – j 200 A
E= 4346.72 ∟4.55˚
EL = 7528.74 V
% rgn = 14.07
2
03-03-2020
Problem 2
A 3-phase, 1 MVA, 11 kV, star-connected Alternator has
resistance of 0.7Ω per phase & synchronous reactance 12Ω
per phase. Determine the percentage voltage regulation for a
load of 600kW at 0.8 pf leading and at rated voltage.
I = 31.49 + j 23.62 A
E = 6102.21 ∟3.71˚ V
EL = 10.56 kV
% rgn = -3.92
3
03-03-2020
Methods used
A. Indirect Methods
1. Synchronous impedance method or EMF method
2. Ampere-turn method or MMF method
3. Zero Power Factor method or Potier method
4
03-03-2020
5
03-03-2020
To obtain the open circuit characteristics the machine is driven at rated
speed without the load.
Readings of the line-to-line voltage are taken for various values of field
current.
The voltage, except in very low voltage machines, is stepped down by the
means of a potential transformer. 11
O.C.C
If not for the magnetic saturation of the iron, the open circuit
characteristics would be linear as represented by the air gap
line
12
6
03-03-2020
c) short-circuit test
13
7
03-03-2020
Calculation of zs
O.C.C. is plotted in a graph sheet by selecting suitable voltage
scale for Y-axis, such that the O.C.C occupies the entire graph
sheet.
With separate current scale S.C.C. is drawn on the same graph
sheet.
The current scale should be selected in such a manner that the
extended straight line S.C.C. lies below the O.C.C.
Zs will be equal to the open-circuit voltage divided by the short-
circuit current at that field current which gives the rated e.m.f.
per phase.
Zs =open-circuit voltage per phase
short-circuit armature current
15
Calculation of zs
16
8
03-03-2020
17
Problems
1. A 3-phase, 1500 kVA, star-connected, 50 Hz,2300 V
Alternator has a resistance between each pair of terminals as
measured by direct current is 0.16 Ω. Assume that the
effective resistance is 1.5 times the ohmic resistance. A field
current of 70 A produces a short-circuit current equal to full-
load current of 376 A in each line. The same field current
produces an e.m.f. of 700 V on open circuit. Determine the
synchronous reactance of the machine and its full load
regulation at 0.8 pf lagging.
Xs = 1.068 Ω
|E| = 1631
% rgn = 22.8
18
9
03-03-2020
problems
1. A 50 kVA, 415 V, 50 Hz, star-connected alternator has an
effective resistance of 0.2Ω per phase. A field current of 8A
causes an emf of 415 V on open circuit and a current of 185
Aon short-circuit. Calculate (i) the synchronous impedance, (ii)
the synchronous reactance (iii) the full-load voltage regulation
at 0.8 pf lagging and (iv) the 3/4th full-load voltage regulation
at 0.9 pf leading.
(i) |Zs| = 1.261 Ω
(ii) Xs = 1.245 Ω
(iii) 28.86 %
(iv) -4.22 %
19
20
10
03-03-2020
problems
1. A 3-phase, star-connected, 1000kVA, 2000V, 50Hz alternator
gave the following open-circuit & short-circuit test readings:
Field A 10 20 25 30 40 50
current
problems
2. A 3.3 kV alternator gave the following test results:
Field 16 25 37.5 50 70
current (A)
OC Voltage 1.55 2.45 3.3 3.75 4.15
(kV)
22
11
03-03-2020
Isc,rated
If (A)
If_V rated If_Isc rated 23
24
12
03-03-2020
2 methods
1. Loading the alternator by pure inductive loads
25
26
13
03-03-2020
28
14
03-03-2020
29
30
15
03-03-2020
G2
Gn
31
necessity
1. Many generators can supply a bigger load than
one machine by itself.
2. Having many generators increases the reliability
of the power system, since failure of any one of
them does not cause a total power loss to the
load.
3. Having many generators operating in parallel
allows one or more of them to be removed for
shutdown and preventive maintenance.
4. If only one generator is used and it is not
operating at near full load, then it will be
32
16
03-03-2020
Conditions to be satisfied
1. Alternator voltage magnitude should be equal to supply
voltage magnitude.
2. Alternator voltage phase sequence should be equal to
supply voltage phase sequence.
3. Alternator voltage frequency should be equal to supply
voltage frequency
33
Conditions to be satisfied
34
17
03-03-2020
35
36
18
03-03-2020
3. Using synchroscope
37
38
19
03-03-2020
Load sharing
Total real & reactive power delivered to the load depends on
1. Prime mover characteristics/ input
2. Excitation level
39
1. Prime-mover characteristics
Difference in prime-mover characteristics causes the real
power shared by the synchronous generators to change in
accordance with their characteristics
1. Two similar 500kVA Alternators operate in parallel. Their
prime-mover characteristics are such that the frequency of
Alternator 1 drops uniformly from 50Hz on no-load to 48Hz on
full-load and that of Alternator 2 from 50Hz to 48.5Hz. (i) How
will the two Alternators share a load of 400kW? (ii) what is the
maximum load at UPF that can be delivered without
overloading either Alternator?
(i) f1= 48.875Hz,P11=175.45kW, P21= 228.55kW
(ii) f2= 48.5Hz, P12 = 225kW, P22 = 300kW, P= 525kW
40
20
03-03-2020
1. Prime-mover characteristics
2. Two similar 1500kVA Alternators operate in parallel. Their
prime mover characteristics is such that the frequency of
Alternator 1 drops uniformly from 50.5Hz on no-load to 49Hz
on full-load and that of Alternator 2 from 50Hz to 48Hz. How
will the Alternators share a load of 2250kW?
f= 49Hz, P1=1500kW, P2=750kW
3. Two 50MVA, 3-phase Alternators operate in parallel. The
setting of governors in the prime-mover are such that the rise
in speed from full-load to no-load is 1% in Alternator 1 and 2%
in Alternator 2, the characteristics being straight lines in both
cases. If each Alternator is fully loaded when the total load is
100MW, what will be the load on each Alternator when the
total load is reduced to 85MW?
41
N=100.2%, P1=40MW, P2=45MW
42
21
03-03-2020
43
22