DPU30A-N06A1, DPU30D-N06A1, and DPU40D-N06A1 Distributed

Power Quick Guide


Issue: 05
Date: 2019-11-01

Copyright © Huawei Technologies Co., Ltd. 2019. All rights reserved.

1 Overview
AC power supply unit (PSU): Lithium battery: Lithium battery: DC distribution box:
DPU30A-N06A1 DBU20B-N12A2 DBU25B-N12A1/DBU40B-N12A2 DOU-DCD01
DC PSU:
DPU30D-N06A1
DPU40D-N06A1

(Unit: mm) (Unit: mm) (Unit: mm) (Unit: mm)

PSU Lithium Battery


Color Status Meaning Color Status Meaning
Indicator Indicator
No power input, or
Off No power input, or module fault Off
module fault
Blinking slowly (0.5 Run indicator Blinking
Run Normal communication Green Normal communication
Green Hz) (RUN) slowly (0.5 Hz)
indicator
Abnormal communication with Blinking fast Abnormal
Blinking fast (4 Hz)
the upstream monitoring device (4 Hz) communication
Steady on Module alarm Module fault alarm,
Alarm
Yellow Blinking slowly (0.5 Abnormal communication with Steady on which requires module
indicator Alarm indicator
Hz) its own monitoring device Red replacement
(ALM)
Fault Blinking Module protection alarm,
Red Steady on Module fault
indicator slowly (0.5 Hz) which can be cleared

Installation Installation
Max. Capacity/Layer Max. System Configuration
Scenario Method
2 PSUs +2 lithium batteries or 3 lithium 4 DC PSUs (DPU30D) /2 AC PSUs (DPU30A) + 5 lithium
batteries (Install the first battery exactly batteries (DBU20B)
Side
Small pole on the pole, the second battery on its left 4 DC PSUs (DPU40D) /2 AC PSUs (DPU30A) + 8 lithium
mounting
side, and the third battery or two PSUs batteries (DBU25B / DBU40B)
on its right side.)
Small pole, wall,
Flush If the system configuration exceeds the maximum
large pole, channel 1 PSU + 1 lithium battery or 2 PSUs
mounting capacity/layer, install the modules on different layers.
steel, angle steel

2 Installation Preparations

 Wear gloves during installation.


 Never install a module with power on. Ensure that the angle between a module and the line vertical to the ground is within 10 degrees.
 Do not assemble a lithium battery with an RRU. Do not install a PSU on the left side of an RRU or lithium battery.
 The paint on the module exterior should be intact. If paint flakes off, repaint the area to avoid corrosion.
 An upstream AC SPD of at least 30 kA is required for the PSU.
 When securing a large-pole mounting kit, ensure that the hoops are closely attached to the pole and that there are no sundries between
the hoops and the pole.
 When the PSU is assembled with the RRU or lithium battery, ensure that the PSU, RRU, and lithium battery are installed in the same
direction and that the handles are on the same side.
 After unpacking the equipment, you must power it on within 24 hours. When the equipment is maintained, the power-off duration cannot
exceed 24 hours.

1
Installing the connecting kit to the lithium battery

DBU20B-N12A2 DBU25B-N12A1、DBU40B-N12A2
NOTE
 The installation and cable connection methods
for all lithium batteries are the same. The
DBU20B-N12A2 is used as an example.
 The connecting kit and hanging kit for the
DBU20B-N12A2 is different from that of the
DBU25B-N12A1 and DBU40B-N12A2, as
shown below.

Installing the hanging kit on the side of the lithium battery


DBU20B-N12A2
Remove the hanging kit from the rear of the lithium battery and Remove the hanging kit from the rear of the lithium battery and
install the kit on its right side. install the kit on its left side.

DBU25B-N12A1, DBU40B-N12A2

Remove the hanging kit from the rear of the lithium battery and Remove the hanging kit from the rear of the lithium battery and
install the kit on its right side. install the kit on its left side.

3 Installing PSUs and Lithium Batteries


3.1 Installing the RJ45 Communications Cable for a Lithium Battery

2
3.2 Side Mounting on a Small Pole (Mode 1): 1 PSU + 1 Lithium Battery (Pole Diameter: 60–114 mm)
Space Planning Required Accessories Installation Procedure
Pole mounting kit Install the pole mounting Install the connecting
(Unit: mm) Cx1 kits. kit to the lithium battery.
Bx1
Ax1

Connecting kit x 1

Connecting
plate x 1

Install the lithium battery to Install the PSU to the Install the connecting plate.
the pole. lithium battery.

3.3 Side Mounting on a Small Pole (Mode 2): 1 PSU + 1 Lithium Battery (Pole Diameter: 60–114 mm)
Space Planning Required Accessories Installation Procedure
(Unit: mm) Pole mounting kit Cx1 Install the pole mounting kits.
Ax1 Bx1

Dx1
Hanging
kit A x 1

Connecting
plate x 1

Install hanging Install the lithium Install the PSU to the pole. Install the connecting plate.
kit A to the PSU. battery to the pole.

3
3.4 Flush Mounting on a Small Pole (Mode 1): 2 PSUs + 1 Lithium Battery (Pole Diameter: 60–114 mm)
Space Planning Required Accessories Installation Procedure
(Unit: mm) Pole mounting kit Install the pole mounting
Install the connecting kit.
Bx1 Cx1 kits.
Ax2

Hanging
kit B x 1
Connecting
kit x 1

Connecting
plate x 2

Install hanging Install the lithium battery to Install PSUs to the pole. Install the connecting plates.
kit B to PSUs. the pole.

3.5 Side Mounting on a Small Pole (Mode 2): 2 PSUs + 1 Lithium Battery (Pole Diameter: 60–114 mm)
Space Planning Required Accessories Installation Procedure
(Unit: mm) Pole mounting kit
Cx1 Install the pole mounting kit.
Ax1 Bx1

Dx2
Hanging
kit A x 2

Connecting
plate x 2

Install hanging Install the lithium battery to Install PSUs to the pole. Install the connecting plates.
kits A to PSUs. the pole.

4
3.6 Flush Mounting on a Small Pole: 1 PSU + 1 Lithium Battery (Pole Diameter: 60–114 mm)
Space Planning Required Accessories Installation Procedure
(Unit: mm) Pole mounting kit Install the pole Remove the hanging kit from the rear
mounting kits. of the lithium battery and install the kit
Bx1 Cx1
on its left side.
Ax1

Connecting
kit x 1
Connecting
plate x 1

Install the connecting kit Install the lithium Install the PSU to Install the connecting plate.
to the lithium battery. battery to the pole. the lithium battery.

3.7 Flush Mounting on a Small Pole: 2 PSUs + 1 Lithium Battery (Pole Diameter: 60–114 mm)
Space Planning Required Accessories Installation Procedure
(Unit: mm) Pole mounting kit Install the pole mounting Assemble the PSUs and install
Bx2 Cx2 kits. the PSU hanging kit B.
Ax2

Connecting Hanging kit


kit x 1 Bx1

Connecting
plate x 1

Install the connecting Remove the hanging kit from the rear Install the PSUs to the Install the lithium battery to
plate. of the lithium battery and install the pole. the pole.
kit on its right side.

5
3.8 Flush Mounting on a Large Pole: 1 PSU + 1 Lithium Battery (Pole Diameter: 114–400 mm)
Space Planning Required Accessories Installation Procedure
Pole mounting kit Assemble the large pole Secure the large pole
(Unit: mm) Bx1 Cx0 installation kit. installation kit to the large pole.
Ax1

Large pole Connecting


installation kit x 1
kit x 1 set
Rear

Front

Ensure that the hoops are


attached closely to the pole
Connecting so that they do not slide.
plate x 1

Remove the hanging kit from the Install the Install the lithium battery to Install the PSU to
rear of the lithium battery and install connecting kit. the large pole. the lithium battery.
the kit on its left side.

Install the connecting plate.

3.9 Flush Mounting on a Large Pole: 2 PSUs + 1 Lithium Battery (Pole Diameter: 114–400 mm)
Space Planning Required Accessories Installation Procedure
Large pole Assemble the large pole Secure the large pole
installation installation kits. installation kits
kit x 2 sets to the large pole.

Connecting kit x 1
Hanging kit B x 1

Pole mounting kit


Bx2 Cx0 Rear
Ax2

Front
Ensure that the hoops
are attached closely to
(Unit: mm) the pole so that they
Connecting do not slide.
plate x 1

6
Assemble the PSUs Install the connecting plate. Remove the hanging kit from the rear
and install the PSU of the lithium battery and install the
hanging kit B. kit on its right side.

Install the PSUs to the large pole. Install the lithium battery to the large pole.

3.10 Flush Mounting on a Wall (Mode 1): 1 PSU + 1 Lithium Battery


The wall must be able to bear a weight four times the weight of all PSUs and lithium batteries and the bolts' pulling force of
1.25 kN vertical to the wall.

Space Planning Required Accessories Installation Procedure


(Unit: mm) Connecting Install Install pole Install pole Install the
kit x 1 expansion mounting kit B. mounting connecting kit.
Connecting anchor bolts. kit A.
plate x 1
Hole depth: 55–
60 mm

Pole mounting kit


Bx1 Cx0
Ax1

(Unit: mm)

Remove the hanging kit from the Install the lithium Install the PSU to
Install the connecting plate.
rear of the lithium battery and battery to the wall. the lithium battery.
install the kit on its left side.

7
3.11 Flush Mounting on a Wall (Mode 2): 1 PSU + 1 Lithium Battery

The wall must be able to bear a weight four times the weight of all PSUs and lithium batteries and the bolts' pulling force of 1.25 kN vertical to
the wall.
Space Planning Required Accessories Installation Procedure
(Unit: mm) Wall mounting Install expansion anchor bolts. Install the wall Install the
kit x 1 mounting kit. connecting kit.
Hole depth: 55–60 mm

Connecting
kit x 1

Connecting
plate x 1 (Unit: mm)

Remove the hanging kit from the Install the lithium Install the PSU to Install the connecting plate.
rear of the lithium battery and install battery to the wall. the lithium battery.
the kit on its left side.

3.12 Flush Mounting on a Wall (Mode 1): 2 PSUs + 1 Lithium Battery


The wall must be able to bear a weight four times the weight of all PSUs and lithium batteries and the bolts' pulling force of
1.25 kN vertical to the wall.
Space Planning Required Accessories Installation Procedure
(Unit: mm) Pole mounting kit Install expansion Install pole mounting
Cx0 anchor bolts. kits B and A.
Bx2
Ax2
Hole depth: 55–
60 mm

Connecting Hanging kit


kit x 1 Bx1

Connecting
plate x 1 (Unit: mm)

Remove the hanging kit from the rear Assemble the PSUs Install the connecting plate.
of the lithium battery and install the kit and install the PSU
on its right side. hanging kit B.

8
Install the lithium battery to the wall. Install the PSUs to the wall.

3.13 Flush Mounting on a Wall (Mode 2): 2 PSUs + 1 Lithium Battery


The wall must be able to bear a weight four times the weight of all PSUs and lithium batteries and the bolts' pulling force of
1.25 kN vertical to the wall.
Space Planning Required Accessories Installation Procedure
Wall mounting kit x 2 Install expansion anchor bolts. Install the wall mounting
(Unit: mm) kits.
Connecting
plate x 1 Hole depth: 55–60 mm

Connecting Hanging
kit x 1 kit B x 1

(Unit: mm)

Remove the hanging kit from the Install the lithium Assemble the PSUs and Install the PSUs to the
rear of the lithium battery and battery to the wall. install the PSU hanging wall.
install the kit on its right side. kit B.

3.14 Flush Mounting on Channel or Angle Steel


NOTE
Channel steel
 As shown in the left figures, when
size and
the narrow edge size of channel
installation steel is less than 40 mm, only
method installation methods a and b are
supported.
 When channel or angle steel is
Angle steel used for installation, each layer
supports a maximum of 1 PSU + 1
size and lithium battery or 2 PSUs. Refer to
installation the procedure for flush mounting
on a small pole.
method

3.15 Installing a Single PSU


A single PSU can be flush-mounted on a small pole, wall, or large pole. For details, refer to installation procedures in sections 3.6, 3.8, 3.10,
and 3.12.

4 Installing a DC Distribution Box


If the DC distribution box is not configured, there is no need to install the DC distribution box and its cables.

The DC distribution box can be installed in the same way as the PSU. For details, refer to the relevant sections.

9
5 Installing Cables
5.1 Installing a Ground Cable
NOTE  It is recommended that the ground cable be prepared indoors.
 The following figure uses one PSU, one lithium battery, and
one DC distribution box as an example. Core cross-sectional area: 10 mm²

Site ground bar


Core cross-sectional
area: 16 mm²

PSU Lithium battery DC distribution box


5.2 Preparing AC and DC Cables
DC wiring terminal
Cable Type Core Cross-Sectional Area Cable Outer Diameter
Negative (blue)
AC (3-core) 1.5–4 mm2 9.0–14.5 mm

Positive (red)
AC wiring terminal
PE (green) DC (2-core) DPU30A/DPU30D: 3.3–6 mm2
DPU40D:
N/L2/HVDC negative (blue) 4–8.2 mm2(O-type DC power cable)
4–10 mm2(D-type DC power cable)
L/L1/HVDC positive (brown)
NOTE
 PSU load cables and AC input cables should be prepared onsite. DC load cables are used as an example here. Refer to this proc edure
when preparing AC cables.
 Multi-core cables should be used as AC and DC power cables; otherwise, water may seep into the waterproof connectors.
 It is recommended that AC and DC power cables be prepared indoors.
 Before assembling the waterproof connector, check whether the connection between the cable and terminal is firm and reliable.
Preparing DC Cables and Connecting Waterproof Connectors
• If the cable diameter is less than 6 mm2, prepare cables as follows:

Scale line

(Unit: mm)

• If the cable diameter is greater than 6 mm2, prepare cables as follows:

Scale
line

Crimping
tool

Bare crimp
(Unit: mm) terminal

Heat
shrink
Heat gun tubing

10
Installing Ground Clips for DC Load Cables
Cable binding hole (4 mm2) Cable binding hole (≥ 6 mm2)

Cable tie

Waterproof tape Insulation tape Cable tie Load cable Ground cable

5.3 Installing Power Cables and Communications Cables

 The system does not simultaneously support AC input and DC input.


 Ensure that caps and waterproof connectors are installed at all idle ports on the modules.

1 AC PSU + 1 Lithium Battery 1 DC PSU + 1 Lithium Battery


Lithium battery Lithium battery

PSU PSU
Other lithium
batteries

Ground clip

Monitoring Monitoring
device Site ground bar device
AC input AC load
AC/DC input DC load

NOTE If all DC loads (Huawei RRU 5xxx or AAU 5xxx series) support the MBUS protocol, the DC power system model is DPU40D-
N06A1, and the lithium battery model is DBU25B-N12A1 or DBU40B-N12A2, no communications cable needs to be installed
between the DC power system and the monitoring device (RRU/AAU).

DB15 Female Signal Signal


Pin Description Pin Description
Connector Definition Name Name
AC outage alarm RS485_RX
1 ALM1+ 9 Northbound RS485 reception +
(High resistance: alarm; low +
resistance: normal; port voltage
2 ALM1- range: 0–12 V; current: 1–50 mA) 10 RS485_RX- Northbound RS485 reception –
Common dry contact (normally
3 ALM2+ Common dry contact (normally open) 11 ALM4+
open)
Common dry contact (normally
4 ALM2- Common dry contact (normally open) 12 ALM4-
open)
5 ALM3+ Common dry contact (normally open) 13 Reserved Reserved
CAN data transmission and
6 ALM3- Common dry contact (normally open) 14 CANH
reception H
7 RS485_TX+ Northbound RS485 transmission + CAN data transmission and
15 CANL
8 RS485_TX- Northbound RS485 transmission – reception L

11
NOTE
The PSU is connected to the RRU and BBU to communicate with the NetEco or U2000.

The PSU connect with RRU5XXX The PSU connect with RRU3XXX The PSU connect with BBU
(RRU5520 as an example) (RRU3936 as an example) (BBU3910 as an example)

NOTE
The PSU communicate RRU3936
with RRU via MBUS.

NOTE
Label 1
RRU5520 connect to
EXT_ALM
of RRU;
Label
NOTE
connect to
When the U2000 is used for management, if
COM_ALM
port MON0 is occupied and port MON1 is used,
of PSU.
change the connection serial port number on the
U2000 to 1.

Cascading Multiple AC PSUs and Lithium Batteries


 If multiple PSUs are configured, it is recommended that AC loads be equally distributed on the PSUs.
 If multiple lithium batteries are configured, they should be cascaded by interconnecting BAT ports.

 Signal cable cascading:


PSUs should be interconnected using DB9–DB15 cables.
PSUs should be connected to lithium batteries using DB9–RJ45 cables.
Lithium batteries should be interconnected using RJ45–RJ45 cables.
 Connecting remote monitoring cables (two optional methods):
PSUs should be connected to the RRU using DB15–DB15 cables.
PSUs should be connected to a monitoring device using DB15–dry contact cables.

AC AC AC AC AC AC AC AC Monitoring device
input load load load input load load load

PSU 1 PSU 2

Lithium battery 1 Lithium battery 2 Lithium battery 3 Lithium battery 4 Lithium battery 5

Cascading Multiple DC PSUs and Lithium Batteries

 If multiple PSUs are configured, they can be cascaded by connecting BAT and LOAD ports or by interconnecting LOAD ports. It is
recommended that DC loads be equally distributed on the PSUs.
 If multiple lithium batteries are configured, they should be cascaded by interconnecting BAT ports.
 When all DC loads, DC power modules, and lithium batteries can communicate with each other through power cables, no
communications cable is required between the DC power module and the communications device or lithium battery.

 Signal cable cascading:


PSUs should be interconnected using DB9–DB15 cables.
PSUs should be connected to lithium batteries using DB9–RJ45 cables.
Lithium batteries should be interconnected using RJ45–RJ45 cables.
 Connecting remote monitoring cables (two optional methods):
PSUs should be connected to the RRU using DB15–DB15 cables.
PSUs should be connected to a monitoring device using DB15–dry contact cables.

12
DC DC DC
load load load

DC distribution box

Monitoring
AC/DC DC DC AC/DC DC DC AC/DC DC DC AC/DC DC DC device
input load load input load load input load load input load load

PSU 1 PSU 2 PSU 3 PSU 4

Lithium battery 1 Lithium battery 2 Lithium battery 3 Lithium battery 4

Lithium battery 5 Lithium battery 6 Lithium battery 7 Lithium battery 8

6 Verifying the Installation


1. Check that the mounting kits are securely installed and all screws are tightened.
2. Check that all cables are reliably connected with correct polarity and there is no short circuit.
3. Check whether any screw hole is not installed with a screw. If yes, install a screw in the hole.

7 Power-On Commissioning

AC PSU Power-On Commissioning


1. Measure the PSU input voltage. Ensure that the AC input voltage is in the range of 85–300 V AC.
2. Check the indicators on the PSUs and lithium batteries. Ensure that the green indicators are blinking slowly and that the yellow and red
indicators are off.
3. Measure the AC output voltage at each load port. Ensure that the output voltage is equal to the input voltage when there is mains input,
and that the output voltage is 220 V AC±3% (220 V system) or 110 V AC±3% (110 V system) when there is no mains input.
4. Measure the DC output voltage at each BAT port. Ensure that the voltage is in the range of –42 V DC to –58 V DC.
5. Observe the power system for about 15 minutes. If no alarm indicator is on, the system is running properly.

DC PSU Power-On Commissioning


1. Measure the PSU input voltage. Ensure that AC input voltage is in the range of 85–300 V AC and the HVDC input voltage is in the
range of 85–400 V DC.
2. Check the indicators on the PSUs and lithium batteries. Ensure that the green indicators are blinking slowly and that the yellow
and red indicators are off.
3. Measure the DC output voltage at each load port. Ensure that the voltage is in the range of –42 V DC to –58 V DC.
4. Observe the power system for about 15 minutes. If no alarm indicator is on, the system is running properly.

13
8 LIVE-C APP
8.1 Installing the LIVE-C APP
NOTE
LIVE-C APP iCON
 There is a mobile phone running Android 4.3 or later.
 The mobile phone can properly connect to the Internet.

1. Obtain the latest LIVE-C APP installation package from Huawei technical support.
2. Install the LIVE-C APP on the mobile phone.

8.2 Logging In to the LIVE-C APP


Prerequisite
The mobile phone should be within 10 m away from the power equipment.

• After the first login, change the password in time to ensure account security and prevent
unauthorized network attacks, such as data tampering.
• Huawei will not be liable for any security issues caused by your failure to change the
default password in time or password loss after changing. (The password cannot be
retrieved if it is lost.)

Password Change: System Settings > Change Password.

Procedure
1. Tap the LIVE-C APP icon access the home page.
2. Tap Power System Delivery, access the login screen.
3. Tap Bluetooth connection in the login screen of the APP, to search and connect for
power equipment with Bluetooth nearby.
NOTE
 The mobile phone app may be occasionally disconnected due to difference in phone model
and Bluetooth signal strength. Please try again 5 minutes later.
 Certain mobile phones may fail to connect in automatic Bluetooth pairing mode due to
Android system differences. Please select the manual pairing mode to connect. Locate the
pairing request in the notice column and enter the pairing PIN 0000 or 000000.
 The power equipment SN and Bluetooth name have the same last six digits.

4. Enter the user name and password. (initial user name: liveapp, initial password:
Changeme_123)
5. Tap Login to access Main Function Menu and view the operating parameters of the
power equipment.

9 Follow-up Operations
1. Reinstall caps and waterproof connectors on all unused ports of the modules.
2. Ensure that the paint on the module exterior is intact. If paint has flaked off, repaint the area to avoid corrosion.
3. Clean the site and leave.

Huawei Technologies Co., Ltd.