TeSys is IE3/IE4 Ready

Type 2 coordination charts

schneider-electric.co.in
IND2018T2CV1 2
Contents
Premium-efficiency motor current load.....................................................................................p. 4
Circuit breaker and thermal relay..............................................................................................p. 5
Contactor..................................................................................................................................p. 5

Coordination Charts............................................... p.6


Coordination between Protection and Control..........................................................................p. 6
TeSys motor starters - Type 2 coordination...............................................................................p. 7
Direct-on-Line starters with circuit-breaker and overload protection built into the circuit-breaker

TeSys motor starters - Type 2 coordination...............................................................................p. 7


Direct-on-Line starters with circuit-breaker and thermal overload relay

TeSys motor starters - Type 2 coordination...............................................................................p. 9


Direct-on-Line starters with circuit-breaker and electronic thermal overload relay

Type 2 coordination (IEC 60947-4-1) 415 V............................................................................p. 10


Direct-on-Line Starter with Electronic Circuit Breaker

TeSys motor starters - Type 2 coordination.............................................................................p. 11


Star Delta starters with circuit-breaker and overload protection by separate thermal overload relay

Motor Management System.................................p. 13


TeSys T Motor Management System - Type 2 coordination ...................................................p. 14
Direct-on-Line starters with Fuse protection (DIN fuses, Type aM) and intelligent motor protection relay

TeSys T Motor Management System - Type 2 coordination....................................................p. 15


Direct-on-Line starter with circuit breaker and intelligent Motor Protection Relay

Tesys U starter - Total coordination.........................................................................................p. 16


Direct-on-Line & R Direct-on-Line upto 15kW 415 V, 50/60 Hz

TeSys Accessories...............................................p. 17
TeSys D...................................................................................................................................p. 18
Reversers - screw clamp terminals

TeSys F...................................................................................................................................p. 19
Reversers - screw type terminals for lugs or bars

TeSys D...................................................................................................................................p. 20
Star-Delta starters - Kits for customer assemblies

TeSys D...................................................................................................................................p. 21
Star-Delta starters - Kits composition

TeSys F...................................................................................................................................p. 22
Star-Delta starters - screw terminals for lugs or bars - Components for customer assemblies

Glossary.................................................................................................................................p. 23

IND2018T2CV1 3
Premium-efficiency motor current load
IE3 premium motors are more energy efficient than IE2 motors. In Figure 1, IE3 motors have an higher
inrush current and an higher starting current but in full run will have a lower current consumption than
IE2. Figure 1 is a simplified version of Figure 2 made after some measurement on physical motors in our
laboratory.

Figure 1 Figure 2

This higher inrush current has a potential impact on important information when selecting the right
the performance of protection and control products circuit breakers– will be.
due to the fact that the locked rotor current
The ratio between the highest inrush peak and the
increases the thermal stress on all devices, risking
locked rotor current is commonly called the kappa
untimely
ratio (k) and its order of magnitude is on average
thermal tripping of circuit breakers and relays. The
between 1.4 and 1.6 for IE3 motors; it can be as
high peak of the inrush may also lead to circuit
high as 2.0 for very high torque according to IEC
breaker nuisance tripping.
60034-12. The kappa ratio is calculated as follows:
Motor manufacturers usually state the locked rotor Ipeak
current as an Id/In ratio. However, it is hard to know K=
in advance how high the initial peak of the inrush– Locked Rotor Current

IND2018T2CV1 4
Circuit breaker and thermal relay
As starting current increases, so does the risk of nuisance tripping. Figure 9
shows the hypothetical case of a suboptimal circuit breaker and thermal relay. lE3 ln FLC

The green curve shows the starting current of an IE2 motor, and the red curve,
T(s)
its IE3 version. If the values between the motor’s starting current and the IE3 current
equipment’s threshold are too close to each other, using the IE2 configuration Thermal relay
for the IE3 motor may result in nuisance tripping and downtime. This depends
on the motor technology, the electrical equipment brand, and correct
Td
installation of all electrical wiring, devices, and equipment. (0.5 to 30s)
IE2 current Locked Rotor Current
To select the right circuit breaker and overload relay, you should:
 Follow the recommendations of your motor protection manufacturer.

 Avoid over-dimensioning cable sections. Short-circuit


protection
 Verify that the electrical characteristics stated by the motor manufacturer are (magnetic
Td circuit breaker)
in accordance with the motor starters used. (0.010 to
0.015s)
 Verify the coordination of the motor starter components if there are selected
separately, without using a recommended coordination tables. lE2 l FLC lE2 l LRC lE2 l PEAK
I(A)

 Schneider Electric TeSys circuit breakers and thermal relays have


lE3 l LRC lE3 l PEAK
undergone magnetic, electrical, and thermal endurance testing in laboratory
conditions to ensure their compatibility with IE3 motors. The compatibility Figure 9. In the red zone: nuisance tripping with IE3 motors.

with IE4 has also been verified after performing relevant tests.

Contactor
A contactor is an electromechanical device designed to switch the current
in an electrical circuit on and off. The maximum breaking current
of a contactor is often given as a ratio of the nominal current: In.
For standard applications, a contactor rated 12 In for closing and 10 In
for opening is sufficient. But for IE3 motors, the contactor should be able
to break and make even during the higher inrush peak at startup to avoid
harm to people or equipment.

TeSys contactors are suitable for IE3 or IE4. The compatibility has been
succesfully tested.

IND2018T2CV1 5
Coordination between Protection and Control
This coordination is the optimal combination of must be capable of operating afterwards. The risk
different protection devices (for short circuits and of contact welding is accepted; if this occurs, the
overloads) and the control device (contactor) manufacturer must state the action to be taken for
which make up a motor starter. Designed for a the maintenance of the equipment.
given power rating, it provides the best protection v Total Coordination: There is a very high
for the equipment controlled by the motor starter performance version, provided in CPS (control
(see Fig. 40 ). and protective switching devices) and offered by
It has the double advantage of reducing equipment some manufacturers, called “Total Coordination”
and maintenance costs, since the different protection (IEC 60947-6-2).
devices are matched with each other as precisely as This type of coordination requires that, in shortcircuit
possible, without unnecessary redundancy. conditions, the contactor or starter must not create
any risk for personnel or installations, and must be
b There are different types of coordination.
capable of operating afterwards. The risk of contact
Two types of coordination (type 1 and type 2) are
welding is not acceptable; the motor starter must be
defined by IEC 60947-4-1.
capable of being restarted immediately.
v Type 2 coordination: this is the high performance
v When immediate restarting of the motor is
version; it requires that the contactor or starter must
essential, “Total Coordination” must be chosen. No
not create any risk for personnel or installations, and
maintenance is required.

t(s) Thermal withstand limits: To enable a motor starter to operate correctly, the
- contactor
- circuit-breaker coordination between all the devices must meet all the
- overload relay following requirements:
b the overload relay must protect the magnetic circuit-
breaker in the overload zone : its curve “1” must pass
1
below that of the thermal withstand of the circuit-breaker;
b and, conversely, in the short-circuit zones, in order to
3
protect the thermal relay, the short-circuit trip curve must
2
pass below that of the thermal withstand of the relay;
I(A) b finally, in order to protect the contactor, its thermal
In 0.75Ic Ic 1.25Ic
withstand limit must be above the curves of the two trip
Overload Impedance- Short-circuit releases (thermal, “1”, and magnetic, “3”) (or the fuse, “2”).
zone earthed zone
short-circuit Note that the standard specifies the limit test currents:
Tripping curves: b up to 0.75 Ic only the thermal protection must operate;
1 overload relay
2 magnetic trip release
b above 1.25 Ic only the short-circuit protection must
3 fuse operate.

Fig. 40 : The principles of coordination.

IND2018T2CV1 6
TeSys motor starters - Type 2 coordination
Direct-on-Line starters with circuit-breaker and overload protection built into the circuit-breaker
0.06 to 110 kW at 400/415 V, 50/60 Hz
Short Circuit Current (Iq) = 50kA

Standard power ratings Setting range of


400/415 V Circuit-breaker Contactor
of 3-phase motors thermal trips

P Ie Reference (1) Reference


kW A A
0.06 0.2 GV2 P02 or GV2 ME02 0.16…0.25 LC1 D09

0.09 0.3 GV2 P03 or GV2 ME03 0.25…0.4 LC1 D09

0.12 0.44 GV2 P04 or GV2 ME04 0.4…0.63 LC1 D09

0.18 0.6 GV2 P04 or GV2 ME04 0.4…0.63 LC1 D09

0.25 0.85 GV2 P05 or GV2 ME05 0.63…1 LC1 D09

0.37 1.1 GV2 P05 or GV2 ME05 0.63…1 LC1 D09

0.55 1.5 GV2 P06 or GV2 ME06 1…1.6 LC1 D09

0.75 1.9 GV2 P07 or GV2 ME07 1.6…2.5 LC1 D09

1.1 2.7 GV2 P08 or GV2 ME08 2.5…4 LC1 D09

1.5 3.6 GV2 P08 or GV2 ME08 2.5…4 LC1 D09

2.2 4.9 GV2 P10 or GV2 ME10 4…6.3 LC1 D09

3 6.5 GV2 P14 or GV2 ME14 6…10 LC1 D09

4 8.5 GV2 P14 or GV2 ME14 6…10 LC1 D09

5.5 11.5 GV2 P16 9…14 LC1 D25

7.5 15.5 GV2 P20 13…18 LC1 D25

9 18.1 GV2 P21 17…23 LC1 D25

11 22 GV2 P22 20…25 LC1 D25

15 29 GV2 P32 25…40 LC1 D32

18.5 35 GV3 P40 30…40 LC1 D50A

22 41 GV3 P50 37…50 LC1 D50A

30 55 GV3 P65 48…65 LC1 D65A

37 66 GV3 P73 62…73 LC1 D80A

45 80 GV4P115N 65…115 LC1 D115

55 97 GV4P115N 65…115 LC1 D115

55 97 GV7 RS150 90…150 LC1 D150

75 132 GV7 RS150 90…150 LC1 D150

90 160 GV7 RS220 132…220 LC1 F185

110 195 GV7 RS220 132…220 LC1 F225

(1) The breaking performance of circuit-breakers GV2 P can be increased by adding a current limiter GV1 L3

IND2018T2CV1 7
TeSys motor starters - Type 2 coordination
Direct-on-Line starters with circuit-breaker and thermal overload relay
0.06 to 250 kW at 400/415 V, 50/60 Hz
Short circuit current (Iq)= 50kA

Standard power ratings


400/415 V Circuit-breaker Contactor Thermal Overload relay
of 3-phase motors
P Ie Reference Rating Reference Reference Setting Range
kW A A A
0.06 0.2 GV2 L03 or LE03 0.4 LC1 D09 LRD 02 0.16…0.25
0.09 0.3 GV2 L03 or LE03 0.4 LC1 D09 LRD 03 0.25…0.40
0.12 0.44 GV2 L04 or LE04 0.63 LC1 D09 LRD 04 0.4…0.63
0.18 0.6 GV2 L04 or LE04 0.63 LC1 D09 LRD 04 0.4…0.63
0.25 0.85 GV2 L05 or LE05 1 LC1 D09 LRD 05 0.63…1
0.37 1.1 GV2 L05 or LE05 1 LC1 D09 LRD 05 0.63…1
0.55 1.5 GV2 L06 or LE06 1.6 LC1 D09 LRD 06 1…1.7
0.75 1.9 GV2 L07 or LE07 2.5 LC1 D09 LRD 07 1.6…2.5
1.1 2.7 GV2 L08 or LE08 4 LC1 D09 LRD 08 2.5…4
1.5 3.6 GV2 L08 or LE08 4 LC1 D09 LRD 08 2.5…4
2.2 4.9 GV2 L10 or LE10 6.3 LC1 D09 LRD 10 4…6
3 6.5 GV2 L14 or LE14 10 LC1 D09 LRD 12 5.5…8
4 8.5 GV2 L14 or LE14 10 LC1 D09 LRD 14 7…10
5.5 11.5 GV2 L16 14 LC1 D25 LRD 16 9…13
7.5 15.5 GV2 L20 18 LC1 D25 LRD 21 12…18
9 18.1 GV2 L22 25 LC1 D25 LRD 22 16…24
11 22 GV2 L22 25 LC1 D25 LRD 22 16…24
15 29 GV3 L32 32 LC1 D40A LRD 332 23…32
18.5 35 GV3 L40 40 LC1 D50A LRD 340 30…40
22 41 GV3 L50 50 LC1 D50A LRD 350 37…50
30 55 GV3 L65 65 LC1 D65A LRD 365 48…65
37 66 GV4L80N 80 LC1 D80 LRD 3363 63…80
45 80 GV4L115N 115 LC1 D115 LR9 D5367 60…100
55 97 GV4L115N 115 LC1 D115 LR9 D5369 90…150
75 132 NSX160*MA (2) 150 LC1 D150 LR9 D5369 90…150
90 160 NSX250*MA (2) 220 LC1 F185 LR9 F5371 132…220
110 195 NSX250*MA (2) 220 LC1 F225 LR9 F5371 132…220
132 230 NSX400* + Mic 1.3M (2) 320 LC1 F265 LR9 F7375 200…330
160 280 NSX400* + Mic 1.3M (2) 320 LC1 F330 LR9 F7375 200…330
200 350 NSX630* + Mic 1.3M (2) 500 LC1 F400 LR9 F7379 300…500
220 388 NSX630* + Mic 1.3M (2) 500 LC1 F500 LR9 F7379 300…500
250 430 NSX630* + Mic 1.3M (2) 500 LC1 F500 LR9 F7379 300…500
(1) For reversing operation, replace the prefix LC1 with LC2.
(2) Reference to be completed by replacing the * with the breaking performance code:

Breaking performance NSX160*MA, NSX400*


NSX100*MA
Iq (kA) NSX250*MA NSX630*
400/415 V 50 50 50
Code N N N

IND2018T2CV1 8
TeSys motor starters - Type 2 coordination
Direct-on-Line starters with circuit-breaker and electronic thermal overload relay
0.06 to 30 kW at 400/415 V, 50/60 Hz
Short Circuit current (Iq) = 50kA
SelectableTrip class - 5, 10, 20, 30

Standard power ratings Electronic Thermal


400/415 V Circuit-breaker Contactor
of 3-phase motors Overload relay
P Ie Reference Rating Reference Reference (1) Setting Range
kW A A A
0.06 0.2 GV2 L03 0.4 LC1 D09 LR9D 01 0.1…0.5
0.09 0.3 GV2 L03 0.4 LC1 D09 LR9D 01 0.1…0.5
0.12 0.44 GV2 L04 0.63 LC1 D18 LR9D 02 0.4…2.0
0.18 0.6 GV2 L04 0.63 LC1 D18 LR9D 02 0.4…2.0
0.25 0.85 GV2 L05 1 LC1 D18 LR9D 02 0.4…2.0
0.37 1.1 GV2 L05 1 LC1 D18 LR9D 02 0.4…2.0
0.55 1.5 GV2 L06 1.6 LC1 D18 LR9D 02 0.4…2.0
0.75 1.9 GV2 L07 2.5 LC1 D18 LR9D 08 1.6…8.0
1.1 2.7 GV2 L08 4 LC1 D18 LR9D 08 1.6…8.0
1.5 3.6 GV2 L08 4 LC1 D18 LR9D 08 1.6…8.0
2.2 4.9 GV2 L10 6.3 LC1 D18 LR9D 08 1.6…8.0
3 6.5 GV2 L14 10 LC1 D25 LR9D 32 6.4…32
4 8.5 GV2 L14 10 LC1 D25 LR9D 32 6.4…32
5.5 11.5 GV2 L16 14 LC1 D25 LR9D 32 6.4…32
7.5 15.5 GV2 L20 18 LC1 D25 LR9D 32 6.4…32
11 22 GV2 L22 25 LC1 D25 LR9D 32 6.4…32
15 29 GV3 L32 40 LC1 D65A LR9D 110S 22…110
18.5 35 GV3 L40 40 LC1 D65A LR9D 110S 22…110
22 41 GV3 L50 50 LC1 D65A LR9D 110S 22…110
30 55 GV3 L65 65 LC1 D65A LR9D 110S 22…110

(1) Ambient insensitive Overload Protection.

IND2018T2CV1 9
Type 2 coordination (IEC 60947-4-1) 415 V
Direct-on-Line Starter with Electronic Circuit Breaker
0.18 to 55 kW at 415 V, 50/60 Hz
Short Circuit current (Iq) = 50kA
Selectable Trip class - 10, 20

Standard power ratings Setting range of


400/415 V Circuit-breaker Contactor
of 3-phase motors thermal trips

P Ie Reference Reference
kW A
0,18 0,58 GV4P, PE or PEM02N 0.8...2 LC1D25

0,25 0,82 GV4P, PE or PEM02N 0.8...2 LC1D25

0.37 1,06 GV4P, PE or PEM02N 0.8...2 LC1D25

0.55 1,45 GV4P, PE or PEM02N 0.8...2 LC1D25

0.75 1,83 GV4P, PE or PEM02N 0.8...2 LC1D25

1.1 2,60 GV4P, PE or PEM03N 1.4...3.5 LC1D32

1.5 3,5 GV4P, PE or PEM07N 2.9...7 LC1D50A

2.2 4,7 GV4P, PE or PEM07N 2.9...7 LC1D50A

3 6,3 GV4P, PE or PEM07N 2.9...7 LC1D50A

4 8,2 GV4P, PE or PEM12N 5...12.5 LC1D50A

5.5 11,1 GV4P, PE or PEM12N 5...12.5 LC1D50A

7.5 15 GV4P, PE or PEM25N 10...25 LC1D65A

10 18 GV4P, PE or PEM25N 10...25 LC1D65A

11 21 GV4P, PE or PEM25N 10...25 LC1D65A

15 28 GV4P, PE or PEM25N 10...25 LC1D65A

18.5 34 GV4P, PE or PEM50N 20...50 LC1D65A

22 40 GV4P, PE or PEM50N 20...50 LC1D65A

30 53 GV4P, PE or PEM80N 40...80 LC1D65A

37 64 GV4P, PE or PEM80N 40...80 LC1D80

45 77 GV4P, PE or PEM115N 65...115 LC1D115

55 94 GV4P, PE or PEM115N 65...115 LC1D115

*Ambient Insensitive Overload Protection


*Advanced motor protection & fault differentiation with add on module

IND2018T2CV1 10
TeSys motor starters - Type 2 coordination
Star Delta starters with circuit-breaker and overload protection by separate thermal overload relay
5.5 to 250 kW at 400/415 V: 50/60 Hz
Short Circuit Current (Iq) =50kA

Standard power
Contactor Contactor Contactor
ratings of 400/415 V Circuit-breaker Thermal Overload relay
(line) (delta) (star)
3-phase motors
P Ie Reference Rating Reference(1) Reference(1) Reference(1) Reference Setting Range
kW A A A
5.5 11.5 GV2 L16 14 LC1 D25 LC1 D25 LC1 D09 LRD 12 5.5…8
7.5 15.5 GV2 L20 18 LC1 D25 LC1 D25 LC1 D09 LRD 14 7…10
9 18.1 GV2 L22 25 LC1 D25 LC1 D25 LC1 D09 LRD 16 9…13
11 22 GV2 L22 25 LC1 D25 LC1 D25 LC1 D09 LRD 21 12…18
15 29 GV3 L32 32 LC1 D40A LC1 D40A LC1 D09 LRD 318 12…18
18.5 35 GV3 L40 40 LC1 D50A LC1 D50A LC1 D09 LRD 325 17…25
22 41 GV3 L50 50 LC1 D50A LC1 D50A LC1 D18 LRD 332 23…32
30 55 GV3 L65 65 LC1 D65A LC1 D65A LC1 D18 LRD 340 30…40
37 66 GV3 L73 80 LC1 D80A LC1 D80A LC1 D32 LRD 3357 37…50
45 80 GV4 LE115N 115 LC1 D115 LC1 D115 LC1 D32 LRD 3357 37…50
55 97 GV4 LE115N 115 LC1 D115 LC1 D115 LC1 D65A LR D3359 48…65
75 132 NSX160*MA150 150 LC1 D150 LC1 D150 LC1 D65A LR9 D5367 60…100
90 160 NSX250*MA220 220 LC1 F185 LC1 F185 LC1 D80 LR9 F5367 60…100
110 195 NSX250*MA220 220 LC1 F185 LC1 F185 LC1 D115 LR9 F5369 90…150
132 230 NSX400*Mic 1.3M 320 LC1 F265 LC1 F265 LC1 D115 LR9 F5369 90…150
160 280 NSX400*Mic 1.3M 320 LC1 F330 LC1 F330 LC1 D150 LR9 F5371 132…220
200 350 NSX630*Mic 1.3M 500 LC1 F400 LC1 F400 LC1 F185 LR9 F5371 132…220
220 388 NSX630*Mic 1.3M 500 LC1 F400 LC1 F400 LC1 F185 LR9 F7375 200…330
250 430 NSX630*Mic 1.3M 500 LC1 F500 LC1 F500 LC1 F225 LR9 F7375 200…330

(1) For contactor mounting accessories refer page 20”


(2) Reference to be completed by replacing the * with the breaking performance code:

Breaking
NSX160*MA, NSX400*
performance NSX100*MA
NSX250*MA NSX630*
Iq (kA)
400/415 V 50 50 50
Code N N N

IND2018T2CV1 11
IND2018T2CV1 12
Motor
Management
System

IND2018T2CV1 13
TeSys T Motor Management System - Type 2 Coordination
Direct-on-Line starters with Fuse protection (DIN fuses, Type aM) and intelligent motor
protection relay
0.37 to 365 kW at 400/415 V: 50/60 Hz

Standard power
Switch- TeSys External current
ratings of 3-phase 400/415 V aM Fuses Contactor
disconnector T Controller transformer
motors
P Ie Reference(1) Size Rating Reference Reference Reference
kW A A A
0.37 1.1 GS1 DD 10 x 38 2 LC1D09 LTMR08** -
0.55 1.5 GS1 DD 10 x 38 2 LC1D09 LTMR08** -
0.75 1.9 GS1 DD 10 x 38 4 LC1D09 LTMR08** -
1.1 2.7 GS1 DD 10 x 38 4 LC1D09 LTMR08** -
1.5 3.6 GS1 DD 10 x 38 4 LC1D09 LTMR08** -
2.2 4.9 GS1 DD 10 x 38 6 LC1D09 LTMR08** -
3 6.5 GS1 DD 10 x 38 8 LC1D09 LTMR27** -
4 8.5 GS1 DD 10 x 38 10 LC1D09 LTMR27** -
5.5 11.5 GS1 DD 10 x 38 16 LC1D12 LTMR27** -
7.5 15.5 GS1 DD 10 x 38 16 LC1D25 LTMR27** -
10 19 GS* F 14 x 51 25 LC1D25 LTMR27** -
11 22 GS* F 14 x 51 25 LC1D25 LTMR27** -
15 29 GS* F 14 x 51 32 LC1D32 LTMR100** -
18.5 35 GS* F 14 x 51 40 LC1D40A LTMR100** -
22 41 GSv J 22 x 58 50 LC1D50A LTMR100** -
30 55 GSv J 22 x 58 80 LC1D65A LTMR100** -
37 66 GS* J 22 x 58 100 LC1D80 LTMR100** -
45 80 GS* J 22 x 58 100 LC1D95 LTMR100** -
55 97 GS* K T00 125 LC1D115 LTMR08** LT6CT2001
75 132 GS* L T0 160 LC1D150 LTMR08** LT6CT2001
90 160 GS* N T1 200 LC1F185 LTMR08** LT6CT4001
110 195 GS* N T1 250 LC1F225 LTMR08** LT6CT4001
132 230 GS* QQ T2 315 LC1F265 LTMR08** LT6CT4001
160 280 GS* QQ T2 355 LC1F400 LTMR08** LT6CT4001
200 350 GS2 S T3 500 LC1F400 LTMR08** LT6CT8001
250 430 GS2 S T3 500 LC1F500 LTMR08** LT6CT8001
315 540 GS2 S T3 630 LC1F630 LTMR08** LT6CT8001
355 610 GS2 V T4 800 LC1F630 LTMR08** LT6CT8001

(1) GS*: GS1 for direct operator, GS2 for external operator.

**Control voltage
Voltage Code
24DC BD
110 VAC - 240 VAC FM

IND2018T2CV1 14
TeSys T Motor Management System - Type 2 Coordination
Direct-on-Line starter with circuit breaker and intelligent Motor Protection Relay
0.06 to 250 kW at 400/415 V, 50/60 Hz
Short Circuit Current (Iq) = 50kA

Standard power ratings of External Current


400/415 V Circuit-breaker Contactor TeSys T Controller
3-phase motors Transformer
P Ie Reference Reference Reference Reference
kW A
0.06 0.2 GV2 L03 LC1 D09 LTM R08** -
0.09 0.3 GV2 L03 LC1 D09 LTM R08** -
0.12 0.44 GV2 L04 LC1 D09 LTM R08** -
0.18 0.6 GV2 L04 LC1 D09 LTM R08** -
0.25 0.85 GV2 L05 LC1 D09 LTM R08** -
0.37 1.1 GV2 L05 LC1 D09 LTM R08** -
0.55 1.5 GV2 L06 LC1 D09 LTM R08** -
0.75 1.9 GV2 L07 LC1 D09 LTM R08** -
1.1 2.7 GV2 L07 LC1 D18 LTM R08** -
1.5 3.6 GV2 L08 LC1 D18 LTM R08** -
2.2 4.9 GV2 L10 LC1 D18 LTM R08** -
3 6.5 GV2 L14 LC1 D18 LTM R27** -
4 8.5 GV2 L14 LC1 D18 LTM R27** -
5.5 11.5 GV2 L16 LC1 D25 LTM R27** -
7.5 15.5 GV2 L20 LC1 D25 LTM R27** -
9 18.1 GV2 L22 LC1 D25 LTM R27** -
11 22 GV2 L22 LC1 D25 LTM R27** -
15 29 GV3 L32 LC1 D40A LTM R100** -
18.5 35 GV3 L40 LC1 D50A LTM R100** -
22 41 GV3 L50 LC1 D50A LTM R100** -
30 55 GV3 L65 LC1 D65A LTM R100** -
37 66 GV4 L80 LC1 D80 LTM R100** -
45 80 GV4L115 LC1 D115 LTM R100** -
55 97 GV4L115 LC1 D115 LTM R08** LT6CT2001
75 132 NSX160HMA LC1D150 LTM R08** LT6CT2001
90 160 NSX250HMA LC1F185 LTM R08** LT6CT2001
110 195 NSX250HMA LC1F225 LTM R08** LT6CT2001
132 230 NSX400HMA LC1F265 LTM R08** LT6CT4001
160 280 NSX400HMA LC1F330 LTM R08** LT6CT4001
200 350 NSX630HMA LC1F400 LTM R08** LT6CT4001
220 388 NSX630HMA LC1F500 LTM R08** LT6CT4001
250 430 NSX630HMA LC1F500 LTM R08** LT6CT8001

**Control voltage
Voltage Code
24DC BD
110 VAC - 240 VAC FM

IND2018T2CV1 15
Tesys U starter - Total Coordination
Direct-on-Line & R Direct-on-Line upto 15kW 415 V, 50/60 Hz

Control Unit
Performs all the electrical protection functions
 Overload, over current, & short circuit protection
 Ground fault protection
 Phase loss & phase unbalance protection

Control auxiliary contacts


 For additional remote indication contacts

Power auxiliary contacts (trip status)


 To supervise motor starter status

400/440 500 V 600 V Control Unit


Tesys U Power
Base Rating Standard Advanced Multifunction
kW kW kW Setting Range
Class 10 Class 10 Class 20 Class 5..30
0.09 - - LUB12 0.15...0,6 LUCAX6** LUCBX6** LUCDX6** LUCMX6BL
0.25 - - LUB12 0.35...1,4 LUCA1X** LUCB1X** LUCD1X** LUCM1XBL
1.5 2.2 3 LUB12 1.25...5 LUCA05** LUCB05** LUCD05** LUCM05BL
5.5 5.5 9 LUB12 3...12 LUCA12** LUCB12** LUCD12** LUCM12BL
7.5 9 15 LUB32 4.5...18 LUCA18** LUCB18** LUCD18** LUCM18BL
15 15 18.5 LUB32 8...32 LUCA32** LUCB32** LUCD32** LUCM32BL

*reverser block or LU2B* base to be chosen for RDOL starter


refer to catalog for other functions & Coil voltages

Voltage Coil Code


24VDC BL
24VAC B
48-72VDC, 48VAC ES
110-220VDC, 110-240VAC FU

IND2018T2CV1 16
TeSys
Accessories

IND2018T2CV1 17
TeSys D
Reversers - screw clamp terminals
Kits for customer assembly
Power links, electrical interlockings, mechanical interlockings for TeSys D contactors.

Kits for 9 to 38 A Kit for 40 to 80 A

LAD9R1 LAD9R1V LAD9R3


Assembling kit comprising: Assembling kit comprising: Assembling kit comprising:
• LAD9V5 parallel link • LAD9V5 parallel link • LA9D65A6 parallel link
• LAD9V6 inversing link • LAD9V6 inversing link • LA9D65A9 inverser link
• LAD9V2 mechanical interlock • LAD9V2 mechanical interlock • LAD4CM mechanical interlock
• Assembling staple • LAD9V1 electrical interlock
• Assembling staple

Components for 80 A Components for 95A

LA9D8069 LA9D4002 LA9D8002 LA9D50978 LA9D80978


Parallel + inversing links AC electro-mechanical DC electro-mechanical AC mechanical interlocking DC mechanical interlocking
for 80, 95 A interlocking for 80 A interlocking for 80 A for 95 A for 95 A

Components for 115, 150 A

LA9D11569 LA9D11502
Parallel + inversing links Set of electro-mechanical
for 115, 150 A interlocking components for
115, 150 A

Bill of material (contactors to be completed with…)


Contactors Set of electrical power links Mechanical interlocking Electrical interlocking
2x LC1D09••
2x LC1D12••
Kits:
2x LC1D18•• LAD9R1: power links + mechanical interlock
2x LC1D25•• or
LAD9R1V: power link + mechanical interlock + electrical interlock (white power links)
2x LC1D32••
2x LC1D38••
2x LC1D40A••(1)
Kit:
2x LC1D65A••(1) Customer cabling
LAD9R3: power links + mechanical interlock
2x LC1D65A••(1)
2x LC1D80•• Mechanical + electrical interlocks: LA9D4002 for AC - LA9D8002 for DC
Power links: LA9D8069
95 2x LC1D95•• Mechanical interlocks: LA9D50978 for AC / LA9D80978 for DC
115 2x LC1D115••
Power links: LA9D11569 Mechanical + electrical interlocks: LA9D11502
150 2x LC1D150••

(1) Power connection by EverLink® BTR screw connectors and control by screw clamp terminals
Coil voltage: replace 2 dots at end of commercial references by voltage code (P7 = 230 V 50-60 Hz; BD = 24 V DC; BW3 = 24 V DC low consumption; other codes, see page 48).

IND2018T2CV1 18
TeSys F
Reversers - screw type terminals for lugs or bars
Components for customer horizontal assemblies
TeSys F contactors, power links, mechanical interlocks.

Horizontal assembly: 3-pole contactors LA9FJ970 LA9FJ976


with mechanical interlock Mechanical interlocks 6 power links

Bill of material (contactors to be completed with…)


Contactors Set of power connections Mechanical interlocking
2x LC1F115 LA9FF976 LA9FF970
2x LC1F150 LA9F15076 LA9FF970
2x LC1F185 LA9FG976 LA9FG970
2x LC1F225 LA9F22576 LA9FG970
2x LC1F265 LA9FH976 LA9FJ970
2x LC1F330 LA9FJ976 LA9FJ970
2x LC1F400 LA9FJ976 LA9FJ970
2x LC1F500 LA9FK976 LA9FJ970
2x LC1F630 LA9FL976 LA9FL970
2x LC1F800 LA9FL976 LA9FL970

To be ordered as a necessary complement (refer to TeSys catalogue ref. MKTED210011 – chapter B9):
2 contactor coils (AC or DC) - 2 LADN.1 contact blocks for electrical interlocking.

Vertical contactor
assembly is also possible.
refer TeSys Tech Catalogue 2017.
www.schneider-electric.com/tesys
All power connections are
to be made by customer.

IND2018T2CV1 19
TeSys D
Star-Delta starters
Kits for customer assemblies
TeSys D contactors, kits with power links, electrical interlockings, mechanical interlockings, time delays.

LAD91218* LAD91217 LAD93218 LAD93217* LAD912GV

LAD9SD3 LA9D8017 LA9D8018 LA9D11517 LA9D15017

Bill of material
Kits (with or without interlocking devices)
Contactors
Separate interlocking devices
contactor 1 contactor 2 contactor 3 Electrical power links Interlocking devices
Parellel / Reverse / Star Mechanical Electrical
LC1D09 LC1D09 LC1D09 LAD91218 / LAD91217 / LAD912GV (1) (2) LA9D11502
LC1D12 LC1D12 LC1D09
LC1D09 LAD91218 / LAD91217 / LAD912GV (1) (2)
LC1D18 LC1D18 LC1D12
LC1D12 LC1D09
LC1D09
LC1D18 LAD91218 / LAD91217 / LAD912GV (1) (2)
LC1D18 LC1D12
LC1D18
LC1D09
LC1D12 LAD93218 / LAD93217 (1)
LC1D25 LC1D25
LC1D18
LC1D25 LAD91218 / LAD91217 (1)
LC1D18 LAD93218 / LAD93217 (1)
LC1D32 LC1D32 LC1D25
LAD91218 / LAD91217 (1)
LC1D32
LC1D38 LC1D38 LC1D38 LAD91218 / LAD91217
LC1D40A LC1D40A LC1D40A
LC1D40A
LC1D50A LC1D50A
LC1D50A
LAD9SD3 Customer cabling
LC1D40A
LC1D65A LC1D65A LC1D50A
LC1D65A
LC1D50
LA9D8017 - Customer cabling
LC1D80 LC1D80 LC1D65
LC1D80 LA9D8018 Customer cabling
LC1D80
LC1D95 LC1D95 LA9D8018 Customer cabling
LC1D95
LC1D80
LA9D11517 - Customer cabling
LC1D115 LC1D115 LC1D95
LC1D115 LA9D15017 LA9D11502
LC1D115
LC1D150 LC1D150 LA9D15017 LA9D11502
LC1D150

(1) LAD91218 if time delay not needed, LAD91217 if time delay needed (both kits to compose a block of 3 contactors)
(2) LAD912GV if time delay needed (this kit to compose a block of 1 GV2 circuit breaker + 3 contactors).

IND2018T2CV1 20
TeSys D
Star-Delta starters
Kits composition
Hardware
Raising
Time delay to fix
Kit adaptor,
Mechanical Electrical auxiliary contactor To be ordered
composition to align Power links
interlocking interlocking contact on separately
> contactor front
block mounting
face
plate
Short Parallel Reverser
circuit connection connection
LAD91217 > LAD9V2 LAD9V1 - LAD9P3 LAD9V5 LAD9V6 LADS2 2 x LAD9V17 LA9D12974
LAD91218 > LAD9V2 LAD9V1 - LAD9P3 LAD9V5 LAD9V6 - 2 x LAD9V17 LA9D12974
LAD93217 > LAD9V2 LAD9V1 LAD9V16 LAD9P3 LAD9V5 Yes LADS2 2 x LAD9V17 LA9D32974
LAD93218 > LAD9V2 LAD9V1 LAD9V16 LAD9P3 LAD9V5 Yes - 2 x LAD9V17 LA9D32974
LAD9SD3 > LAD4CM - - LAD9SD3S LA9D65A6 LA9D65A9 LADS2 - -
LA9D5017 > - - - Yes Yes Yes LADS2 Yes LA9D40973
LA9D5018 > LA9D50978 - - Yes Yes Yes LADS2 Yes LA9D40973
LA9D8017 > - - - Yes Yes Yes LADS2 Yes LA9D80973
LA9D8018 > Yes - - LA9D8069 Yes LADS2 Yes -
LA9D11517 > Set of power links -
LA9D15017 > Set of power links LA9D11502

LAD9V2 LA9DV1 LADS2 2 x LAD9V17 Mounting plates


LA9D12974,
LA9D32974,
LA9D40973,
LAD9V16 LAD9P3 LAD9V5 LAD9V6 LA9D80973:
products with
same aspect, with
LAD4CM different length

LAD9SD3S LA9D65A6 LA9D65A9

LA9D50978

LA9D8069 Electro-mechanical
Do not fit EverLink® interlocking kit
terminals LA9D11502

IND2018T2CV1 21
TeSys F
Star-Delta starters - screw terminals for lugs or bars
Components for customer assemblies

Power links dimensions for 3 identical contactors


E1 E2 E3 E4 E5 E6
3 x LC1-
(mm) (mm) (mm) (mm) (mm) (mm)
F115 LA9-FF600 77 151 225 112 186 260
F150 LA9-F15000 71 151 231 102 182 262 KM1

KM3
F185 LA9-FG600 78 158 238 102 182 262 KM2

F225 LA9-F22500 62 158 254 86 182 278


F265 LA9-FH600 100 196 292 120 216 312
F330/400 LA9-FJ600 107 203 299 127 223 319
F500 LA9-FK600 112 222 332 132 242 352
F630 LA9-FL600 137 297 457 157 317 477 Mounting example

Components for 3P customer assemblies


Contactor types Mechanical interlock included Mechanical horizontal interlock
Contactor 1 Contactor 2 Contactor 3
LC1D80 LA9FF610 -
LC1F115 LC1F115
LC1F115 LA9FF600 LA9FF970 Warning:
LC1F115 LA9FG610 LA9FF970 Remember that electrical
LC1F150 LC1F150 AND mechanical
LC1F150 LA9F15000 LA9FF970
interlocking should always
LC1F150 LA9F18517 - be preferred to ensure
LC1F185 LC1F185 LC1F150 LA9FG610 - assembly reliability.
LC1F185 LA9FG600 LA9FG970
LC1F185 LA9F22510 LA9FG970
LC1F225 LC1F225
LC1F225 LA9F22500 LA9FG970
LC1F185 LA9FH610 -
LC1F265 LC1F265 Warning:
LC1F265 LA9FH600 LA9FJ970
When no mechanical
LC1F265 LA9FJ610 LA9FJ970 interlock is available,
LC1F330 LC1F330
LC1F330 LA9FJ600 LA9FJ970 beware to add an electrical
LC1F265 LA9FJ610 - interlock with sufficient time
LC1F400 LC1F400 LC1F330 LA9FJ600 - delay to avoid short-circuit.
LC1F400 LA9FJ600 LA9FJ970
LC1F500 LC1F500 LC1F500 LA9FK600 LA9FJ970
LC1F630 LC1F630 LC1F630 LA9FL600 LA9FJ970

LA9FF610 LA9FG610 LA9F18517

LA9FF600, G, H, K,… LA9F22510, LA9FF970..LA9FL970


LA9FL600 LA9FH610, LA9FJ610 Mechanical horizontal interlocks
LA9F15000

IND2018T2CV1 22
Glossary
IE3: Premium-efficiency class for single-speed motors according to IEC 60034-30.

IE4: Super Premium-efficiency class for single-speed motors according to IEC 60034-30 version 2014.

DOL (direct on line) motor starter: The simplest type of motor starter, also includes protection
devices, and in some cases, monitoring.

Inrush peak: A short, high-current transient occurring during the first milliseconds when the motor
is started.

OEM: Original Equipment Manufacturer.

RMS (Root Mean Square): The RMS value of an AC supply is the steady DC equivalent, which
would convert electrical energy to thermal energy at the same rate in a given resistance.

LRA (Locked Rotor Amps), also called LRC (Locked Rotor Current):
The amount of electrical current drawn at the moment the motor is started, but not yet turning.

Disclaimer
The Type-2 coordination tables are based on internal testing conducted by Schneider Electric.
Schneider Electric reserves the right to make technical changes or modify the contents of this document without prior notice.
Schneider Electric does not accept any responsibility whatsoever for potential errors or possible lack of information in this
document. Any disclosure to third parties or utilization of its content - in whole or in parts - is forbidden without Schneider
Electric’s prior written consent.
For more information, please contact Schneider Electric Customer Care: customercare.in@schneider-electric.com

IND2018T2CV1 23
Getting started with TeSys by Schneider Electric

Schneider Electric’s TeSys motor starter range will help you make the transition to more energy efficient
motors with total peace of mind. TeSys products are fully compatible with IE3 and IE4 motors as confirmed
in laboratory testing for magnetic, thermal, and electrical endurance. Using TeSys circuit breakers,
contactors, and thermal relays ensures optimal energy efficiency for your installation and compliance
with the latest regulations.

You can also stay up to date on the latest TeSys news


at www.schneider-electric.com/tesys

TeSys Quick Selector is available to make motor starter selection fast, simple, and effective
• Quick selection of TeSys motor starter most common combinations
• Motor rated power up to 75 kw
• For Smartphone & tablet

Flash the QR code and update your app!

IND2018T2CV1 24
Note

IND2018T2CV1 25
Note

IND2018T2CV1 26
Note

IND2018T2CV1 27
Schneider Electric India Pvt. Ltd.
Corporate Office
9th Floor, DLF Building No.10,
Tower C, DLF Cyber City, Phase II,
Gurgaon - 122002, Haryana.
Tel: 0124 3940400, Fax: 0124 4222036
www.schneider-electric.co.in
Customer Care Centre
Toll-free numbers: 1800 103 0011, 1800 419 4272
General number: 0124 4222040
Email: in.campaign@schneider-electric.com
IND2018T2CV1 28

Potrebbero piacerti anche