Sei sulla pagina 1di 9

This article has been accepted for publication in a future issue of this journal, but has not been

fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TCPMT.2018.2882626, IEEE
Transactions on Components, Packaging and Manufacturing Technology
1

Detection of Poor Contacts in Low-Voltage


Electrical Installations
Nedzad Hadziefendic, Nemanja Kostic, Jovan Trifunovic, and Miomir Kostic

Abstract—Effects of a reduced torque on heating and the devices for the detection of poor electrical connections in
electrical resistance of wire-screw terminal connections in an electrical circuits [12]–[14], as well as to improve
old (used) receptacle and two new receptacles with procedures for the design, maintenance and verification of
intentionally corroded connections were experimentally
low-voltage electrical installations in buildings, given in the
investigated in laboratory. In one of the new receptacles the
corrosion process was accelerated by treating the line relevant standards [15]–[18].
connection with a mixture of nitric acid and hydrochloric acid, There are two glowing contact detection techniques worth
and in the other by treating the neutral connection with mentioning. The first is the acoustic sensing technique,
sulfuric acid. It was shown that by using these acids both the which represents an effective means for the detection of
temperature rise and electrical behavior of long-serving glowing contacts in industrial applications, based on the fact
receptacles can be simulated.
that the propagation of an acoustic signal through large and
The possibility to detect a poor contact in an electrical
circuit by measuring both the line to earth resistance and the
uninterrupted copper wires and bus bars is characterized by
line to neutral short circuit loop resistance during a periodic a very small attenuation. However, this technique might not
verification of low-voltage electrical installations was also be feasible in residential applications, where high-
analyzed. In laboratory conditions, a test electrical circuit with attenuation connectors are common in electrical installations
a poor contact in each of the tested receptacles was formed and [19]. The second technique, infrared thermography (IRT), is
the influence of that contact on both of the mentioned widely used for the inspection of electrical connections,
resistances was observed during long-lasting heating processes.
Based on the results of both the laboratory experiments and
representing a useful and efficient preventive maintenance
periodic verifications of low-voltage electrical installations in measure [20]. However, it was concluded in [21] that in
public and commercial buildings with the total of 11,243 earlier stages of poor electrical connections the cool
receptacles, a new procedure for detecting poor contacts in metalwork surrounding a small overheated area prevents the
low-voltage electrical installations, valid for the TN (Terra latter from being identified. In addition, it is impossible to
Neutral) protection system, is recommended. The procedure, detect a hot spot by IRT if there is no visual contact between
intended for periodic verification, provides information about
poor contacts and their location in the tested receptacle (on the
the spot and the thermal imager.
phase, neutral and/or equipment grounding conductor) by Receptacles represent typical electrical components the
comparing both the line to earth resistance and the line to malfunction of which can cause fire, usually initiated by
neutral short circuit loop resistance to the limit values obtained overheating at their poor terminal connections [3], [22],
during the verification. [23]. Poor contacts are usually formed due to a reduced
effective area [24], a decreased torque on the wire-screw
Index Terms—Poor electrical contact, contact resistance, hot
terminal connection in low-voltage equipment [25] and/or
spot temperature, poor contact detection, new procedure.
the presence of various films (such as oxides, contaminants
and reaction products) [26]. The standard procedure for
I. INTRODUCTION
periodic verification of electrical circuits with receptacles is
Failures in old, damaged or improperly designed, to measure their line to earth resistance [27]. In the period of
installed or maintained low-voltage electrical installations 2012–2017, experts from the Laboratory for testing low-
represent a frequent cause of fire in residential, public, voltage electrical installations at the Faculty of Electrical
industrial and other buildings [1]–[3]. Frequent types of Engineering, University of Belgrade, performed numerous
such failures are glowing connections [4]–[8] and series arc verifications of low-voltage electrical installations in public
[9]–[11], especially when long-lasting. They usually occur and commercial buildings. In all of those buildings the TN
due to overheating of a poor electrical connection (Terra Neutral) protection system was used. By examining
characterized by a high electrical resistance. Therefore, there the measured line to earth resistances, it was noticed that
is a constant need to develop more efficient methods and their values generally ranged from several hundreds of mΩ
_______________________________________ (for electrical circuits on lower floors of the buildings where

This research was partially supported by the Ministry of Education, the MV/LV (medium voltage/low voltage) transformer
Science and Technological Development of the Republic of Serbia (project station was positioned inside the building or in its vicinity)
TR 36018). to around 1 Ω (for electrical circuits on upper floors).
The authors would like to thank Prof. Jovan Cvetic, Ph.D., from the
Faculty of Electrical Engineering, University of Belgrade for his useful However, for some receptacles the measured line to earth
advice regarding the means for accelerating the corrosion process, as well resistance amounted to a few ohms. The current standard
as Dragana Djordjevic, Ph.D., Sanja Sakan, Ph.D., and Aleksandra procedure [28] is based on the comparison of the measured
Mihajlida-Zelic, M.Sc., all from the Institute of Chemistry, Technology and
Metallurgy, Njegoseva 12, Belgrade, for chemical preparation of line to earth resistance with the limit value which enables
receptacles used in the experiments. sufficiently quick operation of the corresponding protection
N. Hadziefendic, N. Kostic, J. Trifunovic, and M. Kostic are with the device (in order to prevent a dangerous electric shock).
Faculty of Electrical Engineering, University of Belgrade, Bulevar kralja
Aleksandra 73, 11000 Belgrade, Serbia (e-mail: nedzad@etf.rs; Since the limit values are high, all of the circuits where the
nmkostic@etf.rs; jovan.trifunovic@etf.rs; kostic@etf.rs). measured line to earth resistance amounted to a few ohms

2156-3950 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TCPMT.2018.2882626, IEEE
Transactions on Components, Packaging and Manufacturing Technology
2

were declared as in order, although some of them contained trace atmospheric components. In their opinion, the testing
a poor contact. should include at least a sulfur-containing gas, a chlorine-
The objective of this paper is the development of a containing gas (e.g. HCl) and a nitrogen-containing gas (e.g.
procedure for detecting poor contacts in receptacles, based HNO3 (nitric acid)). Đorđević et al. [33] investigated the
on measuring both the line to earth resistance and the line to composition of atmospheric aerosols in Belgrade, Serbia,
neutral short circuit loop resistance during periodic and showed that the most abundant aerosol precursor gases
verification of low-voltage electrical installations. It was are NH3 (ammonia), H2SO4 (sulfuric acid) and HNO3,
shown in [25] that poor contacts with the electrical followed by HCl and various condensable organic acids.
resistance ranging from 80 mΩ to 250 mΩ represent a threat In order to determine the range of the poor contact
to safety if the circuit current is high (the current of 16 A, resistance in actual electrical installations (needed for a
limited by the applied protection device, generally novel verification procedure), a set of experiments was
represents the maximum rated current in electrical circuits carried out on a receptacle that has been loaded for over 30
installed in residential, commercial and public buildings years, as well as on new receptacles with electrical contacts
connected to the mains with the rated voltage of 230 V). If intentionally exposed to corrosion (by chemical means).
smaller currents follow, the electrical resistance of a poor
contact continues to rise and can reach values above 1 Ω, as II. EXPERIMENTAL WORK
shown below. If in such a circuit (with the contact resistance In order to analyze the effects of a reduced torque on
exceeding 1 Ω) the current is increased to around 16 A, a heating and the electrical resistance of wire-screw terminal
high power will be dissipated on the poor contact, enhancing connections, an old (used) receptacle and two new
conditions for burning of the surrounding plastics. In order receptacles (but with intentionally corroded connections)
to prevent this, it is important to improve the current were tested in the Laboratory. In order to accelerate the
procedure for periodic verification of electrical circuits in corrosion process, in one of the new receptacles the line
order to be able to detect a poor contact. The idea elaborated (phase) connection was treated with aqua regia (conc.
in this research is based on the detection of noticeable HNO3 : conc. HCl = 1:3 (v/v)), and in the other new
increases of the line to earth resistance and/or the line to receptacle the neutral connection was treated with H2SO4.
neutral short circuit loop resistance during periodic Using these acids, the effect of long-term exposure of
verification of low-voltage electrical installations. electrical contacts to an acidic atmosphere was simulated.
According to the standard [29], the usually applied After treating both receptacles in a way that 0.2 ml of the
(conventional) measuring equipment for verification of low- chemical was poured out on the selected contact, the
voltage electrical installations enables the measurement of receptacles were left in a cabinet under normal atmospheric
both of those resistances. Line to earth (L-PE) resistance in conditions (room temperature and relative humidity in the
the TN system consists of the resistance of the power range 50–60%) for a month before they were tested.
transformer’s secondary, phase conductor resistance In laboratory conditions, a test electrical circuit was
between the power transformer and the test location, and formed containing a conductor 3 m long and with a cross-
equipment grounding conductor resistance between the test section of 2.5 mm2 (PP-Y 3x2.5 mm2), a protection device
location and the power transformer. Line to neutral (L-N) and one of the three tested receptacles (the old one, the new
short circuit loop resistance in the TN system consists of the one treated with aqua regia or the new one treated with
resistance of the power transformer’s secondary, phase sulfuric acid). The protection device was a miniature circuit
conductor resistance between the power transformer and the breaker (MCB, also known as thermal-magnetic circuit
test location, and neutral conductor resistance between the breaker) of type B and the rated current of 16 A, installed in
test location and the power transformer. a plastic switchboard. The switchboard was connected to the
Poor contacts often occur in receptacles which have been wall receptacle in the Laboratory. The tests were performed
loaded for many years, especially if exposed to humidity, with the mains voltage of 230 V and frequency of 50 Hz.
environmental gases and other pollutants. In such cases The current (load) was changed using a resistance decade
corrosion of contacts can occur, causing a gradual box 230 V, 60 A. The experimental setup is shown in Fig. 1.
deterioration of metal surfaces. At the beginning of each experiment, the torque on all
Glass et al. [30] exposed electrical receptacles to H2S wire-screw terminal connections in the tested receptacle was
(hydrogen sulfide) and tested them both electrically and adjusted to 1 Nm (very good contact) using a mechanical
thermally. Neither an increase of the electrical resistance nor torque screwdriver (Wiha TorqueVario-S26462, with a
overheating was detected. Nevertheless, it was suggested measuring range 0.5–2.0 Nm and an accuracy of ±6%).
that other corrosive environments which could cause Then, both the line to earth resistance (RsL-PE) and the line to
overheated connections should be tested. neutral short circuit loop resistance (RsL-N) were measured
Babrauskas [1] stated that an overheated poor connector using a conventional installation tester instrument (FLUKE
liberates HCl (hydrochloric) gas (from the PVC (polyvinyl 1653B). Afterwards, the torque on one wire-screw terminal
chloride) material), which is corrosive for copper. Over long connection of the receptacle was adjusted to 0.1 Nm (very
periods, this can lead toward a complete breakage of the poor contact) using a digital torque screwdriver (TSD-50,
connection. HCl vapors form a white crystalline deposit on with a measuring range 0.05–0.5 Nm and an accuracy of
the copper conductor surface, which creates more heat and ±2% clockwise and ±3% counterclockwise). In the old
continues the heating-corrosion-heating cycle [31]. receptacle it was the contact connected with the line (phase)
Franey and Graedel [32] stated that the corrosion is wire. In one of the new receptacles it was also the contact
almost always a result of the synergistic action of several

2156-3950 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TCPMT.2018.2882626, IEEE
Transactions on Components, Packaging and Manufacturing Technology
3

TABLE I
PARAMETERS DESCRIBING THE PERFORMED EXPERIMENTS
Initial test Initial heating Two series of repeated heatings with smaller currents
Torque 0.1 Nm and 1 Nm 0.1 Nm 0.1 Nm 0.1 Nm
Current / 16 A 13 A, 10 A and 8 A 6 A and 4 A
Until phenomena preceding Until phenomena preceding a Until the hot spot
Duration /
a series arc occurred series arc occurred temperature stabilized

All experiments were made with an old and two new receptacles, the one treated with aqua regia and the other with sulfuric acid.

temperature. Note that each of the conducted experiments


with the currents of 8–16 A was intentionally interrupted
when at least one of the phenomena preceding a series arc
occurred. They were: contact cracking, sparks on the
contact, sudden increase of the contact temperature (which
could not have been measured by the applied infrared
thermometer, because it was out of its temperature range), as
well as a sudden rise of the contact resistance and its rapid
changes in time. In the experiments with the currents of 4 A
and 6 A the interruption was intentionally done when the hot
spot temperature stabilized (it occurred at 770–870 °C) –
there was no indication for the occurrence of an electric arc
in any of these cases.
The contact temperature was measured using an infrared
thermometer (Cole-Parmer No. 800-323-4350, the accuracy
of which is ±0.75 °C or ±0.75%, whichever is greater). The
Fig. 1. Experimental setup (1 – tested receptacle, 2 – clamp meter FLUKE maximum temperature which can be measured by this
323, 3 – digital multimeter PeakTech 3360, 4 – plastic switchboard, 5 –
installation tester instrument FLUKE 1653B, 6 – type-K (Chromel/Alumel)
thermometer is 900 °C.
thermocouple probe, 7 – infrared thermometer Cole-Parmer, and 8 – Prior to the experiments, the infrared thermometer was
resistance decade box 230 V, 60 A) calibrated using the referent type-K (Chromel/Alumel)
thermocouple probe (an accessory to the digital multimeter
connected with the line wire (the contact previously treated
PeakTech 3360), measuring temperatures up to 1260 °C
with aqua regia), and in the other new receptacle the contact
with the accuracy of ±1.1 °C or 0.4%, whichever is greater.
connected with the neutral wire (the contact treated with
The only visible part of each of the tested poor contacts was
sulfuric acid). Using FLUKE 1653B, the RsL-PE and RsL-N
the head of the steel nickel-plated contact screw. The
resistances were measured again.
emission coefficient was adjusted on the infrared
After these initial measurements, the current of 16 A was
thermometer to 0.8, 0.85, 0.9 and 0.95 for the temperature
established in the circuit until the poor contact reached a
ranges of 0–350 °C, 350–550 °C, 550–800 °C and 800–
high temperature (750–900 °C), which occurred after 11–15
900 °C, respectively. The checks showed that, using these
hours (after 15 hours for the old receptacle, 12 hours for the
adjustments, the measured temperatures deviated less than
new one treated with aqua regia and 11 hours for the new
4% from those obtained by the reference thermocouple.
one treated with sulfuric acid). In each of the three cases, the
During each measurement of the contact temperature, the
current was intentionally interrupted before the appearance
contact electrical resistance was also measured using the V–I
of a series arc, which was followed by natural cooling of the
method. The current and voltage were measured by a current
contact for about 30 minutes. After that the contact
clamp meter (FLUKE 323) and the digital multimeter,
temperature approximately equaled the ambient
respectively.
temperature. Then, the RsL-PE and RsL-N resistances were
All parameters describing the performed experiments are
measured again. For each of the tested receptacles, the presented in Table I.
experiment was continued the next day (after a pause of
about 12 hours, during which the contact was at the ambient III. RESULTS AND DISCUSSION
temperature). First, the RsL-PE and RsL-N resistances were
measured again and it was found that in all three cases they The measurement results, showing the effects of a
remained practically the same (none of the contact reduced torque on heating and the electrical resistance of a
resistances changed during the pause of 12 hours). phase wire-screw terminal connection in the old receptacle,
Afterwards, the whole procedure of the poor contact heating as well as the new one treated with aqua regia, are presented
to a high temperature (750–900 °C), followed by its natural in Figs. 2–9 (t represents the time elapsed from the start of
cooling for about 30 minutes, was repeated with the current the experiment, I – the current through the contact, R – the
of 13 A, and then by the currents of 10 A, 8 A, 6 A and 4 A, contact electrical resistance, P – the power dissipated on the
respectively (in all of these cases the procedure lasted much contact, and T – the contact temperature). The results
shorter than with the current of 16 A – see Section III). In obtained for the new receptacle treated with sulfuric acid are
each case, after 30 minutes of cooling the contact not given, because they are very similar to the ones obtained
temperature was approximately equal to the ambient for the new receptacle treated with aqua regia. In all

2156-3950 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TCPMT.2018.2882626, IEEE
Transactions on Components, Packaging and Manufacturing Technology
4

Fig. 2. Current through the contact within the heating periods, valid for the Fig. 6. Current through the contact within the heating periods, valid for the
old receptacle new receptacle treated with aqua regia

Fig. 3. Contact temperature within both the heating and cooling periods, Fig. 7. Contact temperature within both the heating and cooling periods,
valid for the old receptacle valid for the new receptacle treated with aqua regia

Fig. 4. Dissipated power within the heating periods, valid for the old Fig. 8. Dissipated power within the heating periods, valid for the new
receptacle receptacle treated with aqua regia

Fig. 9. Contact electrical resistance within both the heating and cooling
Fig. 5. Contact electrical resistance within both the heating and cooling
periods, valid for the new receptacle treated with aqua regia
periods, valid for the old receptacle

2156-3950 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TCPMT.2018.2882626, IEEE
Transactions on Components, Packaging and Manufacturing Technology
5

experiments, a long-lasting process of reaching the hot spot Note that the tests of both the old receptacle and the new
temperature with the current of 16 A established in the one treated with aqua regia (in both cases the poor contact
circuit was similar to the one described in [25]. In order to was formed with the line conductor) showed that the values
focus on the relevant values of the parameters describing the of RsL-PE and RsL-N measured after each cooling period were
heating and cooling periods, only the results measured almost equal to the sums of their initially measured values
during the second day of each experiment are given in given in Table II and the poor contact electrical resistances
Figs. 2–9. given in Figs. 5 and 9, measured using the V–I method. For
Analyzing the measurement results presented in Figs. 2– example, for the old receptacle the initial value of RsL-PE was
9, it was noticed that the temperature rise of the poor contact 0.46 Ω (Table II), and the electrical resistance of its poor
contact, measured using the V–I method after heating with
had similar behavior for the old and new, but intentionally
the current of 4 A and 30 minutes of cooling, was 1.92 Ω
corroded, wire-screw terminal connections. After the last
(Fig. 7). The sum of these two values (2.38 Ω) is almost
cooling period, following the last heating period (with the
equal to the value of RsL-PE measured after heating with the
current of 4 A), the electrical resistance of the poor contacts current of 4 A and 30 minutes of cooling, which amounted
reached high values (1.92 Ω for the old receptacle, 1.84 Ω to 2.35 Ω (Table II). Of course, this was not the case with
for the new one treated with aqua regia and 1.83 Ω for the RsL-PE corresponding to the receptacle treated with sulfuric
new one treated with sulfuric acid). Based on their similar acid, which practically remained the same after each heating
values, it was concluded that new, but intentionally and cooling cycle, because the poor contact in that
corroded, wire-screw terminal connections in receptacles receptacle was formed with the neutral conductor (only RsL-N
can also be used to simulate electrical behavior of the was increased). All initially measured values of RsL-PE and
connections in old receptacles. However, it should be RsL-N were in the range 0.43–0.47 Ω, even when the torque
emphasized that the use of acids aimed to accelerate the on one of the wire-screw terminal connections was adjusted
aging process of loose connections is not a realistic to 0.1 Nm (very poor contact). However, measured after
simulation of the natural aging process in air. For currents in each of the heating and cooling cycles, the RsL-PE values
the range 4–16 A, the power dissipated on the contacts ranged from 0.59 Ω to 2.35 Ω for the old receptacle and the
(copper conductor – steel nickel-plated contact screw) new one treated with aqua regia, indicating the presence of
belonged to the range 29–76 W for the old receptacle, 27– at least one poor contact in these circuits. On the other hand,
45 W for the new receptacle treated with aqua regia, and the RsL-N values ranged from 0.66 Ω to 2.26 Ω for the
30–55 W for the new receptacle treated with sulfuric acid. receptacle treated with sulfuric acid, precisely indicating
These results are in accordance with those obtained in [31], that the poor contact is the one connected with the neutral
conductor.
where power dissipated on glowing copper connections was
reported to be in the range 17–57 W for currents between
IV. PROCEDURE FOR DETECTING A POOR CONTACT IN LOW-
1 A and 15 A.
VOLTAGE ELECTRICAL INSTALLATIONS
For all three receptacles, tests with the current of 2 A
(which should have simulated low-power single-phase The maximum line to earth resistances that ensure an
electrical loads with the rated power of about 500 W) were effective operation of the protection device in case of failure
also attempted. However, the test could not have been in the TN system (RsMAX), determined for the most
completed for any of the receptacles. In case of the old frequently applied fuse-links (both fast and slow) and
miniature circuit breakers of types B and C (with the rated
receptacle, at the beginning of the test with the current of
currents (Ir) of 6–25 A), are given in Tables III and IV,
2 A a short circuit occurred between the phase receptacle
respectively. For each of the considered fuse-links, first the
contact and the receptacle contact to which the equipment
minimal current (Ia) for which it operates within 0.4 s (a
grounding conductor was connected. The short circuit, condition from standard [28]) was taken from the
which occurred through the carbonated surface of the corresponding fuse-link overheating characteristic [34].
receptacle ceramic body, caused the action of the protection According to standard [35], the minimal MCB currents (Ia)
device, which interrupted the circuit power supply. for which they react within 0.1 s (and, therefore, within
Regarding the new receptacles loaded with the current of 0.4 s) amount to 5 Ir and 10 Ir for types B and C,
2 A, also at the beginning of each test, there was a break of a respectively. In all cases, the value of RsMAX was obtained by
conductor at the poor contact (a phase conductor in one dividing the value of the rated mains voltage (230 V) with
case, and a neutral conductor in the other). This probably the corresponding value of Ia.
occurred due to mechanical fatigue and material wear It can be seen from Tables III and IV that the RsMAX values
caused by the long-lasting previous testing. The damaged are relatively high, which is why the conditions for a
bodies of all three receptacles, each with a wire connected to required quick operation of the protection device (a fuse-
the poor contact and without a plastic casing, are shown in link or MCB) and prevention of electric shock are most
Fig. 10. It can be observed that PVC insulation of the copper frequently met. As a consequence, in many cases a
wires was heavily damaged by high temperatures. conventional verification can show that a circuit is in order,
Using the installation tester instrument, the RsL-PE and although at least one poor connection exists. This can easily
RsL-N resistances were measured at the beginning of each be seen analyzing examples of the most common circuits
experiment (for the torques adjusted to 1 Nm (very good protected by fast or slow fuse-links with the rated current of
10 A or 16 A, as well as by MCBs of type B or C with the
contact) and 0.1 Nm (very poor contact)), as well as after
same rated currents, in which the RsMAX values are rather
each cooling period. The measured values are given in
high. They amount to 6.74 Ω and 4.50 Ω (for the considered
Table II for all three tested receptacles.

2156-3950 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TCPMT.2018.2882626, IEEE
Transactions on Components, Packaging and Manufacturing Technology
6

TABLE III
VALUES OF Ia AND RsMAX FOR FAST AND SLOW FUSE-LINKS (Ir = 6–25 A)

Ia (A) RsMAX (Ω)


Ir (А)
Fast Slow Fast Slow
6 16.71 29.65 13.76 7.75
10 34.08 55.65 6.74 4.13
16 51.07 86.86 4.50 2.64
20 67.62 110.01 3.40 2.09
25 94.69 138.13 2.42 1.66

Fig. 10. Receptacles after the conducted experiments: the old (left), the one TABLE IV
treated with sulfuric acid (in the middle) and the one treated with aqua regia VALUES OF Ia AND RsMAX FOR MCBS OF TYPES B AND C (Ir = 6–25 A)
(right)
Ia (A) RsMAX (Ω)
TABLE II Ir (А)
THE MEASURED RsL-PE AND RsL-N RESISTANCES PRIOR TO THE Type B Type C Type B Type C
EXPERIMENT AND AFTER EACH COOLING PERIOD 6 30 60 7.67 3.83
8 40 80 5.75 2.87
New receptacle New receptacle 10 50 100 4.60 2.30
Old receptacle
(aqua regia) (sulfuric acid)
13 65 130 3.53 1.76
RsL-PE RsL-N RsL-PE RsL-N RsL-PE RsL-N
(Ω) (Ω) (Ω) (Ω) (Ω) (Ω) 16 80 160 2.87 1.43
torque = 1 Nm, no current 20 100 200 2.30 1.15
0.46 0.45 0.44 0.43 0.47 0.46 25 125 250 1.84 0.92
torque = 0.1 Nm
no current
0.46 0.45 0.45 0.44 0.47 0.46
after heating with the current of I ≈16 A + 30 minutes of cooling
0.74 0.73 0.59 0.58 0.48 0.66
after heating with the current of I ≈13 A + 30 minutes of cooling
0.87 0.86 0.69 0.68 0.49 0.75
after heating with the current of I ≈10 A + 30 minutes of cooling
1.01 0.98 0.80 0.78 0.49 0.92
after heating with the current of I ≈8 A + 30 minutes of cooling
1.25 1.23 1.08 0.95 0.49 1.04
after heating with the current of I ≈6 A + 30 minutes of cooling
1.60 1.59 1.49 1.46 0.50 1.30
after heating with the current of I ≈ 4 A + 30 minutes of cooling
2.35 2.32 2.18 2.05 0.50 2.26
Fig. 11. Number of receptacles for which RsL-PE belonged to each of the
fast fuse-links), 4.13 Ω and 2.64 Ω (for the considered slow ranges 0.1 Ω wide
fuse-links), 4.60 Ω and 2.30 Ω (for the considered MCBs of
type B), and 2.87 Ω and 1.43 Ω (for the considered MCBs of ranges 0–0.1 Ω, 0.1–0.2 Ω,…, 1.1–1.2 Ω and 1.2–1.3 Ω. The
type C). In the conducted experiment, RsL-PE ranged from receptacles for which the RsL-PE resistance was higher than
0.59 Ω to 2.35 Ω and in all those cases very high hot spot 1.3 Ω (1.5% of their total number) are not shown in Fig. 11,
temperatures were recorded on the poor contact. However, because their resistances were scattered within the range
these values are less than most of the RsMAX values 1.31–7.68 Ω.
characterizing the common circuits (with the protection By examining the measured RsL-PE resistances, it was
devices with the rated current of 10 A or 16 A). noticed that the majority of them belonged to the range
Similar conclusions can be reached analyzing the results 0.3–1 Ω. The values lower than 0.3 Ω were measured in
of periodic verifications of low-voltage electrical cases where the MV/LV transformer station was positioned
installations done by the Laboratory in public and inside the building or in its vicinity and for electrical circuits
commercial buildings with the total area of over 150,000 m2, on lower floors of the building. The values higher than 1 Ω
where the RsL-PE resistance was measured for 11,243 were measured for electrical circuits on upper floors,
receptacles. Interruption of the equipment grounding because RsL-PE increases with the distance between the
conductor was detected in circuits containing 84 receptacles, electrical circuit and the transformer station.
which is why the users of the facilities were obliged to make On 82 receptacles the RsL-PE resistances higher than the
the necessary repairments (it should be emphasized that the corresponding RsMAX values were measured. These circuits
interruption of the equipment grounding conductors were also declared as inappropriate for use, because the
occurred exclusively in the receptacles). Therefore, a new
conditions for the prevention of an electric shock were not
total number of receptacles used in the further analysis was
met. In these cases, the RsL-PE resistances ranged from
11,159 (the RsL-PE resistance was measured for each of
them). Fig. 11 shows the number of receptacles for which 1.79 Ω to 7.68 Ω, indicating at least one poor contact in each
the measured RsL-PE resistances belonged to each of the of the corresponding circuits. After tightening all electrical
contacts in their receptacles or replacing the receptacles, as

2156-3950 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TCPMT.2018.2882626, IEEE
Transactions on Components, Packaging and Manufacturing Technology
7

TABLE V
LOOP RESISTANCE ANALYSIS IN CASES IN WHICH THE MEASURED RSL-PE RESISTANCE IS LOWER THAN THE MAXIMUM VALUE OF THE LINE TO EARTH
RESISTANCE (RSMAX) WHICH ENSURES AN EFFICIENT OPERATION OF THE PROTECTION DEVICE

RsL-PE<Rlim RsL-PE>Rlim RsL-PE<Rlim RsL-PE>Rlim


RsL-N<Rlim RsL-N<Rlim RsL-N>Rlim RsL-N>Rlim
 poor electrical contact on the phase conductor, or
The electric circuit
Location of a Poor electrical contact Poor electrical  poor electrical contacts on two conductors (all three
probably has no
poor electrical on the equipment contact on the combinations are possible), or
poor electrical
contact
contact
grounding conductor neutral conductor  poor electrical contacts on all three conductors (the
worst case)
None (in case of
Fire hazards failure, the protection Possible, due to a Possible, due to a hot spot on the phase and/or neutral
Probably do not
(consequences device responds hot spot on the conductor (in case of failure, the protection device
exist
of malfunction) within the safe neutral conductor operates within the safe interval)
interval)

well as tightening all electrical contacts in the supplying The conducted experiments also showed that a poor
distribution boards, the RsL-PE resistance were measured contact can occur only on the neutral conductor, which
again and in all cases their values were not only lower than cannot be detected by measuring the RsL-PE resistance (see
RsMAX, but also lower than 1.3 Ω. the data presented in Table II valid for the new receptacle
There were circuits where the RsL-PE resistances were with the neutral contact treated with sulfuric acid). If the
lower than RsMAX, but high enough to indicate the presence RsL-PE (RsL-N) resistance measured on a receptacle is higher
of at least one poor contact. In those cases (84 receptacles) than Rlim, this indicates that there is at least one poor contact
the RsL-PE resistances ranged from 1.3 Ω to 4.38 Ω. Although on the receptacle (on the phase, neutral and/or equipment
the conditions for a proper operation of the protection device grounding conductor). Also, if RsL-PE is significantly higher
and the prevention of an electric shock were met, the users than RsL-N, a poor contact is on the equipment grounding
of the facilities were instructed to make the necessary conductor, and if RsL-N is significantly higher than RsL-PE, a
repairments. After tightening all electrical contacts, in all poor contact is on the neutral conductor.
cases the measured RsL-PE resistance was lower than 1.3 Ω. Therefore, not only the RsL-PE values, but also the RsL-N
Note that poor contacts were also found in receptacles values should be measured in every circuit (the duration of
where RsL-PE was lower than 1.3 Ω, but over 0.5 Ω higher each additional measurement is about 5 s when using a
than the RsL-PE resistances measured on the surrounding conventional installation tester instrument). By the analysis
receptacles. This is well correlated with the results obtained of the measured results, it can be determined if there is a
by the conducted experiment (see Table II). For the old poor contact in the circuit. Table V contains guidelines for
receptacle the initial RsL-PE value was 0.46 Ω, and after the potential locations of poor contacts and possible fire hazards
formation of a poor contact (after 15 hours of its heating in all situations which can occur in practice. It should be
with the circuit current of 16 A) it equaled 0.74 Ω. The applied when the measured RsL-PE resistance is lower than
change of the RsL-PE resistance in this case was smaller than RsMAX (in the opposite case, the corresponding circuit should
0.5 Ω, but it should be taken into consideration that in real be declared unsafe).
cases there is a cumulative effect (for example, Table II The measurements of RsL-PE and RsL-N, along with the
shows that, due to additional heating with smaller currents, analysis based on Tables III–V, represent a new procedure
the RsL-PE resistance rose from 0.74 Ω to 2.35 Ω). Also, there for detecting poor contacts in low-voltage electrical
are other contacts in the circuits that can cause an additional installations. It is valid for both types of receptacles –
increase of the RsL-PE resistance. Although it would be more intended for single-phase and three-phase loads. The
convenient to have the fixed recommended maximum safe difference is that in the case of a three-phase receptacle the
acceptable resistance level (Rlim), it was not possible to measurements of RsL-PE and RsL-N must be performed, and the
determine its unique value valid for each electrical circuit, obtained results analyzed, for each of the three phase
which can be illustrated by the following example. In a conductors.
building all but one RsL-PE resistance measured for Upon completion of the periodic verification of the
receptacles at the ground floor were in the range considered low-voltage electrical installations, it is
0.27–0.36 Ω, while for the exceptional receptacle the necessary to specify in the expert report which electrical
resistance was 0.89 Ω (this receptacle had a poor contact). In circuits potentially have poor contacts. The obligation of the
the same building all RsL-PE resistances measured for electrician or technical service is to find and tighten all poor
receptacles at the attic were higher than 0.89 Ω, belonging to electrical contacts detected in those electrical circuits or
the range 0.97–1.16 Ω, although none of them had a poor replace the damaged electrical components. This refers to
contact. Therefore, when doing periodic verification of low- the protection devices located in the distribution board,
voltage electrical installations, as the limit RsL-PE resistance switches and distribution boxes, but particularly to the
which indicates that there is at least one poor contact in an receptacles. In order to obtain the confirmation that the
electrical circuit (Rlim), we propose the one which is 0.5 Ω defects which caused poor electrical contacts were
higher than the highest RsL-PE resistance measured on the eliminated by the action of the electrician or technical
surrounding receptacles. service, it is necessary to re-measure RsL-PE and RsL-N in those
electrical circuits and check if their new values meet the

2156-3950 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TCPMT.2018.2882626, IEEE
Transactions on Components, Packaging and Manufacturing Technology
8

conditions for an electric circuit without a poor electrical [3] J. R. Hall. (Apr. 2013). Home electrical fires. NFPA, USA. [Online].
Available: http://www.nfpa.org/~/media/files/news-and-research/fire-
contact and safe protection against electric shock in case of
statistics/major-causes/oshomeelectricalfires.pdf?la=en
failure. [4] W. J. Meese and R. W. Beausoliel, “Exploratory study of glowing
The application of the new procedure when verifying the electrical connections,” Center for Building Technology, Institute for
state of electrical contacts would considerably reduce the Applied Technology, National Bureau of Standards, NBS Building Science
Series, vol. 103. Washington, DC, USA, Oct. 1977, pp. 1–22.
probability for the occurrence of dangerous hot spots. This
[5] T. Kuroyanagi, S. Inoue, and H. Suzuki, “Glowing phenomena of
would solve the problem of the inability to detect hot spots copper and copper materials and their electrical characteristics,” (in
by infrared thermography in cases where there is no visual Japanese), Copper Promotion Tech. Res. Group J., vol. 20, pp. 198–204,
contact (in addition, the infrared thermography is usually not 1981.
[6] J. J. Shea and X. Zhou, “Material effect on glowing contact properties,”
mandatory, but represents a recommended method for the
IEEE T. Compon. Pack. T., vol. 32, no. 4, pp. 734–740, Dec. 2009.
detection of hot spots). [7] J. J. Shea, “Glowing contact physics,” in Proc. Holm, New York, NY,
USA, Sep. 2006, pp. 48–57.
V. CONCLUSIONS [8] J. Sletbak, R. Kristensen, H. Sundklakk, G. Navik, and M. Runde,
“Glowing contact areas in loose copper wire connections,” IEEE Trans.
The first objective of this research was to establish Compon., Hybrids, Manuf. Technol., vol. 15, no. 3, pp. 322–327, Jun. 1992.
experimentally the effects of a reduced torque on heating [9] J. J. Shea, “Conditions for series arcing phenomena in PVC wiring,”
and the electrical resistance of wire-screw terminal IEEE Trans. Compon. Packag. Technol., vol. 30, no. 3, pp. 532–539, Sep.
2007.
connections in an old (used) receptacle and two new [10] P. Müller, S. Tenbohlen, R. Maier, and M. Anheuser, “Current
receptacles with intentionally corroded connections. It was characteristics of serial and parallel low current arc faults in distribution
concluded that new, but intentionally corroded, wire-screw networks,” in Proc. CIRED, Frankfurt, Germany, 2011, pp. 1-4, paper
terminal connections in receptacles can be used to simulate 0181.
[11] B. Maas, H. Krompholz, M. Kristiansen, and M. Hagler, “Arc current,
both the temperature rise and electrical behavior of long- voltage, and resistance in a high energy, gas filled spark gap,” in Proc. 5th
serving receptacles. IEEE Pulsed Power Conf., Arlington, TX, USA, Jun. 1985, pp. 99–101.
The second objective of this research was to investigate [12] J. J. Shea, “Method and apparatus for detecting a glowing contact in a
the possibility to detect a poor contact in an electrical circuit power circuit,” U.S. Patent 8 854 066 B2, Oct. 7, 2014.
[13] J. C. Engel, “Electrical switching apparatus including glowing contact
during a periodic verification of low-voltage electrical protection,” U.S. Patent 6 707 652 B2, Mar. 16, 2004.
installations by measuring not only the circuit line to earth [14] M. Baxter, G. Spacht, and B. Baxter, “Systems and methods for
resistance (RsL-PE), but also the line to neutral short circuit reducing electrically-caused fires in wiring devices,” U.S. Patent 8 139 337
loop resistance (RsL-N). The field measurement results B2, Mar. 20, 2012.
[15] Electrical Installations for Buildings, document IEC 60364, 2016.
showed that the resistance 0.5 Ω higher than the highest [16] M. W. Earley, J. S. Sargent, C. D. Coache, and R. J. Roux, “National
RsL-PE (RsL-N) resistance measured on the surrounding electrical code handbook,” Nat. Fire Protection Assoc., Quincy, MA, USA,
receptacles can be recommended as the limit receptacle 2011.
RsL-PE (RsL-N) resistance which indicates that there is a poor [17] Plugs and Socket-Outlets for Household and Similar Purposes,
document IEC 60884, 2002.
contact in the corresponding electrical circuit (Rlim). [18] Low-Voltage Electrical Installations—Part 5-52: Selection and
The final objective of this research was the development Erection of Electrical Equipment—Wiring Systems, document IEC 60364,
of a new procedure for detecting poor contacts in low- 2012.
voltage electrical installations, based on the measurement of [19] X. Zhou, J. Hastings, and T.J. Schoepf, “Application feasibility of
detecting glowing contacts using acoustic sensing technology,” in Proc.
both the RsL-PE and RsL-N resistances and their comparison to Holm, Vancouver, British Columbia, Canada, Sep. 2009, pp. 1–7.
Rlim. [20] S. Taib, M. S. Jadin, and S. Kabir, “Thermal imaging for enhancing
The application of the new procedure is limited to the TN inspection reliability: Detection and characterization,” in Infrared
system, which is the most frequently applied protection Thermography. Rijeka, Croatia: InTech, 2012.
[21] C. Wilson, G. McIntosh, and R. S. Timsit, “Contact spot temperature
system. Also, it has to be emphasized that some poor and the temperature of external surfaces in an electrical connection,” in
contacts cannot be detected by the application of the new Proc. ICEC, Beijing, China, May 2012, pp. 12–17.
procedure. A connection can be loose but still with a very [22] M. Benfer and D. Gottuk, “Electrical receptacles—Overheating,
low contact resistance, especially if the connection is still arcing, and melting,” Fire Safety Sci., vol. 11, pp. 1010–1023, Feb. 2014
[23] J. L. Ferrino-McAllister, R. J. Roby, and J. A. Milke, “Heating at
clean. Metal-to-metal contact, even under a low contact electrical contacts: Characterizing the effects of torque, contact area, and
force, can be low in resistance, leading the inspector of movement on the temperature of residential receptacles,” Fire Technol.,
electrical installations to misconclude that the circuit is in vol. 42, no. 1, pp. 49–74, Jan. 2006.
order. This is why it is not recommended to apply the [24] N. Hadziefendic, M. Davidovic, V. Djordjevic, and M. Kostic, “The
impact of an incomplete overlap of a copper conductor and the
proposed procedure during the initial verification of corresponding terminal on the contact temperature,” IEEE T. Compon.
electrical installations. As the electrical installation is Pack. T., vol. 7, no. 10, pp. 1644–1654, Oct. 2017.
getting older, especially if being exposed to increased [25] N. Hadziefendic, J. Trifunovic, and M. Kostic, “Effects of a reduced
humidity, environmental gases and other pollutants, the torque on heating of electrical contacts in plugs and receptacles,” accepted
for publication in IEEE T. Compon. Pack. T., 2018, DOI:
application of the recommended procedure will constantly 10.1109/TCPMT.2018.2827080.
become more efficient in detecting poor contacts. [26] M. Braunovic, V. V. Konchits, and N. K. Myshkin, “Reliability issues
in electrical contacts,” in Electrical Contacts: Fundamentals, Applications
REFERENCES and Technology. Boca Raton, FL, USA: Taylor & Francis, 2006.
[27] Low-voltage electrical installations – Part 6: Verification, document
[1] V. Babrauskas, “How do electrical wiring faults lead to structure IEC 60364-6, 2016.
ignitions?,” in Proc. Fire Materials Conf., London, UK, 2001, pp. 39–51. [28] Low-voltage electrical installations – Part 4-41: Protection for safety
[2] J. J. Shea, “Identifying causes for certain types of electrically initiated – Protection against electric shock, document IEC 60364-4-41, 2005.
fires in residential circuits,” Fire Mater., vol. 35, no 1, pp. 19–42, Jan. [29] Electrical safety in low voltage distribution systems up to 1000 V a.c.
2011. and 1500 V d.c. - Equipment for testing, measuring or monitoring of

2156-3950 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TCPMT.2018.2882626, IEEE
Transactions on Components, Packaging and Manufacturing Technology
9

protective measures - Part 3: Loop impedance, document IEC 61557-3, Jovan Trifunovic was born in
2007.
Belgrade, Serbia, in 1979. He received
[30] S. Glass, C. Mowry, and N. Sorensen, Report on study of electrical
component corrosion related to problem drywall, document SAND2011- the Dipl.Ing.El., M.Phil. and Ph.D.
1539, Sandia National Laboratories, USA, 2011. degrees from the University of
[31] M. Benfer and D. Gottuk, Development and Analysis of Electrical Belgrade, Serbia, all in electrical
Receptacle Fires, document NIJ-2010-DNBX-K218, Baltimore, MD, USA,
engineering, in 2003, 2009 and 2016,
2013.
[32] J. P. Franey and T. E. Graedel, “Corrosive effects of mixtures of respectively. In 2005 he joined the
pollutants,” JAPCA J. Air Waste Ma., vol. 35, pp. 644-648, 1985. University of Belgrade, where he is
[33] D. Đorđević, A. Mihajlidi-Zelić, D. Relić, Lj. Ignjatović, J. presently employed as Assistant
Huremović, A. M. Stortini and A.Gambaro, “Size-segregated mass
Professor. In 2017 and 2018 he was Acting Director of the
concentration and water soluble inorganic ions in an urban aerosol of the
Central Balkans (Belgrade),” Atmos. Environ., vol. 46, pp. 309-317, 2012. Center for the Promotion of Science of the Republic of
[34] Low-voltage fuses - Part 1: General requirements, document IEC Serbia. His areas of interest currently include grounding
60269-1, 2006. systems, low-voltage electrical installations and energy
[35] Electrical accessories - Circuit-breakers for overcurrent protection for
efficiency.
household and similar installations - Part 1: Circuit-breakers for a.c.
operation, document IEC 60898-1, 2015.
Miomir Kostic was born in Vranje,
Nedzad Hadziefendic was born in Serbia, in 1956. He received the
Prokuplje, Serbia, in 1971. He Dipl.Ing.El., M.Sc. and Ph.D. degrees
received the Dipl.Ing.El. and M.Sc. from the University of Belgrade,
degrees from the University of Serbia, all in electrical engineering, in
Belgrade, Serbia, both in electrical 1980, 1982 and 1988, respectively. In
engineering, in 1997 and 2001, 1980 he joined the University of
respectively. He is now a Ph.D. Belgrade, where he is presently
candidate at the same University, employed as Professor. His current research interests
where he has been working as a include grounding systems, low-voltage electrical
laboratory engineer since 1998. His installations, thermal issues of poor electrical contacts,
current research interests include low-voltage electrical energy efficiency in public lighting, as well as ambient and
installations, fire safety, safety and health management, as architectural lighting.
well as thermal issues of poor electrical contacts.

Nemanja Kostic was born in


Belgrade, Serbia, in 1984. He received
his Dipl.Ing.Org. and M.Sc. degrees
from the University of Belgrade, both
in organizational sciences (project
management), in 2008 and 2010,
respectively. He is a PhD student at
the same University and works as a
researcher and Fire Protection
Manager in the Laboratory for testing low-voltage electrical
installations at the University of Belgrade.

2156-3950 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.

Potrebbero piacerti anche