Sr.No.

Description UOM Quantity


A Available
1 Pipe size NB 40
2 Steam velocity m/s 25
3 Pipe length mtr 200
4 Pressure at boiler kg/cm2g 10.54
5 pressure Available at PRS kg/cm2g 8.8
6 steam available at PRS entry Kg/hr 647
7 steam requirment for ejector Kg/hr 24
8 Total no of ejectors Nos. 11
9 Diversity for Ejectors. 60%
10 Total ejectors in working Nos. 6.6
11 Considered 7 nos ejectors working Kg/hr 158.4
B New requirment.
12 Pure steam generator Kg/hr 360
13 WFI Generator Lit/hr 300
14 Steam requirment @ 6.0bar for WFI generator Kg/hr 212

15 Total steam requirment for Ejectors+WFI Kg/hr 730.4


Generator+PSG @6.0bar

Total steam requirment for Ejector and pure stean


16 generator ,as these two equipment requirment is Kg/hr 518.4
6.0bar (Ejector requirment might be 7.0 bar
pressure ,need to check.)
17 Kg/hr 138
Steam requirment @ 3.0bar for WFI generator
Remark

Existing
Consideration
Approx.
In Boiler House
around 0.9bar drop for 100Mter pipe run considered.
after 175meter pipe run and considering pressure drop.
one Ejector requirment.
Available
As per discussion & Operation .

Considered for 7 ejectors in running condition.

data as per discussion.


Water for injection generation capacity.
As per data of Pharmalab WFI Generator
As we have steam availabilty of 647 kg/hr,and our requirment excceds the availability.

If we cater only Ejectors and pure steam generator then this will suffic ethe requirment.

Low pressure tapping can be given from existing header with 3.0 bar pressure.Using low
pressure steam WFI generation capacity will become 300Lit/hr.