Sei sulla pagina 1di 28

Technical Manual

Carrier Dataport Driver


Contents
CONTENTS ................................................................................................... 1

INTRODUCTION.......................................................................................... 3

SUPPORTED CONFIGURATION ............................................................... 3

SUPPORTED POINTS .................................................................................. 3


MONITORING .................................................................................................... 3
CONTROL ......................................................................................................... 3
YEAR 2000..................................................................................................... 3

PREREQUISITES ......................................................................................... 4

INITIAL SOFTWARE SETUP ..................................................................... 4


SOFTWARE CONFIGURATION OF THE CARRIER DATAPORT DRIVER....................... 4
Communication Baud Rate: ......................................................................... 4
M-Bus Configuration: .................................................................................. 5
Carrier Dataport Driver Node address: ....................................................... 5
INITIAL HARDWARE SETUP.................................................................... 6
HARDWARE CONFIGURATION OF THE CARRIER DATAPORT DRIVER ..................... 6
Overview: .................................................................................................... 6
Physical Connection Details:....................................................................... 7
DATABASE PROPERTIES .......................................................................... 7
REQUIRED CONTROL POINTS. ............................................................................ 7
STANDARD DATABASE POINTS .......................................................................... 9
Read Digital Data Points. ............................................................................ 9
Read Analogue Data Points. .......................................................................10
Database Point Types .................................................................................11
Database Point Mapping Region (Drop) .....................................................11
DATABASE DOWNLOAD ..........................................................................12
Correct Download Procedure .....................................................................12
Incorrect Download Procedure ...................................................................12
COMMUNICATIONS..................................................................................13
VERIFYING COMMUNICATIONS:.........................................................................13
Verifying Database Points...........................................................................13
Verifying PPCL Routines ............................................................................13
COMMISSION THE SYSTEM ...................................................................14

POINT MAPS ...............................................................................................15


Carrier Chiller 19XR Generic Point Map ...................................................15
Point 1- Control mode States ..........................................................................18
Point 2- Run Status States...............................................................................18
Page 2 of 28 Siemens Apogee Carrier Dataport Driver: Technical Manual

Carrier Chiller 30HX Generic Point Map ...................................................19


Point 1- Control mode States ..........................................................................22
Point 2- Run Status States...............................................................................23
Point 6- Alarm States......................................................................................23
Point 109- CCN Load-Shed.............................................................................23
Carrier Chiller 30GX Generic Point Map ...................................................24
Point 1- Control mode States ..........................................................................26
Point 2- Run Status States...............................................................................27
Point 6- Alarm States......................................................................................27
Application Notes: ..........................................................................................27
RELEASE NOTICE .....................................................................................28

CDTech.doc REV 0.1 October, 00


Page 3 of 28 Siemens Apogee Carrier Dataport Driver: Technical Manual

Introduction
The Apogee Carrier Dataport Driver is a read only driver to devices on the Carrier
CCN network via the Carrier Dataport Interface.

The Apogee Carrier Dataport Driver gathers data from the Carrier Dataport
interface and makes it available for use within the Apogee system. This is achieved
by defining the data gathered from the Carrier Dataport Interface as standard
systems point information.

Supported
Configuration

The Apogee Carrier Dataport Driver enables the Siemens Apogee System 600 to
communicate with Carrier CCN nodes via the Carrier Dataport Interface. Read only
functionality is supported. Commanding of parameters on the CCN network is not
supported by this driver.

Supported
Points

The current version (ver. 1.1) of the Apogee Carrier Dataport Driver supports the
following functions:

Monitoring • Monitoring of all points from up to 15 nodes on the Carrier CCN network.
The Carrier Dataport supports a total maximum of 900 points. Therefore,
the Carrier Dataport driver also supports up to this number of points.

Control • The Carrier Dataport Interface only supports monitoring of devices on the
CCN network. Commanding is not supported.

Year 2000
Version 1.1 of the Apogee Carrier Dataport Driver is year 2000 compliant, year
2000 compliant issues regarding the Carrier Dataport products should be checked
with a Carrier representative.

CDTech.doc REV 0.1 October, 00


Page 4 of 28 Siemens Apogee Carrier Dataport Driver: Technical Manual

Prerequisites

Before you begin, the following prerequisites must be met:

• All hardware installed as per the MBC-based Installation Instructions (565-950).


• Apogee Carrier Dataport Driver module installed.
• Power available to all devices.
• The Siemens Carrier Dataport Carrier Dataport Interface components installed,
running, checked out and configured by Siemens personnel.
• Consult the Installation documentation for details of the mandatory wiring
requirements for the Apogee Carrier Dataport Driver.

• Entire Apogee database programmed and completed.


• Extended Timeout to be enabled for the BLN.

Initial Software Setup


Software Configuration
of the Carrier Dataport
Driver

Communication Baud Rate:

Set the FLN 1 communication speed to 9600 bps:

1. >Point, Application, Time, Message, Cancel, System, Bye? (S)

2. >Diagnostics, Users, dAtes, deStinations, Error_msgs, Hardware, Text, Quit?


(H)

3. >Fieldpanels, Disks, Partners, Quit? (F)

4. >Log, Display, Add, dElete, Modify, Config, Ostracize, Quit? (C)

5. >Mmi, bLn, Fln, mBus, mOdem, Address, Quit? (F)

6. >fln1, fln2, fln3, Quit? (1)

7. >Enter baud rate : 9600

8. <RETURN>.

9. Command successful

NOTE: The Apogee Carrier Dataport Driver only uses the FLN 1 port. FLN 2
and 3 ports are redundant.

CDTech.doc REV 0.1 October, 00


Page 5 of 28 Siemens Apogee Carrier Dataport Driver: Technical Manual

M-Bus Configuration:

Disable the M-Bus Configuration:

The Apogee Carrier Dataport Driver does not control any of the Point Termination
Modules (PTMs).

CAUTION:

Only one Controller Module/Driver per cabinet can have the M-Bus
enabled. If the Apogee Carrier Dataport Driver Module is the only
controller present within the MBC enclosure, then the M-Bus may be
enabled.

1. >Point, Application, Time, Message, Cancel, System, Bye? (S)

2. >Diagnostics, Users, dAtes, deStinations, Error_msgs, Hardware, Text, Quit?


(H)

3. >Fieldpanels, Disks, Partners, Quit? (F)

4. >Log, Display, Add, dElete, Modify, Config, Ostracize, Quit? (C)

5. >Mmi, bLn, Fln, mBus, mOdem, Address, Quit? (B)

6. >Enable, Disable : (D)

7. Command successful

Carrier Dataport Driver Node address:

Configure the Carrier Dataport Driver Node Address:

1. >Point, Application, Time, Message, Cancel, System, Bye? (S)

2. >Diagnostics, Users, dAtes, deStinations, Error_msgs, Hardware, Text, Quit?


(H)

3. >Fieldpanels, Disks, Partners, Quit? (F)

4. >Log, Display, Add, dElete, Modify, Config, Ostracize, Quit? (C)

5. >Mmi, bLn, Fln, mBus, mOdem, Address, Quit? (A)

6. >Field panel address : (1)

7. >Ok to coldstart (Y/N) : (Y)

8. <RETURN>.

The Carrier Dataport Driver will coldstart, completing the node address
configuration.

CDTech.doc REV 0.1 October, 00


Page 6 of 28 Siemens Apogee Carrier Dataport Driver: Technical Manual

Initial Hardware Setup


Hardware Configuration
of the Carrier Dataport
Driver

Overview:

The communication standard for the Carrier Dataport Interface is ASCII characters
transmitted via RS-232 at 9600 bps with 8 data bits, 1 stop bit and no parity. The
communication standard for the FLN1 port of the Carrier Dataport Driver is ASCII
characters via RS-485.

To effect correct communications a communication converter will be required,


Siemens Trunk Interface II, (Part Number: 538 675). Refer to figure 1 for
configuration details.

The physical connector of the communication port of the TI-2 is via a 25DB male
connector. The physical connector of the Carrier Dataport Interface is via a 25DB
male connector to the RS-232 port. Refer to figure 2 for wiring termination details.

Figure 1. Apogee/Carrier Dataport Integration configuration.

Carrier CCN Dataport

TI-II
Apogee panel with
the Carrier Dataport COMM 2 (RS-232)
Driver DB 25

SCU panel

Apogee Insight

CDTech.doc REV 0.1 October, 00


Page 7 of 28 Siemens Apogee Carrier Dataport Driver: Technical Manual

Physical Connection Details:

TRUNK INTERFACE II Carrier Dataport, COM 2


(Male DB 25) (Male DB 25 RS-232 port)

Gnd (7) Gnd (7)

Tx (3) Tx (3)

Rx (2) Rx (2)

Figure 2. Carrier Dataport Driver to Carrier Dataport Interface Connection


Details.

Database Properties
Required Control
Points.

Control points must be created for the Carrier Dataport Driver to map data from
CCN nodes into S600/Apogee memory addresses. The property names are
optional, noting that the point type should be LAO and created at Point address 00
of each drop. The Initial value should contain the CCN node address (1-15), using a
Slope of 1.0 and an intercept of 0.0. CCN node addresses supported by the Carrier
Dataport are 1-15. The COV should be equal to the Slope. This will map data from
the CCN node address whose number equals the initial value of the control point
into the drop corresponding to the control point. If the CCN node contains more than
99 points, the next drop will be used to map the rest of these points.

Example Control Point for CCN node 1:

• FLN number = 1

• DROP number = 01

• POINT number = 00

This will map data from CCN node address 1 into FLN1, Drop01, Points 01-99 of
the Carrier Dataport Driver. If there are more than 99 parameters for this particular
CCN node, FLN1, Drop02, Points 00-99 will be used to map the rest of these
parameters.

Adding a Control point for CCN Node address 1.

• Create an LAO point with the following properties:

1. >Point, Application, Time, Message, Cancel, System, Bye? (P)

CDTech.doc REV 0.1 October, 00


Page 8 of 28 Siemens Apogee Carrier Dataport Driver: Technical Manual

2. >Log, Display, Command, Edit, Operation, Monitor, Alarm, Trend, Quit? (E)

3. >Add, Modify, Copy, Delete, Look, Quit? (A)

4. >Point system name : Node.Address.01---------------

5. >Point name : Node.Address.01---------------

6. >Point type : (LAO)---

7. >Descriptor : Node.Addr----

8. > Float, Integer, Time, Date, date-time : (I)----------------

9. >Engineering Units : -------------------------

10. >Access group(s) : ----------------------------------------

11. >Alarmable (Y/N) : (N)

12. >Totalize (Y/N) : (N)

13. >Field panel : (1)--

14. >Physical, Virtual Point address: (P)

15. > FLN : (1)--

16. > Drop : (0)--

17. > Point : (0)---

18. > Slope : (1)

19. >Intercept : (0)

20. >Dynaminc COV (Y/N) : (N)

21. >COV : (1)

22. >Initial Value : (1)

23. Command successful

CDTech.doc REV 0.1 October, 00


Page 9 of 28 Siemens Apogee Carrier Dataport Driver: Technical Manual

Standard Database
Points

The following is an outline of how to create data points within the Carrier Dataport
Driver. Because the Carrier CCN Dataport is user configurable, consult the Carrier
representative for the point map for each CCN node being used.

Read Digital Data Points.

Adding a point to monitor a unit status received from the Carrier Dataport Carrier
Dataport Interface. Example:

• Create an LDI point with the following properties:

1. >Point, Application, Time, Message, Cancel, System, Bye? (P)

2. >Log, Display, Command, Edit, Operation, Monitor, Alarm, Trend, Quit? (E)

3. >Add, Modify, Copy, Delete, Look, Quit? (A)

4. >Point system name : Unit.Status.1-----------------

5. >Point name : Unit.Status.1-----------------

6. >Point type : (LDI)---

7. >Descriptor : Status-----

8. >State text table : ----------------

9. >Access group(s) : ----------------------------------------

10. >Alarmable (Y/N) : (Y)

11. >Enhanced alarms (Y/N) : (N)

12. >Print alarms (Y/N) : (N)

13. >Alarm count 2 (Y/N) : (N)

14. >Normal ack enabled (Y/N) : (Y)

15. >Totalize (Y/N) : (N)

16. >Field panel : (1)--

17. >Physical, Virtual Point address: (P)

18. > FLN : (1)--

19. > Drop : (1)--

20. > Point : (1)----

21. > Normally closed (Y/N) : (N)

CDTech.doc REV 0.1 October, 00


Page 10 of 28 Siemens Apogee Carrier Dataport Driver: Technical Manual

22. Command successful

Read Analogue Data Points.

Adding a point to monitor a temperature setpoint received from the Carrier Dataport
Interface. Example:

• Create an LAI point with the following properties:

1. >Point, Application, Time, Message, Cancel, System, Bye? (P)

2. >Log, Display, Command, Edit, Operation, Monitor, Alarm, Trend, Quit? (E)

3. >Add, Modify, Copy, Delete, Look, Quit? (A)

4. >Point system name : Temp.Setpoint.10---------------

5. >Point name : Temp.Setpoint.10---------------

6. >Point type : (LAI)---

7. >Descriptor : Temp setpnt----

8. > Float, Integer, Time, Date, date-time : (F)

9. > Number of decimal places : (3)----------------

10. >Engineering Units : --------------------------------------

11. >Access group(s) : ----------------------------------------

12. >Alarmable (Y/N) : (N)

13. >Totalize (Y/N) : (N)

14. >Field panel : (1)--

15. >Physical, Virtual Point address: (P)

16. > FLN : (1)--

17. > Drop : (1)--

18. > Point : (10)---

19. > Slope : (1)

CDTech.doc REV 0.1 October, 00


Page 11 of 28 Siemens Apogee Carrier Dataport Driver: Technical Manual

20. >Intercept : (0)

21. >Sensor type : (L)

22. >Dynaminc COV (Y/N) : (N)

23. >COV : (1)

24. Command successful

Database Point Types

The Carrier Dataport Driver supports both LAI and LDI point types for the reading of
data points. Any other point types created, other than those created for diagnostic or
control purposes will be created with an error type status of (E253).

• LAI, LDI - Reading of Carrier Dataport Points.

Database Point Mapping Region (Drop)

The Carrier Dataport Driver utilises 94 drops allocated for point mapping purposes.

• LAI, LDI – Monitor points. All LAI points to have a Slope of 1, Intercept
of 0 and COV of 1.

• LAO – Control points for CCN node addresses. (Point 00 of each drop
only)

If a point is created beyond the mapping region specified, the point will be created with
an error type status of (E253), rendering the point unusable in a priority failed (*F*)
state.

CDTech.doc REV 0.1 October, 00


Page 12 of 28 Siemens Apogee Carrier Dataport Driver: Technical Manual

Database
Download

Correct Download Procedure

The Correct procedure for downloading the database is as follows.

1. Verify that the Carrier Dataport Carrier Dataport Interface is operating correctly,
by contacting a Carrier representative to ensure that the Carrier Dataport
System has been installed and certified, and that it is operating according to
their procedures.

2. Cold Start the Carrier Dataport Driver and download the database

3. If for any period of time communication is lost, database points will enter a
Failed *F* state, on communications being re-established the Carrier Dataport
Driver will automatically unfail all database points and continue with normal
communications.

Incorrect Download Procedure

If the correct download procedure of downloading the database to the Carrier


Dataport Driver from a known database utility is not performed, ie: the database is
created from within the Carrier Dataport Driver itself.

Then communications will not be established until the Carrier Dataport Driver is
Made Ready.

CDTech.doc REV 0.1 October, 00


Page 13 of 28 Siemens Apogee Carrier Dataport Driver: Technical Manual

Communications

Verifying
communications:

1. Verify that the STATUS LED on the front of the Carrier Dataport Driver is
blinking approximately once a second. If not, the Carrier Dataport Driver is
malfunctioning.

2. The FLN 1 TX and RX LEDs on the Carrier Dataport Driver flash together while
the Carrier Dataport Driver transmits data. Then the RX LED on the Carrier
Dataport Driver flashes while the Carrier Dataport Driver receives data from the
Carrier Dataport Interface. This sequence repeats in quick succession.
3. Verify that the Carrier Dataport Driver is communicating with the Carrier
Dataport Interface as with step 2.

Verifying Database Points

Display a Point Log and verify that the Carrier Dataport Driver points are entered
and that they read the correct information from the Carrier Dataport Interface.

Make sure the points are normal (-N-). If the points do not contain the expected
information:

1. Recheck the prerequisites given in the Installation Instructions for Carrier


Dataport Driver.

2. Check all the connections made during installation.

3. If these checks do not uncover the problem, refer to the Diagnostic and
troubleshooting document.

Verifying PPCL Routines

On verifying communication.

1. Verify that all lines of PPCL execute as intended. If there are problems, refer to
the Diagnostic and Troubleshooting document.

CDTech.doc REV 0.1 October, 00


Page 14 of 28 Siemens Apogee Carrier Dataport Driver: Technical Manual

Commission
the System

Consult as needed with the building engineer to make sure Carrier Dataport Driver
is providing accurate information and performing the intended functions. In
particular, verify that:

• All Apogee/System 600 databases are loaded.


• Values read as LAI points match the values reported at the Carrier Dataport
Interface.
• Values read as LDI points match the states reported at the Carrier Dataport
Interface.
• Any other functions that the Carrier Dataport Driver is to perform are carried out
as intended.

If the above tests do not check out, refer to the Diagnostic and troubleshooting
document.

CDTech.doc REV 0.1 October, 00


Page 15 of 28 Siemens Apogee Carrier Dataport Driver: Technical Manual

Point Maps
Carrier Chiller 19XR Generic Point Map

Point Type Units Description


Number
0 LAO - CCN Address Control point (1-15)
1 LAI - Control mode
2 LAI - Run Status
3 LAI mins Start Inhibit Timer
3 LDI NO/YES Occupied?
4 LAI - System Alert/Alarm
5 LDI STOP/START Chiller Start/Stop
6 LAI OFF/ON Remote Start Contact
7 LAI DEG F Temperature Reset
8 LAI DEG F Control Point
9 LAI DEG F Chilled Water Temp
10 LAI % Active Demand Limit
11 LAI % Average Line Current
12 LAI % Motor Percent Kilowatts
13 LAI mA Auto Demand Limit Input
14 LAI mA Auto Chilled Water Reset
15 LAI DEG F Remote Reset Sensor
16 LAI - Entering Condenser Water
17 LAI - Total Compressor Starts
18 LAI - Starts in 12 Hours
19 LAI Hrs Compressor Ontime
20 LAI Hrs Service Ontime
21 LAI OPEN/CLOSE Ice Build Contact
22 LAI mA Refrigerant Leak Sensor
23 LAI % Actual Guide Vane Pos
24 LAI OFF/ON Chilled Water Pump
25 LAI NO/YES Chilled Water Flow
26 LAI OFF/ON Condenser Water Pump
27 LAI NO/YES Condenser Water Flow
28 LAI OFF/ON Oil Pump Relay
29 LAI ^PSI Oil Pump Delta P
30 LAI OFF/ON Compressor Start Relay
31 LAI OPEN/CLOSE Compressor Start Contact
32 LAI OFF/ON Starter Trans Relay
33 LAI OPEN/CLOSE Compressor Run Contact
34 LAI OFF/ON Tower Fan Relay Low
35 LAI OFF/ON Tower Fan Relay High
36 LAI OFF/ON Tower Fan Relay High
37 LAI ALARM/NORMAL Starter Fault
38 LAI ALARM/NORMAL Spare Safety Input

CDTech.doc REV 0.1 October, 00


Page 16 of 28 Siemens Apogee Carrier Dataport Driver: Technical Manual

Point Type Units Description


Number
39 LAI OFF/ON Shunt Trip Relay
40 LAI - ISM Fault Status
41 LAI % Actual Guide Vane Pos
42 LAI % Guide Vane Delta
43 LAI % Target Guide Vane Pos
44 LAI DEG F Oil Sump Temp
45 LAI DEG F Oil Pump Delta P
46 LAI DEG F Comp Discharge Temp
47 LAI DEG F Comp Thrust Brg Temp
48 LAI DEG F Comp Motor Winding Temp
49 LAI DEG F Spare Temperature 1
50 LAI DEG F Spare Temperature 2
51 LAI On/Off Oil Heater Relay
52 LAI % Diffuser Actuator
53 LAI % Target VFD Speed
54 LAI % Actual VFD Speed
55 LAI - Surge Protection Counts
56 LAI PSI Chilled Water Delta P
57 LAI DEG F Entering Chilled Water
58 LAI DEG F Leaving Chilled Water
59 LAI ^F Chilled Water Delta T
60 LAI ^F Chill Water Pulldown/Min
61 LAI DEG F Evaporator Refrig Temp
62 LAI PSI Evaporator Pressure
63 LAI ^F Evaporator Approach
64 LAI PSI Condenser Water Delta P
65 LAI DEG F Entering Condenser Water
66 LAI DEG F Leaving Condenser Water
67 LAI DEG F Condenser Refrig Temp
68 LAI PSI Condenser Pressure
69 LAI ^F Condenser Approach
70 LAI OFF/ON Hot Gas Bypass Relay
71 LAI NO/YES Surge / HGBP Active ?
72 LAI PSI Active Delta P
73 LAI DEG F Active Delta T
74 LAI DEG F Surge/HGBP Delta T
75 LAI - Head Pressure Reference
76 LAI % Average Line Current
77 LAI A Actual Line Current
78 LAI % Average Line Voltage

CDTech.doc REV 0.1 October, 00


Page 17 of 28 Siemens Apogee Carrier Dataport Driver: Technical Manual

Point Type Units Description


Number
79 LAI V Actual Line Voltage
80 LAI - Power Factor
81 LAI KW Motor Kilowatts
82 LAI KWH Motor Kilowatt-Hours
83 LAI KW Demand Kilowatts
84 LAI A Line Current Phase 1
85 LAI A Line Current Phase 2
86 LAI A Line Current Phase 3
87 LAI V Line Voltage Phase 1
88 LAI V Line Voltage Phase 2
89 LAI V Line Voltage Phase 3
90 LAI A Ground Fault Phase 1
91 LAI A Ground Fault Phase 2
92 LAI A Ground Fault Phase 3
93 LAI HZ Frequency
94 LAI % I2T Sum Heat-Phase 1
95 LAI % I2T Sum Heat-Phase 2
96 LAI % I2T Sum Heat-Phase 3
97 LAI - ISM Fault Status
98 LDI NORMAL/ALARM Single Cycle Dropout
99 LDI NORMAL/ALARM Phase Loss
100 LDI NORMAL/ALARM Over Voltage
101 LDI NORMAL/ALARM Under Voltage
102 LDI NORMAL/ALARM Current Imbalance
103 LDI NORMAL/ALARM Voltage Imbalance
104 LDI NORMAL/ALARM Overload Trip
105 LDI NORMAL/ALARM Locked Rotor Trip
106 LDI NORMAL/ALARM Starter LRA Trip
107 LDI NORMAL/ALARM Ground Fault
108 LAI NORMAL/ALARM Phase Reversal
109 LDI NORMAL/ALARM Frequency Out of Range
110 LDI NORMAL/ALARM ISM Power On Reset
111 LDI NORMAL/ALARM Phase 1 Fault
112 LDI NORMAL/ALARM Phase 2 Fault
113 LDI FALSE/TRUE Phase 3 Fault
114 LDI NORMAL/ALARM 1CR Start Complete
115 LDI NORMAL/ALARM 1M Start/Run Fault
116 LDI NORMAL/ALARM 2M Start/Run Fault
117 LDI NORMAL/ALARM Pressure Trip Contact
118 LDI NORMAL/ALARM Starter Fault

CDTech.doc REV 0.1 October, 00


Page 18 of 28 Siemens Apogee Carrier Dataport Driver: Technical Manual

Point Type Units Description


Number
119 LDI NORMAL/ALARM Motor Amps Not Sensed
120 LDI NORMAL/ALARM Start Acceleration Fault
121 LDI NORMAL/ALARM High Motor Amps
122 LDI NORMAL/ALARM Hardware Failure
123 LAI - Disable Service Password
124 LAI - Remote Reset Option
125 LAI - Reset Alarm ?
126 LAI - CCN Mode ?

Point 1- Control mode States

Point Parameter Value Description


Number
1 Control Mode 0 Off
1 Control Mode 1 Reset
1 Control Mode 2 Local
1 Control Mode 3 CCN
1 Control Mode 9999 OffCt

Point 2- Run Status States

Point Parameter Value Description


Number
2 Run Status 4 Timeout
2 Run Status 5 Ready
2 Run Status 6 Recycle
2 Run Status 7 Prestart
2 Run Status 8 Startup
2 Run Status 9 Ramping
2 Run Status 10 Running
2 Run Status 11 Demand
2 Run Status 12 Override
2 Run Status 18 Shutdown
2 Run Status 13 Tripout
2 Run Status 14 Pumpdown
2 Run Status 15 Lockout
2 Run Status 999 Ctl Test

CDTech.doc REV 0.1 October, 00


Page 19 of 28 Siemens Apogee Carrier Dataport Driver: Technical Manual

Carrier Chiller 30HX Generic Point Map

Point Type Units Description


Number
0 LAO - CCN Address Control point (1-15)
1 LAI - Control mode
2 LAI - Run Status
3 LDI NO/YES Occupied?
4 LAI - CCN Enable
5 LDI STOP/START Chiller Start/Stop
6 LAI - Alarm State
7 LAI - Current Alarm 1
8 LAI - Current Alarm 2
9 LAI - Current Alarm 3
10 LAI - Current Alarm 4
11 LAI - Current Alarm 5
12 LAI % Active Demand Limit
13 LAI % Percent Total Capacity
14 LAI DEG F Water/Brine Setpoint
15 LAI DEG F Control Point
16 LAI DEG F Entering Fluid Temp
17 LAI DEG F Leaving Fluid Temp
18 LDI - Emergency Stop
19 LAI mins Minutes left for Start
20 LAI - Heat-Cool Status
21 LAI % Total Capacity
22 LAI % Circuit A Available Capacity
23 LAI PSI Circuit A Discharge Pressure
24 LAI PSI Circuit A Suction Pressure
25 LAI PSI A1 Oil Pressure Diff
26 LAI PSI A2 Oil Pressure Diff
27 LAI PSI A1 Oil Pressure
28 LAI PSI A2 Oil Pressure
29 LAI DEG F Discharge Gas Temp A
30 LAI DEG F A1 Motor Temp
31 LAI DEG F A2 Motor Temp
32 LAI DEG F SAT Condensing Temp A
33 LAI DEG F Saturated Suction Temp A
34 LAI % Circuit A EVX Percent Open
35 LAI - Circuit A Motormaster Speed
36 LAI - Circuit A Water valve position
37 LAI - Circuit A Cooler Level indicator
38 LAI - CPM A1 Feedback

CDTech.doc REV 0.1 October, 00


Page 20 of 28 Siemens Apogee Carrier Dataport Driver: Technical Manual

Point Type Units Description


Number
39 LAI - CPM A2 Feedback
40 LAI - Circuit A Econ Pressure
41 LDI ON/OFF Compressor A1
42 LDI ON/OFF Compressor A2
43 LDI ON/OFF Loader A1
44 LDI ON/OFF Loader A2
45 LDI ON/OFF Minimum Load Valve A
46 LDI ON/OFF Circuit A Oil Heater
47 LDI ON/OFF A1 Mtr Cooling Solenoid
48 LDI ON/OFF A2 Mtr Cooling Solenoid
49 LDI ON/OFF Circuit A Oil Pump
50 LDI ON/OFF Oil Solenoid A1
51 LDI ON/OFF Oil Solenoid A2
52 LDI OPN/CL Circuit A Oil Switch
53 LDI ON/OFF Compressor A1 Feedback
54 LDI ON/OFF Compressor A2 Feedback
55 LAI % Total Capacity Circuit B
56 LAI % Available Capacity Circuit B
57 LAI PSI Discharge Pressure B
58 LAI PSI Suction Pressure B
59 LAI ^ PSI B1 Oil Pressure Diff
60 LAI ^ PSI B2 Oil Pressure Diff
61 LAI PSI B1 Oil Pressure
62 LAI PSI B2 Oil Pressure
63 LAI DEG F Discharge Gas Temp B
64 LAI PSI B1 Motor Temp
65 LAI DEG F B2 Motor Temp
66 LAI DEG F SAT Condensing Temp B
67 LAI DEG F Saturated Suction Temp B
68 LAI % Circuit B EVX Percent Open
69 LAI % Circuit B Motormaster Speed
70 LAI - Circuit B Cooler Level indicator
71 LAI V CPM B1 Feedback
72 LAI V CPM B2 Feedback
73 LAI PSI Circuit B Econ Pressure
74 LDI ON/OFF Compressor B1
75 LDI ON/OFF Compressor B2
76 LDI ON/OFF Loader B1
77 LDI ON/OFF Loader B2
78 LDI ON/OFF Minimum Load Valve B

CDTech.doc REV 0.1 October, 00


Page 21 of 28 Siemens Apogee Carrier Dataport Driver: Technical Manual

Point Type Units Description


Number
79 LDI ON/OFF Circuit B Oil Heater
80 LDI ON/OFF B1 Mtr Cooling Solenoid
81 LDI ON/OFF B2 Mtr Cooling Solenoid
82 LDI ON/OFF Circuit B Oil Pump
83 LDI ON/OFF Oil Solenoid B1
84 LDI ON/OFF Oil Solenoid B2
85 LDI OPN/CL Circuit B Oil Switch
86 LDI ON/OFF Compressor B1 Feedback
87 LDI ON/OFF Compressor B2 Feedback
88 LAI DEG F Cooler Entering Fluid
89 LAI DEG F Cooler Leaving Fluid
90 LAI DEG F Condenser Entering Fluid
91 LAI DEG F Condenser Leaving Fluid
92 LAI DEG F Reclaim Entering Fluid
93 LAI DEG F Reclaim Leaving Fluid
94 LAI V 5 Volt Supply
95 LAI mA 4-20 mA Reset Signal
96 LAI DEG F Return Reset Signal
97 LAI DEG F External Reset Temperature
98 LAI DEG F Outdoor Reset Temperature
99 LAI DEG F Calculated Reset
100 LDI ON/OFF Fan Relay 1
101 LDI ON/OFF Fan Relay 2
102 LDI ON/OFF Fan Relay 3
103 LDI ON/OFF Fan Relay 4
104 LDI ON/OFF Fan Relay 5
105 LDI ON/OFF Fan Relay 6
106 LAI mA 4-20 mA Demand Signal
107 LDI ON/OFF Demand Switch 1
108 LDI ON/OFF Demand Switch 2
109 LAI - CCN Load-Shed Signal
110 LAI % Max Allowable CAP
111 LDI ON/OFF Cooler Pump Relay
112 LDI ON/OFF Cooler Pump Flow Switch
113 LDI ON/OFF Condenser Pump Relay
114 LDI ON/OFF Condenser Pump Flow Switch
115 LDI ON/OFF Ice Valve
116 LDI ON/OFF Ice build Complete
117 LDI CL/HT Heat/Cool Switch
118 LDI ON/OFF Dual Setpoint Switch

CDTech.doc REV 0.1 October, 00


Page 22 of 28 Siemens Apogee Carrier Dataport Driver: Technical Manual

Point Type Units Description


Number
119 LDI ON/OFF Cooler Heater
120 LAI DEG F Option Temperature 1
121 LAI DEG F Option Temperature 2
122 LDI ON/OFF Local Off
123 LDI ON/OFF CCN Off
124 LDI ON/OFF Clock Off
125 LDI ON/OFF Local On
126 LDI ON/OFF CCN On
127 LDI ON/OFF Clock On
128 LDI ON/OFF Dual Sp1 Active
129 LDI ON/OFF Dual Sp2 Active
130 LDI ON/OFF Temperature Reset Active
131 LDI ON/OFF Demand Limit Active
132 LDI ON/OFF Load Limit Active
133 LDI ON/OFF Low Source Temperature Protect
134 LDI ON/OFF Ramp Loading Active
135 LDI ON/OFF Timed Override Active
136 LDI ON/OFF Low Cooler Suction temp
137 LDI ON/OFF WSM Controlling
138 LDI ON/OFF Slow Change Override
139 LDI ON/OFF Off to On Delay Active
140 LDI ON/OFF FSM Controlling
141 LDI ON/OFF 2 Chiller Lead Lag Active
142 LDI ON/OFF 2 Chiller LL Comm Failure
143 LDI ON/OFF Circuit A Low Discharge SuperHeat
144 LDI ON/OFF Circuit B Low Discharge SuperHeat
145 LDI ON/OFF Circuit A High Suction
146 LDI ON/OFF Circuit B High Suction

Point 1- Control mode States

Point Parameter Value Description


Number
1 Control Mode 24 Local On
1 Control Mode 30 EMStop
1 Control Mode 26 CCN On
1 Control Mode 29 Clock On
1 Control Mode 27 Delay Off
1 Control Mode 23 Local Off
1 Control Mode 25 CCN Off
1 Control Mode 28 Clock Off
1 Control Mode 9999 OffCt

CDTech.doc REV 0.1 October, 00


Page 23 of 28 Siemens Apogee Carrier Dataport Driver: Technical Manual

Point 2- Run Status States

Point Parameter Value Description


Number
2 Run Status 0 Off
2 Run Status 21 On
2 Run Status 22 Test
2 Run Status 999 Ctl Test

Point 6- Alarm States

Point Parameter Value Description


Number
6 Alarm State 16 Normal
6 Alarm State 17 Partial
6 Alarm State 18 Shutdown

Point 109- CCN Load-Shed

Point Parameter Value Description


Number
109 CCN Load-Shed 16 Normal
109 CCN Load-Shed 32 Redline
109 CCN Load-Shed 33 Shed

CDTech.doc REV 0.1 October, 00


Page 24 of 28 Siemens Apogee Carrier Dataport Driver: Technical Manual

Carrier Chiller 30GX Generic Point Map

Point Type Units Description


Number
0 LAO - CCN Address Control point (1-15)
1 LAI - Control mode
2 LAI - Run Status
3 LDI NO/YES Occupied?
4 LDI STOP/START Chiller Start/Stop
5 LDI COOL/HEAT Heat/Cool Select
6 LAI - Reclaim Select
7 LAI - Alarm State
8 LAI - Current Alarm 1
9 LAI - Current Alarm 2
10 LAI - Current Alarm 3
11 LAI - Current Alarm 4
12 LAI - Current Alarm 5
13 LAI % Percent Total Capacity
14 LAI % Active Demand Limit
15 LAI DEG F Current Setpoint
16 LAI DEG F Control Point
17 LAI DEG F Exchanger Entering Water
18 LAI DEG F Exchanger Leaving Water
19 LAI - Active Modes 1-8
20 LAI - Active Modes 9-16
21 LAI - Active Modes 17-22
22 LAI - Emergency Stop
23 LAI % Percent Total Capacity A
24 LAI PSI Circuit A Discharge Pressure
25 LAI PSI Circuit A Suction Pressure
26 LAI PSI A1 Oil Pressure
27 LAI PSI A2 Oil Pressure
28 LAI PSI A1 Oil Pressure Diff
29 LAI PSI A2 Oil Pressure Diff
30 LAI PSI Economizer Pressure Cp1
31 LAI PSI Economizer Pressure Cp2
32 LAI DEG F SAT Condensing Temp A
33 LAI DEG F Saturated Suction Temp A
34 LAI DEG F Discharge Temp A
35 LAI - Circuit A Discharge Superheat
36 LAI DEG F Circuit A Motor Temp Cp1
37 LAI DEG F Circuit A Motor Temp Cp2
38 LAI - EVX Position A

CDTech.doc REV 0.1 October, 00


Page 25 of 28 Siemens Apogee Carrier Dataport Driver: Technical Manual

Point Type Units Description


Number
39 LAI - Head Pressure Actuator Pos A
40 LAI - Cooler Level Indicator
41 LAI -- Compressor 1 Output
42 LAI - Compressor1 Motor Cool Solenoid 1
43 LAI - Compressor1 Motor Cool Solenoid 2
44 LAI - Cp1 Oil Solenoid Out
45 LAI - Compressor 2 Output
46 LAI - Compressor2 Motor Cool Solenoid 1
47 LAI - Compressor2 Motor Cool Solenoid 2
48 LAI - Cp2 Oil Solenoid Out
49 LAI - Cir A Loader 1 Output
50 LAI - Cir A Loader 2 Output
51 LAI - Cir A Oil Heater Output
52 LAI - Cir A Oil Pump Output
53 LAI - Cir A Oil Level Input
54 LAI - Fan Stage 1 Output
55 LAI - Fan Stage 2 Output
56 LAI - Fan Stage 3 Output
57 LAI - Fan Stage 4 Output
58 LAI % Percent Total Capacity B
59 LAI PSI Circuit B Discharge Pressure
60 LAI PSI Circuit B Suction Pressure
61 LAI PSI B1 Oil Pressure
62 LAI PSI B2 Oil Pressure
63 LAI PSI B1 Oil Pressure Diff
64 LAI PSI B2 Oil Pressure Diff
65 LAI PSI Economizer Pressure Cp1 B
66 LAI PSI Economizer Pressure Cp2 B
67 LAI DEG F SAT Condensing Temp B
68 LAI DEG F Saturated Suction Temp B
69 LAI DEG F Discharge Temp B
70 LAI - Circuit B Discharge Superheat
71 LAI DEG F Circuit B Motor Temp Cp1
72 LAI DEG F Circuit B Motor Temp Cp2
73 LAI - EVX Position B
74 LAI - Cir B Head Pressure Actuator Pos A
75 LAI - Cooler Level Indicator B
76 LAI - Cir B Compressor 1 Output
77 LAI - Cir B Compressor1 Motor Cool Solenoid 1
78 LAI - Cir B Compressor1 Motor Cool Solenoid 2

CDTech.doc REV 0.1 October, 00


Page 26 of 28 Siemens Apogee Carrier Dataport Driver: Technical Manual

Point Type Units Description


Number
79 LAI - Cir B Cp2 Oil Solenoid Out
80 LAI - Cir B Loader 1 Output
81 LAI - Cir B Loader 2 Output
82 LAI - Cir B Oil Heater Output
83 LAI - Cir B Oil Pump Output
84 LAI - Cir B Oil Level Input
85 LAI - Cir B Fan Stage 1 Output
86 LAI - Cir B Fan Stage 2 Output
87 LAI - Cir B Fan Stage 3 Output
88 LAI - Cir B Fan Stage 4 Output
89 LAI - Cooler Entering Fluid B
90 LAI - Cooler Leaving Fluid B
91 LAI - Condenser Entering Fluid B
92 LAI - Condenser Leaving Fluid B
93 LAI - Reclaim Entering Fluid B
94 LAI - Reclaim Leaving Fluid B
95 LAI V External 0-10 Volt DC Signal
96 LAI DEG F External Temp
97 LAI DEG F Current Conden. Set-point
98 LAI DEG F Remote On/Off Switch
99 LAI DEG F Remote Setpoint Switch
100 LAI DEG F Remote Heat/Cool Switch
101 LAI ON/OFF Remote Reclaim Switch
102 LAI ON/OFF Limit Switch Status
103 LAI ON/OFF Cooler Lock Status
104 LAI ON/OFF Condenser/Thermostat SW
105 LAI ON/OFF Cooler Pump Status
106 LAI ON/OFF Condenser Pump Status
107 LAI - Cooler Heater Lock
108 LAI ON/OFF Cooler Heater Thermostat
109 LAI ON/OFF Cooler Heater

Point 1- Control mode States

Point Parameter Value Description


Number
1 Control Mode 31 Stop
1 Control Mode 2 Local
1 Control Mode 3 CCN
1 Control Mode 9999 OffCt

CDTech.doc REV 0.1 October, 00


Page 27 of 28 Siemens Apogee Carrier Dataport Driver: Technical Manual

Point 2- Run Status States

Point Parameter Value Description


Number
2 Run Status 0 Off
2 Run Status 21 On
2 Run Status 22 Test
2 Run Status 999 Ctl Test

Point 6- Alarm States

Point Parameter Value Description


Number
6 Alarm State 16 Normal
6 Alarm State 17 Partial
6 Alarm State 18 Shutdown

Application Notes:

• Example mapping for 4 Chillers:

• Chiller 1 or ‘A’: Create LAO point at FLN1, Drop1, Point 00. Map data points
into FLN1, Drop1, Points 01-99 and FLN1, Drop2, Points 00-26.

• Chiller 2 or ‘B’: Create LAO point at FLN1, Drop3, Point 00. Map data points
into FLN1, Drop3, Points 01-99 and FLN1, Drop4, Points 00-26.

• Chiller 3 or ‘C’: Create LAO point at FLN1, Drop5, Point 00. Map data points
into FLN1, Drop5, Points 01-99 and FLN1, Drop6, Points 00-26.

• Chiller 4 or ‘D’: Create LAO point at FLN1, Drop7, Point 00. Map data points
into FLN1, Drop7, Points 01-99 and FLN1, Drop8, Points 00-26.

CDTech.doc REV 0.1 October, 00


Page 28 of 28 Siemens Apogee Carrier Dataport Driver: Technical Manual

Release notice

Siemens Apogee Carrier Dataport Driver: Technical Manual

______________________________________ ___________________
Wayne Moules
Manager, Service Marketing Date
(PRODUCT MANAGER )

______________________________________ ___________________
Paul Kendall
Technical Writer Date
(AUTHOR)

______________________________________ ___________________
Wayne Moules
Engineering Manager Date
(TECHNICAL REVIEWER)

CDTech.doc REV 0.1 October, 00

Potrebbero piacerti anche