Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Convertible Models
WCC030,040,050
IPB-99-7-EN-10-6-99
T-Top™
Corrosion Resistant Screws
Powder Paint
Water-Shed™ Base
High Efficiency
Climatuff® Compressor
DuraTuff™ Plate Fin Coil
Time Defrost Control
Sloped Drain Pan
100% Foil Faced Insulation
Easy Access
Feature Summary 2
Features and Benefits 4
Standard Equipment 4
Impack Accessories 5
Optional Equipment 6
Selection Procedure 7
Model Number Nomenclature 7
General Data 8
English Units
WCC030FD00B 8
WCC040FD00B 8
WCC050FD00B 8
Metric Units
WCC030FD00B 9
WCC040FD00B 9
WCC050FD00B 9
Performance Data 10
Cooling English Units 10
Cooling Metric Units 11
Heating English Units 12
Heating Metric Units 13
Indoor Blower Performance 14
Optional Equipment 15
Controls 16
Field Wiring 17
Dimensions 20
Mechanical Specification Options 26
IPB-99-7-EN-10-6-99 3
Standard Equipment
• High Efficiency • Water-Shed™ Base • Handling
Impack performance is among the highest Superior water integrity is accomplished The three-way wooden skid allows for easy
in the industry. with the Water-Shed™ base pan having loading between the wheel wells on pickup
• Climatuff® Compressor elevated downflow openings and a perim- trucks for transporting to job sites.
Protection against chemical, electrical, and eter channel that prevents water from • Structure
mechanical stresses are built in for draining into the ductwork. The units are lighter weight through the use
efficiency and a longer life. The compressor • Easy Access of high technology components thereby
is backed by a 5-year limited warranty, with All electrical components can be diagnosed reducing mounting structure requirements
an optional warranty for 5 more years. and replaced with the removal of one panel and difficulty when handling.
that is attached with two screws.
• Duct Flanges
• Service Only Impack has downflow duct flanges for
All wiring is both numbered and color coded duct attachments that preserve the built-in
thereby reducing training and servicing water integrity.
costs related to circuit tracing and compo-
• Corrosion
nents replacements.
The drain pan is engineered material and
eliminates the need for coatings and sealers
to prevent sweating and corrosion. The
heavy gauge, zinc-coated steel cabinet has
a weather resistant enamel finish that stays
attractive and protects your investment for
years.
• Low Ambient Control
Zero degree ambient cooling is accom-
• Time Defrost Control plished with two kits. One for low cost
This is an electronic, time initiated, tempera- installations when full tonnage is not
ture terminated defrost system that offers a needed. The other kit maintains head
choice of 50, 70, or 90 minute cycles. The pressure and full capacity at zero degrees.
time override limits the defrost cycle to 10 • Quality and Reliability Testing
minutes. We perform a 100% coil leak test at the
• Convertibility factory. The evaporator and condenser
Impack units are easily converted from • Maintenance coils are leak tested at the factory. The
horizontal to downflow with the removal of A plug on the outdoor fan motor allows the evaporator and condenser coils are leak
one screw from each panel. Accordingly, the top cover to be removed completely without tested at 200 psig and pressure tested to
need to stock both dedicated horizontal and the hassle of cumbersome wires. The 450 psig respectively. In addition the Impack
dedicated downflow models has been unique service orifice ring allows the indoor designs were rigorously rain
eliminated. fan motor/blower to be removed as a unit. tested at the factory to ensure water
integrity. Shipping tests are performed to
• Installation • Plate Fin Coil
determine packaging requirements. Factory
The ease of installation and application Refrigeration coils are built with internally
shake and drop tests are used as part of
flexibility exhibited through the design enhanced copper tubing for high efficiency
the package design process to help assure
reduce both field time and material. with less coil area.
that the unit will arrive at the job site in top
• Application • Shipping condition. Additionally, all components are
The low profile horizontal duct take-offs Unit dimensions were carefully selected to inspected at the point of final assembly.
eliminate the need for expensive transition provide an attractive aspect ratio and for Substandard parts and components are
ducts in crawl space applications. shipping and handling considerations. identified and rejected immediately. Every
unit receives a 100% run test before leaving
• Commonality • Good Neighbor
the production line to make sure it lives up
The common cabinet among the TCC’s, Most units can be installed flush with the
to rigorous Trane® requirements. We at
WCC’s, and YCC’s minimizes both the residence or building thereby minimizing the
Trane test our designs at our factory and not
training of sales and service personnel and ground space required. Blankets of
on our customers!
replacement parts inventory. insulation reduce blower noise and energy
• Flexibility losses to the outside environments.
A single curb fits the entire Impack line from • Rooftop Mounting
1.5 tons through 5 tons thereby providing The cabinets are physically smaller than
great installation flexibility on shopping most competitive models. This means less
malls, factories, schools, and other intrusive installations on residential rooftops
commercial buildings where a mix-match of where aesthetics are critical.
tonnages and utilities is desired.
4 IPB-99-7-EN-10-6-99
• Economizer
The economizer fits inside the unit with only
the rain hood and barometric relief on the
outside. Cabling (with polarized plugs) is
shipped with the economizer. This cabling is
easily routed to the control box where it
terminates in low voltage pigtails. The
economizer features a fully modulating low
voltage motor eliminating the need for any
high voltage wiring. The economizer must
be used with the filter frame kit . . . no return
air filter in the economizer kit. A dry bulb
sensor is shipped with the economizer. The
economizer was not designed for use in
horizontal applications. Heat pump applica-
tions require a relay kit.
• Enthalpy Control Kit • Single Power Entry Kit
For those applications specifying an econo- The kit minimizes installation costs by
mizer with enthalpy control, this control can reducing the load center circuit requirement
be used in place of the dry bulb sensor or, and reducing the number of circuit pulls
alternately, two enthalpy controls can be needed.
paired to provide differential enthalpy control.
IPB-99-7-EN-10-6-99 5
OPTIONAL EQUIPMENT FOR PACKAGE UNITS (Check mark [✓ ✓ ] indicates accessories included).
Indoor Thermostats — 3H/2C Auto Changeover ............................................................................................................................... BAY28X153A [ ]
2H/1C Auto ................................................................................................................................................... BAY28X138A [ ]
Prog. Setback Thermostat (WCC-F) ........................................................................................................... BAYSTAT024B [ ]
2 Stage Htg/Clg Thermostat (WCC-F) .......................................................................................................... BAYSTAT239 [ ]
Remote Sensor for Prog. Thermostat ............................................................................................................ BAYSTAT021 [ ]
Fan Control Relay Kit (DPDT Relay (WCC-F) ................................................................................................. BAY24X042 [ ]
5 or 7 Minute Delay Relay ............................................................................................................................. BAY41X171A [ ]
Locking Thermostat Cover (Thermostats) ....................................................................................................... BAY28X190 [ ]
Man. Prog. 2 Htg/1 Clg ................................................................................................................................... TAYSTAT500 [ ]
Man. Prog. 2 Htg/1 Clg ................................................................................................................................... TAYSTAT501 [ ]
Man. 2 Htg/1 Clg with Subbase ..................................................................................................................... BAYSTAT240 [ ]
Outdoor Thermostat .................................................................................................................................... BAYSTAT033A [ ]
Roof Curb (Flat Roof) (WCC-F) 5 ................................................................................................................................................. BAYCURB030A [ ]
Roof Curb (Flat Roof) (WCC040-050F) ........................................................................................................................................ BAYCURB034A [ ]
0-25% Manual Fresh Air Damper (WCC030F) 2 ........................................................................................................................ BAYDMPR040A [ ]
0-25% Manual Fresh Air Damper (WCC040,050F) 2 ................................................................................................................. BAYDMPR041A [ ]
12" Round Duct Adapter (2 per box) (WCC030F) ........................................................................................................................ BAYDUCT004A [ ]
14" Round Duct Adapter (1 per box) (WCC040,050F) ................................................................................................................. BAYDUCT005A [ ]
0-100% Mod. Economizer w/Baro. Relief (WCC030F) 12345 .............................................................................................. BAYECON054A [ ]
0-100% Mod. Economizer w/Baro. Relief (WCC040,050F) 12345 ....................................................................................... BAYECON055A [ ]
0-100% Horizontal Economizer 23 ............................................................................................................................................ BAYECON073A [ ]
Enthalpy Control (solid state) (WCC-F) 3 ..................................................................................................................................... BAYENTH001A [ ]
Economizer Relay Kit (WCC-F) 1 ................................................................................................................................................. BAYRLAY003A [ ]
Filter Frame (20x25x1" filter not incl.) WCC030F 2 ....................................................................................................................... BAYFLTR012A [ ]
Filter Frame (3-10x25x1" filters not incl.) WCC040,050F 2 .......................................................................................................... BAYFLTR014A [ ]
Lifting Lug Kit (WCC-F) ..................................................................................................................................................................... BAYLlFT002A [ ]
Evaporator Defrost Control (Low Ambient Cool) Kit (WCC-F) 1 ................................................................................................. BAYLOAM011A [ ]
Condenser Coil Guard (WCC030F) .............................................................................................................................................. BAYGARD017A [ ]
Condenser Coil Guard (WCC040,050F) ....................................................................................................................................... BAYGARD022A [ ]
High Static Motor (WCC030F) (230/460) (3/4 hp) ........................................................................................................................ BAYHSMT043A [ ]
High Static Motor (WCC040,050F) (230/460) (1 hp) .................................................................................................................... BAYHSMT044A [ ]
Anti-Short Cycle Timer (WCC-F) ...................................................................................................................................................... BAYASCT001 [ ]
Indoor Fan Delay Kit (WCC-F) ............................................................................................................................................................ BAY24X045 [ ]
Notes:
1 Relay required with economizer on WCC-F models. 4 Ships knocked down.
2 Must use filter frame when economizer/fresh air kit is used. 5 Downflow only.
3 Dry bulb control standard with economizer.
6 IPB-99-7-EN-10-6-99
1 2 3 4 5 6 7 8 9 10 11 12
W C C 0 3 0 F D 0 0 B A
PRODUCT TYPE
TC = Package Cooling PRODUCT
WC = Package Heat Pumps SERVICE CHANGE
ELECTRICAL CHARACTERISTICS
D = 380-415V/3/50
IPB-99-7-EN-10-6-99 7
8 IPB-99-7-EN-10-6-99
IPB-99-7-EN-10-6-99 9
WCC030FD00B AT 1000 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.
D.B. W.B. CAP. 72 74 76 78 80 KW
CORRECTION FACTORS - OTHER AIRFLOWS
59 29.3 23.6 25.4 27.2 29.1 30.0* 2.29 (MULTIPLY OR ADD AS INDICATED)
85 63 31.5 20.1 21.9 23.7 25.5 27.3 2.37
67 33.8 16.2 18.0 19.8 21.6 23.4 2.44 AIRFLOW 875 1125
71 36.2 12.3 14.1 15.9 17.7 19.5 2.52 TOTAL CAP. X0.98 X1.02
59 28.6 23.3 25.1 26.9 28.7* 29.4* 2.41 SENS. CAP. X0.94 X1.05
90 63 30.8 19.8 21.6 23.4 25.2 27.0 2.48 COMPR. KW X0.99 X1.01
67 33.0 15.9 17.7 19.5 21.3 23.1 2.56
71 35.3 11.9 13.7 15.5 17.3 19.1 2.64 VALUES AT 95/80/67 RATING CONDITIONS
59 27.9 23.0 24.8 26.6 28.2* 28.8* 2.53
95 63 30.0 19.5 21.3 23.1 24.9 26.7 2.60 GROSS CAPACITY = 32200 BTUH
67 32.2 15.6 17.4 19.2 21.0 22.8 2.67 AIRFLOW = 1000 CFM
71 34.4 11.6 13.4 15.2 17.0 18.8 2.75 COMPRESSOR POWER = 2673 WATTS
59 27.0 22.6 24.4 26.2 27.5* 28.1* 2.65 I.D. FAN POWER = 340 WATTS
100 63 29.0 19.1 20.9 22.7 24.5 26.3 2.72 O.D. FAN POWER = 250 WATTS
67 31.1 15.2 17.0 18.8 20.6 22.4 2.79 E.E.R. = 9.50 BTUH/WATT
71 33.3 11.2 13.0 14.8 16.6 18.4 2.86 NOTE: RATED WITH 25 FEET OF 7/8
59 26.2 22.2 24.1 25.9 26.7* 27.4* 2.77 SUCT. AND 3/8 LIQUID LINE
105 63 28.1 18.7 20.5 22.3 24.1 25.9 2.84
67 30.1 14.8 16.6 18.4 20.2 22.0 2.91 * DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)
71 32.2 10.8 12.6 14.4 16.2 18.0 2.98 TOTAL CAPACITY,COMP. KW AND APP. DEW PT. ARE VALID ONLY
59 24.4 21.5 23.3 24.7* 25.3* 25.9* 3.02 FOR WET COIL
115 63 26.2 17.9 19.7 21.5 23.3 25.1 3.08 ALL TEMPERATURES IN DEGREES F.
67 28.1 14.0 15.8 17.6 19.4 21.2 3.14
71 30.0 10.0 11.8 13.6 15.4 17.2 3.20
WCC040FD00B AT 1325 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.
D.B. W.B. CAP. 72 74 76 78 80 KW
CORRECTION FACTORS - OTHER AIRFLOWS
59 37.1 30.9 33.4 35.9 37.7* 38.6* 2.60 (MULTIPLY OR ADD AS INDICATED)
85 63 40.0 25.9 28.5 31.0 33.5 36.1 2.68
67 42.9 20.5 23.1 25.6 28.1 30.7 2.75 AIRFLOW 1150 1500
71 46.0 15.0 17.6 20.1 22.6 25.1 2.84 TOTAL CAP. X0.98 X1.01
59 36.5 30.6 33.1 35.7 37.2* 38.1* 2.73 SENS. CAP. X0.94 X1.06
90 63 39.3 25.7 28.2 30.7 33.3 35.8 2.81 COMPR. KW X0.98 X1.02
67 42.2 20.3 22.8 25.3 27.9 30.4 2.89
71 45.2 14.8 17.3 19.8 22.4 24.9 2.97 VALUES AT 95/80/67 RATING CONDITIONS
59 35.9 30.4 32.9 35.4 36.7* 37.6* 2.87
95 63 38.6 25.4 28.0 30.5 33.0 35.5 2.95 GROSS CAPACITY = 41600 BTUH
67 41.5 20.0 22.5 25.1 27.6 30.1 3.02 AIRFLOW = 1325 CFM
71 44.5 14.5 17.0 19.6 22.1 24.6 3.10 COMPRESSOR POWER = 3022 WATTS
59 34.9 29.9 32.5 35.0* 35.9* 36.8* 3.01 I.D. FAN POWER = 560 WATTS
100 63 37.6 25.0 27.5 30.1 32.6 35.1 3.09 O.D. FAN POWER = 500 WATTS
67 40.4 19.6 22.1 24.7 27.2 29.7 3.16 E.E.R. = 9.70 BTUH/WATT
71 43.2 14.1 16.6 19.1 21.7 24.2 3.24 NOTE: RATED WITH 25 FEET OF 7/8
59 33.9 29.5 32.1 34.2* 35.1* 35.9* 3.16 SUCT. AND 3/8 LIQUID LINE
105 63 36.5 24.6 27.1 29.6 32.2 34.7 3.23
67 39.2 19.2 21.7 24.2 26.8 29.3 3.30 * DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)
71 42.0 13.7 16.2 18.7 21.3 23.8 3.37 TOTAL CAPACITY,COMP. KW AND APP. DEW PT. ARE VALID ONLY
59 32.0 28.7 31.3 32.6* 33.4* 34.2* 3.45 FOR WET COIL
115 63 34.4 23.8 26.3 28.8 31.3 33.9 3.51 ALL TEMPERATURES IN DEGREES F.
67 37.0 18.4 20.9 23.4 25.9 28.5 3.57
71 39.6 12.8 15.4 17.9 20.4 22.9 3.64
WCC050FD00B AT 1675 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.
D.B. W.B. CAP. 72 74 76 78 80 KW
CORRECTION FACTORS - OTHER AIRFLOWS
59 47.9 40.4 43.6 46.9 48.7* 49.9* 4.22 (MULTIPLY OR ADD AS INDICATED)
85 63 51.3 34.0 37.3 40.5 43.7 47.0 4.35
67 55.0 27.0 30.3 33.5 36.8 40.0 4.48 AIRFLOW 1450 1900
71 58.8 19.9 23.2 26.4 29.6 32.9 4.61 TOTAL CAP. X0.98 X1.01
59 47.3 40.2 43.4 46.7 48.3* 49.4* 4.17 SENS. CAP. X0.94 X1.06
90 63 50.8 33.8 37.1 40.3 43.5 46.8 4.29 COMPR. KW X0.99 X1.01
67 54.5 26.8 30.1 33.3 36.5 39.8 4.41
71 58.2 19.7 23.0 26.2 29.4 32.7 4.54 VALUES AT 95/80/67 RATING CONDITIONS
59 46.9 40.0 43.2 46.4 47.9* 49.0* 4.11
95 63 50.3 33.6 36.9 40.1 43.3 46.6 4.22 GROSS CAPACITY = 54000 BTUH
67 53.9 26.6 29.9 33.1 36.3 39.6 4.34 AIRFLOW = 1675 CFM
71 57.7 19.5 22.8 26.0 29.2 32.5 4.46 COMPRESSOR POWER = 4339 WATTS
59 45.1 39.2 42.4 45.3* 46.5* 47.6* 4.28 I.D. FAN POWER = 680 WATTS
100 63 48.5 32.8 36.1 39.3 42.6 45.8 4.39 O.D. FAN POWER = 500 WATTS
67 51.9 25.9 29.1 32.3 35.6 38.8 4.51 E.E.R. = 9.35 BTUH/WATT
71 55.6 18.8 22.0 25.2 28.5 31.7 4.63 NOTE: RATED WITH 25 FEET OF 7/8
59 43.4 38.4 41.7 44.0* 45.0* 46.1* 4.46 SUCT. AND 3/8 LIQUID LINE
105 63 46.6 32.1 35.3 38.6 41.8 45.0 4.57
67 50.0 25.1 28.4 31.6 34.8 38.1 4.68 * DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)
71 53.5 18.0 21.3 24.5 27.7 31.0 4.80 TOTAL CAPACITY,COMP. KW AND APP. DEW PT. ARE VALID ONLY
59 39.9 36.9 40.0* 41.1* 42.1* 43.1* 4.82 FOR WET COIL
115 63 42.9 30.6 33.8 37.1 40.3 43.1* 4.92 ALL TEMPERATURES IN DEGREES F.
67 46.0 23.6 26.9 30.1 33.3 36.6 5.03
71 49.3 16.6 19.8 23.0 26.3 29.5 5.13
10 IPB-99-7-EN-10-6-99
IPB-99-7-EN-10-6-99 11
12 IPB-99-7-EN-10-6-99
IPB-99-7-EN-10-6-99 13
14 IPB-99-7-EN-10-6-99
IPB-99-7-EN-10-6-99 15
ECONOMIZER APPLICATION
MODEL MODELS A B C D E F G H
Controls
16 IPB-99-7-EN-10-6-99
NOTES:
1. FUSED DISCONNECT SIZE, POWER WIRING AND
GROUNDING OF EQUIPMENT MUST COMPLY
WITH CODES.
2. BE SURE POWER SUPPLY AGREES WITH
EQUIPMENT AND HEATER NAMEPLATE.
3. LOW VOLTAGE WIRING TO BE 18 AWG MINIMUM
CONDUCTOR.
4. SEE HEATER NAMEPLATE FOR CURRENT
RATING OF HEATER USED.
5. SEE UNIT AND HEATER DIAGRAM FOR
ELECTRICAL CONNECTION DETAILS.
6. IF ELECTRIC HEATER ACCESSORY IS NOT
INSTALLED OMIT THE ELECTRIC HEATER,
ASSOCIATED POWER WIRES AND THE ‘W’ AND
‘X2’ THERMOSTAT WIRES.
7. FIG. 3 DEMONSTRATES CONNECTION OF THE
OUTDOOR THERMOSTAT ACCESSORY ONLY.
FOR FURTHER UNIT CONNECTION DETAILS
REFER TO THE OTHER FIGURES.
8. THE 41A(BR) WIRE IS FIRST STAGE ELECTRIC
HEAT. IF THE ELECTRIC HEATER ACCESSORY
HAS TWO HEATING STAGES THE 41C(BR) WIRE
IS SECOND STAGE ELECTRIC HEAT.
9. WHEN THE BAYECON054A OR –055A
ECONOMIZER IS INSTALLED THE BAYRLAY003
RELAY ACCESSORY KIT IS REQUIRED TO
INTERFACE THE ECONOMIZER TO THE HEAT
PUMP FOR PROPER SYSTEM OPERATION.
WHEN THE BAYECON054B OR –055B OR 073A
ECONOMIZER IS INSTALLED, THE BAYRLAY004A
RELAY ACCESSORY KIT IS REQUIRED TO
INTERFACE THE ECONOMIZER TO THE HEAT
PUMP FOR PROPER SYSTEM OPERATION.
10. THE BAYSTAT033A OUTDOOR THERMOSTAT
ACCESSORY KIT CONTAINS A THERMOSTAT
AND A RELAY. THE RELAY IS NOT REQUIRED
TO BE USED IN THIS APPLICATION.
IPB-99-7-EN-10-6-99 17
18 IPB-99-7-EN-10-6-99
IPB-99-7-EN-10-6-99 19
31
11/2 (790)
(38)
A B 13
/16
SUPPLY (2.1)
14
83/4 (355)
D (222)
1
1 /4
11/2 8 (32)
(38) RETURN (200)
11/2
(38) 41/2
C
11/2
(108) (38)
11/2 11/2
(38) (38)
AIR DUCT
MODEL NO. OPENINGS A B C D
Required Clearance for Unit Installation and Roof Penetration Hole Size Required
ALL DIMENSIONS ARE IN INCHES (MM)
20 IPB-99-7-EN-10-6-99
11/4
43 (32) 621/16
(1090) (1575)
11/2
(38)
12
(305) 41/2 (114)
B 177/8
A (450)
SUPPLY 40
(1015) 14
(355)
A C
11/2 11/2
(38) RETURN (38)
MODEL NO. AIR DUCT A B C
OPENINGS
SUPPLY 21 19 —
(533) (482) 13
11/2
WCC040F /16 (38)
WCC050F (21)
RETURN 21 — 22-1/8
(533) (565) 11/2
All dimensions are in inches (mm). (38) From Dwg. 21C662034
Required Clearance for Unit Installation and Roof Penetration Hole Size Required
ALL DIMENSIONS ARE IN INCHES (MM)
IPB-99-7-EN-10-6-99 21
P.V.C. Rubber Gasket Position on BAYCURB030A for Unit Placement — WCC030-050F Units
ALL DIMENSIONS ARE IN INCHES (MM)
NOTES:
1. OVERLAP AND POSITION JOINTS IN P.V.C. RUBBER
GASKET.
2. AIR SEALS – APPLY P.V.C. RUBBER LAST TO INSURE
THERE IS ADEQUATE P.V.C. FOR THE WATER SEAL.
3. USE TYPICAL SEALING METHODS TO PREVENT AIR
DUCT LEAKAGE AT CURB-DUCT JOINT.
22 IPB-99-7-EN-10-6-99
CABINET MODEL BAYCURB "A" "B" "C" "D" "E" "F" "G" "H"
SIZE
WCC030F 030A 14-1/8 16-5/8 36 34 29-3/16 13-3/4 — —
"B" (360) (425) (915) (865) (740) (350)
WCC040F 030A 14-13/16 21 45 34 33-3/8 13-3/4 10-1/8 9-7/8
"D" WCC050F (380) (535) (1145) (865) (850) (350) (261) (251)
WCC040F 14-13/16 21 45 43 33-3/8 13-3/4
"D" WCC050F 034A (380) (533) (1145) (1092) (850) (350) — —
IPB-99-7-EN-10-6-99 23
MODEL A B C D E F
24 IPB-99-7-EN-10-6-99
13/8
(35)
11/8
(30)
CONDENSATE DRAIN
FOR 3/4" (19) FEMALE NPT
3 (75)
3/4 (19)
(16) 3/4
(19)
1/2 (12)
IPB-99-7-EN-10-6-99 25
26 IPB-99-7-EN-10-6-99
IPB-99-7-EN-10-6-99 27