Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
UH11 Series-1kVA/2kVA/3kVA
User Manual
E1-20010915-C-1.0
Av a n s ys Po w e r Co . , Lt d .
iTrust Intelligent High Frequency Online UPS
UH11 Series-1kVA/2kVA/3kVA
User Manual
Homepage http://www.avansys.com
E-mail info@huawei.com
Copyright Information
Thank you for using iTrust series UPS by Avansys Power Co.,
Ltd. UH11 series is the latest single-phase input single-phase
output intelligent online UPS developed by Avansys incorporating
years of experience in power supply development. As a
world-leading standard UPS product, this series delivers
excellent electrical performance, is fully compliant with safety
regulations and EMC standards, features perfect intelligent
monitoring and network management, and is well-shaped with
beautiful appearance.
Readers
Conventions
Symbol
. Prohibitions
5. Please keep the air inlet and outlet unblocked. Poor ventilation
will increase the internal temperature, which will shorten the
lifetime of the UPS components, hence that of the UPS.
9. If the UPS will not be used for long, it should be placed in dry
environment. Storage temperature of standard UPS (with battery):
–20 +55 , storage temperature of long backup time UPS
(without battery): –40 +70 .
1.4 Features - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2
Chapter 2 Installation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 12
Chapter 3 Operation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 20
Chapter 4 Maintenance - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 33
I. Fan - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 33
II. Battery Maintenance - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 33
V. Function Inspection - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 35
Chapter 5 Troubleshooting - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 36
1.1 Application
1.2 Model
iTrust series UPS has among others 1kVA, 2kVA, and 3kVA UPS
products available, as listed below:
Capa
1kVA 2kVA 3kVA
city
UH11-0020 UH11-0020L
Model UH11-0010 UH11-0010L UH11-0030 UH11-0030L
UH11-0020(B) UH11-0020L(B)
E1-20010915-C-1.0
2 Chapter 1 Product Introduction
Bypass
Input fuse
Mains Electronic transfer Load
Rectifier Inverter
switch
Charger
Charger
(a) 1kVA
Bypass
Input switch
AC mains Electronic Load
Rectifier Inverter transfer switch
Charger
Charger
(b) 2kVA/3kVA
1.4 Features
E1-20010915-C-1.0
Chapter 1 Product Introduction 3
E1-20010915-C-1.0
4 Chapter 1 Product Introduction
1.5.1 Appearance
E1-20010915-C-1.0
Chapter 1 Product Introduction 5
Battery indicator
OFF button
E1-20010915-C-1.0
6 Chapter 1 Product Introduction
Battery indicator
Bypass indicator
Inverter indicator
Air inlet
I. Functions
When the UPS is supplying power through bypass, pressing and holding
this button for 1 second can start the inverter output (i.e., turn on the
ON/SILENC inverter); when the UPS is supplying power through inverter, which
E button obtains power from rectifier, pressing and holding this button for 4
seconds can perform manual battery test; when the UPS is giving
audible alarm, pressing this button can silence the alarm sound.
There are several LED indicators on the panel, showing the UPS state,
LED
load, battery backup capacity, fault, etc.
E1-20010915-C-1.0
Chapter 1 Product Introduction 7
II. LED
The LED indicators on the panel are divided into 2 groups according
to their use: one group indicates the load, battery backup capacity or
fault, totally 5 LED indicators, 4 green and 1 yellow; the other group
indicates the UPS state, including the mains indicator, battery
indicator, bypass indicator, inverter indicator and fault indicator.
Below is the detailed description of these indicators:
E1-20010915-C-1.0
8 Chapter 1 Product Introduction
In the event of UPS fault (the fault indicator shines), these indicators
tell the fault reason (as shown in the following table), so that the fault
can be located quickly.
E1-20010915-C-1.0
Chapter 1 Product Introduction 9
Rectifier fault The 1st green light from the left flashes
Internal
The 3rd green light from the left flashes
overtemperature
Auxiliary supply
The 4th green light from the left flashes
fault
Output
The yellow light flashes
short-circuit
Dry contact
SNMP adaptor
RS232 slot/false panel
Fan
Output socket
External battery socket
(Long backup time UPS)
Input socket
Input fuse EXTERNAL BATT.
OUTPUT
INPUT
E1-20010915-C-1.0
10 Chapter 1 Product Introduction
Fan
Output socket
Input switch
Mains input power line
INPUT
E1-20010915-C-1.0
Chapter 1 Product Introduction 11
Functions:
E1-20010915-C-1.0
12 Chapter 2 Installation
Chapter 2 Installation
1. Open the packing box and take out the UPS, be careful not to
drop it as it is heavy.
2.2 Installation
2. The distance from the rear and side panels of the UPS to the wall
or other equipment should be greater than 10cm, and the air inlets
on the front panel should be kept unblocked, so as to facilitate
ventilation and heat dissipation. Otherwise, the UPS internal
temperature will rise, which will shorten UPS lifetime.
E1-20010915-C-1.0
Chapter 2 Installation 13
heat source and direct sunlight, and better keep the air inlet/outlet
free of dust.
5. Install the UPS in environment free of dust, volatile gas, salt, and
corrosive materials.
Input Output
live line live line
L U
Input Output Load
P
neutral line neutral line
N S
Double-pole linkage
circuit breaker
Input Output
live line live line
L
U
Input Output Load
P
neutral line neutral line
S
N/E
E1-20010915-C-1.0
14 Chapter 2 Installation
1. Please match the UPS model with the battery voltage: 1kVA UPS
uses 36V battery consisting of 3 12V cells in series ; among 2kVA UPS,
UH11-0020 UPS and UH11-0020L UPS use 120V battery consisting
of 10 12V cells in series , UH11-0020B UPS and UH11-0020LB UPS
use 96V battery consisting of 8 12V cells in series ; 3kVA UPS uses
120V battery consisting of 10 12V cells in series . To avoid abnormal
condition, see to it that the cell number is correct, no more, no less;
Notice
2. Use voltmeter to check and make sure the external battery socket
has no voltage output;
4. As shown in Fig. 6(a) and Fig. 6(b), connect the battery cables to
the external battery socket. Make sure that the battery poles are not
reversely connected.: red indicates positive pole (+), and black
indicates negative pole ( ). The cables should have redundant
length to avoid inadvertent pulling off. If the external battery cables
delivered with the UPS are not long enough, lengthen them
according to actual need, yet, to maximally 8 meters. The sectional
area of the cables should increase with the length, if the cables are
relatively long, twist them;
E1-20010915-C-1.0
Chapter 2 Installation 15
AWG size 11 10 9 8 8 7
Notice
DRY CONTACT
RS-232
INTELLIGENT SLOT
OUTPUT
INPUT
E1-20010915-C-1.0
16 Chapter 2 Installation
O
U
T
P
U
T
O
U
T
P
U
T
EXTERNAL BATT
3. Make sure that the socket capacity is correct: 1kVA UPS adopts
socket with capacity greater than 10A, 2kVA/3kVA UPS adopts
socket with capacity greater than 16A. As to 3kVA UPS, if needing
larger input current (for instance, when the mains voltage is usually
low and the UPS assumes full load), please connect the UPS to
distribution switchboard. When the load is fixed and far lower than
E1-20010915-C-1.0
Chapter 2 Installation 17
4. As shown in Fig. 7(a) and Fig. 7(b), connect the UPS input power
line to a wall socket or a distribution switchboard.
Notice
Don’t reversely connect the input neutral line and live line!
1. Please note that the max capacity of each output socket is 10A;
2. As shown in Fig. 7(a) and Fig. 7(b), directly connect the load
power line to the UPS output socket.
E1-20010915-C-1.0
18 Chapter 2 Installation
User equipment
DRY CONTACT
RS-232 cable
RS-232
INTELLIGENT SLOT
Output cable
External batt
Output
Input
Input cable
E1-20010915-C-1.0
Chapter 2 Installation 19
O Communication cable
U
T
P
U
T
Output cable
O
U
T
P
U
T
EXTERNAL BATT.
Input cable
INPUT
INPUT BREAKER
Use the RS-232 cable (universal type) delivered with the UPS to
connect the RS-232 port of the UPS to that of the computer. Dry
contact cable is delivered with 2kVA/3kVA UPS, use it to connect
the dry contact port of the UPS to the RS-232 port of the computer
(connect the cable end marked with “UPS” to the dry contact port, and
the end marked with “PC” to the computer), as shown in Fig. 7(a) and
Fig. 7(b).
E1-20010915-C-1.0
20 Chapter 3 Operation
Chapter 3 Operation
After the UPS is installed, press and hold the ON/SILENCE button
for 1 second, with a beep, the UPS begins to operate in Normal
mode.
When the input mains voltage and the load are within specifications,
the load is supplied by inverter, which obtains power from rectifier;
meanwhile, the charger charges the battery. When in Normal mode,
the mains indicator and inverter indicator on the front panel shine
green.
Notice
E1-20010915-C-1.0
Chapter 3 Operation 21
When the UPS is supplied with AC mains without being turned on,
or in the event of overload or other faults after the UPS is turned on,
the load is supplied by Bypass AC source, which comes directly
from the AC mains input; and meanwhile the charger charges the
battery. When in Bypass mode, the bypass indicator on the front
panel shines green.
Notice
In the event of mains failure or mains voltage outside the range from
120V to 253V in Bypass mode, the UPS is unable to supply the
load.
E1-20010915-C-1.0
22 Chapter 3 Operation
Notice
3.2 Operation
Connect the input power line as described in Section 2.2.2 (for long
backup time UPS, turn on the external battery switch at first), turn on
the input switch (in the case of 2kVA/3kVA UPS), then the system
starts up, the fan inside the rear panel begins to run, and the system
begins self-test (including battery test). After system self-test (the
buzzer beeping twice means normal startup), the system enters in
Bypass mode, the mains indicator and bypass indicator shine on the
front panel, as shown in Fig. 8(a) and Fig. 8(b):
E1-20010915-C-1.0
Chapter 3 Operation 23
BATTERY LOAD
OFF
FAULT
BATTERY LOAD
ON SILENCE
E1-20010915-C-1.0
24 Chapter 3 Operation
bypass indicator goes off and the inverter indicator shines, as shown
in Fig. 9(a) and Fig. 9(b), which means the UPS is operating in
Normal mode.
BATTERY LOAD
OFF
FAULT
BATTERY LOAD
ON SILENCE
E1-20010915-C-1.0
Chapter 3 Operation 25
Notice
BATTERY LOAD
E1-20010915-C-1.0
26 Chapter 3 Operation
OFF
FAULT
BATTERY LOAD
ON SILENCE
3. If all load indicators shine and the buzzer beeps every 0.5
second, it indicates that overload exists. In this case, some less
critical loads should be disconnected. Usually it is recommended the
UPS assume no more than 70% rated load so that the system
operation won’t be affected by abrupt load fluctuation and the UPS
lifetime can be extended.
Notice
In the event of mains failure, user may turn on the UPS to start
Battery mode to supply the load.
E1-20010915-C-1.0
Chapter 3 Operation 27
1. Press and hold the ON/SILENCE button for about 1 second, after
a beep and system self-test, the battery indicator and inverter
indicator shine, as shown in Fig. 11(a) and Fig. 11(b), and the
buzzer beeps every 3 seconds, indicating the UPS is operating in
Battery mode.
BATTERY LOAD
OFF
FAULT
BATTERY LOAD
ON SILENCE
E1-20010915-C-1.0
28 Chapter 3 Operation
Notice
Battery test includes automatic test, manual test, and regular test set
through background monitoring software. For the method of regular
test through background monitoring software, please see the
documents delivered with the monitoring software.
1. Automatic test
E1-20010915-C-1.0
Chapter 3 Operation 29
Notice
2. When the system has no AC mains input (in Battery mode), press
and hold the OFF button for about 1 second, then a beep is heard,
E1-20010915-C-1.0
30 Chapter 3 Operation
the UPS stops running. About 30 seconds later, the auxiliary supply
shuts off, all panel indicators go off, and the fan stops running.
1. After turning off the inverter, pull off the system input plug, or
place the switch of the wall socket or the distribution switchboard to
OFF, all panel indicators go off, and the fan stops running (if there is
a battery, a delay time of 30 seconds is needed before the fan
stops). Up to now, the system is powered off.
3. After system power-off, the UPS has no output to supply the load.
In normal case, user should set the UPS to Normal mode. When
operating in Normal mode, in the event of mains failure, the UPS
automatically transfers to Battery mode without interruption to load;
in the event of overload, the UPS automatically transfers to Bypass
mode without interruption to load; in the event of inverter fault or
internal overtemperature, the UPS operates in Fault mode.
When the UPS remains overloaded for a specified time, the UPS
transfers from Normal mode to Bypass mode, and meanwhile gives
audible alarm every 0.5 second. In such case, the UPS output is
mains voltage. At this time, some loads should be disconnected until
the alarm stops and the yellow load indicator on the front panel goes
off, and 5 minutes after that, the UPS automatically transfers back to
Normal mode. To protect the load and UPS, the transfer times within
1 hour from Normal mode to Bypass mode due to overload should
E1-20010915-C-1.0
Chapter 3 Operation 31
be less than 3, otherwise, the UPS will remain in Bypass mode for 1
hour before it transfers back to Normal mode.
In the event of load short-circuit, the UPS stops output, the fault
indicator shines red, the yellow fault locating indicator flashes, and
the UPS gives alarm. In such case, disconnect the concerned load,
and cut off the input power of the UPS. 10 minutes later, the UPS
automatically shuts down (or manually shut down the UPS 10
seconds later by pressing the OFF button). After removing the
E1-20010915-C-1.0
32 Chapter 3 Operation
short-circuit fault, connect the load back to the UPS, supply the UPS
with AC mains and turn it on.
E1-20010915-C-1.0
Chapter 4 Maintenance 33
Chapter 4 Maintenance
I. Fan
When the UPS hasn’t been used for a long time, and the battery
hasn’t been charged for 3 months at specified ambient
temperature, or 2 months at high ambient temperature, please
charge it for at least 12 hours.
E1-20010915-C-1.0
34 Chapter 4 Maintenance
Notice
1. Regularly clean the system, especially the air inlet and air outlet.
Make sure the air flows freely inside the chassis. Use dust collector
for cleaning when necessary.
2. Check the air vents on the front, rear, and side panels, make sure
they are not blocked.
3. The 2kVA/3kVA long backup time UPS has high capacity rectifier
fan at the bottom of the chassis, make sure that the air vent at the
bottom of the chassis is not blocked.
E1-20010915-C-1.0
Chapter 4 Maintenance 35
please find out the reason, for instance: mains failure, battery test,
operator intervention, etc.
V. Function Inspection
1. Press the OFF button, check whether the buzzer and LED
indications are normal (see Section 3.1 Operation Mode). Please
do this after confirming that the AC mains is normal and data
backup has been done.
E1-20010915-C-1.0
36 Chapter 5 Troubleshooting
Chapter 5 Troubleshooting
In the event of UPS fault, please check it and remove the fault in the
first instance following the methods described in the table below. If
the fault still exists, please contact the distributor, we’ll help you out
of trouble in the shortest time.
Serial
Alarm or Condition Possible Cause Action
No.
E1-20010915-C-1.0
Chapter 5 Troubleshooting 37
Serial
Alarm or Condition Possible Cause Action
No.
E1-20010915-C-1.0
38 Chapter 5 Troubleshooting
Serial
Alarm or Condition Possible Cause Action
No.
E1-20010915-C-1.0
Chapter 6 After-sales Service 39
1. User can obtain service through dialing our free toll telephone.
http://www.avansys.com
hwdy@huawei.com
upsserver@huawei.com
E1-20010915-C-1.0
40 Chapter 6 After-sales Service
E1-20010915-C-1.0
Appendix 1 Communication Port 41
NC 1
6 NC
RXD 2
7 NC
TXD 3
8 NC
NC 4
9 NC
GND 5
E1-20010915-C-1.0
42 Appendix 1 Communication Port
Port description
NC 1
6 OFF
MAINS FAILURE 2
7 GND
NC 3
8 NC
GND 4
9 NC
BATTERY LOW 5
Pin 2: this pin turns from OPEN to CLOSE in the event of mains failure, its
normal state is OPEN;
Pin 5: this pin turns from OPEN to CLOSE in the event of battery low voltage, its
normal state is OPEN;
Pin 6: when applying +5V voltage for more than 1 second, the UPS is turned off;
Pin 4: signal ground;
Pin 7: signal ground;
Other pins: unconnected.
E1-20010915-C-1.0
Appendix 2 Grounding & Lightning Protection 43
To ensure that the ground cable inside the UPS is reliably and
safely connected, the iTrust UPS had undergone stringent internal
ground resistance test at factory before despatch.
E1-20010915-C-1.0
44 Appendix 2 Grounding & Lightning Protection
harm that the lightning strike may do to the UPS machine room is
minimized.
E1-20010915-C-1.0
Appendix 2 Grounding & Lightning Protection 45
User
UPS
Protective
ground
Ground
bar
wiring
diagram
Notes:
E1-20010915-C-1.0
46 Appendix 2 Grounding & Lightning Protection
further before the C-class SPD. User may buy and install the
B-class SPD by itself under the technical guidance of Avansys.
E1-20010915-C-1.0
Appendix 3 Technical Specifications 47
E1-20010915-C-1.0
48 Appendix 3 Technical Specifications
Internal cell
3 8 10
number
Backup time at
full load 6min 8min 10min 8min
Battery standard UPS
Recharge time
8 hours to 90% rated capacity
standard UPS
Display LED
E1-20010915-C-1.0
Appendix 3 Technical Specifications 49
Standard UPS
14 40 45 45
(kg)
Weight
Long backup
8 20 21 21
time UPS (kg)
E1-20010915-C-1.0
50 Appendix 4 Optional Component
E1-20010915-C-1.0