Sei sulla pagina 1di 12

This article has been accepted for inclusion in a future issue of this journal.

Content is final as presented, with the exception of pagination.

IEEE TRANSACTIONS ON POWER DELIVERY 1

A Novel Fault-Location Algorithm


for Double-Circuit Transmission Lines
Without Utilizing Line Parameters
Christos A. Apostolopoulos and George N. Korres, Senior Member, IEEE

Abstract—This paper puts forward a novel algorithm for lo- However, their accuracy is dependent on the fault type and line
cating faults on double-circuit transmission lines using two-end parameters uncertainty, although it is not highly influenced by
unsynchronized current measurements. The algorithm does not the fault resistance and source impedances. Moreover, most of
require line parameters, which is a radical step forward compared
to existing approaches, which require this information, so it can be these algorithms cannot deal effectively with intercircuit faults
considered as a settings-free algorithm. Only the positive-sequence which are more likely to occur on double-circuit lines sharing
current phasors during the fault are processed for determining the the same tower structure.
sought distance to fault and the synchronization angle, limiting Contrary to one-terminal algorithms, there are few two-ter-
thus the amount of data needed to be transferred from each line
terminal. The proposed algorithm is derived by applying the
minal algorithms for double-circuit lines reported in the litera-
Kirchhoff’s voltage law around the parallel circuits loops during ture [9]–[14]. These algorithms employ measurements at both
the fault. The algorithm is applicable for both transposed and terminals of a double-circuit line and, thus, a larger amount of
untransposed double-circuit lines and is independent of the fault information is available, which makes their performance supe-
type. Evaluation studies using reliable Alternative Transients Pro- rior in comparison to one-terminal algorithms. Based on how the
gram-Electromagnetic Transients Program simulation data verify
that the accuracy of the proposed algorithm is very high under digital measurements at the line ends are acquired, two-terminal
various fault resistances, fault locations, and source impedances. algorithms are divided into two categories: 1) those using syn-
Index Terms—Double-circuit transmission lines, fault location,
chronized measurements, if the global positioning system (GPS)
settings-free method, unsynchronized current measurements. is available and 2) those using unsynchronized measurements,
if the signal from the GPS gets lost and there is no common time
reference between measurements. In order to make the unsyn-
I. INTRODUCTION chronized measurements useful for fault-location estimation,
OUBLE-CIRCUIT transmission lines have been ex- analytical synchronization must be achieved. This involves the
D tensively utilized in modern power systems to enhance
the reliability and security for the transmission of electrical
introduction of the synchronization angle as an additional un-
known to the sought distance to fault. Then, the two unknowns
energy. The different possible configurations of double-circuit can be solved by performing iterative [15]–[17] or noniterative
lines, combined with the effect of mutual coupling, makes their calculations [18].
protection and fault-location estimation a very challenging References [9]–[11] present methods that employ unsynchro-
problem. nized measurements for estimating the distance to fault and
Many fault-location algorithms for double-circuit lines have the synchronization angle between measurements from different
been proposed in recent years [1]–[14]. These algorithms terminals of a double-circuit line. They can be classified into
are based either on one-terminal [1]–[8] or two-terminal data two groups: 1) phasor-based methods [9] and 2) time-domain
[9]–[14]. Although less precise than two-terminal algorithms, methods [10], [11]. Algorithms based on synchronized mea-
one-terminal algorithms appear more attractive since they surements have been discussed in [12]–[14]. Some of these al-
rely only on voltage and current measurements captured at gorithms require determination of the fault type [13], [14], while
one common terminal and, hence, no communication links others make use of both prefault and postfault data [12], [13].
have to be provided between both terminals of the line. While Moreover, two-terminal algorithms can be further separated into
different in their considered assumptions and implementation those using two-end voltages [13] or currents only [10], [11], or
issues, these algorithms attempt to estimate the fault current both of them [9], [12], [14].
contribution from the other terminal by solving the Kirchhoff’s Based on the length of the double-circuit transmission line,
Voltage Law (KVL) equations around parallel lines loops. short line [1]–[5], [8], [13] and long line [6], [7], [9]–[12], [14]
algorithms have been developed using lumpled RL line parame-
ters and distributed RLC line parameters, respectively. Most of
Manuscript received January 07, 2010; revised May 11, 2010; accepted De-
cember 19, 2010. Paper no. TPWRD-00015-2010. these algorithms [1]–[6], [11], [13], [14] have focused on trans-
The authors are with the Electrical and Computer Engineering Department, posed transmission lines. Therefore, symmetrical components
National Technical University of Athens, Athens GR-15780, Greece (e-mail: are used to determine the fault location. However, technical,
apostolo@power.ece.ntua.gr; gkorres@softlab.ece.ntua.gr).
Color versions of one or more of the figures in this paper are available online economical and ecological aspects lead to untransposed trans-
at http://ieeexplore.ieee.org. mission lines. Full transposition schemes are often too expen-
Digital Object Identifier 10.1109/TPWRD.2010.2102777

0885-8977/$26.00 © 2011 IEEE


This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

2 IEEE TRANSACTIONS ON POWER DELIVERY

In the rest of this paper, Section II presents the proposed fault-


location algorithm. Section III describes the evaluation studies,
followed by the conclusion.

II. BASICS OF THE FAULT-LOCATION ALGORITHM


The proposed fault-location scheme on double-circuit two-
terminal transmission line SR is shown schematically in Fig. 1.
At both line ends (S,R), there are current transformers (CTs)
which provide the transformed current signals to the measure-
ment units (MUs). Digital measurements are performed in these
units for determining the fundamental frequency phasors of the
three-phase currents. Then, the well-known symmetrical com-
ponent transformation is applied to obtain the positive-sequence
current phasors. The measurement data are transmitted to the
fault locator (FL), which is regarded as a stand-alone device,
via communication links upon occurrence of a fault. It is to be
noted that there is no GPS control of the digital measurements
Fig. 1. Proposed measurement arrangement for fault location on double-circuit performed at the two line ends and, thus, a more general case of
transmission lines. unsynchronized measurements is considered.
The star of fault resistances shown in Fig. 1 enables repre-
senting any type of fault on double-circuit lines, even intercir-
sive and not applicable to short- and medium-length double-cir- cuit faults, eliminating, when necessary, those legs that are not
cuit lines [19]. Although some fault-location methods [7]–[10], present in the type of fault considered. For instance, the IAIIBG
[12] have been proposed for untransposed double-circuit lines, fault is reflected when the legs containing the resistances ,
most of them require the line parameters to be known exactly. , and are maintained and the rest are eliminated. Using
The authors of [12] describe a method for estimating line this generic circuit model for fault representation, the math-
parameters, but this method needs continuously monitoring of ematical formulation of the proposed algorithm is derived in
the double-circuit line during normal operations and demands the following paragraphs for both transposed and untransposed
phasor measurement units (PMUs) for data synchronization. double-circuit lines.
Recent methods that obviate the need for knowing the line pa-
rameters to locate the fault have been presented in [20]–[23]. Al- A. Transposed Double-Circuit Transmission Line
though very instructive and innovative, these methods are only Fig. 2 depicts the positive, negative, and zero-sequence net-
applicable to fully transposed single-circuit transmission lines works of a double-circuit transmission line for a generic unbal-
and do not consider the effect of mutual coupling in double-cir- anced fault at F by using the lumped parameter line model.
cuit lines. It is assumed that the two circuits of the line have identical pa-
This paper puts forward a novel fault-location algorithm rameters and are well transposed. In the figure, the following
which is independent of line parameters and can be applied for nomenclature is adopted:
both transposed and untransposed double-circuit transmission
lines. The algorithm utilizes two-end unsynchronized current , sequence voltages and currents
measurements during the fault and the only assumption made , during the fault at terminal S;
for its successful implementation is the unchangeability of line
parameters after the fault inception, regardless of the tempera-
, sequence voltages and currents
ture rise in conductors, which is a common assumption made
, during the fault at terminal R;
by the majority of the reported fault-location algorithms.
The mathematical derivation of the proposed algorithm is
based on the nominal- line model, providing thus charging cur- , sequence voltages and currents
rent compensation in case of long lines also. The algorithm em- , during the fault at point F;
ploys the Kirchhoff’s voltage law around the parallel circuits ,
loops during the fault to derive a complex equation which con-
tains the sought distance to fault and the corresponding synchro- , positive, zero, and mutual
nization angle. Then, the two unknowns are calculated by using zero-sequence series impedances
a noniterative process, which is also one step beyond the ex- and shunt admittances of the line,
isting methods. Only the positive-sequence current phasors are respectively;
utilized, limiting thus the amount of data needed to be trans-
ferred from each terminal of the double-circuit line. Moreover, unknown distance to fault from
classification of the fault type and selection of the faulted phase reference terminal S in per unit
are generally not required. (p.u.).
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

APOSTOLOPOULOS AND KORRES: NOVEL FAULT-LOCATION ALGORITHM FOR DOUBLE-CIRCUIT TRANSMISSION LINES 3

Based on Fig. 2(a), we can derive the following equations for


the positive-sequence voltage at terminal R:

(1)

(2)

where is the synchronization angle between measurements at


S and R, representing any possible synchronization error.
Rewriting (1) and (2), we have

(3)

(4)

Subtracting (4) from (3), we obtain Fig. 2. (a) Positive, (b) negative, and (c) zero-sequence networks of a trans-
posed double-circuit transmission line during the fault.

Based on Fig. 2(b) and following a similar procedure as be-


(5) fore, we can derive an equation analogous to (6) relating the
or negative-sequence currents between the line terminals:
(6) (7)

(8)

(9)
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

4 IEEE TRANSACTIONS ON POWER DELIVERY

In case of the zero-sequence network, it follows from Fig. 2(c) After the synchronization angle is obtained, the fault location
that the zero-sequence voltage at R satisfies [24]: See (8) and (9) is calculated by taking the real part of (14)
at the bottom of the previous page.
Equations (8) and (9) can be expressed as (18)

Limiting the synchronization angle range to , two so-


lutions generally exist for in (17). One solution lies in the
interval while the other one lies in the interval
and the difference between them is radians. To
decide which solution is the correct one, we can check their cor-
(10) responding fault locations calculated by (18). If one obtained
per-unit fault location is in the boundary and the other
one is out of the boundary , the solution for the synchro-
nization angle that corresponds to the former is the correct one,
while the other one can be rejected or characterized as unreal-
istic [15]–[17], [25].
In case of transposed double-circuit lines, the positive-se-
(11) quence quantities exist in all possible fault types encountered,
while the negative-sequence quantities appear only in the occur-
Subtracting (11) from (10), we obtain rence of unbalanced faults and the zero quantities in case of un-
balanced faults involving ground. Thus, if we want to avoid the
use of a fault-type selection algorithm, we must apply (14) for
fault-location estimation by employing the positive-sequence
currents at the opposite line ends.
(12)

or
B. Untransposed Double-Circuit Transmission Line

(13) Fig. 3 shows the -network representation of an untransposed


double-circuit line during a generic unbalanced fault at point F
Equations (6), (7), and (13) form the basis for determining the [26]. In the figure, the following notations are adopted:
sought synchronization angle and the corresponding distance
to fault, without requiring line parameters, by employing either
vectors of phase voltages
the positive, negative, or zero-sequence currents at the opposite
, and currents during the fault
ends of a transposed double-circuit transmission line. It follows
at terminal S;
from (6), (7), and (13) that
,

(14)

vectors of phase voltages


where and are constants defined in the Appendix. Since
, and currents during the fault
is a real number, the imaginary part of (14) should be zero,
at terminal R;
i.e.,
,

(15)

vectors of phase voltages


where the bar over a variable designates the complex conjugate.
, and currents during the fault
Simplifying (15) leads to
at point F;
,
(16)
,
where and are defined in the Appendix. Finally, the syn-
chronization angle can be determined as follows:
, , , uknown fault and ground
, , , resistances involved in the
(17) fault;
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

APOSTOLOPOULOS AND KORRES: NOVEL FAULT-LOCATION ALGORITHM FOR DOUBLE-CIRCUIT TRANSMISSION LINES 5

inverse of the symmetric


self-circuit series impedance
(or symmetric self-circuit
series admittance) matrix
of the untransposed
double-circuit line SR,
where and
denote the phases of circuit I
and II of the line, respectively
[27], [28];
inverse of the mutual series
impedance (or symmetric
mutual series admittance)
matrix of the untransposed
double-circuit line SR;

Fig. 3. 5-network representation of an untransposed double-circuit transmis-


symmetric self-circuit shunt sion line during the fault.
admittance matrix of the
untransposed double-circuit
line SR; A similar expression as (19) exists for the phase currents at
terminal R, as shown in (21) at the bottom of the page.
Subtracting from , we have

symmetric mutual shunt


admittance matrix of the
untransposed double-circuit
line SR. (22)

Combining (20) and (22), we obtain

Based on Fig. 3, we can derive the following equation for the


phase currents at terminal S in matrix formation, as shown in
(19) at the bottom of the page. (23)
Subtracting from , we have Equation (23) forms the basis for determining the sought syn-
chronization angle and the corresponding distance to fault on an
untransposed double-circuit transmission line. The line parame-
(20) ters have been totally excluded from the closed-form expression

(19)

(21)
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

6 IEEE TRANSACTIONS ON POWER DELIVERY

TABLE I
PARAMETERS OF THE 400-kV, 50-Hz TRANSMISSION NETWORK

Fig. 4. Configuration of the steel tower and conductor.

in (23), which is only dependent on the so-called phase circu-


lating currents [27], [28] flowing along the parallel circuits of
the double-circuit line.
Multiplying (23) with the symmetrical component transfor-
mation matrix yields

(24)

where

; is the -operator and

stands for the zero-, positive-, and negative-sequence


components.
Then, (24) can be written as the expression in (14) and the
unknown fault location can be obtained by using a procedure
source impedance data at the line terminals are gathered in
similar to the one presented in the previous paragraph. It is to be
Table I.
noted that in case of untransposed double-circuit lines, either the
In order to show the errors of the presented method itself,
positive, negative, or zero-sequence quantities can be utilized in
the CTs located at each line terminal have been intentionally
(14) due to the line asymmetries themselves.
modeled as ideal transforming devices. The secondary signals
of these instrument transformers are passed via a second-order
analog (Butterworth) antialiasing filter with a cutoff frequency
III. EVALUATION STUDIES
of 350 Hz as in [17] and [18]. Then, the signals are sampled at
a frequency of 1000 Hz, which corresponds to 20 samples per
A. Data Generation and Conditioning cycle and are stored for postprocessing.
The next step is to pick out the fault segment in the recorded
The presented fault-location algorithm has been evaluated signals. A prerequisite for this is to determine the individual
by using reliable ATP-EMTP [29] simulation data of faults in fault inception times of the current recordings [30]. The fault
a 400-kV, 50-Hz power system network containing a 250-km inception time is detected by waveshape triggers which look
double-circuit untransposed transmission line. The overhead for an abrupt change in the current waveforms captured on a
transmission-line parameters considered have been obtained cycle-by-cycle basis [31]. After isolating the fault data, the se-
by using the constant distributed parameter line model within lected samples in the fault segment of the recorded signals are
the EMTP line constant subroutine for the Public Power Cor- converted into fundamental frequency phasors by applying the
poration (PPC) geometric data shown in Fig. 4. The related discrete Fourier transform. Then, the positive-sequence com-
parameters, consisting of six unique sets of modal quantities ponents of currents required for fault-location estimation are
and the real modal transformation matrix , along with the obtained.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

APOSTOLOPOULOS AND KORRES: NOVEL FAULT-LOCATION ALGORITHM FOR DOUBLE-CIRCUIT TRANSMISSION LINES 7

TABLE II TABLE III


(a) FAULT-LOCATION ESTIMATION ERRORS OBTAINED BY THE PROPOSED FAULT-LOCATION ERROR WITH VARYING FAULT RESISTANCE
ALGORITHM (FAULTED CIRCUIT II, FAULT RESISTANCE: 10
). (b) AND FAULT DISTANCE (FAULTED CIRCUIT II)
SYNCHRONIZATION ANGLE ESTIMATES OBTAINED BY THE PROPOSED
ALGORITHM (FAULTED CIRCUIT II, FAULT RESISTANCE: 10
)

(a)

(b)

It is to be noted that if the developed fault-location algorithm


is intended for use with digital protective relays, the operations
of windowing (triggering the recordings and marking the fault
data) as well as computing the positive-sequence current pha-
sors should be provided by the relays themselves.
The signals generated using ATP-EMTP are, in a natural way,
perfectly synchronized. To simulate the synchronization error,
the phasors at terminal R have been rotated by 18 in all cases
studied. The continuous phasor data are singled by averaging
to test the accuracy of the proposed algorithm. The fault-loca-
within the interval cycles, after the fault inception. Thus,
tion estimation errors, along with the synchronization angle es-
it becomes apparent that in case of self-extinguished or short du-
timates, are gathered in Tables II(a) and (b), respectively.
ration faults (e.g., faults that last less than two cycles after their
It is observed that the maximum error reached for the cases
occurence), the proposed algorithm cannot be safely applied.
considered is less than: 0.15% for phase-to-ground faults (AG,
The proposed algorithm has been implemented in Matlab.
BG, CG), 0.17% for phase-to-phase faults (AB, BC, CA), 0.22%
The percentage error used to measure the fault-location accu-
for phase-to-phase-to-ground faults (ABG, BCG, CAG), and
racy is defined as
0.14% for three-phase faults (ABC), which is an indication that
Actual location - Estimated location the proposed algorithm is very accurate. It can be also seen that
Error (25)
Total line length the estimation error is almost totally eliminated for faults in the
middle of the line because of the symmetry of the double-circuit
line under these conditions.
B. Accuracy Analysis Similar observations can be made for the results obtained for
All possible types of faults (AG, BG, CG, AB, BC, CA, ABG, the synchronization angle. For all cases analyzed, the solution
BCG, CAG, ABC) with a fault resistance of 10 have been for is very close to the actual value and the maximum
simulated at nine different fault distances (10–90% of the line error does not exceed 0.5 for unsymmetrical faults and 0.1 for
length) from reference terminal S in circuit II of the line in order the balanced three-phase faults.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

8 IEEE TRANSACTIONS ON POWER DELIVERY

Fig. 6. Effects of distributed parameters on fault-location estimation (actual


Fig. 5. Effects of distributed parameters on fault-location estimation (actual FL: 80% of the line length, faulted circuit II, R = 10
) (a) LG faults. (b) LL
FL: 20% of the line length, faulted circuit II, R = 10
) (a) LG faults. (b) LL faults. (c) LLG faults. (d) LLL faults.
faults. (c) LLG faults. (d) LLL faults.

with varying the line length from 200 to 300 km. The actual
C. Influence of the Fault Resistance fault locations considered are 20% and 80% of the line length,
Table III shows the effects of fault resistance variation on the respectively, in circuit II of the line. It can be seen that while, in
algorithm’s accuracy for all possible fault types that can be en- general, the distributed parameters have adverse effects on the
countered in circuit II of the line. Faults involving ground have algorithm’s accuracy as the line length increases, the errors for
been investigated for fault resistance values varying from 0 to all types of faults are still within 0.25%. This is an indication
1000 . This captures low- and high-resistance faults. Faults not that the proposed fault-location algorithm can be safely applied
involving ground have been investigated for resistance values of to long lines also.
0 to 100 . Most of these values are much above the typical
arc resistance values quoted in [32]. In all cases considered, the E. Influence of the Source Impedance
actual fault location varies from 10 to 90% of the line length Tables IV(a)–(c) present the fault-location estimation errors
and the local and remote source impedances are set equal to the obtained by varying the local, the remote, and local and remote
system values. source impedances respectively. The simulations consider all
It can be seen that the fault-location estimation error possible types of faults (AG, BG, CG, AB, BC, CA, ABG, BCG,
stays well within 0.18% for phase-to-ground faults, 0.22% for CAG, ABC) with a fault distance of 80% of the line length and
phase-to-phase and phase-to-phase-to-ground faults, and 0.16% a typical fault resistance of . The values of impedances in
for three-phase faults, which is an indication that the proposed local and remote line terminals have been set equal to 20%, 50%,
algorithm is highly accurate and virtually independent of the 100%, 200%, and 500% of the actual system values. It appears
fault resistance. that source impedance variations have an insignificant influence
on the algorithm’s accuracy. This is in full accordance with the
D. Influence of the Distributed Nature of Long Lines performance equation of the proposed algorithm which does not
The mathematical derivation of the proposed algorithm is include the source impedances and, hence, is independent of
based on the nominal- model of the double-circuit line, which their changes.
makes it more appropriate for medium length lines 180 km).
To show the effects of distributed parameters in case of long Algorithm’s Performance for Faults Between Circuits
lines, Figs. 5 and 6 depict the fault-location estimation errors Tables V(a) and (b) show the results of the proposed fault-lo-
for all possible fault types with a fault resistance of 10 and cation algorithm for intercircuit faults, which occur simultane-
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

APOSTOLOPOULOS AND KORRES: NOVEL FAULT-LOCATION ALGORITHM FOR DOUBLE-CIRCUIT TRANSMISSION LINES 9

TABLE IV TABLE V
(a) INFLUENCE OF SOURCE IMPEDANCE IN TERMINAL S ON THE ALGORITHM’S (a) FAULT-LOCATION ALGORITHM RESULTS FOR INTERCIRCUIT FAULTS
ACCURACY (ACTUAL FL: 80% OF THE LINE LENGTH, FAULTED CIRCUIT II, (ACTUAL FL: 20% OF THE LINE LENGTH). (b) FAULT-LOCATION ALGORITHM
R = 10
). (b) INFLUENCE OF SOURCE IMPEDANCE IN TERMINAL R ON THE RESULTS FOR INTERCIRCUIT FAULTS (ACTUAL FL: 80% OF THE LINE LENGTH)
ALGORITHM’S ACCURACY (ACTUAL FL: 80% OF THE LINE LENGTH, FAULTED
CIRCUIT II, R = 10
). (c) INFLUENCE OF THE SOURCE IMPEDANCE IN
TERMINALS S&R ON THE ALGORITHM’S ACCURACY (ACTUAL FL: 80% OF THE
LINE LENGTH, FAULTED CIRCUIT II, R = 10
)

(a)
(a)

(b)

(b)

the current phasor measurements are taken as being indepen-


dent and normally distributed in two dimensions as in [34] and
(c) [35]. Moreover, it is assumed that the standard deviation of the
current magnitude errors is 4% for the phases subjected to fault
and 2% for the sound phases, while the standard deviation of
ously between the parallel circuits of the line under study, with the current angle errors is 4 for the phases involved in the fault
various fault and ground resistances at 20% and 80% of the line and 2 for the unfaulted phases.
length, respectively. It can be observed that the algorithm has The unknown distance to fault can be determined as a random
superior performance for all fault cases studied except for sym- value and fault-location results can be expressed by a set of
metrical intercircuit faults, such as ICAIICA (faults involving statistical properties (mean values, standard deviation, confi-
phases A and C in circuits I and II of the line with the same dence intervals, etc). For calculation of these properties, the
fault resistance). In these rare cases, a proper fault-type selec- Monte-Carlo method [36] has been employed as illustrated in
tion algorithm should be applied to discriminate for the phases Fig. 7. The number of trials has been set equal to 1000 in
involved in the fault based on the current differential principal order to achieve the appropriate accuracy.
[33] since the algorithm utilizes only current signals as input Fig. 8 shows the distribution density function of the estimated
data. distance to fault obtained for four representative types of faults
(AG, BC, BCG, and ABC) by the Monte-Carlo method. The
F. Influence of Measurement Errors fault distances are determined by the proposed algorithm when
Current phasors used as input data in the algorithm are ob- the fault occurs at 80% of the line length and the fault resistance
tained through measuring and filtering processes. This makes it is equal to 10 . It can be seen that the error of the mean value
necessary to analyze the effects of measurement errors on the (the mathematical expectation) for all fault types is below 0.22%
accuracy of the proposed algorithm. These errors result from of the line length, while the standard deviation, which describes
the inaccuracy of CTs, recorders, filtering techniques, sample the accuracy of the fault point location for the certain conditions,
mismatch, etc. To study the impacts of measurements errors on does not exceed 1.5% of the line length.
fault-location accuracy, we have taken into account the proba- Moreover, in Fig. 8, a graphical visualization of the 95%
bilistic nature of these errors. This approach seems more real- confidence intervals (lower and upper bounds—LB vs UP) for
istic than the one in [16] which assumes a systematic error for the fault-location estimates of each fault type is given. The
the current measurements. Hence, in these studies, the errors of confidence level of 95% is the most common level statistically
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

10 IEEE TRANSACTIONS ON POWER DELIVERY

TABLE VI
DESCRIPTIVE STATISTICS FOR THE ESTIMATED DISTANCE
TO FAULT (FAULTED CIRCUIT II, R = 10
)

Fig. 7. Procedure for calculating the statistical properties of fault-location re-


sults due to measurement errors using the Monte-Carlo method.
Similar observations can be made in Fig. 9, which represents
the main properties of the proposed algorithm with respect to
the fault location on the line and fault resistance variations in the
presence of measurement errors. Fig. 9(a) and (b) corresponds
to the same measurement errors conditions as before, while in
Fig. 9(c) and (d), it is assumed that the standard deviation of
the current magnitudes and angles is 5% and 5 for the phases
subjected to fault and 3% and 3 for the phases not involved in
the fault, respectively. Actually, two values of fault resistances
are utilized. Fig. 9(a) and (c) corresponds to and
Fig. 9(b) and (d) corresponds to . It can be ob-
served that for a given measurement error set, the fault resistance
increases the standard deviation value for all types of faults con-
sidered. Moreover, it is evident from the obtained results that
for a given fault resistance, the standard deviation increases as
the error in the magnitude and angle of the measured currents
Fig. 8. Distribution of the estimated distances to fault in case of uncertainty of gets higher. However, the standard deviation for a given fault
the measurements. (a) AG. (b) BC. (c) BCG. (d) ABC. resistance has a similar trend irrespective of the measurement
errors. It can be also seen that in all cases studied, the maximum
standard deviation is kept below the pertubation in the current
adopted—because of the balance between the accuracy and measurements.
reliability—and it gives an estimated range of values where Finally, it is to be noted that further reduction of errors can be
the fault probably is located. Among many existing methods achieved by applying advanced digital filtering techniques [37],
to perform this task, the percentiles method has been chosen [38], instead of the applied standard Fourier filtration.
to determine the confidence interval bounds. This method has
a great advantage: it can be used regardless of what the data
IV. CONCLUSION
probability distribution is, as is the case herein.
Table VI summarizes the descriptive statistics results of the This paper has outlined a new efficient settings-free algo-
estimated distances to fault obtained for nine different fault lo- rithm for fault-location estimation on double-circuit transmis-
cation points (10–90% of the line length). It can be observed sion lines with the use of two-end unsynchronized current mea-
that while the real error existence margins of the current mag- surements during the fault. The algorithm is capable of locating
nitudes and angles are 4% and 4 for the faulted phases and 2% faults when both parallel circuits are in operation. Preliminary
and 2 for the unfaulted phases, respectively, the standard de- test results have proved satisfactory performance and high ac-
viation of the estimated distances is within 1.7% for each fault curacy of the proposed algorithm. In summary, the algorithm’s
type considered, which indicates that the accuracy of the pro- main features and contributions are as follows.
posed algorithm is not significantly influenced by the current 1) Line parameters are not required to determine the fault lo-
measurement errors. cation. Hence, the presented algorithm can overcome the
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

APOSTOLOPOULOS AND KORRES: NOVEL FAULT-LOCATION ALGORITHM FOR DOUBLE-CIRCUIT TRANSMISSION LINES 11

[2] Z. Qingchao, Z. Yao, S. Wennan, Y. Yixin, and W. Zhigang, “Fault


location of two-parallel transmission line for nonearth fault using one-
terminal data,” IEEE Trans. Power Del., vol. 14, no. 3, pp. 863–867,
Jul. 1999.
[3] L. B. Sheng and S. Elangovan, “A fault location method for parallel
transmission lines,” Int. J. Elect. Power Energy Syst., vol. 21, no. 4, pp.
253–259, May 1999.
[4] Y. J. Ahn, M. S. Choi, S. H. Kang, and S. J. Lee, “An accurate fault
location algorithm for double-circuit transmission systems,” in Proc.
IEEE Power Eng. Soc. Summer Meeting, Seattle, WA, Jul. 2000, pp.
1344–1349.
[5] T. Kawady and J. Stenzel, “A practical fault location approach for
double circuit transmission lines using single end data,” IEEE Trans.
Power Del., vol. 18, no. 4, pp. 1166–1173, Oct. 2003.
[6] J. Izykowski, E. Rosolowski, and M. M. Saha, “Locating faults in
power transmission lines under availability of complete measurements
at one end,” Proc. Inst. Elect. Eng., Gen. Transm. Distrib., vol. 151,
no. 2, pp. 268–273, Mar. 2004.
[7] G. Song, J. Suonan, and Y. Ge, “An accurate fault location algorithm
for parallel transmission lines using one-terminal data,” Elect. Power
Energy Syst., vol. 31, no. 2–3, pp. 124–129, Feb./Mar. 2009.
[8] S. H. Kang, Y. J. Ahn, Y. C. Kang, and S. R. Nam, “A fault location
algorithm based on circuit analysis for untransposed parallel transmis-
Fig. 9. Standard deviation of the estimated fault distances as a function of the sion lines,” IEEE Trans. Power Del., vol. 24, no. 4, pp. 1850–1856, Oct.
fault-location point and fault resistance values at various measurement errors
(a), (b)  = 4% (faulted phases),  = 2% (healthy phases) for current mag-
2009.
nitude, and  =4 (faulted phases),  =2 (healthy phases) for current
[9] A. T. Johns and S. Jamali, “Accurate fault location technique for power
angle. (c) and (d)  = 5% (faulted phases),  = 3% (healthy phases) for
transmission lines,” Proc. Inst. Elect. Eng., Gen., Transm. Distrib., vol.
current magnitude and  =5 =3
(faulted phases),  (healthy phases) for
137, no. 6, pp. 395–402, Nov. 1990.
R = 10

current angle (a), (c) (b), (d)R = 100


.
[10] G. Song, J. Suonan, Q. Xu, P. Chen, and Y. Ge, “Parallel transmis-
sion lines fault location algorithm based on differential component net,”
IEEE Trans. Power Del., vol. 20, no. 4, pp. 2396–2406, Oct. 2005.
[11] J. Suonan, G. Song, Q. Xu, and Q. Chao, “Time-domain fault location
degradation of line parameters uncertainty on the existing for parallel transmission lines using unsynchronized currents,” Elect.
Power Energy Syst., vol. 28, no. 4, pp. 253–260, May 2006.
fault locators for double-circuit lines. [12] C. S. Chen, C. W. Liu, and J. A. Jiang, “A new adaptive PMU based
2) Fault-type selection is generally not required, except for protection shceme for transposed/untransposed parallel transmission
the case of symmetrical intercircuit faults. lines,” IEEE Trans. Power Del., vol. 17, no. 2, pp. 395–404, Apr. 2002.
[13] N. Kang and Y. Liao, “Fault location for double-circuit lines utilizing
3) Source impedances and fault resistance have very little in- sparse voltage measurements,” presented at the IEEE Power Eng. Soc.
fluence on the fault-location calculation. Gen. Meeting, Calgary, AB, Canada, Jul. 2009.
4) The distributed parameter effects of long lines, which are [14] E. Rosolowski, J. Izykowski, and M. M. Saha, “Fault location algo-
rithm for use with current differential protective relays of double-circuit
not considered in the algorithm formulation, do not signif- line,” presented at the IEEE Bucharest Power Tech Conf., Bucharest,
icantly affect the accuracy of the fault-location estimates. Romania, Jul. 2, 2009.
5) Even with untransposed transmission lines, the algorithm [15] D. Novosel, D. G. Hart, E. Udren, and J. Garitty, “Unsynchronized
two-terminal fault location estimation,” IEEE Trans. Power Del., vol.
yields fairly accurate results. 11, no. 1, pp. 130–138, Jan. 1996.
6) Noniterative calculations are required for determining the [16] Y. Liao, “Unsynchronized fault location based on distributed parameter
sought distance to fault and the synchronization angle. line model,” Elect. Power Compon. Syst., vol. 35, no. 9, pp. 1061–1077,
2007.
7) Limited amount of data are transferred between the line [17] J. Izykowski, R. Molag, E. Rosolowski, and M. Saha, “Accurate loca-
terminals to locate the fault (only the positive-sequence tion of faults on power transmission lines with use of two-end unsyn-
current phasors during the fault). chronized measurements,” IEEE Trans. Power Del., vol. 21, no. 2, pp.
627–633, Apr. 2006.
8) The algorithm is favorably not very sensitive to measure- [18] J. Izykowski, E. Rosolowski, P. Balcerek, M. Fulczyk, and M. M. Saha,
ment errors. “Accurate noniterative fault-location algorithm utilizing two-end un-
synchronized measurements,” IEEE Trans. Power Del., vol. 25, no. 1,
APPENDIX pp. 72–80, Jan. 2010.
[19] H. Hupfauer, P. Schegner, and R. Simon, “Distance protection of un-
The constants defined in deducing (14) are shown as follows: symmetrical lines,” Eur. Trans. Elect. Power, vol. 6, no. 2, pp. 91–96,
Mar./Apr. 1996.
(A1) [20] Y. Liao and S. Elangovan, “Unsynchronized two-terminal transmis-
sion line fault location without using line parameters,” Proc. Inst. Elect.
(A2) Eng., Gen. Transm. Distrib., vol. 153, no. 6, pp. 639–643, Nov. 2006.
[21] Y. Liao, “Transmission line fault location algorithms without requiring
where 0,1,2 stands for the zero-, positive-, and negative- line parameters,” Elect. Power Compon. Syst., vol. 36, no. 11, pp.
sequence components. 1218–1225, 2008.
[22] Y. Liao and N. Kang, “Fault-location algorithms without utilizing line
The constants defined in deducing (16) are given parameters based on the distributed parameter line model,” IEEE Trans.
Power Del., vol. 24, no. 2, pp. 579–584, Apr. 2009.
(A3) [23] Z. M. Radojevic, C. H. Kim, M. Popov, G. Preston, and V. Terzija,
“New approach for fault location on transmission lines not requiring
line parameters,” presented at the Int. Power Syst. Transients, Kyoto,
REFERENCES Japan, Jun. 2–6, 2009.
[1] Y. Liao and S. Elangovan, “Digital distance relaying algorithm for first- [24] Y. Liao, “Equivalent PI circuit for zero-sequence networks of parallel
zone protection for parallel transmission lines,” Proc. Inst. Elect. Eng., transmission lines,” Elect. Power Compon. Syst., vol. 37, no. 7, pp.
Gen. Transm. Distrib., vol. 145, no. 6, pp. 531–536, Sep. 1998. 787–797, 2009.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

12 IEEE TRANSACTIONS ON POWER DELIVERY

[25] C.-S. Yu, “An unsynchronized measurements correction method for [36] G. S. Fishman, Monte Carlo: Concepts, Algorithms and Applica-
two-terminal fault-location problems,” IEEE Trans. Power Del., vol. tions. New York: Springer-Verlag, 1995.
25, no. 3, pp. 1325–1333, Jul. 2010. [37] S. R. Nam, S. H. Kang, and J. K. Park, “An analytic method for
[26] M. H. Hesse and J. Sabath, “EHV double-circuit untransposed trans- measuring accurate fundamental frequency components,” IEEE Trans.
mission line-analysis and tests,” IEEE Trans. Power App. Syst., vol. Power Del., vol. 17, no. 2, pp. 405–411, Apr. 2002.
PAS-90, no. 3, pp. 984–992, May 1971. [38] C.-S. Yu, “A discrete fourier transform-based adaptive mimic phasor
[27] M. H. Hesse, “Circulating currents in parallel untransposed multicir- estimator for distance relaying applications,” IEEE Trans. Power Del.,
cuit lines: I-Numerical evaluations,” IEEE Trans. Power App. Sys., vol. vol. 21, no. 4, pp. 1836–1846, Oct. 2006.
PAS-85, no. 7, pp. 802–811, Jul. 1966.
[28] M. H. Hesse, “Circulating currents in parallel untransposed multicir-
cuit lines: II-Methods for estimating current unbalance,” IEEE Trans.
Power App. Syst., vol. PAS-85, no. 7, pp. 812–820, Jul. 1966.
[29] H. W. Dommel, Electromagnetic Transients Program. Portland, OR:
BPA, 1986.
[30] M. Moreto and J. G. Rolim, “Automated analysis of digital fault
recorder data in power generating plants,” presented at the Power Syst. Christos A. Apostolopoulos was born in Larisa, Greece, in 1981. He received
Comput. Conf., Glasgow, Scotland, Jul. 14–18, 2008. the Diploma in Electrical and Computer Engineering from the National Tech-
[31] “User Manual,” 2005, PowerXplorer PX5, Dranetz-BMI, Tech. Doc- nical University of Athens, Athens, Greece, in 2004, where he is currently pur-
umentation, Rev. G. suing the Ph.D. degree.
[32] J. L. Blackburn, Symmetrical Components For Power System Engi- Since 2005, he has been a Protection Engineer with PROT.A.S.I.S. S.A.,
neering. New York: Marcel Dekker, 1993, pp. 98–99. Athens. His main research interests are in power system protection, computer
[33] B. Kasztenny, B. Campbell, and J. Mazereeuw, “Phase selection for relaying, and fault location.
single-pole tripping: Weak infeed conditions and cross-country faults,”
presented at the 27th Annu. Western Protective Relay Conf., Spokane,
WA, Oct. 2000.
[34] M. Bockarjova, G. Andersson, and A. Sauhats, “Statistical algorithm George N. Korres (SM’05) received the Diploma and Ph.D. degree in electrical
for power transmission lines distance protection,” presented at the Int. and computer engineering from the National Technical University of Athens,
Conf. Probabilistic Methods Appl. Power Syst., Stockholm, Sweden, Athens, Greece, in 1984 and 1988, respectively.
Jun. 11–15, 2006. Currently, he is Associate Professor in the School of Electrical and Computer
[35] A. Sauhats and M. Danilova, “Fault location algorithms for super high Engineering, National Technical University of Athens. His research interests are
voltage power transmission lines,” presented at the IEEE Power Tech power system state estimation, power system protection, and industrial automa-
Conf., Bologna, Italy, Jun. 26, 2003. tion. He is a member of CIGRE.

Potrebbero piacerti anche