Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Abstract—This paper puts forward a novel algorithm for lo- However, their accuracy is dependent on the fault type and line
cating faults on double-circuit transmission lines using two-end parameters uncertainty, although it is not highly influenced by
unsynchronized current measurements. The algorithm does not the fault resistance and source impedances. Moreover, most of
require line parameters, which is a radical step forward compared
to existing approaches, which require this information, so it can be these algorithms cannot deal effectively with intercircuit faults
considered as a settings-free algorithm. Only the positive-sequence which are more likely to occur on double-circuit lines sharing
current phasors during the fault are processed for determining the the same tower structure.
sought distance to fault and the synchronization angle, limiting Contrary to one-terminal algorithms, there are few two-ter-
thus the amount of data needed to be transferred from each line
terminal. The proposed algorithm is derived by applying the
minal algorithms for double-circuit lines reported in the litera-
Kirchhoff’s voltage law around the parallel circuits loops during ture [9]–[14]. These algorithms employ measurements at both
the fault. The algorithm is applicable for both transposed and terminals of a double-circuit line and, thus, a larger amount of
untransposed double-circuit lines and is independent of the fault information is available, which makes their performance supe-
type. Evaluation studies using reliable Alternative Transients Pro- rior in comparison to one-terminal algorithms. Based on how the
gram-Electromagnetic Transients Program simulation data verify
that the accuracy of the proposed algorithm is very high under digital measurements at the line ends are acquired, two-terminal
various fault resistances, fault locations, and source impedances. algorithms are divided into two categories: 1) those using syn-
Index Terms—Double-circuit transmission lines, fault location,
chronized measurements, if the global positioning system (GPS)
settings-free method, unsynchronized current measurements. is available and 2) those using unsynchronized measurements,
if the signal from the GPS gets lost and there is no common time
reference between measurements. In order to make the unsyn-
I. INTRODUCTION chronized measurements useful for fault-location estimation,
OUBLE-CIRCUIT transmission lines have been ex- analytical synchronization must be achieved. This involves the
D tensively utilized in modern power systems to enhance
the reliability and security for the transmission of electrical
introduction of the synchronization angle as an additional un-
known to the sought distance to fault. Then, the two unknowns
energy. The different possible configurations of double-circuit can be solved by performing iterative [15]–[17] or noniterative
lines, combined with the effect of mutual coupling, makes their calculations [18].
protection and fault-location estimation a very challenging References [9]–[11] present methods that employ unsynchro-
problem. nized measurements for estimating the distance to fault and
Many fault-location algorithms for double-circuit lines have the synchronization angle between measurements from different
been proposed in recent years [1]–[14]. These algorithms terminals of a double-circuit line. They can be classified into
are based either on one-terminal [1]–[8] or two-terminal data two groups: 1) phasor-based methods [9] and 2) time-domain
[9]–[14]. Although less precise than two-terminal algorithms, methods [10], [11]. Algorithms based on synchronized mea-
one-terminal algorithms appear more attractive since they surements have been discussed in [12]–[14]. Some of these al-
rely only on voltage and current measurements captured at gorithms require determination of the fault type [13], [14], while
one common terminal and, hence, no communication links others make use of both prefault and postfault data [12], [13].
have to be provided between both terminals of the line. While Moreover, two-terminal algorithms can be further separated into
different in their considered assumptions and implementation those using two-end voltages [13] or currents only [10], [11], or
issues, these algorithms attempt to estimate the fault current both of them [9], [12], [14].
contribution from the other terminal by solving the Kirchhoff’s Based on the length of the double-circuit transmission line,
Voltage Law (KVL) equations around parallel lines loops. short line [1]–[5], [8], [13] and long line [6], [7], [9]–[12], [14]
algorithms have been developed using lumpled RL line parame-
ters and distributed RLC line parameters, respectively. Most of
Manuscript received January 07, 2010; revised May 11, 2010; accepted De-
cember 19, 2010. Paper no. TPWRD-00015-2010. these algorithms [1]–[6], [11], [13], [14] have focused on trans-
The authors are with the Electrical and Computer Engineering Department, posed transmission lines. Therefore, symmetrical components
National Technical University of Athens, Athens GR-15780, Greece (e-mail: are used to determine the fault location. However, technical,
apostolo@power.ece.ntua.gr; gkorres@softlab.ece.ntua.gr).
Color versions of one or more of the figures in this paper are available online economical and ecological aspects lead to untransposed trans-
at http://ieeexplore.ieee.org. mission lines. Full transposition schemes are often too expen-
Digital Object Identifier 10.1109/TPWRD.2010.2102777
APOSTOLOPOULOS AND KORRES: NOVEL FAULT-LOCATION ALGORITHM FOR DOUBLE-CIRCUIT TRANSMISSION LINES 3
(1)
(2)
(3)
(4)
Subtracting (4) from (3), we obtain Fig. 2. (a) Positive, (b) negative, and (c) zero-sequence networks of a trans-
posed double-circuit transmission line during the fault.
(8)
(9)
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
In case of the zero-sequence network, it follows from Fig. 2(c) After the synchronization angle is obtained, the fault location
that the zero-sequence voltage at R satisfies [24]: See (8) and (9) is calculated by taking the real part of (14)
at the bottom of the previous page.
Equations (8) and (9) can be expressed as (18)
or
B. Untransposed Double-Circuit Transmission Line
(14)
(15)
APOSTOLOPOULOS AND KORRES: NOVEL FAULT-LOCATION ALGORITHM FOR DOUBLE-CIRCUIT TRANSMISSION LINES 5
(19)
(21)
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
TABLE I
PARAMETERS OF THE 400-kV, 50-Hz TRANSMISSION NETWORK
(24)
where
APOSTOLOPOULOS AND KORRES: NOVEL FAULT-LOCATION ALGORITHM FOR DOUBLE-CIRCUIT TRANSMISSION LINES 7
(a)
(b)
with varying the line length from 200 to 300 km. The actual
C. Influence of the Fault Resistance fault locations considered are 20% and 80% of the line length,
Table III shows the effects of fault resistance variation on the respectively, in circuit II of the line. It can be seen that while, in
algorithm’s accuracy for all possible fault types that can be en- general, the distributed parameters have adverse effects on the
countered in circuit II of the line. Faults involving ground have algorithm’s accuracy as the line length increases, the errors for
been investigated for fault resistance values varying from 0 to all types of faults are still within 0.25%. This is an indication
1000 . This captures low- and high-resistance faults. Faults not that the proposed fault-location algorithm can be safely applied
involving ground have been investigated for resistance values of to long lines also.
0 to 100 . Most of these values are much above the typical
arc resistance values quoted in [32]. In all cases considered, the E. Influence of the Source Impedance
actual fault location varies from 10 to 90% of the line length Tables IV(a)–(c) present the fault-location estimation errors
and the local and remote source impedances are set equal to the obtained by varying the local, the remote, and local and remote
system values. source impedances respectively. The simulations consider all
It can be seen that the fault-location estimation error possible types of faults (AG, BG, CG, AB, BC, CA, ABG, BCG,
stays well within 0.18% for phase-to-ground faults, 0.22% for CAG, ABC) with a fault distance of 80% of the line length and
phase-to-phase and phase-to-phase-to-ground faults, and 0.16% a typical fault resistance of . The values of impedances in
for three-phase faults, which is an indication that the proposed local and remote line terminals have been set equal to 20%, 50%,
algorithm is highly accurate and virtually independent of the 100%, 200%, and 500% of the actual system values. It appears
fault resistance. that source impedance variations have an insignificant influence
on the algorithm’s accuracy. This is in full accordance with the
D. Influence of the Distributed Nature of Long Lines performance equation of the proposed algorithm which does not
The mathematical derivation of the proposed algorithm is include the source impedances and, hence, is independent of
based on the nominal- model of the double-circuit line, which their changes.
makes it more appropriate for medium length lines 180 km).
To show the effects of distributed parameters in case of long Algorithm’s Performance for Faults Between Circuits
lines, Figs. 5 and 6 depict the fault-location estimation errors Tables V(a) and (b) show the results of the proposed fault-lo-
for all possible fault types with a fault resistance of 10 and cation algorithm for intercircuit faults, which occur simultane-
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
APOSTOLOPOULOS AND KORRES: NOVEL FAULT-LOCATION ALGORITHM FOR DOUBLE-CIRCUIT TRANSMISSION LINES 9
TABLE IV TABLE V
(a) INFLUENCE OF SOURCE IMPEDANCE IN TERMINAL S ON THE ALGORITHM’S (a) FAULT-LOCATION ALGORITHM RESULTS FOR INTERCIRCUIT FAULTS
ACCURACY (ACTUAL FL: 80% OF THE LINE LENGTH, FAULTED CIRCUIT II, (ACTUAL FL: 20% OF THE LINE LENGTH). (b) FAULT-LOCATION ALGORITHM
R = 10
). (b) INFLUENCE OF SOURCE IMPEDANCE IN TERMINAL R ON THE RESULTS FOR INTERCIRCUIT FAULTS (ACTUAL FL: 80% OF THE LINE LENGTH)
ALGORITHM’S ACCURACY (ACTUAL FL: 80% OF THE LINE LENGTH, FAULTED
CIRCUIT II, R = 10
). (c) INFLUENCE OF THE SOURCE IMPEDANCE IN
TERMINALS S&R ON THE ALGORITHM’S ACCURACY (ACTUAL FL: 80% OF THE
LINE LENGTH, FAULTED CIRCUIT II, R = 10
)
(a)
(a)
(b)
(b)
TABLE VI
DESCRIPTIVE STATISTICS FOR THE ESTIMATED DISTANCE
TO FAULT (FAULTED CIRCUIT II, R = 10
)
APOSTOLOPOULOS AND KORRES: NOVEL FAULT-LOCATION ALGORITHM FOR DOUBLE-CIRCUIT TRANSMISSION LINES 11
[25] C.-S. Yu, “An unsynchronized measurements correction method for [36] G. S. Fishman, Monte Carlo: Concepts, Algorithms and Applica-
two-terminal fault-location problems,” IEEE Trans. Power Del., vol. tions. New York: Springer-Verlag, 1995.
25, no. 3, pp. 1325–1333, Jul. 2010. [37] S. R. Nam, S. H. Kang, and J. K. Park, “An analytic method for
[26] M. H. Hesse and J. Sabath, “EHV double-circuit untransposed trans- measuring accurate fundamental frequency components,” IEEE Trans.
mission line-analysis and tests,” IEEE Trans. Power App. Syst., vol. Power Del., vol. 17, no. 2, pp. 405–411, Apr. 2002.
PAS-90, no. 3, pp. 984–992, May 1971. [38] C.-S. Yu, “A discrete fourier transform-based adaptive mimic phasor
[27] M. H. Hesse, “Circulating currents in parallel untransposed multicir- estimator for distance relaying applications,” IEEE Trans. Power Del.,
cuit lines: I-Numerical evaluations,” IEEE Trans. Power App. Sys., vol. vol. 21, no. 4, pp. 1836–1846, Oct. 2006.
PAS-85, no. 7, pp. 802–811, Jul. 1966.
[28] M. H. Hesse, “Circulating currents in parallel untransposed multicir-
cuit lines: II-Methods for estimating current unbalance,” IEEE Trans.
Power App. Syst., vol. PAS-85, no. 7, pp. 812–820, Jul. 1966.
[29] H. W. Dommel, Electromagnetic Transients Program. Portland, OR:
BPA, 1986.
[30] M. Moreto and J. G. Rolim, “Automated analysis of digital fault
recorder data in power generating plants,” presented at the Power Syst. Christos A. Apostolopoulos was born in Larisa, Greece, in 1981. He received
Comput. Conf., Glasgow, Scotland, Jul. 14–18, 2008. the Diploma in Electrical and Computer Engineering from the National Tech-
[31] “User Manual,” 2005, PowerXplorer PX5, Dranetz-BMI, Tech. Doc- nical University of Athens, Athens, Greece, in 2004, where he is currently pur-
umentation, Rev. G. suing the Ph.D. degree.
[32] J. L. Blackburn, Symmetrical Components For Power System Engi- Since 2005, he has been a Protection Engineer with PROT.A.S.I.S. S.A.,
neering. New York: Marcel Dekker, 1993, pp. 98–99. Athens. His main research interests are in power system protection, computer
[33] B. Kasztenny, B. Campbell, and J. Mazereeuw, “Phase selection for relaying, and fault location.
single-pole tripping: Weak infeed conditions and cross-country faults,”
presented at the 27th Annu. Western Protective Relay Conf., Spokane,
WA, Oct. 2000.
[34] M. Bockarjova, G. Andersson, and A. Sauhats, “Statistical algorithm George N. Korres (SM’05) received the Diploma and Ph.D. degree in electrical
for power transmission lines distance protection,” presented at the Int. and computer engineering from the National Technical University of Athens,
Conf. Probabilistic Methods Appl. Power Syst., Stockholm, Sweden, Athens, Greece, in 1984 and 1988, respectively.
Jun. 11–15, 2006. Currently, he is Associate Professor in the School of Electrical and Computer
[35] A. Sauhats and M. Danilova, “Fault location algorithms for super high Engineering, National Technical University of Athens. His research interests are
voltage power transmission lines,” presented at the IEEE Power Tech power system state estimation, power system protection, and industrial automa-
Conf., Bologna, Italy, Jun. 26, 2003. tion. He is a member of CIGRE.