Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
4, OCTOBER 2009
Abstract—This paper presents the results of a study on the use of Point-wise incident voltage.
modal analysis for estimating received signal levels of a power-line
carrier (PLC) channel on high voltage transmission lines. The Point-wise reflected voltage.
intent of the paper is to serve as a reference. Numerous papers
have been written on modal analysis and signal propagation on Forward-traveling voltage wave.
overhead lines at PLC frequencies. However, for the information
Reverse-traveling voltage wave.
to be put to practical use requires reading numerous references,
including references on transmission line modeling. Therefore, Phase domain voltage.
this paper provides information on transmission line modeling
and modal analysis theory needed for using modal analysis for Modal domain voltage.
an actual calculation of received signal levels with results in the
phase domain, which is the domain in which measurements are Phase domain current.
usually made. Modal analysis is used to calculate modal prop- Phase domain series impedance per unit length.
agation constants, which are used in an equation that directly
relates sending-end voltage to receiving-end voltage utilizing a Phase domain shunt admittance per unit length.
multiphase reflection coefficient. To validate calculations using
the described methods, field tests were performed on an energized Phase domain characteristic (surge) impedance.
500-kV transmission line. Results from these tests in the form of
Phase domain propagation constant.
a comparison of calculated versus measured voltage levels are
provided. Modal domain propagation constant.
Index Terms—Modal analysis, power-line carrier (PLC), trans- Modal voltage transformation matrix.
mission line modeling.
Diagonal matrix consisting of eigenvalues of the
propagation matrix.
NOMENCLATURE:
Conductor depth of wave penetration.
Designates a matrix. Conductor conductivity per unit length.
(1)
(2)
In (1) and (2), is the series impedance per unit length matrix
and is the shunt admittance per unit length matrix. is
Fig. 1. Simplified single-frequency PLC system at one end of a transmission the propagation matrix, and and are column matrices of
line.
voltage and current phasors.
(12)
where
(18)
and
• are the phase voltages;
• are the shield wire voltages;
• are the self-impedance elements of corre-
sponding to the phase conductors;
• are the self-impedance elements of corre-
sponding to the shield wires;
• are the mutual impedance elements of
between the phase conductors and shield wires.
The procedure for reducing the potential coefficient matrix
is the same; however, the potential coefficient matrix has to be
reduced before inverting to obtain the capacitance matrix.
C. Eliminating Shield Wires From the Analysis Since voltage was the parameter measured in field tests, only
voltage transformations will be considered. Current transforma-
From [5], shield wires may be eliminated from the analysis tions are derived similarly; remembering that current is a func-
when one-fourth of the wavelength of the PLC signal is less than tion of the product as opposed to voltage, which is a func-
a tower-to-tower span of the transmission line. Under this condi- tion of the product.
tion, standing waves will not be present on the shield wires and The modal transformation matrix for voltage is defined as
the potential along the shield wire may be considered constant
and zero, assuming the shield wires are grounded at each tower. (19)
For typical high voltage transmission lines, the shield wires may
be eliminated when analyzing PLC signals with frequencies less Substituting (19) into (1) yields for voltage
than 250 kHz. As shown in [5], the shield wire elements can be
eliminated from both the series impedance and potential coeffi-
cient matrices by partitioning the matrices into phase conductor
voltages and shield wire voltages as follows: (20)
(21)
where
(22)
(16)
If the columns of are chosen to be the eigenvectors of
(17) , then from matrix theory, the result of the product of
2450 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 24, NO. 4, OCTOBER 2009
will be a diagonal matrix with the eigen- The diagonal elements of are given by (25), and is
values of on the main diagonal. That is the line’s series impedance per unit length given by (10).
3) Equation Relating Sending-End Voltage to Receiving-End
Voltage: In [10], Wedepohl utilizes the matrix function in con-
(23) junction with the multiphase reflection coefficient and presents
equations relating sending-end voltage to incident voltage and
The coupled system of equations of (1) becomes a set of uncou- receiving-end voltage to incident voltage. To verify the sequence
pled equations of the form of of multiplication of the matrices presented by Wedepohl, an
equation directly relating sending-end voltage to receiving-end
(24) voltage was derived and given as (29). Another more practical
reason for deriving an equation that relates sending-end to re-
where the modal propagation constant is ceiving-end voltage is that these voltages can be directly mea-
sured in the PLC coupling equipment. The sequence of matrix
(25) multiplication in (29) agrees with that presented by Wedepohl.
The derivation of (29) is presented in the Appendix
The analysis then becomes that of traditional single-phase trans-
mission lines. Descriptions of modal analysis applied to multi-
phase transmission lines can be found in [1] and [6]–[12].
(29)
B. Modal Analysis Using the Multiphase Reflection Coefficient
where can be calculated using the matrix function as
Method
In [10], Wedepohl presents a more concise method of modal (30)
analysis for analyzing signal propagation on multiphase trans-
For practical information, and would be voltages
mission lines by utilizing a multiphase reflection coefficient ma-
measured on the transmission line side of the IMT of Fig. 1, as-
trix in conjunction with a matrix function. Wedepohl’s method
suming the line tuner is adjusted properly. These voltages would
proves to be more suitable for analyzing PLC signal propaga-
also be the phase-to-ground voltage levels (for phase-to-ground
tion in that the transmission line terminating impedances do not
coupling) on the transmission line at their respective ends of the
have to be converted to the modal domain.
line, again assuming the line tuner is adjusted properly and ne-
1) The Matrix Function: From [13], if a matrix can be diag-
glecting the line tuner losses.
onalized, then polynomial functions can easily be performed on
the matrix in terms of the eigenvectors and eigenvalues. That is, V. COMPARISON OF CALCULATED RESULTS TO
let be a square matrix and be a matrix whose columns FIELD MEASUREMENTS
are comprised of the eigenvectors of , then
Field tests were performed to validate calculations. The tests
(26) consisted of applying a signal at one end of a 500-kV line and
measuring the magnitude of the signal at the other end of the
where is a diagonal matrix composed of the eigenvalues of line using a frequency selective voltmeter. At the sending-end
. As an example, let be a 2 2 matrix, and it is desired of the line, the IMT of Fig. 1 was removed from the coupling
to take the square root of . Then, using the matrix function, circuit and the signal was applied directly to the line-tuning unit.
the square root can be found as Thus, the voltage level measured at the terminals of the signal
generator would approximately be the phase-to-ground voltage
level applied to the transmission line, after the series LC unit
was tuned to resonate at the frequency of the test signal. At the
receiving-end of the line, all line tuning equipment was removed
2) The Multiphase Reflection Coefficient Matrix: A multi-
from the phase to which the test signal was coupled so that only
phase reflection coefficient matrix was presented by Wedepohl
the coupling capacitor, drain coil, and line trap of Fig. 1 re-
in [10] and [11]. However, the order of the multiplication for the
mained. The voltage at the receiving-end was measured across
matrices was different in the two references. Therefore, to verify
the drain coil, which was approximately the phase-to-ground
the required order of matrix multiplication, the multiphase re-
voltage level on the line since the drain coil impedance essen-
flection coefficient matrix at the receiving-end of the line was
tially presented an open circuit at the test signal frequency.
derived with the derivation provided in the Appendix, where it
The test line had PLC coupling equipment for phase-to-
is shown that in the phase domain the multiphase reflection co-
ground coupling on the center phase and one outer phase.
efficient matrix at the receiving-end of the line is
This arrangement allowed for voltage measurements at the
(27) receiving-end of the line on the phase to which the test signal
was applied as well as another phase, which provided additional
As shown in [11], the phase domain characteristic (surge) data for validation of calculations. During the tests, the line
impedance of the line can be calculated using (28) was energized. The line has numerous PLC frequencies for
the different protection schemes employed on the line, and
(28) these protection schemes remained in service during the tests,
FRANKLIN: USING MODAL ANALYSIS TO ESTIMATE RECEIVED SIGNAL LEVELS 2451
TABLE I
MEASURED AND CALCULATED VOLTAGE LEVELS AT RECEIVING-END OF LINE
APPENDIX Thus
(32) (43)
FRANKLIN: USING MODAL ANALYSIS TO ESTIMATE RECEIVED SIGNAL LEVELS 2453
From [14], the incident and reflected voltages can be expressed sending-end voltage reflection coefficient is .
in terms of receiving end quantities as But, in (48)
(44)
(50)
(51)
From (34), so
After simplifying, becomes
(55)
(46)
At the sending end of the line and from (36)
At the sending end of the line and the sending-end
voltage reflection coefficient is (56)
(57)
(47) (58)
(59)
Or, after substituting (43) into (47)
(60)
(48)
From (34), so
Or, in terms of the sending-end impedance
(61)
(49)
Or, after substituting (48) into (61)
Of interest is the sequence of matrix multiplication for .
For the single-phase case, the traditional definition of the (62)
2454 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 24, NO. 4, OCTOBER 2009
Rearranging to get [2] J. A. Edminister, Schaum’s Outline of Theory and Problems of Elec-
tromagnetics, 2nd ed. New York: McGraw-Hill, 1993, vol. I, pp.
237–241.
(63) [3] J. R. Carson, “Wave propagation in overhead wires with ground return,”
Bell Syst. Tech. J., vol. 5, pp. 539–554, 1926.
[4] A. Deri, G. Tevan, A. Semlyen, and A. Castanheira, “The complex
And as shown previously, so earth return plane: A simplified model for homogenous and multi-layer
earth return,” IEEE Trans. Power App. Syst., vol. PAS-100, no. 8, pp.
(64) 3686–3693, Aug. 1981.
[5] N. Watson and J. Arrillaga, “Power systems electromagnetic transients
simulation,” in IEE Power and Energy, ser. 39. London, U.K.: Inst.
Now the receiving-end voltage can be expressed in terms of the Elect. Eng., 2003, pp. 123–142.
sending-end voltage and the receiving-end voltage reflection co- [6] G. E. Adams, “Wave propagation along unbalanced high-voltage trans-
mission lines,” AIEE Trans., pt. III (Power App. Syst.), vol. 78, pp.
efficient by substituting (64) into (55) to obtain 639–647, Aug. 1959.
[7] L. O. Barthold, “Radio-frequency propagation on polyphase lines,”
IEEE Trans. Power App. Syst., vol. PAS-83, no. 7, pp. 665–671, Jul.
1964.
(65) [8] M. C. Perz, “Natural modes of power line carrier on horizontal three-
phase lines,” IEEE Trans. Power App. Syst., vol. PAS-83, no. 7, pp.
679–685, Jul. 1964.
where can be calculated using the matrix function as [9] M. C. Perz, “A method of analysis of power line carrier problems on
three-phase lines,” IEEE Trans. Power App. Syst., vol. PAS-83, no. 7,
pp. 686–691, Jul. 1964.
(66) [10] L. M. Wedepohl, “Electrical characteristics of polyphase transmission
systems, with special reference to boundary value calculations at power
Calculated Parameters for 500-kV Line: Using the trans- line carrier frequencies,” Proc. Inst. Elect. Eng., vol. 112, no. 11, pp.
2103–2112, Nov. 1965.
mission line modeling methods described in Section III, the cal- [11] L. M. Wedepohl, “Application of matrix methods to the solution of
culated line series impedance and shunt admittance matrices travelling-wave phenomena in polyphase systems,” Proc. Inst. Elect.
with shield wires eliminated, and the modal propagation con- Eng., vol. 110, no. 12, pp. 2200–2212, Dec. 1963.
[12] IEEE Guide for Power-Line Carrier Applications, IEEE Std. 643-2004,
stants for the 500-kV line are as follows for a frequency of 175 Jun. 2005.
kHz—see the equation at the bottom of the previous page. And, [13] P. M. Derusso, R. J. Roy, and C. M. Close, State Variables for Engi-
using , the modal attenuation constants are neers. New York: Wiley, 1965, pp. 232–285.
[14] D. A. Conner, Electromagnetic Dynamics, 1st Unified Draft. Birm-
as follows: ingham, AL: Univ. Alabama, 1987, pp. 9-5–9-32.
• ;
• ; Gregory A. Franklin (M’03) received the B.S.E.E., M.S.E.E., and Ph.D. de-
grees from the University of Alabama at Birmingham in 1996, 1997, and 2005,
• . respectively.
From 1997 through 2006, he was with Southern Company, Birmingham,
working in the area of substation protection and control. In 2007, he resigned
REFERENCES from Southern Company as a Senior Engineer to join the faculty of the
[1] D. E. Hedman, “Propagation on overhead transmission lines, parts I Electrical and Computer Engineering Department, University of Alabama at
and II,” IEEE Trans. Power App. Syst., vol. PAS-84, no. 3, pp. 200–211, Birmingham.
Mar. 1965. Dr. Franklin is a registered Professional Engineer in the State of Alabama.