Rated Voltage
frecuencia
Desire Maximum Current Rating of Bus bar
Fault Current (Isc)= 50KA ,Fault Duration (t)
Bus bar Temperature details:
Operating Temperature of Bus bar (θ)
Final Temperature of Bus bar during Fault(θ1)=1
Temperature rise of Bus Bar Bar during Fault (θt=θ1-θ)
Ambient Temperature (θn)
Maximum Bus Bar Temperature Rise
Enclosure Details:
Installation of Panel
Altitude of Panel Installation on Site
Panel Length
Panel width
Panel Height
Bus bar Details:
Bus bar Materia
Bus bar Strip Arrangements
Current Density of Bus Bar Material
Temperature Co efficient of Material Resistance at 20°c(α20)
Material Constant(K)
Bus bar Material Permissible Strength
Bus bar Insulating Material
Bus bar Position
Bus bar Installation Media
Bus bar Artificial Ventilation Scheme
Bus bar Size Details:
Bus bar Width(e)
Bus bar Thickness(s)
Number of Bus Bar per Phase(n)
Bus bar Length per Phase(a)
Distance between Two Bus Strip per Phase
Bus bar Phase Spacing (p)
Total No of Circuit
Bus bar Support Insulator Detail:
Distance between insulators on Same Phase(l)
Insulator Height (H)
Distance from the head of the insulator to the bus bar center of gravity (h)
Permissible Strength of Insulator (F’)
(1)De rating Factor for bus Bar:
(1) Per Phase Bus Strip De rating Factor (K1):
Bus bar Width(e)
Bus bar Length per Phase(a)
e/a
No of Bus bar per phase
value of de rating factor
De rating Factor
415 v
50 Hz
630 A
1 seg
85 °C.
185 °C.
100 °C.
50 °C.
55 °C.
Copper
vertical
1.6
0.00403
1.166
1200 kg/cm2
bare
Edge-mounted bars
Non-ventilated ducting
without artificial ventilation
75 mm
10 mm
2 No
500 mm
75 mm
400 mm
3 No
500 mm
100 mm
5 mm
1000 kg/cm2
No of Bus Bar per Phase
e/a
1
0.05 1
0.06 1
0.08 1
0.1 1
75 mm 0.12 1
500 mm 0.14 1
0.15 0.16 1
2 No 0.18 1
1.83 0.2 1
De rating
Bus Bar Position(K3):
Factor
1 Edge-mounted bars 1
1 bar base-mounted 0.95
several base-mounted bars 0.75
De rating
Bus Bar Installation Media(K4):
Factor
Calm indoor atmosphere 1
0.8 Calm outdoor atmosphere 1.2
Non-ventilated ducting 0.8
9000000 sq.mm
of Bus Bar per Phase
2 3
1.63 2.4
1.73 2.45
1.76 2.5
1.8 2.55
1.83 2.6
1.85 2.63
1.87 2.65
1.89 2.68
1.91 2.7
Number of Bus Bar Strip per Phase (K1)
No of Bus Bar per Phase
e/a
1 2 3
0.05 1 1.63 2.4
0.06 1 1.73 2.45
0.08 1 1.76 2.5
0.1 1 1.8 2.55
0.12 1 1.83 2.6
0.14 1 1.85 2.63
0.16 1 1.87 2.65
0.18 1 1.89 2.68
0.2 1 1.91 2.7