Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Pocket Guide
ISSUE APRIL 2019
1 Things You Need to Know
1. The maximum parameters that the Exhaust Gas Cleaning
System (EGCS) is designed to operate under are generally
85% Engine load with a 3.5% fuel sulphur content, operating
in low alkalinity (eastern Baltic) seawater. Check your approved
ETM-B for more details.
2. To keep the DeSOx Tower clean during extended periods
of dry running, wash the system 2-3 times per week for
approx. 40 minutes. This is generally performed using the
CLEANING Mode in the automation. There should be no
need for washing during high EGCS usage periods.
3. Keep the water analysis rack sensors:
4 clean as dirty probes may lead to incorrect readings
4 checked for calibration using the appropriate kit
4 wet at all times to avoid the risk of failure.
4. C
arryover can cause discoloured water to land on open decks.
It is best avoided by using the recommended cold start and full
shutdown procedures when possible, and avoiding extended
periods with higher than needed wash-water flow rates.
5. In case of multiple EGCS units with common supply or
discharge lines: To avoid cross-flooding to another EGCS upon
start-up – ensure all overboard valves for all installed EGCSs are
open and cross-connects closed before starting the system.
6. The 4 regulatory limits that ships in ECAs must comply with are:
the SO2/CO2 ratio of the exhaust gas
the PAH and Turbidity differentials between Rack 2 and Rack 1
and the pH at Rack 3 (and in some cases the pH Differential
between Rack 1 and Rack 3).
6
7
4
1 2 Outlet
5
Inlet
Inlet
Gas Analyzer
Rack 2
Rack 3
Rack 1 Rack 4
Compliance
ECOSPRAY Compliance
Monitoring Ethernet/ Ethernet
Profibus/ PLC Computer
Equipment Modbus/
4..20 mA
Note 1: If the PAH or Turbidity sensors on Rack 1 fail, they will default
to a zero reading; therefore it is possible to continue to operate the
EGCS within compliance as long as the PAH and Turbidity sensors on
Rack 2 are operational.
Automatic Mode
When the system is in its standard automatic operating
mode the EGCS Automation system may be set for either
‘SETPOINT ENGINE LOAD + SO2 CORRECTION’ or only
‘SETPOINT ENGINE LOAD’:
4 Setpoint Engine Load – adjusts the wash-water flow rate
according to a programmed flow rate vs. Engine Load
4 SO2 Correction – make a fine adjustment of the wash-water
flow rate to maintain an SO2/CO2 ratio set point
Manoeuvring Mode
This mode overrides all other selected modes and immediately
adjusts SW flow to the Manoeuvre Set point rate set in
the Parameters Page. The default is 400m3/h but may vary
depending on Engine rating. If not available SET POINT
MANUAL Mode should be used.
Manual Mode
This operating mode gives the operator full control of all the major
components, e.g. SW Pump, pH Buffering Pump and SW Filter.
4
3
5
1
2