CALIBRATION CERTIFICATE Printed: 25.09.

2019 19:55:29
Printed by: Candra

Certificate Number: NIKF-16013


POSITION ID: XG57-W903_2
POSITION DEVICE
Position Name: Perokside vaporization 1-2 temperature probe Device ID: TT WG57-W903_2
SAP / AMM Number: 0227-040-496 Serial Number: N/A
Location: Combiblock 2 Manufacturer Model:
Plant Structure: Kejayan Factory/Liquid Milk Plant/UHT/Filler Combibloc
124-2/
Operational limit: Critical Limit: As per HACCP study
CALIBRATION EVENT
FUNCTION Calibration Date: 9/17/2019 1:39:04 PM
Function: Perokside vaporization 1-2 Temperature Indicator (ti) Next Cal. Date: 12/27/2019
Transfer Function: Linear Environment Temp.: 30.00 °C Humidity: 55.00 %
Range (I/O): 0.00 to 400.00 °C 0.00 to 400.00 °C
CALIBRATORS
PROCEDURE Input Calibrator: MC5 s/n: 25516203 Due Date: 1/11/2020
Due Date: 9/27/2019 Interval: 13 weeks Input Module: ET s/n: 56391 Due Date: 1/11/2020
Reject if Error >: 5.00 °C Adjust To <: 0.00 °C Output Calibrator: Due Date:
Classification: CCP Output Module: Due Date:

10.000 As Found (1)


As Left (2)
Error Limit

5.000
Output Error [°C]

0.000

-5.000

-10.000

0.00 100.00 200.00 300.00 400.00

Input [°C]

1. As Found PASSED 2. As Left PASSED


Max Error: -1.60 °C Max Error: -1.60 °C
Actual Actual Found Actual Actual Found
Input Output Error Input Output Error
[°C] [°C] [°C] [°C] [°C] [°C]
200.58 201 0 200.58 201 0
225.60 224 -2 225.60 224 -2
275.38 274 -1 275.38 274 -1
290.32 291 1 290.32 291 1

Calibration Note: No Adjustment

Calibrated by: Prepared by:


Gunawan / Instrument Engineer
9/17/2019 1:39:04 PM
CALIBRATION CERTIFICATE Printed: 25.09.2019 19:55:29
Printed by: Candra

Certificate Number: NIKF-16015


POSITION ID: XG57-W904_2
POSITION DEVICE
Position Name: Perokside vaporization 3-4 temperature probe Device ID: TT XG57-W904_2
SAP / AMM Number: 0227-040-496 Serial Number: N/A
Location: Combiblock 2 Manufacturer Model:
Plant Structure: Kejayan Factory/Liquid Milk Plant/UHT/Filler Combibloc
124-2/
Operational limit: Critical Limit: As per HACCP study
CALIBRATION EVENT
FUNCTION Calibration Date: 9/17/2019 1:41:05 PM
Function: Perokside vaporization 3-4 Temperature Indicator (ti) Next Cal. Date: 12/27/2019
Transfer Function: Linear Environment Temp.: 30.00 °C Humidity: 55.00 %
Range (I/O): 0.00 to 400.00 °C 0.00 to 400.00 °C
CALIBRATORS
PROCEDURE Input Calibrator: MC5 s/n: 25516203 Due Date: 1/11/2020
Due Date: 9/27/2019 Interval: 13 weeks Input Module: ET s/n: 56391 Due Date: 1/11/2020
Reject if Error >: 5.00 °C Adjust To <: 0.00 °C Output Calibrator: Due Date:
Classification: CCP Output Module: Due Date:

10.000 As Found (1)


As Left (2)
Error Limit

5.000
Output Error [°C]

0.000

-5.000

-10.000

0.00 100.00 200.00 300.00 400.00

Input [°C]

1. As Found PASSED 2. As Left PASSED


Max Error: -3.60 °C Max Error: -3.60 °C
Actual Actual Found Actual Actual Found
Input Output Error Input Output Error
[°C] [°C] [°C] [°C] [°C] [°C]
200.58 197 -4 200.58 197 -4
225.60 222 -4 225.60 222 -4
275.38 272 -3 275.38 272 -3
290.32 287 -3 290.32 287 -3

Calibration Note: No Adjustment

Calibrated by: Prepared by:


Gunawan / Instrument Engineer
9/17/2019 1:41:05 PM
CALIBRATION CERTIFICATE Printed: 25.09.2019 19:55:29
Printed by: Candra

Certificate Number: NIKF-16016


POSITION ID: XG57-W905_2
POSITION DEVICE
Position Name: Perokside vaporization 5-6 temperature probe Device ID: TT XG57-W905_2
SAP / AMM Number: 0227-040-496 Serial Number: N/A
Location: Combiblock 2 Manufacturer Model:
Plant Structure: Kejayan Factory/Liquid Milk Plant/UHT/Filler Combibloc
124-2/
Operational limit: Critical Limit: As per HACCP study
CALIBRATION EVENT
FUNCTION Calibration Date: 9/17/2019 1:42:32 PM
Function: Perokside vaporization 5-6 Temperature Indicator (ti) Next Cal. Date: 12/27/2019
Transfer Function: Linear Environment Temp.: 30.00 °C Humidity: 55.00 %
Range (I/O): 0.00 to 400.00 °C 0.00 to 400.00 °C
CALIBRATORS
PROCEDURE Input Calibrator: MC5 s/n: 25516203 Due Date: 1/11/2020
Due Date: 9/27/2019 Interval: 13 weeks Input Module: ET s/n: 56391 Due Date: 1/11/2020
Reject if Error >: 5.00 °C Adjust To <: 0.00 °C Output Calibrator: Due Date:
Classification: CCP Output Module: Due Date:

10.000 As Found (1)


As Left (2)
Error Limit

5.000
Output Error [°C]

0.000

-5.000

-10.000

0.00 100.00 200.00 300.00 400.00

Input [°C]

1. As Found PASSED 2. As Left PASSED


Max Error: -3.38 °C Max Error: -3.38 °C
Actual Actual Found Actual Actual Found
Input Output Error Input Output Error
[°C] [°C] [°C] [°C] [°C] [°C]
200.58 198 -3 200.58 198 -3
225.60 223 -3 225.60 223 -3
275.38 272 -3 275.38 272 -3
290.32 287 -3 290.32 287 -3

Calibration Note: No Adjustment

Calibrated by: Prepared by:


Gunawan / Instrument Engineer
9/17/2019 1:42:32 PM
CALIBRATION CERTIFICATE Printed: 25.09.2019 19:55:29
Printed by: Candra

Certificate Number: NIKF-16012


POSITION ID: XW20-W903-B3_2
POSITION DEVICE
Position Name: Swivel coupling 1-2 temperature probe Device ID: TT XW20-W903-B3_2
SAP / AMM Number: 0227-040-495 Serial Number: N/A
Location: Combiblock 2 Manufacturer Model:
Plant Structure: Kejayan Factory/Liquid Milk Plant/UHT/Filler Combibloc
124-2/
Operational limit: Critical Limit: As per HACCP study
CALIBRATION EVENT
FUNCTION Calibration Date: 9/17/2019 1:32:53 PM
Function: Swivel coupling 1-2 Temperature Indicator (ti) Next Cal. Date: 12/27/2019
Transfer Function: Linear Environment Temp.: 25.00 °C Humidity: 60.00 %
Range (I/O): 0.00 to 200.00 °C 0.00 to 200.00 °C
CALIBRATORS
PROCEDURE Input Calibrator: MC4 s/n: 50254 Due Date: 8/15/2019
Due Date: 9/27/2019 Interval: 13 weeks Input Module: Due Date:
Reject if Error >: 2.00 °C Adjust To <: 0.00 °C Output Calibrator: MC4 s/n: 50254 Due Date: 8/15/2019
Classification: CCP Output Module: Due Date:

4.000 As Found (1)


As Left (2)
Error Limit

2.000
Output Error [°C]

0.000

-2.000

-4.000

0.00 50.00 100.00 150.00 200.00

Input [°C]

1. As Found PASSED 2. As Left PASSED


Max Error: -1.17 °C Max Error: -1.17 °C
Actual Actual Found Actual Actual Found
Input Output Error Input Output Error
[°C] [°C] [°C] [°C] [°C] [°C]
99.95 99 -1 99.95 99 -1
115.08 115 0 115.08 115 0
125.01 125 0 125.01 125 0
140.11 140 0 140.11 140 0
145.17 144 -1 145.17 144 -1
150.10 150 0 150.10 150 0

Calibration Note: NO ADJUSTMENT

Calibrated by: Prepared by:


Candra / Instrument Engineer
9/17/2019 1:32:53 PM
CALIBRATION CERTIFICATE Printed: 25.09.2019 19:55:29
Printed by: Candra

Certificate Number: NIKF-16014


POSITION ID: XW20-W904-B4_2
POSITION DEVICE
Position Name: Swivel coupling 3-4 temperature probe Device ID: TT XW20-W904-B4_2
SAP / AMM Number: 0227-040-495 Serial Number: N/A
Location: Combiblock 2 Manufacturer Model:
Plant Structure: Kejayan Factory/Liquid Milk Plant/UHT/Filler Combibloc
124-2/
Operational limit: Critical Limit: As per HACCP study
CALIBRATION EVENT
FUNCTION Calibration Date: 9/17/2019 1:37:57 PM
Function: Swivel coupling 3-4 Temperature Indicator (ti) Next Cal. Date: 12/27/2019
Transfer Function: Linear Environment Temp.: 25.00 °C Humidity: 60.00 %
Range (I/O): 0.00 to 200.00 °C 0.00 to 200.00 °C
CALIBRATORS
PROCEDURE Input Calibrator: MC4 s/n: 50254 Due Date: 8/15/2019
Due Date: 9/27/2019 Interval: 13 weeks Input Module: Due Date:
Reject if Error >: 2.00 °C Adjust To <: 0.00 °C Output Calibrator: MC4 s/n: 50254 Due Date: 8/15/2019
Classification: CCP Output Module: Due Date:

4.000 As Found (1)


As Left (2)
Error Limit

2.000
Output Error [°C]

0.000

-2.000

-4.000

0.00 50.00 100.00 150.00 200.00

Input [°C]

1. As Found PASSED 2. As Left PASSED


Max Error: -1.17 °C Max Error: -1.17 °C
Actual Actual Found Actual Actual Found
Input Output Error Input Output Error
[°C] [°C] [°C] [°C] [°C] [°C]
99.95 99 -1 99.95 99 -1
115.08 114 -1 115.08 114 -1
125.01 124 -1 125.01 124 -1
140.11 140 0 140.11 140 0
145.17 144 -1 145.17 144 -1
150.10 150 0 150.10 150 0

Calibration Note: NO ADJUSTMENT

Calibrated by: Prepared by:


Candra / Instrument Engineer
9/17/2019 1:37:57 PM
CALIBRATION CERTIFICATE Printed: 25.09.2019 19:55:29
Printed by: Candra

Certificate Number: NIKF-16017


POSITION ID: XW20-W906-B6_2
POSITION DEVICE
Position Name: Swivel coupling 5-6 temperature probe Device ID: TT XW20-W906-B6_2
SAP / AMM Number: 0227-040-495 Serial Number: N/A
Location: Combiblock 2 Manufacturer Model:
Plant Structure: Kejayan Factory/Liquid Milk Plant/UHT/Filler Combibloc
124-2/
Operational limit: Critical Limit: As per HACCP study
CALIBRATION EVENT
FUNCTION Calibration Date: 9/17/2019 1:42:26 PM
Function: Swivel coupling 5-6 Temperature Indicator (ti) Next Cal. Date: 12/27/2019
Transfer Function: Linear Environment Temp.: 25.00 °C Humidity: 60.00 %
Range (I/O): 0.00 to 200.00 °C 0.00 to 200.00 °C
CALIBRATORS
PROCEDURE Input Calibrator: MC4 s/n: 50254 Due Date: 8/15/2019
Due Date: 9/27/2019 Interval: 13 weeks Input Module: Due Date:
Reject if Error >: 2.00 °C Adjust To <: 0.00 °C Output Calibrator: Due Date:
Classification: CCP Output Module: Due Date:

4.000 As Found (1)


As Left (2)
Error Limit

2.000
Output Error [°C]

0.000

-2.000

-4.000

0.00 50.00 100.00 150.00 200.00

Input [°C]

1. As Found PASSED 2. As Left PASSED


Max Error: -1.11 °C Max Error: -1.11 °C
Actual Actual Found Actual Actual Found
Input Output Error Input Output Error
[°C] [°C] [°C] [°C] [°C] [°C]
99.95 99 -1 99.95 99 -1
115.08 115 0 115.08 115 0
125.01 125 0 125.01 125 0
140.11 139 -1 140.11 139 -1
145.17 145 0 145.17 145 0
150.10 149 -1 150.10 149 -1

Calibration Note: NO ADJUSTMENT

Calibrated by: Prepared by:


Candra / Instrument Engineer
9/17/2019 1:42:26 PM
CALIBRATION CERTIFICATE Printed: 25.09.2019 19:55:29
Printed by: Candra

Certificate Number: NIKF-16020


POSITION ID: XW20-W905-B5_2
POSITION DEVICE
Position Name: Steam barrier temperature probe Device ID: TT XW20-W905-B5_2
SAP / AMM Number: 0227-040-495 Serial Number: N/A
Location: Combiblock 2 Manufacturer Model:
Plant Structure: Kejayan Factory/Liquid Milk Plant/UHT/Filler Combibloc
124-2/
Operational limit: Critical Limit: As per HACCP study
CALIBRATION EVENT
FUNCTION Calibration Date: 9/17/2019 1:49:59 PM
Function: Steam barrier Temperature Indicator (ti) Next Cal. Date: 12/27/2019
Transfer Function: Linear Environment Temp.: 25.00 °C Humidity: 60.00 %
Range (I/O): 0.00 to 200.00 °C 0.00 to 200.00 °C
CALIBRATORS
PROCEDURE Input Calibrator: MC4 s/n: 50254 Due Date: 8/15/2019
Due Date: 9/27/2019 Interval: 13 weeks Input Module: Due Date:
Reject if Error >: 2.00 °C Adjust To <: 0.00 °C Output Calibrator: Due Date:
Classification: CCP Output Module: Due Date:

4.000 As Found (1)


As Left (2)
Error Limit

2.000
Output Error [°C]

0.000

-2.000

-4.000

0.00 50.00 100.00 150.00 200.00

Input [°C]

1. As Found PASSED 2. As Left PASSED


Max Error: -1.17 °C Max Error: -1.17 °C
Actual Actual Found Actual Actual Found
Input Output Error Input Output Error
[°C] [°C] [°C] [°C] [°C] [°C]
99.95 99 -1 99.95 99 -1
115.08 115 0 115.08 115 0
125.01 125 0 125.01 125 0
140.11 140 0 140.11 140 0
145.17 144 -1 145.17 144 -1
150.10 150 0 150.10 150 0

Calibration Note: NO ADJUSTMENT

Calibrated by: Prepared by:


Candra / Instrument Engineer
9/17/2019 1:49:59 PM
CALIBRATION CERTIFICATE Printed: 25.09.2019 19:55:29
Printed by: Candra

Certificate Number: NIKF-16019


POSITION ID: XW35-W901-B1_2
POSITION DEVICE
Position Name: PAL Filter temperature probe Device ID: TT XW35-W901-B1_2
SAP / AMM Number: 0227-040-495 Serial Number: N/A
Location: Combiblock 2 Manufacturer Model:
Plant Structure: Kejayan Factory/Liquid Milk Plant/UHT/Filler Combibloc
124-2/
Operational limit: Critical Limit: As per HACCP study
CALIBRATION EVENT
FUNCTION Calibration Date: 9/17/2019 1:45:50 PM
Function: PAL Filter Temperature Indicator (ti) Next Cal. Date: 12/27/2019
Transfer Function: Linear Environment Temp.: 25.00 °C Humidity: 60.00 %
Range (I/O): 0.00 to 200.00 °C 0.00 to 200.00 °C
CALIBRATORS
PROCEDURE Input Calibrator: MC4 s/n: 50254 Due Date: 8/15/2019
Due Date: 9/27/2019 Interval: 13 weeks Input Module: Due Date:
Reject if Error >: 2.00 °C Adjust To <: 0.00 °C Output Calibrator: Due Date:
Classification: CCP Output Module: Due Date:

4.000 As Found (1)


As Left (2)
Error Limit

2.000
Output Error [°C]

0.000

-2.000

-4.000

0.00 50.00 100.00 150.00 200.00

Input [°C]

1. As Found PASSED 2. As Left PASSED


Max Error: -1.17 °C Max Error: -1.17 °C
Actual Actual Found Actual Actual Found
Input Output Error Input Output Error
[°C] [°C] [°C] [°C] [°C] [°C]
99.95 99 -1 99.95 99 -1
115.08 115 0 115.08 115 0
125.01 125 0 125.01 125 0
140.11 139 -1 140.11 139 -1
145.17 144 -1 145.17 144 -1
150.10 150 0 150.10 150 0

Calibration Note: NO ADJUSTMENT

Calibrated by: Prepared by:


Candra / Instrument Engineer
9/17/2019 1:45:50 PM
CALIBRATION CERTIFICATE Printed: 25.09.2019 19:55:29
Printed by: Candra

Certificate Number: NIKF-16018


POSITION ID: XS54-W901_2
POSITION DEVICE
Position Name: Over press of aseptic zone pressure transmitter Device ID: PT 27823101005
SAP / AMM Number: 0227-040-496 Serial Number: 27823101005
Location: Combibloc 2 Manufacturer Model: Beck Gmbh Senswitch Display P2
Plant Structure: Kejayan Factory/Liquid Milk Plant/UHT/Filler Combibloc
124-2/
Operational limit: Critical Limit: As per HACCP study
CALIBRATION EVENT
FUNCTION Calibration Date: 9/17/2019 1:44:05 PM
Function: Over press of aseptic zone Pressure Indicator (pi) Next Cal. Date: 12/27/2019
Transfer Function: Linear Environment Temp.: 30.00 °C Humidity: 55.00 %
Range (I/O): 0.00 to 100.00 mbar (G) 0.00 to 100.00 mbar (G)
CALIBRATORS
PROCEDURE Input Calibrator: MC5 s/n: 25516203 Due Date: 1/11/2020
Due Date: 9/27/2019 Interval: 13 weeks Input Module: INT2C s/n: 49025 Due Date: 1/11/2020
Reject if Error >: 1.00 % of span Adjust To <: 0.00 % of span Output Calibrator: Due Date:
Classification: NCP Output Module: Due Date:

2.000 As Found (1)


As Left (2)
Error Limit
Output Error [% of span]

1.000

0.000

-1.000

-2.000

0.00 25.00 50.00 75.00 100.00

Input [mbar]

1. As Found PASSED 2. As Left PASSED


Max Error: -0.08 % of span Max Error: -0.08 % of span
Actual Actual Found Actual Actual Found
Input Output Error Input Output Error
[mbar] [mbar] [% of span] [mbar] [mbar] [% of span]
0.00 0.0 0.00 0.00 0.0 0.00
10.05 10.0 -0.05 10.05 10.0 -0.05
20.03 20.0 -0.03 20.03 20.0 -0.03
30.08 30.0 -0.08 30.08 30.0 -0.08
40.01 40.0 -0.01 40.01 40.0 -0.01
50.06 50.0 -0.06 50.06 50.0 -0.06

Calibration Note: No Adjustment

Calibrated by: Prepared by:


Gunawan / Instrument Engineer
9/17/2019 1:44:05 PM

Potrebbero piacerti anche