Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
– Original –
Technical Documentation
Wind Turbine Generator Systems
3 MW Platform - 50/60Hz
Grid Interconnection
Applicable for Wind Turbine Generators from 3.4 MW to 3.8 MW
imagination at work
© 2016 General Electric Company. All rights reserved.
GE Renewable Energy
– Original –
www.gepower.com
Visit us at
https://renewables.gepower.com
This document is to be treated confidentially. It may only be made accessible to authorized persons. It may
only be made available to third parties with the expressed written consent of General Electric Company.
All documents are copyrighted within the meaning of the Copyright Act. The transmission and reproduction of
the documents, also in extracts, as well as the exploitation and communication of the contents are not allowed
without express written consent. Contraventions are liable to prosecution and compensation for damage. We
reserve all rights for the exercise of commercial patent rights.
Other company or product names mentioned in this document may be trademarks or registered trademarks of
their respective companies.
imagination at work
Grid_Interconnection_Documents_3.4-3.8-DFIG-xxHz_3MW_IEC_EN_r03.docx.
GE Renewable Energy
– Original –
Grid Interconnection
Table of Contents
1 Introduction.................................................................................................................................................................................................................. 5
2 Technology ................................................................................................................................................................................................................... 5
3 Turbine Transformer ............................................................................................................................................................................................... 5
4 Frequency Tolerance .............................................................................................................................................................................................. 6
5 Voltage Tolerance & Fault Ride-Thru ............................................................................................................................................................. 6
6 Protection ...................................................................................................................................................................................................................... 7
7 Minimum Grid Strength ......................................................................................................................................................................................... 7
8 Reactive Power Capability ................................................................................................................................................................................... 8
9 WindFREE Reactive Power ................................................................................................................................................................................... 8
10 Wind Inertia ............................................................................................................................................................................................................ 8
11 Plant Level Control and Voltage Regulation ......................................................................................................................................... 9
12 Harmonic Distortion........................................................................................................................................................................................... 9
12.1 IEEE 60 Hz Harmonic Distortions........................................................................................................................................................... 9
12.2 IEC 50Hz Harmonics Distortion ........................................................................................................................................................... 10
13 System Modeling .............................................................................................................................................................................................. 10
13.1 Wind Turbine Short Circuit Modeling ............................................................................................................................................... 10
13.2 Wind Turbine Dynamic Modeling ....................................................................................................................................................... 10
13.3 Wind Turbine Transient Modeling ...................................................................................................................................................... 10
13.4 Wind Dynamic Model Validation ........................................................................................................................................................ 10
13.5 Wind Turbine Transient Model Validation ..................................................................................................................................... 11
14 Power Demand .................................................................................................................................................................................................. 11
Appendix I – General Data (reference only) ....................................................................................................................................................... 12
Appendix II – Active/Reactive Power Capability Curves 3.4 ...................................................................................................................... 13
Appendix III - Active/Reactive Power Capability Curves 3.6 ..................................................................................................................... 14
Appendix IV - Active/Reactive Power Capability Curves 3.8 ..................................................................................................................... 15
Appendix VI – WindRIDE-THRU ................................................................................................................................................................................. 16
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company.
UNCONTROLLED when printed or transmitted electronically.
© 2016 General Electric Company. All rights reserved
Grid_Interconnection_Documents_3.4-3.8-DFIG-xxHz_3MW_IEC_EN_r03.docx x
GE Renewable Energy
– Original –
Grid Interconnection
1 Introduction
This document is intended to describe the electrical specifications of the 3 MW Platform wind turbines and
highlight common topics related to grid interconnection and applicable for:
3.4-130
3.6-137
3.8-130
2 Technology
The 3 MW Platform wind turbine is variable speed and employs a doubly fed induction generator with a partial
power converter interfacing to the grid.
Unless stated otherwise, all the data shown is based on the secondary connection of the Wind Turbine
Generator System (WTGS) transformer (6000 V and 690 V connections).
3 Turbine Transformer
Each wind turbine should be connected through a three-winding step-up transformer to the MV wind farm
collection system.
If the turbine transformer is not supplied by GE it should comply with the general specifications as follows:
For additional details on transformer not supplied by GE, refer to the GE padmount specification.
Permanent changes to the steady state voltage at the LV terminals due to changes of the MV level in the grid
or collector system may result in a reduction of the active and reactive power range or even in a turbine trip. If
such a permanent change is desired, a turbine transformer tap changer can be used, which usually offer
+/- 2 x 2.5 % voltage change. If greater change in voltage is required a different transformer should be
selected. Additionally, changes to steady state voltages can be addressed utilizing the substation transformer
where applicable.
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company.
UNCONTROLLED when printed or transmitted electronically.
© 2016 General Electric Company. All rights reserved
Grid_Interconnection_Documents_3.4-3.8-DFIG-xxHz_3MW_IEC_EN_r03.docx 5/16
GE Renewable Energy
– Original –
Grid Interconnection
4 Frequency Tolerance
The 3 MW Platform wind turbine is capable of operating within the following frequencies and for the
corresponding time durations:
50Hz Frequency Range (Hz) 60Hz Frequency Range (Hz) Time Duration(s)
47.0 – 53.0 57.0 - 63.0 Continuous
Where requested the Seller is also able to extend this fault ride through capability with the zero-voltage ride-
thru (ZVRT) optional feature described below.
The voltages in Table 2 are referenced to the turbine transformer high side voltage (e.g.: 30 kV)
Time (s)
Dynamic Voltage Range (%)
LVRT ZVRT
130 – 180 Capacitor switching transients1
110 – 115 1
90 - 110 Continuous
85 - 90 600
75 - 85 10
70 - 75 3
20 – 70 1.0 – 3.02
0.5 – 3.03 4
0 – 20
1 A specific waveform based on field experience has been used to represent transients while evaluating capability against capacitor switch
transients ride through capability
2 Linear behavior between 20% with up to 1s and 70 % with up to 3 s
3 The converter will stop pulsing after 200 ms. No control of reactive power during initial voltage recovery.
4 Linear behavior between 0% with up to 500 ms and 70 % with up to 3 s
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company.
UNCONTROLLED when printed or transmitted electronically.
© 2016 General Electric Company. All rights reserved
6/16 Grid_Interconnection_Documents_3.4-3.8-DFIG-xxHz_3MW_IEC_EN_r03.docx
GE Renewable Energy
– Original –
Grid Interconnection
6 Protection
The GE wind turbine has the following built-in protection functions:
Additionally, the medium voltage breaker located on the controller level at the bottom of the tower provides
overcurrent protection (51) and includes configurable instantaneous, short-time and long-time settings.
These functions are designed to offer a level of protection to the wind turbine hardware from disturbances
caused by the electrical system.
The Seller strongly recommends protecting the MV system against transient and temporary overvoltage, which
are caused by:
The customer is resposible for overvoltage mitigation actions on the MV system. Grounding transformers,
automatic grounding switches on the feeder breakers or special surge arrester configurations will be required
to prevent MV overvoltages when the feeder breakers are opened and the MV system loses its ground
reference at the substation.
Note that the CSCR capability of 2.5 is determined based on a broad set of operating points, network
parameters and grid contingencies. However, the turbines can operate at CSCR values that are much lower
depending on evaluation of actual condition associated with the wind farm. The evaluation of operation at low
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company.
UNCONTROLLED when printed or transmitted electronically.
© 2016 General Electric Company. All rights reserved
Grid_Interconnection_Documents_3.4-3.8-DFIG-xxHz_3MW_IEC_EN_r03.docx 7/16
GE Renewable Energy
– Original –
Grid Interconnection
CSCR values is typically based on transient simulations of the network considering a range of operating points,
network parameters and grid contingencies, which differ from project to project. If a grid operator has a
concern on the short circuit ratio, GE can provide a black box PSCAD model of the wind farm that can be used
for transient simulations of the network for the purpose of determining expected performance. If a grid
operator decides to perform such a study, it is essential that GE be involved to highlight how changes within
the product capability can achieve the desired performance. Alternatively, If the grid operator can define the
requirements for such a study and is willing to provide GE with the details of the network, then GE Energy
Consulting can be contracted to perform the study.
Arc flash requirements necessitate a minimum short circuit MVA of 33 at the turbine medium voltage (MV)
terminals.
An option for expanded reactive power capability 0.90 leading to 0.90 lagging under derated conditions is
available upon request. An option for expanded reactive power capability 0.87 leading to 0.87 lagging under
derated conditions is available upon request for 50 Hz only. This wider reactive power capability could help
meet a 0.95 power factor requirement at the point of interconnection if required. Please refer to Appendix II; III
and IV for the reactive power capability of the 3.4 MW, 3.6 MW and 3.8 MW machines. Note that the reactive
power capability may be affected in Noise reduced operation (NRO) modes.
10 Wind Inertia
With the optional “WindINERTIA” feature, the 3 MW Platform wind turbine generator can provide inertial
response to help stabilize grid frequency. This feature supports the grid during under frequency events by
providing a temporary increase in power production (6-7 %) increase in kW) for a short duration (10 sec),
contributing towards frequency recovery. This is achieved by tapping into the stored kinetic energy in the rotor
mass. The response is equivalent to that of a synchronous generator with an inertia constant of 3.5 sec.
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company.
UNCONTROLLED when printed or transmitted electronically.
© 2016 General Electric Company. All rights reserved
8/16 Grid_Interconnection_Documents_3.4-3.8-DFIG-xxHz_3MW_IEC_EN_r03.docx
GE Renewable Energy
– Original –
Grid Interconnection
WindCONTROL is available with the following optional grid friendly features (see WindCONTROL overview for
more info):
12 Harmonic Distortion
Harmonic distortion data for respective 50 Hz and 60 Hz machines are presented relevant to IEEE and IEC
requirements.
Voltage @ Current
h < 11 11 ≤ h < 17 17 ≤ h < 23 23 ≤ h < 35 h ≥ 35
PCC TDD%
V ≤ 69 kV 4.0 2.0 1.5 0.6 0.3 5.0
Table 3: IEEE Current Distortion Limits
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company.
UNCONTROLLED when printed or transmitted electronically.
© 2016 General Electric Company. All rights reserved
Grid_Interconnection_Documents_3.4-3.8-DFIG-xxHz_3MW_IEC_EN_r03.docx 9/16
GE Renewable Energy
– Original –
Grid Interconnection
Switching procedures: the 3 MW Platform wind turbine does not have any significant in-rush kmax = Imax/InG = 1
(parameter as per IEC 61400-21).
13 System Modeling
13.1 Wind Turbine Short Circuit Modeling
The 3 MW Platform wind turbine generator is a doubly-fed asynchronous generator with the stator directly
connected to the grid while the rotor is interfaced through a frequency converter to the grid. For most faults
that occur on the grid, the turbine will act as a controlled current source- contributing up to 3 per unit fault
current for up to 5 cycles, after which it returns to normal current contribution (i.e. 1 per unit). For faults on the
grid, the contribution from the turbines is minimal compared to that from the grid.
One exception is for “close in” faults (e.g.: inside the wind farm, at the wind farm substation etc.) where,
depending on the severity, the converter may “crowbar” (i.e. disconnect itself to protect the power electronics
within). In this case the turbine rotor is short circuited like that of a squirrel cage induction generator. The
behavior can be approximated to X’ = 0.2, contributing a max of 5 per unit fault current.
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company.
UNCONTROLLED when printed or transmitted electronically.
© 2016 General Electric Company. All rights reserved
10/16 Grid_Interconnection_Documents_3.4-3.8-DFIG-xxHz_3MW_IEC_EN_r03.docx
GE Renewable Energy
– Original –
Grid Interconnection
14 Power Demand
The Power demand of the wind turbine generator system during calm wind periods can include of the yaw
rotor, control system, lighting and hydraulic pump and amount to a maximum 50 kW if all loads are operating
at the same time.
The annual energy demand at a site with rated average wind speed is 5000 to 12000 kWhr/annum per turbine
unit.
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company.
UNCONTROLLED when printed or transmitted electronically.
© 2016 General Electric Company. All rights reserved
Grid_Interconnection_Documents_3.4-3.8-DFIG-xxHz_3MW_IEC_EN_r03.docx 11/16
GE Renewable Energy
– Original –
Grid Interconnection
Parameter 50 60 50 60 50 60 Hz
Rated Voltage
690/6000 V
(Rotor/Stator)
Apparent Power
3610 3821 4031 kVA
(@ PF = 0.95 lag)
5Enhanced power factor of 0.9 is available as an option - 0.87 as an option for the 50 Hz variant.
620 kA at -30 °C internal ambient temperature while the WTGS is connected to the grid. MVSG will be disconnected from grid
automatically during cold soak for ambient temperatures below -30 °C.
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company.
UNCONTROLLED when printed or transmitted electronically.
© 2016 General Electric Company. All rights reserved
12/16 Grid_Interconnection_Documents_3.4-3.8-DFIG-xxHz_3MW_IEC_EN_r03.docx
GE Renewable Energy
– Original –
Grid Interconnection
When the plant level controller is in the voltage control or in the VAR control mode, and derating is required
due to the conditions listed above, the turbines will operate with a Q priority i.e they will sacrifice active power
if necessary to meet the reactive power demand up to the listed capability.
When the turbines are operating in the power factor control mode, their capability is shown by the dotted lines.
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company.
UNCONTROLLED when printed or transmitted electronically.
© 2016 General Electric Company. All rights reserved
Grid_Interconnection_Documents_3.4-3.8-DFIG-xxHz_3MW_IEC_EN_r03.docx 13/16
GE Renewable Energy
– Original –
Grid Interconnection
When the plant level controller is in the voltage control or in the VAR control mode, and derating is required
due to the conditions listed above, the turbines will operate with a Q priority i.e they will sacrifice active power
if necessary to meet the reactive power demand up to the listed capability.
When the turbines are operating in the power factor control mode, their capability is shown by the dotted lines.
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company.
UNCONTROLLED when printed or transmitted electronically.
© 2016 General Electric Company. All rights reserved
14/16 Grid_Interconnection_Documents_3.4-3.8-DFIG-xxHz_3MW_IEC_EN_r03.docx
GE Renewable Energy
– Original –
Grid Interconnection
When the plant level controller is in the voltage control or in the VAR control mode, and derating is required
due to the conditions listed above, the turbines will operate with a Q priority i.e they will sacrifice active power
if necessary to meet the reactive power demand up to the listed capability.
When the turbines are operating in the power factor control mode, their capability is shown by the dotted lines.
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company.
UNCONTROLLED when printed or transmitted electronically.
© 2016 General Electric Company. All rights reserved
Grid_Interconnection_Documents_3.4-3.8-DFIG-xxHz_3MW_IEC_EN_r03.docx 15/16
GE Renewable Energy
– Original –
Grid Interconnection
Appendix VI – WindRIDE-THRU
Figure 4: WindRIDE-THRU
NOTE
This plot represents the standard settings for LVRT and ZVRT which meet most grid codes.
This does not represent the complete capability of these features.
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company.
UNCONTROLLED when printed or transmitted electronically.
© 2016 General Electric Company. All rights reserved
16/16 Grid_Interconnection_Documents_3.4-3.8-DFIG-xxHz_3MW_IEC_EN_r03.docx