ENGLISH Quick Start Guide - ATV12

S1A5614601
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Read and understand this quick start guide before performing any procedure with this drive.
• The user is responsible for compliance with all international and national electrical code requirements with respect to grounding of all
equipment.
• Many parts of this drive, including the printed circuit boards, operate at the line voltage. DO NOT TOUCH. Use only electrically insulated tools.
• DO NOT touch unshielded components or terminal strip screw connections with voltage present.
• DO NOT short across terminals PA/+ and PC/- or across the DC bus capacitors.
• Before servicing the drive:
- Disconnect all power, including external control power that may be present.
- Place a "DO NOT TURN ON" label on all power disconnects.
- Lock all power disconnects in the open position.
- WAIT 15 MINUTES to allow the DC bus capacitors to discharge.
- Measure the voltage of the DC bus between the PA/+ and PC/- terminals to ensure that the voltage is less than 42 Vdc.
- If the DC bus capacitors do not discharge completely, contact your local Schneider Electric representative. Do not repair or operate
the drive
• Install and close all covers before applying power or starting and stopping the drive.
Failure to follow these instructions will result in death or serious injury.

Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider
Electric for any consequences arising out of the use of this product.

Information below is designed to use single drive connected to single motor with a motor cable length less than 50 meters (164 ft).
In any other case, consult the ATV12 user manual on www.schneider-electric.com.
Check your cables before connecting the drive with motor (length, power, shielded or unshielded). Motor cable length is _______(< 50 meters, 164 ft)

1 Check the delivery of the drive


• Remove ATV12 from the packaging and check that it has not been damaged.

WARNING
DAMAGED DRIVE EQUIPMENT
Do not operate or install any drive or drive accessory that appears damaged.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

• Check that the drive reference printed on the label is the same as that on the delivery note corresponding to the
purchase order. ATV12HU15M2
1.5KW - 2HP - 200 / 240V

Write the drive Model Reference: _____________ ___________and Serial Number: ____________________________

2 Check the line voltage compatibility


8B0915316127
• Check that the line voltage is compatible with the supply range of the drive.
Line voltage _______ Volts Drive voltage range _______ Volts
Drive range: ATV12 F1 = 100 ... 120 V single phase / ATV12 M2=200 ... 240 V single phase / ATV12 M3 = 200 ... 240 V three-phase.

3 Mount the drive vertically


For a surrounding air temperature up to 50 °C (122 °F)
(a)

(a) (a)

(b)
(a)

(a) 50 mm (2 in.) (b) 10 mm (0.4 in.)

See user manual on www.schneider-electric.com for other thermal conditions.

www.schneider-electric.com 1/4 S1A56146 - 05/2010


4 Connect the drive: Power Connect the drive:
5
• Wire the drive to the ground.
• Check circuit breaker rating or fuse rating. Control choice
• Check that the motor voltage is compatible with the drive voltage.
Motor voltage ______Volts. [REMOTE configuration]
• Wire the drive to the motor. 5.1 (Control by external reference)
• Wire the drive to the line supply.
• Wire the speed reference:

AI 1

COM
+5v
Do: 6 + 7 + 8 + 9.1

or
ATV12F1 2.2 KΩ

• Wire the command:


Control command 2-wire:
ATV12M2 Parameter tCC = 2C

LI1: forward ATV 12


LIx: reverse
+24 V LI1 LIx Do: 6 + 7 + 8 + 9.1
ATV12M3

Control command 3-wire:


Parameter tCC = 3C
LI1: stop ATV 12
0,8...1,2 N.m 6 + 7 + 8 + 9.1
LI2: forward Do:
7.1...10.6 lb.in +24 V LI1 LI2 LIx
LIx: reverse

200...240V

[LOCAL configuration]
5.2 (control by internal reference).
.
Do: 6 + 7 + 8 + 9.2

6 Apply power to the drive


• Check that used Logic Inputs are not active (see Li1, Li2, Lix ).
• Apply power to the drive.
• Drive displays bFr at first power up.
• On next start-ups, drive displays rdY .

7 Set motor parameters


• See on the motor Nameplate to set the following parameters.
Customer
Menu Code Description Factory setting
setting
[Standard motor frequency]:
bFr 50.0
COnF > FULL > Standard motor frequency (Hz)
drC- [Rated motor power]:
nPr drive rating
[Motor control menu] Nominal motor power on motor nameplate
[Rated motor current]:
nCr drive rating
Nominal motor current on motor nameplate (A)

8 Set basic parameters


Customer
Menu Code Description Factory setting
setting
[Acceleration]:
ACC 3.0
Acceleration time (s)
[Deceleration]:
dEC 3.0
COnF Deceleration time (s)
[CONFIGURATION] [Low speed]:
LSP 0.0
Motor frequency at minimum reference (Hz)
[High speed]:
HSP 50.0
Motor frequency at maximum reference (Hz)

www.schneider-electric.com 2/4 S1A56146 - 05/2010


9 Set control choice
Menu Code Description 5.1 [REMOTE configuration] 5.2 [LOCAL configuration] Customer Setting
COnF > FULL >
[Reference channel1]:
Ctl- Fr1 Al1 AlU1
Reference control
[Control menu]
COnF > FULL >
[Type of control]: 2C: 2-wire control
I_0- tCC _
Command control 3C: 3-wire control
[Input Output menu]

9.1 [REMOTE configuration] 9.2 [LOCAL configuration]


(configuration factory setting)

Parameters factory settings: Parameters factory settings:


Fr1 = AI1 Fr1 = AIU1
tCC = 2C
MODE

3s
LOC rdY

35.
1

[Analog input virtual] (Hz)

10 Start the motor

www.schneider-electric.com 3/4 S1A56146 - 05/2010


Menus structure

[REMOTE configuration] [LOCAL configuration]


MODE
ESC
3s LOC
rdY 2s rdY
rEN
MODE ESC ENT

3s
35. [Analog input virtual] (Hz)

ESC ESC
ESC

rEF MODE MOn MODE COnF MODE

[SPEED REFERENCE] [MONITORING] [CONFIGURATION]

rEF MOn COnF

ESC
(2) 0 HErt
2s / ESC

(1) ENT bFr 50

Fr1 AI1
ESC (2) 0.
0
2s / ESC
ACC 3 SEC
2s / ESC
ENT Frh 0 HErt
51.
3 HErt 2s / ESC dEC 3 SEC
2s / ESC
2s / ESC
rFr 0.
0 HErt
LSP 0 HErt
(1) LFr 2s / ESC
2s / ESC
AIU1
LCr 0.
0 AMP HSp 50 HErt
FrH 2s / ESC 2s / ESC

rPI nPr
rPE At
rPC 2s / ESC
2s / ESC
nCr AMP
2s / ESC
rPF
2s / ESC
AI1t 5U
rPC
2s / ESC SCS

2s / ESC
FCS

CFG
2s / ESC

I_0-
2s / ESC
drC-

2s / ESC
CtL-
rdY
FUn-

(2) LFr FLt-


AIU1
COd (2) LFr CON-
AIU1

Refer to the user manual for comprehensive menu description.

A dash appears after menu codes to differentiate them from parameter codes.
Example: [Motor control menu] (drC-), bFr parameter.

www.schneider-electric.com 4/4 S1A56146 - 05/2010