12 kV, 40 kA
Arc guard system™ TVOC-2
Arc incident reasons
Mechanical
fault 2 Contact elements misaligned or worn
– During an arc flash event – For selectivity reasons a time delay is often put into the
• After an initial small increase of the current the arc itself will breaker. Such a delay can be from 100ms and upwards before
act as a resistor limiting further current increase. the breaker even starts to open.
So even if the breaker might for some reason detect an
• The threshold of short circuit protection needs to be high overcurrent, the breaker will open by the time the copper
enough to take into account that power spikes might occur. components have started to burn.
– This will result in that the breaker is very unlikely to detect the
arc through the short circuit protection
– During an arc flash event in closed cabinet – With the door open during work inside the switchgear the
• Directs the energy in less harmful direction energy will be directed outward.
• Contains the damage to only a portion of the switchgear – Downtime will still be extensive since all the equipment inside
the afflicted cubicle will be destroyed.
– Since incident energy calculations have to be done taking worst
case scenario into account (door open) there will be no
lowering the energy thanks to arc resistance
Arc resistant switchgear will not replace the need for TVOC-2
TVOC-2 is the only optical arc flash mitigation device with SIL-2 in the market
• A measure of safety system performance in terms of Probability of Failure on Demand (PFD), established to define a
metric for evaluating a system’s (or function’s) level of operational reliability with regards to maintaining safety
-03
• TVOC-2 is certified with a PFD of 3.49 x 10 (0.00349) per year for a period of 10 years after it is first connected (as
long as suggested maintenance is performed according to recommended intervals)
60W at 2 cm
Trip level
Facts
Specification
Overview