Sei sulla pagina 1di 4

Qurayyah Independent Power Project

Document Transmittal

Vendor name : WETICO-WATER & ENVIRONMENT Date : 17-Dec-2012


Address : ALNAHDA ROAD , RIYADH Transmittal No. QIPP-MPN013-SCT-VD-0128
SAUDI ARABIA No. of Pages : 2

Attention : Mr. HYOJIN BAEK / Project Engineer


Cc : Mr. SAENGGON KIM / Project Manager

Ref. No. :

Attached drawing and / or documents are provided for Approval

Issued for Dwg / Doc No. Sht Rev Title


IFA QIPP-MPN013-M00-2302 1 D Piping Tie-In Points List

Mohamed El-Dardiry
Project Manager
WETICO
For Approval

D IFA 17-Dec-12 Piping Tie-In Points List HM MD ABK


Prepared Reviewed Approved
Rev Purpose Issue Date Description
by: by: by:
Owner:

HAJR Electricity Production Company

Contractor:

Sub Contractor:

Project:

Qurayyah Independent Power Project

Document Title:

DESAL/DEMIN WATER TREATMENT PLANT


PIPING TIE-IN POINTS LIST

Document No.: QIPP-MPN013-M00-2302

Owner’s Document No.:


(QIPP-MPN013-M00-2302) TIE-IN POINT LIST FOR QURAYYAH IPP rev D

Design / Elevation
Design working Ref. to P&ID
Material from ground
T.P NO. Location Pipe line TAG No. T.P Connection T.P Rating Pipe Size *C (BAR) QIPP-MPN013- COOR. E COOR. N Remarks rev.
Spec. Temp. Pressure M00-0100
to center
System line

Horizantal to ground level


Inlet line to DAF system from make up towords desal. Plant
T.P-1 GAF50-BR001-450-GRP Flange (FF) ANSI B16.5 Class # 150 GRP DN450 18" 18-60 6 1/9 2587.500 4074.946 4.40m D
water pumps (Flange given by Wetico
face direction west)

Line from DAF sludge pumps to dewatering Vertical to ground from


T.P 2 GCL58-BR001-50-GRP Flange (FF) ANSI B16.5 Class # 150 GRP DN50 2" 18-60 6 1/9 2619.534 4083.626 4.30m D
waste water treatment scope desal. Plant

Suction line for effluent transfer pumps Direct connection with the
T.P 3 GBL50-BR001-500-GRP Flange (FF) ANSI B16.5 Class # 150 GRP DN500 20" 18-60 1 1/9 2631.196 4055.071 4.68m D
from tank nozzle of RCC tank

Vertical to ground from


T.P 4 Discharge line for effluent transfer pumps GBL50-BR002-350-GRP Flange (FF) ANSI B16.5 Class # 150 GRP DN350 14" 18-60 6 1/9 2631.600 4057.471 4.30m D
desal. Plant

Suction line for backwash pumps from Direct connection with the
T.P 5 GCP53-BR001-400-GRP Flange (FF) ANSI B16.5 Class # 150 GRP DN400 16" 18-60 1 3/9 2624.846 4047.301 4.775m D
filtered water tank nozzle of RCC tank

Suction line for RO pass-1 feed pumps from Direct connection with the
T.P 6 GCK54-BR001-600-GRP Flange ANSI B16.5 Class # 150 GRP DN600 24" 18-60 1 3/9 2624.846 4043.820 4.96m D
filtered water tank nozzle of RCC tank

Filtered water line from Dual media filters No TP direct to tank from
T.P 7 GCB56-BR001-450-GRP - - GRP DN450 18" 18-60 6 3/9 NA NA NA D
to filtered water tank top

Backwash line from dual media filters to No TP direct to tank from


T.P 8 GCB56-BR401-350-GRP - - GRP DN350 14" 18-60 6 2/9 NA NA NA D
effluent transfer tank top

Reject line from RO pass-1 to effluent No TP direct to tank from


T.P 9 GCF53-BR001-350-GRP - - GRP DN350 14" 18-60 6 4/9 NA NA NA D
transfer tank top

Suction line to Sulfuric Acid unloading Coupling from tanker


T.P 10 GCN55-BR001-3"-Alloy20 - - Alloy 20 DN80/3" 3" 18-60 1 9/9 NA NA NA D
pumps from tanker (Flexible hose)

Horizantal to ground level


Permeate line from RO ppass-2 to service towords desal. Plant
T P 11
T.P GCF56 BR001 12"-SS316L
GCF56-BR001-12 SS316L - - SS316L DN300/12"
DN300/12 12"
12 18 60
18-60 6 6/9 2623 396
2623.396 4007 185
4007.185 4 60m
4.60m D
water tank (Flange given by Wetico
face direction east)

Wetico will deliver as a


Discharge line from service water feed
T.P 12 GBK54-BR001-100-GRP Flange (FF) ANSI B16.5 Class # 150 GRP DN100 4" 18-60 1 7/9 BY SC&T BY SC&T BY SC&T lose pipe installed in SC&T D
Pumps
area
Wetico will deliver as a
Discharge line for service water feed
T.P 13 GBK54-BR001-100-GRP Flange (FF) ANSI B16.5 Class # 150 GRP DN100 4" 18-60 8 7/9 BY SC&T BY SC&T BY SC&T lose pipe installed in SC&T D
Pumps to Potable water tank
area

Horizantal to ground level


Inlet line to Mixed bed from mixed bed feed towords desal. Plant
T.P 14 GBK50-BR001-8"-SS316L Flange (RF) ANSI B16.5 Class # 150 SS316L DN200 8" 18-60 8 6/9 2623.399 3999.500 4.68m D
pumps (Flange given by Wetico
face direction east)

Horizantal to ground level


Product line from mixed bed to D.I water towords desal. Plant
T.P 15 GBF54-BR001-8"-SS304 Flange (RF) ANSI B16.5 Class # 150 SS304 DN200 8" 18-60 8 8/9 2623.399 3999.9247 4.68m D
tank (Flange given by Wetico
face direction east)

Prep. by : S.A
Check. by: H.M
App. by : T.M
Design / Elevation
Design working Ref. to P&ID
Material from ground
T.P NO. Location Pipe line TAG No. T.P Connection T.P Rating Pipe Size *C (BAR) QIPP-MPN013- COOR. E COOR. N Remarks rev.
Spec. Temp. Pressure M00-0100
to center
System line

Suction line for regeneration pumps from Flange (WNRF)


T.P 16 GNF50-BR001-4"-SS304 Class # 150 SS304 DN100 4" 18-60 2 8/9 BY SC&T BY SC&T 0.412m D
D.I water tank ANSI B16.5

Discharge line for regeneration pumps from Flange (WNRF)


T.P 17 GNF50-BR002-3"-SS304 Class # 150 SS304 DN80 3" 18-60 6 8/9 BY SC&T BY SC&T 1.520m D
D.I water tank ANSI B16.5

Horizantal to ground level


Inlet line from regeneration pumps to Flange (WNRF) towords desal. Plant
T.P 18 GNF50-BR002-3"-SS304 Class # 150 SS304 DN80 3" 18-60 6 8/9 2623.399 4000.2497 4.615m D
mixed bed ANSI B16.5 (Flange given by Wetico
face direction east)

Discharge line from neutralization pumps to Vertical to ground from


T.P 19 GBR53-BR001-150-cPVC Flange (FF) ANSI B16.5 Class # 150 cPVC DN150 6" 18-60 6 9/9 2634.000 3996.200 4.00m D
final disposal desal. Plant

Suction line to Caustic unloading pumps Coupling from tanker


T.P 20 GCN52-BR001-3"-SS316L - - SS316L DN80 3" 18-60 1 9/9 NA NA NA D
from tanker (Flexible hose)

RO-2 flushing outlet line to effluent transfer No TP direct to tank from


T.P 21 GCF57-BR001-300-GRP - - GRP DN300 12" 18-60 6 6/9 NA NA NA D
tank top

Horizantal to ground level


towords desal. Plant
T.P 22 Feed line for Air resiver tank GNL50-BR001-50-SS304 Flange (RF) ANSI B16.5 Class # 150 SS304 DN50 2" 80-110 1 2/9 2622.696 4044.295 4.63m D
(Flange given by Wetico
face direction east)

Horizantal to ground level


towords desal. Plant DAF
Feed line from service net work water to
T.P 23 GCL59-BR001-50-GRP Flange (FF) ANSI B16.5 Class # 150 GRP DN50 2" 18-38 6 1/9 2618.034 4074.946 4.30m unit D
DAF unit
(Flange given by Wetico
face direction east)
Wetico will deliver as a
T.P 24 Line to service water distribution system DN100-GRP Flange (FF) ANSI B16.5 Class # 150 GRP DN100 4" 18-38 6 7/9 BY SC&T BY SC&T BY SC&T lose pipe installed in SC&T D
area

Horizantal to ground level


towords desal. Plant
T.P 25 Line from SWRO tank drain DN200-GRP Flange (FF) ANSI B16.5 Class # 150 GRP DN200 8" 18-38 1 2/9 2635.996 4018.981 4.50m D
(Flange given by Wetico
face direction east)

No TP direct from top of


T.P 26 Line from service water to saftey shawer DN25-uPVC/SS304 Threaded SCH.40 SS304/uPVC DN25 1" 18-38 6 9/9 2608.646 3988.330 4.50m D
concrete pad

No TP direct from top of


T.P 27 Line from service water to saftey shawer DN25-uPVC/SS305 Threaded SCH.40 SS304/uPVC DN25 1" 18-38 6 9/9 2631.040 3986.172 4.30m D
concrete pad

NOTE : ALL THESE T.Ps ARE REFER TO DRAWINGS: QIPP-MPN013-M00-0100 1/9 SHEETS REV.0.
QIPP-MPN013-M00-0001 1/2 SHEETS REV.0.
QIPP-MPN013-C00-0001 1/2 SHEETS REV.0.
QIPP-MPN013-C00-0002 1/2 SHEETS REV.0.

Prep. by : S.A
Check. by: H.M
App. by : T.M