LIMA – PERU
2019
Resumen
.
Abstract
he elevated tanks when carrying out their design and structuring must comply with an analysis
and design of the structures, which is why in this scientific article it is intended to test their
structural capacity through a three-dimensional model in the SAP2 000 V14 computer
program and for the foundation the SAFE 12.3.2 computer program, both CSI programs,
therefore, the National Building Regulation with the following technical standards has been
Therefore, in terms of analysis, studies were carried out on an elevated tank that is located in
the San Juan de Dios Town Center of the Aucallama District - Huaral Province - Department
of Lima, so currently the elevated tank is in process of expertise since, based on information
from the district municipality of Aucallama, it would not have met all the safety standards
regarding its structural design because of this, an analysis of the situational state of the tank
I- ASPECTOS GENERALES
El tanque Elevado en materia de análisis se encuentra ubicado en el Centro Poblado San Juan
de Dios del Distrito de Aucallama – provincia de Huaral – Departamento de Lima,
Actualmente el tanque elevado se encuentra en proceso de peritaje ya que por información de
la municipalidad distrital de Aucallama esta no habría cumplido con todos los estándares de
seguridad en respecto a su diseño estructural en razón a ello se ha realizado un análisis del
estado situacional del tanque empleando software de cálculos estructurales.
Cisterna
Caseta
Tanque.
1 2.27
2
5.66
.18 .18
.30 .30
1.05 1.05
.33
B .13 .13
B
A .13 .13
A
Escalera de gato
con tub. f°g°,
1.05 1.05
.30 .30
.18 .18
.18 .30 1.05 .13 2.34 .13 1.05 .30 .18
5.66
2.27
1 2
(Escala : 1/50)
Fuente: AUTOCAD 2018 –diseño y calculo estructural.
El modelo empleado para vigas y columnas consistió en barras de eje recto que
incluyen deformaciones por flexión, carga axial, fuerza cortante y torsión.
Este modelo considera el efecto tridimensional del aporte de rigidez de cada elemento
estructural, En las uniones viga columna se han considerado las zonas rígidas,
correspondientes, a fin de proporcionar la rigidez adecuada acorde a la realidad o lo más
próximo posible.
1.7. ANÁLISIS
Esta técnica de análisis fue empleada debido a que el edificio en estudio no presenta
irregularidades y es de baja altura.
FIGURA 5. Deformada.
Fuente: SAP 2000 V14 –diseño y calculo estructural.
FIGURA 6. Desplazamientos.
Fuente: SAP 2000 V14 – diseño y calculo estructural.
Desplazamientos Distorsiones
Limite E.030 Verificación
Absolutos (m) (0.75*R*D/h)
ESTRUCT. Altura
UX UY Δx Δy Dir. X Dir. Y Dir. X Dir. Y
STORY2 3.325 0.0035 0.0035 0.0034 0.0034 0.007 0.007 Ok Ok
STORY1 3.325 0.0017 0.0017 0.0030 0.0030 0.007 0.007 Ok Ok
1.11. COLUMNA 30 X 30
Observando la Figura 8
se determina que se usará el acero para las columnas 30X30, El refuerzo por corte y
torsión
3Ø1/2" 0.30
2Ø1/2"
0.30
3Ø1/2"
0.30
1.12. VIGA 30 X 30
2 ϕ 1/2
14 14
As min = ∗b∗d= ∗30∗( 30−5 )=2.5 c m2 ¿
fy 4200
Observando la Figura 7 se determina que se usará el acero mínimo para las vigas 30X30
3Ø1/2" 0.30
0.30
3Ø1/2"
0.30
1.13. verificacion y diseño de tanque.
MURO.
Propiedades.
fy = 4200 kg/cm2
f'c = 280 kg/cm2
d = 9.73 cm.
t = 15.00 cm.
recub. = 4.00 cm.
Altura a C M
0.10 xH = 0.12 0.29 -5.89 -10.18
0.20 xH = 0.24 0.58 -0.29 -4.06
0.30 xH = 0.36 0.87 0.04 2.07
0.40 xH = 0.48 1.16 0.07 8.19
0.50 xH = 0.60 1.44 0.07 14.32
0.60 xH = 0.72 1.73 0.05 20.44
0.70 xH = 0.84 2.02 0.04 26.57
0.80 xH = 0.96 2.31 0.04 32.69
0.90 xH = 1.08 2.60 0.03 38.82
1.00 xH = 1.20 2.89 0.03 44.94
Por As.
Altura ( h ) As
c Cuantía Consid.
(m) (cm2 ) As (cm2) As (cm2)
0.10 xH = 0.10 0.28 2.70 1.35
0.20 xH = -0.04 -0.11 2.70 1.35
0.30 xH = 0.02 0.06 2.70 1.35
0.40 x H = 0.08 0.22 2.70 1.35
0.50 x H = 0.13 0.39 2.70 1.35
0.60 x H = 0.19 0.56 2.70 1.35
0.70 x H = 0.25 0.72 2.70 1.35
0.80 x H = 0.31 0.89 2.70 1.35
0.90 x H = 0.36 1.06 2.70 1.35
1.00 x H = 0.42 1.22 2.70 1.35
Por As.
Altura ( h )
Cuantía Consid.
(m) As (cm2) cm2
0.10 xH = 2.70 2.70
0.20 xH = 2.70 2.70
0.30 xH = 2.70 2.70
0.40 xH = 2.70 2.70
0.50 xH = 2.70 2.70
0.60 xH = 2.70 2.70
0.70 xH = 2.70 2.70
0.80 xH = 2.70 2.70
0.90 xH = 2.70 2.70
1.00 xH = 2.70 2.70
TABLA 6. Disposición de Acero Horizontal.
Altura ( h )
Ø @
(m)
0.10 xH = 3/8 0.26
0.20 xH = 3/8 0.26
0.30 xH = 3/8 0.26
0.40 xH = 3/8 0.26
0.50 xH = 3/8 0.26
0.60 xH = 3/8 0.26
0.70 xH = 3/8 0.26
0.80 xH = 3/8 0.26
0.90 xH = 3/8 0.26
1.00 xH = 3/8 0.26
Usar Ø 3/8 @ 0.20
LOSA.
Fuente:
SAP 2000 V14 – Grupo de diseño y calculo estructural.
Por As.
As
Cuantía Consid.
As min
(cm2 ) As (cm2)
(cm2)
0.01 3.40 3.40
As = 3.40
FIGURA 11: Modulo de balasto, se emplea el módulo de Winckle como 2.47E+03 ton / m3.
Capacidad portante kg/cm2 > Capacidad portante máxima. 1.40 kgf/cm2 > 2.728E-03
kgf/cm2 , por ello a continuación se presenta los valores de los aceros de refuerzo, calculadas
según el método de Strip Based, con apoyo del programa de cómputo SAFE.
3Ø5/8" 0.30
2Ø1/2"
0.60
2Ø5/8"
0.30
Es uso obligatorio todos y cada una de las normas de estructuras del reglamento
nacional de edificaciones para cualquier verificación o comprobación.
Referencia:
Proyecto : INSPECCION
TECNICA DE SEGURIDAD
EN EDIFICACIONES -
DETALLE
Asunto : AFORO
Profesional : Arquitecto Carlos
Teodoro
CAP 4434
Código SUNARP: CIV Nº
000702VCZRIX
Fecha : Diciembre 2019
CALCULO DE AFORO
MAXIMA CARGA DE OCUPANTES (AFORO)
Artículo 3.-
Todas las edificaciones albergan en su interior a una determinada cantidad de personas en
función al uso, cantidad, forma de mobiliario y/o al área disponible para la ocupación de
personas. El sistema de evacuación debe diseñarse de manera que los anchos “útiles” de
evacuación y la cantidad de los medios de evacuación, puedan satisfacer los requerimientos de
salida para los aforos calculados. Entiéndase por aforo a la cantidad máxima de personas que
puede físicamente ocupar un ambiente, espacio o área de la edificación.
Toda edificación puede tener distintos usos y por lo tanto variar la cantidad de personas
ocupantes, por tal motivo se debe siempre calcular el sistema de evacuación para la mayor
cantidad de ocupantes por piso o nivel. En caso se contemple usos de diferentes tipologías se
deberá utilizar la sumatoria resultante de la cantidad de personas más exigente por piso o nivel
y asegurar el ancho útil de evacuación en todo su recorrido hasta un lugar seguro según A-010
Art. 25.
El aforo de una edificación, piso, nivel o área puede ser modificado incrementando la cantidad
de personas, siempre y cuando no exceda la capacidad de los medios de salida que sirven a la
edificación.
Para calcular la cantidad de ocupantes de una edificación se podrá utilizar de forma parcial,
total o interrelacionada cualquiera de las 3 siguientes opciones:
Articulo 3.1
En los locales tipo cines, teatros, estadios, restaurantes, hoteles, industrias, call center, entre
otros en donde se ubique mobiliario fijo, específico para la actividad a la cual sirve, como
butacas, mesas, maquinarias, deberá considerarse una persona cada unidad de mobiliario.
Artículo 4.-
Sin importar el tipo de metodología utilizado para calcular la cantidad de personas en todas las
áreas de una edificación, para efectos de cálculo de cantidad de personas debe utilizarse la
sumatoria de todas las personas (evacuantes). Cuando exista una misma área que tenga
distintos usos deberá utilizarse para efectos de cálculo, siempre el de mayor densidad de
ocupación.
De otro lado la edificación en el inmueble – Planta APT en su mayor proporción cuentan con
elementos de baja combustibilidad y otros (Almacén de carretes de madera, Almacén de
Rollos) que tienen la posibilidad de arder con moderada rapidez debido al mantenimiento
que se realiza y el sistema de control existente. De lo expuesto se considera el tipo de
Riesgo Moderado Ordinario
Así mismo considerando el RNE – Norma A.010- Articulo 25 – Para efectos de evacuación
la Distancia total del Evacuante, medido de manera horizontal y vertical desde el punto más
alejado hasta el lugar más seguro (salida de escape, área de refugio o escalera de emergencia)
será:
TOTAL
GENERAL DE AFORO
2 2 4
1°-Área Guardianía y Control
6°-Área Marketing 15 10 25
2 0 2
Almacén (Colindante a la Av,
Industrial)
Total 129
Referencias
- REGLAMENTO NACIONAL DE CONSTRUCCIONE(RNC)- TITULO III
- REGLAMENTO NACIONAL DE EDIFICACIONES (RNE), DEL A.050, A.060,
A.070, A.080, A.120
- REGLAMENTO NACIONAL DE EDIFICACIONES (RNE), A.130 art 20