Power Flow Summary Report

Mismatch Report
Iteration MW Mismatch MVAR
Mismatch
Number Bus Name pu Bus Name pu
0 BUS-3 0.00808 BUS-3 0.00495
1 BUS-3 0.00015 BUS-3 0.00010
2 BUS-3 0.00000 BUS-3 0.00000
3 BUS-3 0.00000 BUS-3 0.00000
4 BUS-3 0.00000 BUS-3 0.00000

Generation Summary Report


A Source Scheduled Limits Solution
C
/
D
C
Name Type Rated MW MVAR Vpu MVAR MVAR MW MVAR MVA PF Vpu
MVA Min Max
A UTIL-1 Sw 1.000 4.108 3.017 5.097 0.806 1.000
C

Load Summary Report


Bus Solution
Name Base kV kV Vpu Deg MW MVAR MVA PF
BUS-1 69.000 69.000 1.000 0.00 0.000 0.000 0.000 0.000
BUS-2 13.800 13.534 0.981 -1.37 0.000 0.000 0.000 0.000
BUS-3 13.800 13.534 0.981 -1.37 4.099 2.861 4.999 0.820

System Summary Report


--
Total MW MVAR MVA PF
Generation in System 4.108 3.017 5.097 0.806
Load in System 4.099 2.861 4.999 0.820
Shunt Load in System -0.000 -0.000
Losses in System 0.009 0.156
Check of Balance 0.000 -0.000

Transformer Tap Report


Transformer Connection Base kV Tap kV LTC Description
Name From To From To From To Type LTC LTC Control LTC Control
Bus Name Bus Name Type Side Side Value pu
TX-1 BUS-1 BUS-2 69.000 13.800 69.000 13.800 2Wnd No

Line Overload Report


Overload Threshold = 10.00 %
Line Load
From Bus To Bus Branch Rated Load Loaded% OverLoaded% Comment
Name Name Name Amps Amps
BUS-2 BUS-3 C-1 295.0 213.2 72.3% -27.7%

Transformer Overload Report


Overload Threshold = 10.00 %
Transformer Load
Name From Bus To Bus Rated Load Loaded% OverLoaded% Comment
Name Name Amps Amps
TX-1 BUS-1 BUS-2 585.7 213.2 36.4% -63.6%
Branch Losses Report
From Bus To Bus Losses
Name Base kV Name Base kV MW MVAR
BUS-1 69.000 BUS-2 13.800 0.009 0.156
BUS-2 13.800 BUS-3 13.800 0.000 0.000
Total System Losses 0.009 0.156

Voltage Drop Report


From Bus To Bus Drop
Name Base kV Name Base kV %
BUS-1 69.000 BUS-2 13.800 1.9%
BUS-2 13.800 BUS-3 13.800 0.0%