INSTRUMENTATION SPECIFICATION FOR PACKAGE EQUIPMENT PDP-IN-SP-004 Rev.

APPLICABLE CODES, STANDARDS AND STATUTORY REQUIREMENTS

ANSI B16.104 Shutoff Class.

ANSI/ISA-75.01 Sizing of Control Valves

ANSI/ISA-75.17. Control Valves Sizing - Noise level calculations

ANSI/ISA -75.03. Face to face dimensions of flanged globe-bodied valves

ANSI/FCI 70-02 Shutdown valves leakage rates

API RP 520 Recommended practice for design and installation of pressure relieving
systems in refineries.

ASME PTC19.3 Temperature Measurement

ASME VIII Pressure Vessel Design

ASME MFC-14M Measurement of fluid flow using small bore precision orifice meters

ASTM A269 Specification for Stainless Steel Tubing

DIN EN 837 Bourdon Tube Pressure Gauges

IEC 60332 Test of Cables under Fire Conditions

IEC 534 Industrial process control valves

IEC 60529 Degrees of Protection Provided by Enclosures for Electrical Equipment (IP
code).

IEC 61200 Electrical Installation Guide – Wiring Systems

ISO 5167 Measurement of Fluid Flow in Closed Conduits (All parts).

ISO 5168 Measurement of Fluid Flow. Estimation of Uncertainty of a Flowrate


Measurement

IP 15 Institute of Petroleum Model Code of Safe Practice, Part 15.

BS7671 Requirements for Electrical Installations

AGA Report 3 Orifice metering of natural gas and other related hydrocarbon fluids

AGA Report 8 Compressibility Factors of Natural Gas and Other Related Hydrocarbon Gases

API RP 505 Recommended Practice for Classification of Locations for Electrical


Installations at Petroleum Facilities Classified as Class I, Zone 0, Zone 1, and
Zone 2

API RP 551 Manual on Process Measurement Instrumentation.

API RP 552 Manual on Control Signal Transmission systems.

PAKISTAN PETROLEUM LIMITED Page 41 of 43


INSTRUMENTATION SPECIFICATION FOR PACKAGE EQUIPMENT PDP-IN-SP-004 Rev. 0

API RP 553 Manual on Refinery Control Valves.

API RP 554 Manual on Process Instrumentation and Control.

EIA-RS-232 Interface between Data Terminal Equipment (DTE) and Data Communication
Equipment (DCE) Employing Serial Binary Data Interchange.

EIA-RS-485 Balanced Serial Data Communications Interchange.

IEC 61000 Electromagnetic Compatibility

ISA RP55.1 Hardware Testing of Digital Process Computers.

ISA RP7.1 Pressure Testing of Pneumatic Controlled Equipment’s

ISA S5.1 Instrument Symbols and Identification.

ISA S5.2 Binary Logic Diagrams for Process Operations.

ISA S5.3 Graphic Symbols for Distributed Control/Shared Display Instrumentation, Logic
and Computer Systems.

ISA S5.4 Instrument Loop Diagrams.

ISA S5.5 Graphic Symbols for Process Displays.

ISA S50.1 Compatibility of Analogue Signals for Electronic and Industrial Process
Instruments

PAKISTAN PETROLEUM LIMITED Page 42 of 43


DATA SHEET NO. DS-INS-2001
SHEET 1 of 2
DATE 19-Sep-19
LEVEL TRANSMITTER REV. 0
(GUIDED WAVE RADAR) PREPARED BY MNF
CHECKED BY AMF
APPROVED BY FAS
OWNER: PAKISTAN PERTROLEUM LIMITED (PPL)
PROJECT: BENARI X1 DEVELOPMENT PROJECT
1 Tag Number LIT-2020 LIT-2027
2 Service V-2000 V-2000
3 P&ID No. PID-2000 PID-2000
4 PROCESS SERVICE CONDITIONS
5 Liquid/Fluid HC Liquid+Water (Interface) HC Liquid+Water (Interface)
6 Specific Gravity 0.7-1.0 0.7-1.0
7 Pressure Max. (Psig) 1100 1100
8 Pressure Oper. (Psig) 50 50
9 Pressure Min. (Psig) 20 20
10 Temperature Max. (°F) 135 135
11 Temperature Oper. (°F) 100 100
12 Temperature Min. (°F) 0 0
13 Level Transmit Height (mm) 1220 1220
14 TRANSMITTER
15 Measurement Type Level Level
16 Type Contact Radar Type Contact Radar Type
17 Measuring Principle Time Domain Reflectometry (TDR) Time Domain Reflectometry (TDR)
18 Local Indication Yes (Integral) Yes (Integral)
19 Calibration Range (mm) 0-1220 0-1220
20 Scale Range (mm) =/> Twice of Calibrated Range =/> Twice of Calibrated Range
21 Accuracy ±5 mm ±5 mm
22 Transmitter Output 4-20mA with HART Protocol 4-20mA with HART Protocol
23 Power Supply 24VDC (Loop Powered) 24VDC (Loop Powered)
24 Electrical Connection Note-3 M 20 x 1.5 M 20 x 1.5
25 Process Connection Note-1 3" ANSI Flanged 3" ANSI Flanged
26 Flange Rating / Class 600# RF 600# RF
27 Process Flange Inner Diameter Note-1 (mm) 73.66 73.66
28 Nace Compliance Note-5 No No
29 SENSING PROBE
30 Probe Material 316 SS 316 SS
31 Probe Type Note-4 Coaxial / *VTA Coaxial / *VTA
32 Probe Length (mm) As per Level Transmit Height As per Level Transmit Height
33 TRANSMITTER ENCLOSURE
34 Housing Material Aluminum Aluminum
35 Electrical Classification EEx 'd' IIC T6 EEx 'd' IIC T6
36 Enclosure Protection IP65 IP65
37 ACCESSORIES
38 Cable Gland Required Note-3 (Yes / No) No No
39 SS Tag Required Note-2 (Yes / No) Yes Yes
40 Electrical Entry Plugs Required Note-3 (Yes / No) Yes Yes
41 NOTES:
1- Vendor shall confirm that the Level Transmitter flange outer diameter shall match with process flange diameter.
2- Vendor shall provide SS Tag attached with SS Screws or SS wire. Tag shall contain Tag Number and Model Number of Transmitter.
3- Vendor shall provide Ex'e' plugs for each Electrical Entry
4- Vendor shall provide probe type according to process pressure and temperature.
5- Vendor to ensure that instrument trim material shall be compatiable with the composition
* VTA = Vendor to Advice
DATA SHEET NO. DS-INS-2001
SHEET 1 of 2
DATE 19-Sep-19
LEVEL TRANSMITTER REV. 0
(GUIDED WAVE RADAR) PREPARED BY MNF
CHECKED BY AMF
APPROVED BY FAS
OWNER: PAKISTAN PERTROLEUM LIMITED (PPL)
PROJECT: BENARI X1 DEVELOPMENT PROJECT
1 Tag Number LIT-2019 LIT-2029
2 Service V-2000 V-2000
3 P&ID No. PID-2000 PID-2000
4 PROCESS SERVICE CONDITIONS
5 Liquid/Fluid HC Liquid HC Lquid
6 Specific Gravity 0.7-0.8 0.7-0.8
7 Pressure Max. (Psig) 1100 1100
8 Pressure Oper. (Psig) 50 50
9 Pressure Min. (Psig) 20 20
10 Temperature Max. (°F) 135 135
11 Temperature Oper. (°F) 100 100
12 Temperature Min. (°F) 0 0
13 Level Transmit Height (mm) 1220 1220
14 TRANSMITTER
15 Measurement Type Level Level
16 Type Contact Radar Type Contact Radar Type
17 Measuring Principle Time Domain Reflectometry (TDR) Time Domain Reflectometry (TDR)
18 Local Indication Yes (Integral) Yes (Integral)
19 Calibration Range (mm) 0-1220 0-1220
20 Scale Range (mm) =/> Twice of Calibrated Range =/> Twice of Calibrated Range
21 Accuracy ±5 mm ±5 mm
22 Transmitter Output 4-20mA with HART Protocol 4-20mA with HART Protocol
23 Power Supply 24VDC (Loop Powered) 24VDC (Loop Powered)
24 Electrical Connection Note-3 M 20 x 1.5 M 20 x 1.5
25 Process Connection Note-1 3" ANSI Flanged 3" ANSI Flanged
26 Flange Rating / Class 600# RF 600# RF
27 Process Flange Inner Diameter Note-1 (mm) 73.66 73.66
28 Nace Compliance Note-5 No No
29 SENSING PROBE
30 Probe Material 316 SS 316 SS
31 Probe Type Note-4 Coaxial / *VTA Coaxial / *VTA
32 Probe Length (mm) As per Level Transmit Height As per Level Transmit Height
33 TRANSMITTER ENCLOSURE
34 Housing Material Aluminum Aluminum
35 Electrical Classification EEx 'd' IIC T6 EEx 'd' IIC T6
36 Enclosure Protection IP65 IP65
37 ACCESSORIES
38 Cable Gland Required Note-3 (Yes / No) No No
39 SS Tag Required Note-2 (Yes / No) Yes Yes
40 Electrical Entry Plugs Required Note-3 (Yes / No) Yes Yes
41 NOTES:
1- Vendor shall confirm that the Level Transmitter flange outer diameter shall match with process flange diameter.
2- Vendor shall provide SS Tag attached with SS Screws or SS wire. Tag shall contain Tag Number and Model Number of Transmitter.
3- Vendor shall provide Ex'e' plugs for each Electrical Entry
4- Vendor shall provide probe type according to process pressure and temperature.
5- Vendor to ensure that instrument trim material shall be compatiable with the composition
* VTA = Vendor to Advice
DATA SHEET NO. DS-INS-2011
SHEET 1 of 1
PRESSURE RELIEF VALVE DATE 11-Sep-19
REV. 0
PREPARED BY MNF
PAKISTAN PETROLEUM LIMITED CHECKED BY AMF
BENARI X1 DEVELOPMENT PROJECT APPROVED BY FAS
1 TAG NUMBER PSV-2021
PSV on Three Phase Separator (V-2000) ,Pressure Relief to HP
2 SERVICE
Flare Header
GENERAL

3 EQUIPMENT NUMBER V-2000


4 P & ID PID-2000
5 INLET LINE No. 3"-FRF-203-D2C-B
6 INLET PIPING CLASS D2C
7 OUTLET LINE No. X"-FRF-204-A2C-B
8 OUTLET PIPING CLASS A2C
9 CODE ASME SEC VIII Div 1
DESIGN
BASIS

10 BASIS OF SELECTION BLOCKED DISCHARGE


11 CALCULATION REFERNCE API RP 520 Part 1 & Part 2
12 Relief Conditions Units
13 Fluid Vapour

14 Max Accumulated Pressure, % - 10


15 Inlet Relieving Pressure psia 708
16 Inlet Relieving Temperature °F 238
17 Vapor Mass Rate lb/h 40980
18 PRV Molecular Weight - 19
19 Inlet Compressibility Factor - 0.96
20 Cond k = Cp/Cv - 1.322
21 Liquid Volume Rate ft3/h -
22 Sp Gr (water = 1.000) - -
23 Liquid Viscosity cP -
PROCESS

24 Two-phase Temperature °F -
Calc. -
25 Vapor Mass Rate lb/h
Condition
26 Vapor Molecular Weight - -
(*:90% of
27 Pinlet or Liquid Volume Rate ft3/h -
28 Psat) Liquid Sp Gr (water = 1.000) - -
29 SET PRESSURE Psig 630
30 DESIGN TEMPERATURE °F 300
31 OPERATING /DESIGN PRESSURE Psig 250/1350
32 OPERATING TEMPERATURE °F 100
33 CONSTANT 0
BACK PRESS. Psig
34 VARIABLE 17
MAXIMUM TOTAL BACK PRESSURE FOR EACH CASE
35 50
(Psig)
36 CAUSE OF OVER PRESSURE BLOCKED DISCHARGE
37 VALVE TYPE CONVENTIONAL
38 BONNET TYPE FLANGED (VTA)
39 SEAT TYPE STELLITED SEAT (VTA)
40 NOZZLE TYPE FLANGED (VTA)
41 BODY & BONNET MATERIAL A216 GR. WCB
42 SPRING MATERIAL CHROME ALLOY (VTA)
43 SEAT & DISC MATERIAL SS 316L(VTA)
VALVE

44 BELLOWS MATERIAL VTA


45 INLET SIZE & RATING VTA /VTA
46 INLET FACING VTA
47 OUTLET SIZE & RATING VTA / 150#
48 OUTLET FACING RAISED FACE
49 END CONNECTIONS FLANGED
50 CALC. VTS
ORIFICE AREA(in2)
51 SELECTED VTS
52 ORIFICE DESIGNATION VTS
53 CAP SCREWED / BOLTED VTA
54 LIFTING LEVER NO
ACCESSO 55 TEST GAG YES
RIES 56 STAINLESS STEEL TAG REQD. YES
57
58
59 MANUFACTURER Refer attached AVL with ITB
60
61
62
NOTES
1 Vendor shall stamp the tag nos. on 316SS tag plates and permanently attach to PSVs
2 Vendor shall confirm suitability of supplied equipment for the design parameters stated in data sheet.
3 All Flanges with RF shall be modified spiral serrated finish generated as a continuous spiral groove by a round nosed tool.
4 All NPT threads should be according to ASA B2.1.
5 Vendor to submit the calculation sheet and shall supply the material after Customer approval.
6 Pressure safety valves shall be provided confirming to API RP 521,API RP 520 Part 1 & Part 2.
7 PSV shall meet the requirements of "INSTRUMENT SPECIFICATION FOR PACKAGE EQUIPMENT"
8 Vendor to submit the calculation sheet and will supply the material after Customer approval
9 Vendor to provide the following test certificates for each valve.
I CDTP Test
II Seat tightness Test
III Back Seat tightness Test
IV Shell tightness Test
V Hydrostatic testing
VI Calibration testing
10 AREA CLASSIFICATION TO BE CONFIRMED AS PER HAZARDOUS AREA CLASSIFICATION LAYOUT
11 VTA: VENDOR TO ADVISE, VTC:VENDOR TO CONFIRM
12 TBA: TO BE ADVISED.
DATA SHEET NO. DS-2002
SHEET NO. 1 of 2

SHUTDOWN VALVE DATE


REV.
18-Sep-19
0
(Automatic Ball Valve) PREPARED BY AMF
CHECKED BY MNF
APPROVED BY FAS
OWNER: PAKISTAN PERTROLEUM LIMITED (PPL)
PROJECT: BENARI X1 DEVELOPMENT PROJECT
1 Tag Number ESDV-2015 ESDV-2016
2 Service From Production Wellhead Benari X1 Raw gas metering outlet line
3 Line No. 6"-GRG-201-D2C-B 6"-GRG-208-D2C-B
4 Piping Class ANSI Class 600, WNRF ANSI Class 600. WNRF
5 P&ID No. PID-2000 PID-2001
6 PROCESS SERVICE CONDITIONS
7 Fluid Hydrocabons Raw Gas
8 State Gas/Oil/Water Gas
9 Maximum Flow (lb / hr) 79502 40460
10 Maximum Inlet Pressure (Psig) 250-1000 250-1000
11 Maximum Temperature (oF) 150 150
12 Gas Compressibility Factor 0.98 -
13 Specific Gravity at Oper Cond. (Gas) 0.7 -
14 Specific Gravity at Oper Cond. (Liquid) 0.88 0.64
15 VALVE BODY
JC Valves, Orbit, Kitz, Valvitalia, Metso, Emerson, JC Valves, Orbit, Kitz, Valvitalia, Metso, Emerson,
16 Manufacturer
Dresser, Meridian Dresser, Meridian
17 Valve type Note - 5 Full Bore Ball Full Bore Ball
18 Body Size / Rating/End Connection Note - 1 6"/600#/Flange 6"/600#/Flange
19 Body Material Note - 1 ASTM A216 GR.WCB TRIM: SS316, Seat-Peek ASTM A216 GR.WCB TRIM: SS316, Seat-Peek
20 Flange Face Finish Note - 1 Ra = 3.2 to 6.3 um Ra = 3.2 to 6.3 um
21 Control Characteristics ON/OFF ON/OFF
22 Ball Material 316SS / To be compaitable with Process Fluid 316SS / To be compaitable with Process Fluid
23 Shaft Material VTA VTA
24 Seat Type / Material Soft Seat/ To be compaitable with Process Fluid Soft Seat/ To be compaitable with Process Fluid
25 Shut-off Class / Leakage Tight Shut-Off / Class VI Tight Shut-Off / Class VI
26 Fail Action Fail to Close Fail to Close
27 Max. Valve Stroke Time (Opening) 30 seconds 30 seconds
28 Max. Valve Stroke Time (Closing) 5 seconds 5 seconds
29 ACTUATOR
30 Manufacturer Bettis, Rotork UK, Samson, Valtek Bettis, Rotork UK, Samson, Valtek
31 Actuator Type Pneumatic Spring Return Piston Pneumatic Spring Return Piston
32 Valve Duty (On/Off or Control) ON-OFF ON-OFF
33 Fail (Open/Close) Close Close
34 Fuel gas Supply Pressure (Psig) 60 - 110 60 - 110
35 Pneumatic Connection Size *VTA *VTA
36 SOLENOID VALVE (Tag No.) EY-2015 EY-2016
37 Manufacturer Versa, Emerson,Maxseal, RGS Versa, Emerson,Maxseal, RGS
38 Type 3-Way 3-Way
39 Electrical Cable Entry M20 x 1.5 M20 x 1.5
40 Body Material / Trim Material 316 SS / 316 SS 316 SS / 316 SS
41 Connection Size ½" NPTF ½" NPTF
42 Seat Material To be compaitable with Process Fluid To be compaitable with Process Fluid
43 Enclosure Material Cast Aluminum Cast Aluminum
44 Coil Type Moulded coil with screw terminals Moulded coil with screw terminals
45 Single or Double Single coil Single coil
46 Power Supply 24VDC 24VDC
47 Electrical Area Classification Note - 2 Ex'd' IIC T6 Ex'd' IIC T6
48 Enclosure Protection IP65 IP65
49 LIMIT SWITCH (Tag No.) ZSC/ZSO-2015 ZSC/ZSO-2016
Manufacturer Emerson, metso, Honeywell Emerson, metso, Honeywell
50 Switch Type Micro Switch Contact Type Micro Switch Contact Type
51 Quantity Two Number (Open + Closed) Position Switches Two Number (Open + Closed) Position Switches
52 Contact Rating 24VDC 2-5A 24VDC 2-5A
53 Enclosure Material Note - 3 Cast Aluminum Cast Aluminum
54 Electrical Cable Entry Note - 3 M20 x 1.5 M20 x 1.5
55 Electrical Area Classification Ex'd' IIC T6 Ex'd' IIC T6
56 Enclosure Protection IP65 IP65
57 ACCESSORIES
58 Hand Wheel No No
59 Filter Regulator / Gauge Note - 4 Yes Yes
60 Air Accumulator Tank No No
61 Tag Plate Yes Yes
62 NACE Compliance No No
63 NOTES:
All valves shall be designed, manufactured & tested according to API-6D. Flange construction shall be in accordance with ASME B16.5 and valve Face to Face Std. / Face to Face Length shall be as per
1-
ASME B16.10.
2- Approval for Electrical / Hazardous Area Classification shall be from CENELEC, ATEX, Factory Mutual (FM), IEC or Canadian Standards Association (CSA).
3- Common junction box shall be provided for both limit switches. Junction box shall have two (02) entries with one (01) Metallic plug.
4- Filter regulator, solenoid valve, gauge and all accessories shall be provided installed on valve body. Pneumatic connections shall use 316SS tube and connectors.
5- Shut down valve shall be fire resistant and shall meet requirements of API 607.
*VTA - Vendor to Advise
DATA SHEET NO. DS-2002
SHEET NO. 2 of 2

BLOWDOWN VALVE DATE


REV.
18-Sep-19
0
(Automatic Ball Valve) PREPARED BY AMF
CHECKED BY MNF
APPROVED BY FAS
OWNER: PAKISTAN PERTROLEUM LIMITED (PPL)
PROJECT: BENARI X1 DEVELOPMENT PROJECT
1 Tag Number BDV-2070
2 Service From Inlet Separator to Flare Header
3 Line No. 2"-GRG-204-D2C-B
4 Piping Class ANSI Class 600, WNRF
5 P&ID No. PID-2000

6 PROCESS SERVICE CONDITIONS


7 Fluid HC GAS
8 State GAS
9 Maximum Flow (lb / hr) 10000
10 Maximum Inlet Pressure (Psig) 1200
11 Maximum Temperature (oF) 135
12 Gas Compressibility Factor 0.7
13 Specific Gravity at Oper Cond. (Gas) 0.88
14 Specific Gravity at Oper Cond. (Liquid) -
15 VALVE BODY
JC Valves, Orbit, Kitz, Metso, Emerson, Dresser,
Manufacturer
Meridian
16 Valve type Note - 5 Full Bore Ball
17 Body Size / Rating/End Connection Note - 1 2"/600#/Flange
17 Body Material Note - 1 ASTM A216 GR.WCB TRIM: SS316, Seat-Peek
19 Flange Face Finish Note - 1 Ra = 3.2 to 6.3 um
18 Control Characteristics ON/OFF
19 Ball Material 316SS / To be compaitable with Process Fluid
20 Shaft Material VTA
21 Seat Type / Material Soft Seat/ To be compaitable with Process Fluid
22 Shut-off Class / Leakage Tight Shut-Off / Class VI
23 Fail Action Fail to Open
24 Max. Valve Stroke Time (Opening) 30 seconds
25 Max. Valve Stroke Time (Closing) 5 seconds
26 ACTUATOR
27 Manufacturer Bettis, Rotork UK, Samson, Valtek
28 Actuator Type Pneumatic Spring Return Piston
29 Valve Duty (On/Off or Control) ON-OFF
30 Fail (Open/Close) Open
31 Fuel gas Supply Pressure (Psig) 60 - 110
32 Pneumatic Connection Size *VTA
33 SOLENOID VALVE (Tag No.) EY-2070
34 Manufacturer Versa, Emerson,Maxseal, RGS
35 Type 3-Way
36 Electrical Cable Entry M20 x 1.5
37 Body Material / Trim Material 316 SS / 316 SS
38 Connection Size ½" NPTF
39 Seat Material To be compaitable with Process Fluid
40 Enclosure Material Cast Aluminum
43 Power Supply 24VDC
44 Electrical Area Classification Note - 2 Ex'd' IIC T6
45 Enclosure Protection IP65
46 LIMIT SWITCH (Tag No.) ZSC/ZSO-2070
47 Manufacturer Emerson, metso, Honeywell
48 Switch Type Micro Switch Contact Type
49 Quantity Two Number (Open + Closed) Position Switches
50 Contact Rating 24VDC 2-5A
51 Enclosure Material Note - 3 Cast Aluminum
52 Electrical Cable Entry Note - 3 M20 x 1.5
53 Electrical Area Classification Ex'd' IIC T6
54 Enclosure Protection IP65
55 ACCESSORIES
56 Hand Wheel No
57 Filter Regulator / Gauge Note - 4 Yes
58 Air Accumulator Tank No
59 Tag Plate Yes
60 NACE Compliance No
61 NOTES:
All valves shall be designed, manufactured & tested according to API-6D. Flange construction shall be in accordance with ASME B16.5 and valve Face to Face Std. / Face to Face Length shall be as per
1-
ASME B16.10.
2- Approval for Electrical / Hazardous Area Classification shall be from CENELEC, ATEX, Factory Mutual (FM), IEC or Canadian Standards Association (CSA).
3- Common junction box shall be provided for both limit switches. Junction box shall have two (02) entries with one (01) Metallic plug.
4- Filter regulator, solenoid valve, gauge and all accessories shall be provided installed on valve body. Pneumatic connections shall use 316SS tube and connectors.
5- Blowdown valve shall be fire resistant and shall meet requirements of API 607.
*VTA - Vendor to Advise
DATA SHEET NO. DS-2003
SHEET NO. 1 OF 2
DATE 18-Sep-19
CONTROL VALVE REV. 0.00
PREPARED BY AMF
CHECKED BY MNF
APPROVED BY FAS
OWNER: PAKISTAN PETROLEUM LIMITED (PPL)
PROJECT: BENARI X1 DEVELOPMENT PROJECT
1 Tag Number PCV-2016
2 Service From Feed line to Separator

GENERAL
3 Line No. 6"-GRG-202-D2C-B
4 Piping Class ANSI Class 600, WNRF
5 Pipe Size UP / Pipe Size Down 6" / 6"
6 Pipe Schedule UP / Pipe Schedule Down SCH XS / SCH XS
7 P&ID No. PID-2001
8 Fluid HC FLUIDS
9 State Mixed Phase
10 Conditions
11 Inlet Press at Flow (psig) 72 270 1145 70
PROCESS SERVICE CONDITIONS

12 Dp at Flow (psi) 20 20 20 20
o
13 Temperature ( F) 100 100 100 100
14 Gas Inputs
15 Flow Rate (lb/hr)(min/oper/max) 1000 18170 40230 18170
16 Molecular Weight 18.9 18.4 18.4 18.9 -
17 Gas Ratio of Specfic Heat (Cp/Cv) 1.3 1.3 1.52 1.3
18 Shut-off Pressure (psig) 1350
19 Gas Compressibility Factor 0.99 0.96 0.88 0.99
20 Liquid Inputs
21 Flow Rate (BPD)(min/oper/max) 2 22 3000 25
22 Vapour Pressure (psig) 71 52 1084 330
23 Specific Gravity Mixture at STP 0.7 0.7 0.85 0.7
24 Critical Pressure (psig) 8572 330 108100 330
25 Sour Service (Yes / No) NO
26 Calculated Cv Min./Oper./Max. 7.68 71.44 175.11 142.53
27 Calculated Cv Min./Oper./Max. Same as above (VTC)
28 Valve Body Size Note-1 4" (VTC)
29 Selected/Rated Cv VTC
30 Manufacturer Refer AVL attached with ITB
31 Valve Type / Port Globe / Single
32 Trim / Bearing Material 316 SS compliant (Note 4&5)
33 Body Material ASTM A-216 WCB, Trim SS316+HF
BODY

34 END Connection (Inlet/Outlet) RF Flanged / RF Flanged (ASME B 16.5)


35 Valve Stem Packing Teflon / * VTA
36 Control Characteristic / Rangeability Equal Percentage / VTA
37 Seat Material Note - 5 316 SS
38 Plug Note - 5 316 SS
39 Shaft Note - 5 316 SS
40 Fail (Open / Close) Fail Close
41 Leakage Rate (Class to ASME FCI 70-2) Class IV
42 Comply to NACE Standard No
43 Actuator Type Spring Diaphragm
44 Actuator Size * VTA
ACTUATOR

45 Air Connection Size 1/4" NPT


46 Actuator Action Air to Open
47 Failure Action Close
48 Available Fuel Gas Supply 60-100 Psig
49 Valve Duty (On/Off or Throttle) Throttle
50 Type SMART Electropneumatic
51 Enclosure Type Aluminium / IP 65
52 Input Signal Range 3-15 PSI
53 Output Signal 4- 20 mA, 24 VDC with HART
POSITIONER

54 Action Direct
55 Air Supply Pressure / Air Connection 60 Psig / VTA
56 Air Regulator / Manufacturer Yes / 1/ 2 " NPT (F)
57 Gauges Yes
58 Travel Stop / Handwheel / Solenoid Valve Not Required
59 Electrical Classification / Protection Exd IIC T6
60 Cable Connection M 20 x 1.5
61 NOTES:

1- Vendor to check selection/sizing and materials of valve and actuator and may change body size and to return one completed copy to purchaser with quotation.

2- Vendor shall provide SS Tag attached with SS Screws or SS Wire. Tag shall contain Tag No. & Model No.

3- Noise level shall not be above 85DB. Supplier shall provide noise solution for valve having noise level above 110DB for maximum CV.

4- Vendor to calculate and verify the body size and valve Cv. The trim may be varied as per sizing condition.

5- For flashing service hard face trim material shall be used.


*VTA = Vendor To Advise VTC = Vendor to Confirm
DATA SHEET NO. DS-2003
SHEET NO. 1 OF 2
DATE 18-Sep-19
CONTROL VALVE REV. 0.00
PREPARED BY AMF
CHECKED BY MNF
APPROVED BY FAS
OWNER: PAKISTAN PETROLEUM LIMITED (PPL)
PROJECT: BENARI X1 DEVELOPMENT PROJECT
1 Tag Number LCV-2019 LCV-2020
2 Service From V-2001 to Condensate Flash Vessel From V-2001 to Water disposal

GENERAL
3 Line No. 2"-LHC-206-D2C-B 3"-LPW-207-D2C-B
4 Piping Class ANSI Class 600, WNRF ANSI Class 600, WNRF
5 Pipe Size UP / Pipe Size Down 2"/2" 3"/3"
6 Pipe Schedule UP / Pipe Schedule Down SCH 160 / SCH 160 SCH XS/ SCH XS
7 P&ID No. PID-2001 PID-2001
8 Fluid HC Oil WATER
9 State Liquid Liquid
10 Condition (Summer/Winter) Inlet Outlet Inlet Outlet Inlet Outlet Inlet Outlet Inlet Outlet Inlet Outlet Inlet Outlet Inlet Outlet
11 Liquid Flow Rate (BPD), Normal Operating 250 245 100 99.9 1000 903 1000 999 200 200 100 100 2000 2000 2000 2000
Vapor Flow Rate (ACFM)Normal Operating - 3.5 0.1 - 63.65 - 1.07 - - - - - 0.27 - -
PROCESS SERVICE CONDITIONS

12 Press at Flow (psig) 250 30 50 30 1000 30 50 30 250 15 50 15 1000 15 50 15


14 Temperature (oF) 100 99 100 100 100 90 100 103 100 100 100 103 100 100
15 Vapour Pressure (psig) 249 49.67 966 49.67 7.83 199 -9.4
16 Critical Pressure (psig) 492 378.00 966.00 378.00 3195 3197 3194
17 Critical Temperature (°F) 693 714 670 714 705 705 705
18 Shut-off Pressure (psig) 1350 1350 1350 1350 1350 1350 1350 1350
19 Gas Compressibility Factor
20 Mixture Density lb/ft3 45.5 10.2 46.3 36.6 43.4 2.68 46.3 36.6 62.12 60 62.12 60 62.12 60 62.12 60
21 Specific Gravity Liq. at Oper. Conditions
22 Specific Gravity Gas at Std. Conditions
23 Viscosity (cP) Liquid 0.8 1.1 0.55 1.1 0.6 0.8 0.6 0.8
24 Vapour (Wt%) 0 8 0 0.67 0 29.6 0 0.67 0 0 0 0 0 0 0 0
25 Flow type (Choked/Flashing etc.) Flashing Flashing Flashing Flashing No No No No
26 Sour Service (Yes / No) No No No No No No No No
27 K=CP/CV 1.028 1.001 1.028 1.001
28 Calculated Cv Min./Oper./Max. 0.798 0.785 1.168 8.34 0.406 0.493 2.21 9.95
29
30 Valve Body Size Note-1 1.5" (VTC) 1.5" (VTC)
31 Selected/Rated Cv VTA VTA
32 Manufacturer Refer Attached AVL with ITB Refer Attached AVL with ITB
33 Valve Type / Port Globe / Single Globe / Single
34 Trim / Bearing Material 316 SS compliant (Note 4&5) 316 SS compliant (Note 4&5)
35 Body Material ASTM A216 GR WCB ASTM A-182 GR.F316L
BODY

36 END Connection (Inlet/Outlet) RF Flanged / RF Flanged (ASME B 16.5) RF Flanged / RF Flanged (ASME B 16.5)
37 Valve Stem Packing Teflon / * VTA Teflon / * VTA
38 Control Characteristic / Rangeability Linear / VTA Linear/ VTA
39 Seat Material Note - 5 316 SS 316 SS
40 Plug Note - 5 316 SS 316 SS
41 Shaft Note - 5 316 SS 316 SS
42 Fail (Open / Close) Fail Close Fail Close
43 Leakage Rate (Class to ASME FCI 70-2) Class IV Class IV
44 Comply to NACE Standard Not Required Not Required
45 Actuator Type Spring Diaphragm Spring Diaphragm
46 Actuator Size * VTA * VTA
ACTUATOR

47 Air Connection Size 1/4" NPT 1/4" NPT


48 Actuator Action Air to Open Air to Open
49 Failure Action Close Close
50 Available Air Supply 60-100 Psig 60-100 Psig
51 Valve Duty (On/Off or Throttle) Throttle Throttle
52 Type SMART Electropneumatic SMART Electropneumatic
53 Enclosure Type Aluminium / IP 65 Aluminium / IP 65
54 Input Signal Range 3-15 PSI 3-15 PSI
55 Output Signal 4- 20 mA, 24 VDC with HART 4- 20 mA, 24 VDC with HART
POSITIONER

56 Action Direct Direct


57 Air Supply Pressure / Air Connection 60 Psig / VTA 60 Psig / VTA
58 Air Regulator / Manufacturer Yes / 1/ 2 " NPT (F) Yes / 1/ 2 " NPT (F)
59 Gauges Yes Yes
60 Travel Stop / Handwheel / Solenoid Valve Not Required Not Required
61 Electrical Classification / Protection Exd IIC T6 Exd IIC T6
62 Cable Connection M 20 x 1.5 M 20 x 1.5
63 Solenoid Valve Yes Yes
64 Tag No. SY-2019 SY-2020
SOLENOID

65 Material Stainless Steel Stainless Steel


66 Size 1/2" NPT 1/2" NPT
67 Solenoid Rating 24 VDC, ч5Watt 25 VDC, ч5Watt
68 Enclosure Class IP66, EEx d IP66, EEx d
69 Reset No Local Reset No Local Reset
70 NOTES:

1- Vendor to check selection/sizing and materials of valve and actuator and may change body size and to return one completed copy to purchaser with quotation.

2- Vendor shall provide SS Tag attached with SS Screws or SS Wire. Tag shall contain Tag No. & Model No.

3- Noise level shall not be above 85DB. Supplier shall provide noise solution for valve having noise level above 85DB.

4- Vendor to calculate and verify the body size and valve Cv. The trim may be varied as per sizing condition.

5- For flashing service hard face trim material shall be used.

*VTA = Vendor To Advise


DATA SHEET NO. DS-INS-2004
SHEET 1 of 2
DATE 18-Sep-19
LEVEL GAUGE GLASS REV. 0
PREPARED BY MNF
CHECKED BY AMF
APPROVED BY FAS
OWNER: PAKISTAN PERTROLEUM LIMITED (PPL)
PROJECT: BENARI X1 DEVELOPMENT PROJECT
1 Tag Number LG-2028 LG-2029
2 Service V-2000 (Water Side) V-2000 (Condensate Side)
3 P&ID No. PID-2000 PID-2000
4 PROCESS SERVICE CONDITIONS
5 Level / Interface Measurement Level Level
6 Sp. Gravity Upper Liq../ Sp. Gravity Lower Liq 0.7-1.0 0.7-0.8
7 Pressure Max. (psig) 1100 1100
8 Pressure Oper. (psig) 50 50
9 Pressure Min. (psig) 20 20
10 Temperature Max. (°F) 135 135
11 Temperature Oper. (°F) 100 100
12 Temperature Min. (°F) 0 0
13 GAUGE GLASS
14 Type (Transparent/Reflex) Transparent Reflex
15 No. of Sections Mfg. Std. Mfg. Std.
16 Overall Length Note - 2 (Inches) Mfg. Std. Mfg. Std.
17 Length of Each Section (Inches) Mfg. Std. Mfg. Std.
18 Visible Glass Length (Inches) 24 24
19 Connection Size ¾" NPT ¾" NPT
20 Connection Location Top & Bottom Top & Bottom
21 Body Material SS SS
22 Body Rating/Flange Rating 600 #, RF 600 #, RF
23 Glass Material Tempered Borosilicate Tempered Borosilicate
24 GAUGE COCKS
25 Type and Construction Ball check valve Ball check valve
26 Valve Pattern Offset Offset
27 Connection Size for Vessel/Bridle Flanged 3/4" Flanged 1"
28 Connection Type for Vessel Flanged Spherical Union Flanged Spherical Union
29 Connection Size for Gauge ¾" NPT ¾" NPT
30 Connection Type for Gauge NPT(F) Union with Nipples NPT(F) Union with Nipples
31 Connection Size for Vent ½" NPT(F) Plugged ½" NPT(F) Plugged
32 Connection Size for Drain ½" NPT(F) Plugged ½" NPT(F) Plugged
33 Body Material SS SS
34 Trim Material Note-5 SS SS
35 Packing Material PTFE / Mfg. Standard PTFE / Mfg. Standard
36 Ball Checks / Renewable Yes / Yes Yes / Yes
37 Bonnet Type Standard Standard
38 Closing Quick Quick
39 Flange Center To Center Distance Note-4 (Inches) As per Visibile Glass Length As per Visibile Glass Length
40 ACCESSORIES
41 Calibrated Scale (Inches) Yes Yes
42 Illuminators Required No No
43 NACE Compliance Note-5 No No
44 NOTES:
1- All Threaded connection according to NPT B1.20.1 unless otherwise specified.
2- Vent and Drain shall be provided with Plug .
3- Vendor to quote and supply the gauge glass and gauge cocks in single assembly.
4- Center to center distance between gauge cock flanges for mounting on Vessel.
5- Vendor shall provide SS Tag attached with SS Screws or SS Wire. Tag shall contain Tag No. & Model No.
6- Vendor to ensure that instrument trim material shall be compatiable with the composition
* VTA = Vendor To Advise
DATA SHEET NO. DS-INS-2005
SHEET 1 of 1
DATE 18-Sep-19
PRESSURE INDICATOR REV. 0
PREPARED BY MNF
CHECKED BY AMF
APPROVED BY FAS
OWNER: PAKISTAN PERTROLEUM LIMITED (PPL)
PROJECT: BENARI X1 DEVELOPMENT PROJECT
1 Tag Numbers PI-2023

2 Service PRODUCTION SEPARATOR

3 Line No.or Equipment No. V-2000

4 P&ID No. PID-2000

5 PROCESS SERVICE CONDITIONS

6 State Gas

7 Pressure Max. (psig) 1350

8 Pressure Oper. (psig) 200-250

9 Pressure Min. (psig) 50

10 Temperature Max. (°F) 135

11 Temperature Oper. (°F) 100

12 Temperature Min. (°F) 0

13 GENERAL
14 Pressure Gauge Type Direct Reading
15 Dial Size (mm) 150
16 Case Material 316SS
17 Display Unit Psig
18 Mounting Note - 2 Direct
19 Measuring Element Bourdon Tube
20 Blowout Disc Yes
21 Solid Front Yes
22 Measuring Range (psig) 0-1400
23 Over Range Protection >=1.5 Times of P (range)
24 Connection Note - 2 ½" NPT (M)
25 Connection Location Note - 2 Bottom
26 Accuracy ±1% of Full Scale
27 Case Protection IP55
28 Micrometer Adjustable Pointer Yes
29 Element Material 316SS
30 Movement Material 316SS
31 Socket Material 316SS
32 Background Colour White
33 Numerical Colour Black
34 Lens Safety Laminated Glass
35 Case liquid Filling Yes
36 MANIFOLD
37 Manifold Type 2 Valve
38 Manifold Material 316 SS
39 Mounting Note - 2 Inline Direct Mount
40 Packing Material Note - 3 PTFE
41 Instrument Connection Note - 2 ½" NPT (M)
42 Process Connection ½" NPT (F)
43 ACCESSORIES
44 SS Tag Note - 1 Yes
45 Manufacturer Model No. * VTA
46 Syphon Required Yes
47 NACE Compliance Note - 4 No
48 NOTES:
1 - Vendor shall provide SS Tag attached with SS Screws or SS Wire. Tag shall contain Tag No. & Model No.
2 - Vendor shall ensure that the pressure indicator process connection and manifold connection shall be compatible with each other.
3 - Pressure rating shall be compatible with mentioned pressure range.
4 - Vendor to ensure that instrument trim material shall be compatiable with the composition
* VTA = Vendor
DATA SHEET NO. DS-INS-2006
SHEET 1 of 1
DATE 15-Apr-19
PRESSURE TRANSMITTER REV. 0
PREPARED BY AMF
CHECKED BY MNF
APPROVED BY FAS
PAKISTAN PERTROLEUM LIMITED (PPL)
BENARI X1 DEVELOPMENT PROJECT
1 Tag Number PT-2016 PT-2024

2 Service downstream of PCV-2016 At Production Separator

3 Line No. or Equipment No. 10"-GRG-202-D2C-B V-2000

4 P&ID No. PID-2000 PID-2000

5 PROCESS SERVICE CONDITIONS


6 State Gas + Oil+ Water Gas + Oil+ Water

7 Pressure Max. (psig) 1350 1350

8 Pressure Oper. (psig) 250 250

9 Pressure Min. (psig) 50 50

10 Temperature Max. (°F) 135 135

11 Temperature Oper. (°F) 100 100

12 Temperature Min. (°F) 0 0

13 TRANSMITTER
14 Digital Indicator Yes Yes

15 Unit Psig Psig

16 Mounting Note - 2 Direct Direct

17 Calibrated Range (psig) 0-1450 0-1450

18 Measuring Range Limit (psig) =/> Twice of Calibrated Range =/> Twice of Calibrated Range

20 Power Supply (Loop Powered) 24 VDC 24 VDC

21 Output Signal 4-20 mA with HART protocol 4-20 mA with HART protocol

22 Accuracy 0.075 % of Calibrated Span 0.075 % of Calibrated Span

23 Instrument Process Connection Note - 3 ½" NPT (F) ½" NPT (F)

24 Electrical Connection Note - 3 M20 x 1.5 M20 x 1.5

25 MEASURING ELEMENT
26 Pressure Element Type Diaphragm Diaphragm

27 Element Material 316 SS 316 SS

28 Fill Fluid Silicone Silicone

29 ENCLOSURE
30 Enclosure Material Cast Aluminum Cast Aluminum

31 Enclosure Protection Rating IP65 IP65

32 Tropicalization Yes Yes

33 Electrical Classification Intrinsically Safe Ex (ia) IIC T6 Intrinsically Safe Ex (ia) IIC T6

34 MANIFOLD
35 Manifold Type Note - 2 2 Valve - 316 SS 2 Valve - 316 SS

36 Instrument Connection Note - 3 ½" NPT (F) ½" NPT (F)

37 Process Connection Note - 3 ½" NPT (F) ½" NPT (F)

38 ACCESSORIES
39 SS Tag Required Note - 1 Yes Yes

40 Cable Gland Required No No

41 NACE Compliance Note - 5 No No

42 NOTES:

1- Vendor shall provide SS Tag attached with SS Screws or SS Wire. Tag shall contain Tag No. & Model No.

2- Vendor shall provide accessories required to mount the transmitter on 2" Pipe Stanchion such as bracket, U Bolts for remote mounting.

3- Vendor shall provide Ex'd' metallic plugs for spare electrical connection.

4- Pressure Transmitter shall have multiple selectable standard engineering units e.g. BAR, KPA,PSI etc.

5- Vendor to ensure that instrument trim material shall be compatiable as per gas composition.

VTA = Vendor To Advise


DATA SHEET
DS-INS-2008
NO.
SHEET 1 of 1
SENIOR ORIFICE FITTING / METER TUBE DATE 11-Sep-19
REV. 0
PREPARED BY MNF
PAKISTAN PETROLEUM LIMITED CHECKED BY AMF
BENARI X1 DEVELOPMENT PROJECT APPROVED BY FAS
1 Meter Tag No. FE-2021, FE-2022
2 Quantity 2 Nos.
3 Station Sajawal Gas Facility
GENERAL 4 Service Raw Natural Gas
5 Line Size (Inches) NB / ID 6" / 5.761"
6 Line sch Sch XS
7 Piping Class D2C
8 Station Flow Rate (Min/Nor/Max) MMscfd 1.0/9.0/20.0
9 Stream Flow Rate (Min/Nor/Max) MMscfd 1.0/9.0/20.0
10 Operating Pressure (Min/Nor/Max) psig 50 / 250 / 1000
11 Operating Temperature (Min/Nor/Max) deg F 85 / 100 / 135
12 Design Pressure psig 1350
13 Design Temperature (Min/Max) deg F 150
PROCESS 14 Molecular Weight 18-20
CONDITIONS 15 Gas Composition Refer to ITB
16 Fluid Raw Gas
17 Specific Heat ratio (Cp/Cv) 1.334 - 1.5
18 Density lb/ft3 0.85-3.5
19 Viscosity cp 0.01235-0.0140
20 Compressibility (Min/Max) 0.88-0.96
21 Type Concentric, square edged
22 Flatness & roundness As per AGA3, April 2000
23 Orifice Plate Size 5.761"
24 Beta ratio VTS
25 Orifice Bore Dia VTS
ORIFICE 26 Plate material 316 Stainless Steel Material
PLATES 27 Plate Qty 2
28 Sealing Teflon
29 Plate thickness 0.125 Inch
30 Vent / drain hole Yes
31 Meter max. differential 250 in WC (VTC)
32 Pressure Drop Meter / Profiler 119.30 in WC (VTC)
33 Manufacturer Refer to AVL attached with ITB
34 Type Senior Orifice Flangnek
35 Upstream outer end connection Butt weld to meter tube
36 Downstream outer end connection 6 Inch ANSI 600# RF
37 No. of pressure tapings Two set of tappings on each side
38 Size & type of pressure tapings 2 sets - 1/2" NPT on both sides (FOR DPIT, PIT & CHART RECORDER)
39 Downstream nozzles Please refer general note No 8
ORIFICE 40 Orifice fittings ASTM A216 WCB
FITTINGS 41 Stud/bolts A193-B7 / A194 2H
42 Manufacturer / Model Refer to AVL attached with ITB
43 Painting As per Painting Spec (Doc. No.: 32618-195-05-SP-003)
44 Tag plate Required. SS316/L material
45 Design code AGA 3, April 2000
46 Operating Wrench Orientation Both Sides
47
48 Meter Tube 3-Section meter tube
49 Size and End connection: 6" Sch XS, ANSI 600# RF
50 Flange / Pipe Material : A105 N / A106 Gr B
51 Stud/bolts : Galvanised or Teflon coated
53
METER TUBE 54 Painting Refer to ITB
AND PROFILER 55 Profiler plate Required;
56 Make / Model Number Refer to AVL attached with ITB
57 Size To be mounted between two 6" ANSI 600# RF Flanges
58 Material SS316/L
59 Qty 2 sets
Notes
1 This specification covers the minimum requirements for the Design & Supply of senior orifice fittings for Benari X1 Development Project
The latest editions of the standards / codes shall be referred. Pipe flanges, Flange fittings and finish, Orifice metering of Natural Gas and other related Hydrocarbon fluid.
2
April 2000 AGA Report No.3
3 6" sch XS SS316 profiler - 1 unit shall be supplied along with each fitting.
4 Material test certificates shall be provided as per EN10204-3.1B for Orifice fitting, meter tube and orifice plate.
5 Flange tappings shall be 1/2" NPT (2 set)
3-Section Meter Tube of 6", ANSI 600# RF Sch XS is required to be supplied along with Orifice fittings. Meter tube shall be 9.5D upstream of profiler, 7.5D downstream of
6
profiler & 4.5 D downstream of orifice fitting.
7 Surface Preparation: blasting to sa. 2.5, profile 50 ~ 60 μM:
8 Coating intergrity testing shall be achieved by the use oF holiday detector
Down stream meter tube shall be provided with 3 nos. of 1-1/2", ANSI 900#, RF, Sch XS Flange at & beyond 4.5 D for TT, TR & TG. 3/4" ANSI 600# RF Sch 160 Flange for
9 PG
10 NDE for the meter tube shall be 100% MPI for fillet weld & 100% RT reports for butt weld piping joints.
11 Stud / bolts and gaskets for meter tube shall be galvanised or Teflon coated.
12 Hydrostatic test with chart recorder shall be performed as per ASME B31.3
DATA SHEET NO. DS-INS-2009
SHEET 1 of 1

FLOW TRANSMITTER DATE


REV.
18-Sep-19
0
(TURBINE TYPE) PREPARED BY AMF
CHECKED BY MNF
APPROVED BY FAS
PAKISTAN PERTROLEUM LIMITED (PPL)
BENARI X1 DEVELOPMENT PROJECT
1 TAG NUMBER FIT-2019 FIT-2020
2 SERVICE CONDENSATE METERING WATER
3 LINE / EQUIPMENT NO. 2"-LHC-206-D2C-B 3"-LPW-207-D2C-B
4 LINE SIZE 2" 3"
5 P & ID NO. PID-2000 PID-2000
6 AREA CLASSIFICATION Class- I, Div-2, GR. IIA / IIB, T3 Class- I, Div-2, GR. IIA / IIB, T3
7 END CONNECTION RF FLANGED RF FLANGED
8 BODY RATING ANSI 600# ANSI 600#
9 INSTRUMENT FLOW RANGE (US GPM) 0 ~ 30 0 ~ 65
10 ACCURACY +/-1% OVER THE NORM. FLOW +/-1% OVER THE NORM. FLOW RANGE
11 LINEARITY +/- 1.0 % +/- 1.0 %
12 K FACTOR, CYCLE/VOLT UNIT VTA VTA
13 EXCITATION VTA VTA
METER
14 BODY MATERIAL CS CS
15 SUPPORT MATERIAL 316 SS 316 SS
16 SHAFT MATERIAL 316 SS 316 SS
17 FLANGES MATERIAL CS CS
18 ROTOR MATERIAL 316 SS 316 SS
19 BEARINGS TYPE MFR.STD MFR.STD
20 BEARING MATERIAL TUNGSTEN CARBIDE TUNGSTEN CARBIDE
21 MIN /MAX. SPEED VTA VTA
22 CALIBRATION STANDARD ON WATER STANDARD ON WATER
23 INTERNALS STANDARD STANDARD
24 PICKUP TYPE STANDARD STANDARD
25 BOSSES ONE ONE
26 MFR. / MODEL NO. - / VTA - / VTA
27 FLUID UNSTABILIZED CONDENSATE PRODUCED WATER
28 MIN.FLOW MAX. FLOW (US GPM) 1 50 1 70
29 NORMAL FLOW (US GPM) 8 5
30 PRESSURE @ FLOW MIN. / MAX. (PSIG) 50 1000 50 1000
31 DESIGN PRESSURE (PSIG) 1350 1350
FLUID DATA
32 MAX. ALLOWABLE PRESSURE DROP (PSI) VTA VTA
33 MIN. TEMP MAX.TEMP (°F) 90 135 90 135
34 DESIGN TEMP. (°F) 150 150
35 VISCOSITY (CP) DENSITY (IB/FT3) 0.8-1.1 42~50 0.6-1.0 60-62
36 VAPOR PRESSURE (PISA) 65-980 6-215
37 SECONDARY INSTRUMENT TAG NO. N/A N/A
38 PREAMPLIFIER INTEGRAL INTEGRAL
39 FUNCTION SMART TRANSMITTER SMART TRANSMITTER
40 MOUNTING DIRECT ON TURBINE DIRECT ON TURBINE
SECONDARY
41 POWER SUPPLY 24VDC, 2 - WIRE LOOP POWERED 24VDC, 2 - WIRE LOOP POWERED
INSTRUMENT
42 ENCLOSURE MATERIAL ALUMINUM ALUMINUM
43 OUTPUT RANGE 4-20 MA 4-20 MA
44 AREA CERTIFICATION EEx'd' EEx'd'
45 SECONDARY INSTR. MODEL NO. VTA VTA
46 TOTALIZER TYPE
46 COMPENSATION
BATCH 47 PRESET COUNTER
CONTROLLER 48 ENCLOSURE CLASS
OPTIONS 49 STRAINER SIZE AND MESH
50 LOCATION
51 TAG NUMBER
NOTES
1. VTA: VENDOR TO ADVISE.

2. TURBINE FLOW METER SHALL BE PROVIDED WITH 316 SS IDENTIFICATION TAG PLATE PERMANENTLY ATTACHED.
3. ELECTRICAL ENTRY SHALL BE M20 WITH "EEXD" CERTIFIED PLUGS.
4. INDICATOR DISPLAY SHALL READ DIRECTLY IN ENGINEERING UNITS.
5. ROTOR HUBS, BLADES, AND RIMS MATERIAL SHALL BE OF 316SS AS MINIMUM.
DATA SHEET NO. DS-INS-2010
SHEET 1 OF 1

TEMPERATURE DATE
REV.
18-Sep-19
0
INDICATOR PREPARED BY AMF
CHECKED BY MNF
APPROVED BY FAS
PAKISTAN PERTROLEUM LIMITED (PPL)
BENARI X1 DEVELOPMENT PROJECT
1 Tag Number TW/TI-2025

2 Service Three Phase Separator

3 Line No / Vessel No. V-2000

4 P&ID No. PID-2000

5 PROCESS SERVICE CONDITIONS

6 State Three Phase (Gas/Oil/Water)

7 Pressure Max. (psig) 1000

8 Pressure Oper (psig) 250

9 Pressure Min (psig) 50

10 Temperature Max. (°F) 150

11 Temperature Oper. (°F) 100

12 Temperature Min. (°F) 20

13 GENERAL

14 Element Type Bimetallic Sensor

15 Range (°F) 0-300

16 Dial Size (mm) 150

17 Case Material 316SS

18 Case Protection IP55

19 External Pointer Adjustment Yes

20 Accuracy ±1% of Full Span

21 Background Color White

22 Numerical Color Black

23 Window Transparent Glass shatter proof

24 THERMOWELL

25 Thermowell Type Flanged

26 Material 316 SS

27 Process Connection 1 ½ " Flanged

28 Flange Rating / Class 600 #, RF

29 Instrument Connection at Thermowell ½ " NPT(F)

30 Construction Solid Bar Stock

31 Insertion length (U-Dim.) (mm) 300

32 Lagging Extension (T-Dim.) (mm) VTA

33 ACCESSORIES

34 SS Tag Note - 1 Yes

35 NACE Compliance Note - 4 No

36 NOTES:

1- Vendor shall provide SS Tag attached with SS Screws or SS Wire. Tag shall contain Tag No. & Model No.

2- Vendor to provide complete assembly with thermometer and thermowell.

3- Well length must suit stem length. Thermowell outer diameter shall match with mounting flange inner diameter.

4- Vendor to ensure that instrument trim material shall be compatiable with the process fluids.