SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Pre-pour Inspection for Type I - V Fences SAIC-M-1004 30-Apr-17 CIVIL-
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Dimensions of Footings:
Type of post Diameter of Footing Height of
Footing
Corner Post 300 mm 1075 mm
End Post 300 mm 1075 mm AC-036680
A2
Gate Post 300 mm 1075 mm Sht. No.1
Line Post 250 mm 1075 mm
Brace Post 250 mm 940 mm
The cover of the concrete to the reinforcing bars shall not be less AA-036680
A4
than 75mm for fence anchor blocks except for top protrusions. Sht. No. 1
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Entering point of galvanized post or brace into the concrete shall be AA-036680
A8 coated with one coat of paint conforming to APCS-113 or APCS-22. Sht. No.1
The area affected shall be cleaned with wire brush or light sanding. Note # 2
Paint or treatment at the entering point shall extend 25mm above the AC-036681
A9
concrete and 125mm into the concrete. Sht. No. 1
Type I, II, III, IV and V fence posts shall be extend at least 975mm
into concrete footings and have 100mm concrete footing cast below AA-036680
A10
their ends except special gate posts which shall extend a minimum Sht. No.1
of 1220mm into the concrete.
Type VI corner and gate posts shall be extend 450mm into the
AC-036681
A11 concrete, line posts 550mm into the concrete and brace posts
Sht. No. 1
530mm into the concrete.
AC-036680,
The minimum cover at the bottom of all Posts shall be 100mm,
Sht.1
A12 except type IV corner and gate posts, which shall have 200mm's
& AC-036681,
concrete cover. (SASD AC-036680, Sht. 1 and AC-036681, Sht. 1)
Sht. 1
The minimum cover on all sides of the foundations and anchor block AC-036680
A13
shall be 75mm. Sht. No.1
REMARKS:
REFERENCE DOCUMENTS:
1- SAES-Q-001 -- Criteria for Design and Construction of Concrete Structures, 15 May 2010
2- SAES-M-006 -- Saudi Aramco Security and General Purpose Fencing, 04 July 2010
3- AB-036677, Sht. 1 -- An Overview(Architectural), Saudi Aramco Security and General Purpose Fencing, 01 April 1990
4- AC-036681, Sht. 1 -- Perimeter Fencing for On-Shore Helipads, Footing Details, Type IV Fence, 01 July 1992
5- AC-036680, Sht. 1 -- Saudi Aramco Security and General Purpose Fencing, Footing Details, 01 April 1997