C138/C138M – 10b
Yd = volume of concrete which the batch was designed to TABLE 1 Capacity of Measures
produce, yd3 or m3 Nominal Maximum Size
Capacity of MeasureA
of Coarse Aggregate
Yf = volume of concrete produced per batch, ft3
V = total absolute volume of the component ingredients in. mm ft3 L
in the batch, ft3 or m3 1 25.0 0.2 6
Vm = volume of the measure, ft3 or m3 1 1⁄ 2 37.5 0.4 11
2 50 0.5 14
NOTE 2—The theoretical density is, customarily, a laboratory determi- 3 75 1.0 28
4 1⁄ 2 112 2.5 70
nation, the value for which is assumed to remain constant for all batches
6 150 3.5 100
made using identical component ingredients and proportions. It is calcu-
A
lated from the following equation: The indicated size of measure shall be used to test concrete containing
aggregates of a nominal maximum size equal to or smaller than that listed. The
T 5 M/V (1) actual volume of the measure shall be at least 95 % of the nominal volume listed.
mm] thick with a length and width at least 2 in. [50 mm]
4.1 Balance—A balance or scale accurate to 0.1 lb [45 g] or
greater than the diameter of the measure with which it is to be
to within 0.3 % of the test load, whichever is greater, at any
used. The edges of the plate shall be straight and smooth within
point within the range of use. The range of use shall be
a tolerance of 1⁄16 in. [2 mm].
considered to extend from the mass of the measure empty to
4.6 Mallet—A mallet (with a rubber or rawhide head)
the mass of the measure plus its contents at 160 lb/ft3 [2600
having a mass of 1.25 6 0.50 lb [600 6 200 g] for use with
kg/m3].
measures of 0.5 ft3 [14 L] or smaller, and a mallet having a
4.2 Tamping Rod—A round, smooth, straight steel rod, with
mass of 2.25 6 0.50 lb [1000 6 200 g] for use with measures
a 5⁄8 in. [16 mm] 6 1⁄16 in. [2 mm] diameter. The length of the
larger than 0.5 ft3.
tamping rod shall be at least 4 in. [100 mm] greater than the
4.7 Scoop—of a size large enough so each amount of
depth of the measure in which rodding is being performed, but
concrete obtained from the sampling receptacle is representa-
not greater than 24 in. [600 mm] in overall length (See Note 4).
tive and small enough so it is not spilled during placement in
The rod shall have the tamping end or both ends rounded to a
the measure.
hemispherical tip of the same diameter as the rod.
NOTE 4—A rod length of 16 in. [400 mm] to 24 in. [600 mm] meets the 5. Sample
requirements of the following: Practice C31/C31M, Test Method C138/ 5.1 Obtain the sample of freshly mixed concrete in accor-
C138M, Test Method C143/C143M, Test Method C173/C173M and Test
Method C231.
dance with Practice C172.
4.3 Internal Vibrator—Internal vibrators may have rigid or 6. Procedure
flexible shafts, preferably powered by electric motors. The 6.1 Base the selection of the method of consolidation on the
frequency of vibration shall be 7000 vibrations per minute or slump, unless the method is stated in the specifications under
greater while in use. The outside diameter or the side dimen- which the work is being performed. The methods of consoli-
sion of the vibrating element shall be at least 0.75 in. [19 mm] dation are rodding and internal vibration. Rod concretes with a
and not greater than 1.50 in. [38 mm]. The length of the shaft slump greater than 3 in. [75 mm]. Rod or vibrate concrete with
shall be at least 24 in. [600 mm]. a slump of 1 to 3 in. [25 to 75 mm]. Consolidate concretes with
4.4 Measure—A cylindrical container made of steel or other a slump less than 1 in. by vibration.
suitable metal (see Note 5). The minimum capacity of the
measure shall conform to the requirements of Table 1 based on NOTE 7—Nonplastic concrete, such as is commonly used in the
the nominal size of aggregate in the concrete to be tested. All manufacture of pipe and unit masonry, is not covered by this test method.
measures, except for measuring bowls of air meters which are 6.2 Place the concrete in the measure using the scoop
also used for Test Method C138/C138M tests, shall conform to described in 4.7. Move the scoop around the perimeter of the
the requirements of Test Method C29/C29M. When measuring measure opening to ensure an even distribution of the concrete
bowls of air meters are used, they shall conform to the with minimal segregation. Fill the measure in the number of
requirements of Test Method C231, and shall be calibrated for layers required by the consolidation method (6.3 or 6.4).
2
C138/C138M – 10b
6.3 Rodding—Place the concrete in the measure in three 6.7 Cleaning and Weighing—After strike-off, clean all ex-
layers of approximately equal volume. Rod each layer with 25 cess concrete from the exterior of the measure and determine
strokes of the tamping rod when nominal 0.5-ft3 [14-L] or the mass of the concrete and measure to an accuracy consistent
smaller measures are used, 50 strokes when nominal 1-ft3 with the requirements of 4.1.
[28-L] measures are used, and one stroke per 3 in.2 [20 cm3]
of surface for larger measures. Rod each layer uniformly over 7. Calculation
the cross section with the rounded end of the rod using the 7.1 Density (Unit Weight)—Calculate the net mass of the
required number of strokes. Rod the bottom layer throughout concrete in pounds or kilograms by subtracting the mass of the
its depth. In rodding this layer, use care not to damage the measure, Mm, from the mass of the measure filled with
bottom of the measure. For each upper layer, allow the rod to concrete, Mc. Calculate the density, D, ft3 or yd3,by dividing
penetrate through the layer being rodded and into the layer the net mass of concrete by the volume of the measure, Vm as
below approximately 1 in. [25 mm]. After each layer is rodded, follows:
tap the sides of the measure 10 to 15 times with the appropriate D 5 ~Mc – Mm!/Vm (2)
mallet (see 4.6) using such force so as to close any voids left
by the tamping rod and to release any large bubbles of air that 7.2 Yield—Calculate the yield as follows:
may have been trapped. Add the final layer so as to avoid Y~yd3! 5 M/~D3 27! (3)
overfilling. or
6.4 Internal Vibration—Fill and vibrate the measure in two
approximately equal layers. Place all of the concrete for each Y~m3! 5 M/D (4)
layer in the measure before starting vibration of that layer. 7.3 Relative Yield—Relative yield is the ratio of the actual
Insert the vibrator at three different points for each layer. In volume of concrete obtained to the volume as designed for the
compacting the bottom layer, do not allow the vibrator to rest batch (see Note 10) calculated as follows:
on or touch the bottom or sides of the measure. In compacting Ry 5 Y/Yd (5)
the final layer, the vibrator shall penetrate into the underlying
layer approximately 1 in. [25 mm]. Take care that the vibrator NOTE 10—A value for Ry greater than 1.00 indicates an excess of
concrete being produced whereas a value less than this indicates the batch
is withdrawn in such a manner that no air pockets are left in the
to be “short” of its designed volume. In practice, a ratio of yield in cubic
specimen. The duration of vibration required will depend upon feet per cubic yard of design concrete mixture is frequently used, for
the workability of the concrete and the effectiveness of the example, 27.3 ft3/yd3.
vibrator (see Note 8). Continue vibration only long enough to
7.4 Cement Content—Calculate the actual cement content
achieve proper consolidation of the concrete (see Note 9).
as follows:
Observe a constant duration of vibration for the particular kind
of concrete, vibrator, and measure involved. C 5 Cb /Y (6)
3
C138/C138M – 10b
National Ready Mixed Concrete Association.4 The data repre- 9.1.2 Multi-Operator Precision—The multi-operator stan-
sent concrete mixtures with slump ranging from 3 to 6 in. [75 dard deviation of density of freshly mixed concrete has been
to 150 mm] and density ranging from 115 to 155 lb/ft3 [1842 to found to be 0.82 lb/ft3 [13.1 kg/m3] (1s). Therefore, results of
2483 kg/m3] and included air-entrained and non air-entrained two properly conducted tests by the two operators on the same
concrete. The study was conducted using 0.25 ft3 [7-L] and 0.5 sample of concrete should not differ by more than 2.31 lb/ft3
ft3 [14-L] measures. [37.0 kg/m3] (d2s).
9.1.1 Single-Operator Precision—The single operator stan- 9.2 Bias—This test method has no bias since the density is
dard deviation of density of freshly mixed concrete has been
defined only in terms of this test method.
found to be 0.65 lb/ft3 [10.4 kg/m3] (1s). Therefore, results of
two properly conducted by the same operator on the same
10. Keywords
sample of concrete should not differ by more than 1.85 lb/ft3
[29.6 kg/m3] (d2s). 10.1 air content; cement content; concrete; relative yield;
unit weight; yield
4
Mullings, G. M., NRMCA/NAA Joint Research Lab Study “Series D324
Accuracy of Concrete Density Test,” Feb. 17, 2000.C09
SUMMARY OF CHANGES
Committee C09 has identified the location of selected changes to this test method since the last issue,
C138/C138M–10a, that may impact the use of this test method. (Approved October 1, 2010)
Committee C09 has identified the location of selected changes to this test method since the last issue,
C138/C138M–10, that may impact the use of this test method. (Approved July 1, 2010)
Committee C09 has identified the location of selected changes to this test method since the last issue,
C138/C138M–09, that may impact the use of this test method. (Approved June 15, 2010)
Committee C09 has identified the location of selected changes to this test method since the last issue,
C138/C138M–08, that may impact the use of this test method. (Approved June 1, 2009)
(1) Revised 4.2 to alter requirements of tamping rod. (3) Revised 6.3 to alter wording of tamping rod use.
(2) Added Note 4 describing acceptable tamping rod length.
ASTM International takes no position respecting the validity of any patent rights asserted in connection with any item mentioned
in this standard. Users of this standard are expressly advised that determination of the validity of any such patent rights, and the risk
of infringement of such rights, are entirely their own responsibility.
This standard is subject to revision at any time by the responsible technical committee and must be reviewed every five years and
if not revised, either reapproved or withdrawn. Your comments are invited either for revision of this standard or for additional standards
and should be addressed to ASTM International Headquarters. Your comments will receive careful consideration at a meeting of the
responsible technical committee, which you may attend. If you feel that your comments have not received a fair hearing you should
make your views known to the ASTM Committee on Standards, at the address shown below.
This standard is copyrighted by ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959,
United States. Individual reprints (single or multiple copies) of this standard may be obtained by contacting ASTM at the above
address or at 610-832-9585 (phone), 610-832-9555 (fax), or service@astm.org (e-mail); or through the ASTM website
(www.astm.org). Permission rights to photocopy the standard may also be secured from the ASTM website (www.astm.org/
COPYRIGHT/).