For this project, background color of the graphic page shall be Light Grey.
Title
Title of the graphic page will be in white color and background color will be in
Blue color. The text will have 24-pixel height, Arial font and bold. Following fig
shows the Title of the graphic page. For other text size and fonts refer
summary below.
Title
Graphic
window
Low, High : Yellow blinking till alarm ACK & then steady.
High High, Low Low : Red blinking till alarm ACK & then steady.
Input/output open : Magenta blinking till alarm ACK & then steady.
B. Digital Alarms
HI or LO Yellow
HH or LL Red
CONTROLLER
HI or LO Yellow
HH or LL Red
Normal
Green
Condition
HH or LL
Red
Alarm
Condition
HI or LO
Yellow
Alarm
Condition
Calibration
Cyan
Mode
FANS
Running- Green Color, rotation effect As applicable.
Stopped – Background Color, no rotation effect
Abnormal Condition
Yellow Flashing
Trip condition-Red flashing
IDFAN
VALVES
OPEN – Green Color AS per CS
CLOSE- Background Color library.
Note : Applicable only for valves with limit
switch
CONTROL VALVES – FAIL OPEN
Modifier based on Limit switches (If applicable). AS per CS
OPEN-Green Color library.
CLOSE– Background Color
Position indication
25 %
Note: For pumps, Auto/Manual and Local/Remote indication ll be provided. When interlock acts a lock
shall appear below the pump stating that interlock has acted and clicking on it shall open a window