Sei sulla pagina 1di 8

4.

5 Colors For Process Line / Utility Line

Process Line Colors

SRI RENUKA SUGARS LTD.


GUJARAT REFINERY
Doc. No. BS11-DS1-HMI

Rev 00 Page 54 of 109


FUNCTIONAL DESIGN SPECIFICATION FOR HMI
SRI RENUKA SUGARS LTD.
GUJARAT REFINERY
Doc. No. BS11-DS1-HMI

Rev 00 Page 55 of 109


FUNCTIONAL DESIGN SPECIFICATION FOR HMI
4.6 Graphic window Background color

For this project, background color of the graphic page shall be Light Grey.

Title
Title of the graphic page will be in white color and background color will be in
Blue color. The text will have 24-pixel height, Arial font and bold. Following fig
shows the Title of the graphic page. For other text size and fonts refer
summary below.

Title

GRAPHIC NAME Background

Graphic
window

b. Summary of Text Color Display on Graphics

ITEM COLOR SIZE

1. TITLE WHITE with BLUE background 24 – ARIAL – BOLD

2. TAG NUMBER Black 14 – ARIAL – BOLD

3. ENGINEERING UNIT Black 12 – ARIAL

4. PROCESS LINE CONTINUATION


Black 12 – ARIAL
DESCRIPTION
5. EQUIPMENT Black (Outside the Equipment)
14 – ARIAL – BOLD
NUMBER/DESCRIPTION Black (Inside the equipment)

6. PUMP NUMBERS Black 14 – ARIAL – BOLD

SRI RENUKA SUGARS LTD.


GUJARAT REFINERY
Doc. No. BS11-DS1-HMI

Rev 00 Page 56 of 109


FUNCTIONAL DESIGN SPECIFICATION FOR HMI
4.7 Color Modifier Specification

A. For all Process Data

Font & size : Arial Bold, size 14

Normal condition : Black

Low, High : Yellow blinking till alarm ACK & then steady.

High High, Low Low : Red blinking till alarm ACK & then steady.

Input/output open : Magenta blinking till alarm ACK & then steady.

Velocity/Deviation : Yellow blinking till alarm ACK & then steady.

Calibration/Under Maintenance : Cyan

B. Digital Alarms

Normal Condition - Transparent


DIGITAL TAGNAME
Alarm Condition - RED Color blinking till ACK.

SRI RENUKA SUGARS LTD.


GUJARAT REFINERY
Doc. No. BS11-DS1-HMI

Rev 00 Page 57 of 109


FUNCTIONAL DESIGN SPECIFICATION FOR HMI
4.8 Color modifier scheme for Indicators , Controllers and Level
Bar
INDICATORS

Item Color Symbol

Normal Condition Black

HI or LO Yellow

HH or LL Red

Calibration Mode Cyan

Input/output open Magenta

CONTROLLER

Item Color Symbol

Normal Condition Black

HI or LO Yellow

HH or LL Red

Calibration Mode Cyan

Input/output open Magenta

SRI RENUKA SUGARS LTD.


GUJARAT REFINERY
Doc. No. BS11-DS1-HMI

Rev 00 Page 58 of 109


FUNCTIONAL DESIGN SPECIFICATION FOR HMI
NOTE : “M” indicates Manual Mode of the Controller, same will change to “A” for Auto
Mode.

Color modifier scheme for Level Bar

Item Appearance Description

Normal
Green
Condition

HH or LL
Red
Alarm
Condition

HI or LO
Yellow
Alarm
Condition

Calibration
Cyan
Mode

SRI RENUKA SUGARS LTD.


GUJARAT REFINERY
Doc. No. BS11-DS1-HMI

Rev 00 Page 59 of 109


FUNCTIONAL DESIGN SPECIFICATION FOR HMI
4.9 Color modifier scheme for Pump

SYMBOL COLOUR/MODIFER SIZE


PUMPS
Running- Green Color, rotation effect As applicable.
Stopped – Background Color, no rotation effect
Abnormal Condition
Yellow Flashing
Trip condition-Red flashing

FANS
Running- Green Color, rotation effect As applicable.
Stopped – Background Color, no rotation effect
Abnormal Condition
Yellow Flashing
Trip condition-Red flashing
IDFAN

VALVES
OPEN – Green Color AS per CS
CLOSE- Background Color library.
Note : Applicable only for valves with limit
switch
CONTROL VALVES – FAIL OPEN
Modifier based on Limit switches (If applicable). AS per CS
OPEN-Green Color library.
CLOSE– Background Color

CONTROL VALVES – FAIL CLOSE


Modifier based on controller output or Position AS per CS
feedback. library.
OPEN - Green Color , MV > 0.1 %
CLOSE – Background Color, MV <=
0.1%

INCHING TYPE MOTORIZED VALVE


As applicable.
M OPEN-Green Color
CLOSE–Red Color

Position indication

25 %

SRI RENUKA SUGARS LTD.


GUJARAT REFINERY
Doc. No. BS11-DS1-HMI

Rev 00 Page 60 of 109


FUNCTIONAL DESIGN SPECIFICATION FOR HMI
SYMBOL COLOUR/MODIFER SIZE
MOTORISED VALVES
OPEN-Green Color As applicable.
CLOSE– Background Color
Moving Towards Open
M Green Flashing.
Moving Towards Close
Red Flashing.
Abnormal -
Yellow Color & blinking Till ACK.
DIVERTOR VALVES
Common portion-Green As applicable.
Open portion – Green
Close Portion – Red
(Modifier shall be provided based on Digital inputs
as applicable)
SOLENOID VALVE
OPEN-Green Color As applicable.
CLOSE– Background Color
s Abnormal
Yellow Color blinking till ACK (if limit switches are
available).

Note: For pumps, Auto/Manual and Local/Remote indication ll be provided. When interlock acts a lock
shall appear below the pump stating that interlock has acted and clicking on it shall open a window
showing all the interlock conditions and the acted condition flashing in red.

4.10 Dynamic Data Display

Process data will be shown as per the following table:


Note: The Engineering units will be followed as per the I/O list.

Range Numeric Decimal


Characters Places
0~1000
4 or above 0
or above
0~100 3 1
0~10 2 2
0~1 1 3

Ex: Range 0-9999 : 0-9999


Range 0-999 : 0.0-999.0
Range 0-9 : 0.000-9.000

SRI RENUKA SUGARS LTD.


GUJARAT REFINERY
Doc. No. BS11-DS1-HMI

Rev 00 Page 61 of 109


FUNCTIONAL DESIGN SPECIFICATION FOR HMI