TEST CERTIFICATE FOR TRANSFORMER

Date : 11 /02/2015
CUSTOMER
KVA 315 No load Voltage (Volts) :- HV 11000 Sr. No. EAI/1502/121
Phases 3 LV 415 Type Outdoor
Freqyency 50Hz Full load Current (Amps) :- HV 16.53
Vector Group yyn LV 253
WDG. Mtl. cu Connection :- Delta /Star
Cooling ONAN Temp. Rise :- In Oil : 45°C
In Winding : 50°C by Resistance .
VOLTAGE RATIO
TAP POSITION 1 2 3 4 5
1u1v - 2u2n 26.59 26.00 25.37 24.69 24.10
1v1w - 2v2n 26.58 25.99 25.35 24.68 24.08
1w1u - 2w2n 26.57 25.99 25.34 24.66 24.07
No load losses at rated Current and Frequency 580 Watts
Copper Losses at rated Current and Frequency 3250 Watts
Impedance at 75 'C .4.5%

Insulation Resistance with 2500 volts meggar at: 28°C


LV - Earth 2000 mega ohms
HV - Earth 2000 mega ohms
HV - LV 2500 mega ohms
Separate Source Voltage withstand Test HV to LV & Earth 21KV rms for 60 seconds withstood - OK
LV to HV & Earth 3 KV rms for 60 seconds withstood - OK
Induced Over Voltage withstand Test 500 voltss at 100 Hz for 60 seconds withstood - OK
Dielectric Strength of Transformer Oil tested as per IS : 335 = 64.46 KV
Polarity & Vector Group as per IS : OK
Oil Leakage test at 0.8 Kg. per sq cm. for 10 Minutes : OK
All the above tests were carried out on this transformer and results were found satisfactory .