EN - RMC series

Operating Manual

Ring Main Circuit Breaker with Disconnector switch

Type : EN-RMC

Catalog No.: RMC 6107.M0


Introduction RMC 6107.M0 1 / 19

Over view
EN-RMC Series Ring Main Circuit Breaker is pad mounted fully deadfront switchgear for up to 12kV, 630A
underground system, combining disconnect switches and vacuum fault interrupters.
EN-RMC series switchgear incorporates disconnect switches for every ways to provide added safety
and faster operation.
Every bushing in this switchgear is installed with CTs and voltage sensor each, so all the electrical
values of connected distribution system can be measured.
EN-RMC series Ring Main Circuit Breaker has been fully certified in accordance with IEC 62271-100
to meet and exceed customer specifications.

Design
The EN-RMC Ring Main Circuit Breaker is a non-extensible ring main unit comprising of 4 feeders in
one common stainless steel tank.
The unit is suitable for outdoor applications and can be used either as a freestanding unit or
installed in compact mini-substations.

Stainless steel enclosure


SF6 Gas insulation media which is enclosed in stainless steel tank sealed for life and maintenance free
with less than 0.1% leakage rate per year,
The EN-RMC has normal insulation and interruption performance even at an atmospheric gas pressure.

Circuit Breaker
The circuit breaker comprises of three vacuum interrupters, which have a fault-make, fault-break rating.
Opening of the circuit breaker is achieved by opening of the manually operating push button or openig electrical
push button or via signal of the protection relay.
Motoried spring charge mechanism for Circuit Breaker.

Operation
All operating positions and instructions are indicated on the main panel at the front of the unit.
Operation is by means of manually independent mechanisms, which are mounted external to the main enclosure.
Deadfront design and mechanical interlock between main and earth switch provides a high level of safety and
efficient maintenance.

Cable test Bushings


Each cable can be easily tested with insulated cable testing bushings.

Interlocks and padlocks


Positive safety interlocks are incorporated on all switch positions to prevent mal-operation.
All switch and selector positions can be padlocked.
Introduction RMC 6107.M0 2 / 19

Typical uses
Simple outdoor substation, customer transformer substations and distribution substations
Industrial plants and underground stations

Highly Reliability
At atmospheric gas pressure, it ensure the rated insulation and interruption capabilities.
Pure puffer techniques, no leakage current path between open contacts.
Switchgear vessel made of stainless steel
Maintenance-free concept
SF6 gas insulation and vaccum interruption.(circuit breaker)
Sealed pressure system
Climate-independent

Safety
Operation interlock at front panel
Safe-to-touch and hermetically sealed enclosure
HV parts are only accessible when outgoing feeders are earthed
Overpressure relief device
Pad lock
Easy installation and operation
The speed of close/open is independent of the speed of lever movement.

Ratings
Nominal voltage 11kV
Rated voltage 12kV
Rated frequency 50Hz
Number of phases 3
Mechanical endurance 2000CO
Rated lighting impulse withstand voltage 95㎸
Rated short duration power frequency withstand voltage 28㎸
Rated short time withstand current 25kA for 3seconds
Short circuit breaking current 25kA
Rated normal current 630A
Leak rate Less than 0.1% per year
Rated filling pressure 0.03 Mpa
Protection class IP56
Features - Front view RMC 6107.M0 3 / 19

Front view
Ring main Circuit breaker
3-Position off-load disconnector
Voltage detection system
Ergonomic mimic diagram
Vacuum interrupters for circuit breaker
Common stainless steel chamber
Full insulation ratings at zero atmospheric pressure

3-Position off-load disconnector with VCB is used for cable earthing.


The disconnector is placed between busbar and VCB such that VCB can be used for cable earthing
when disconnector is in earth position.
Features - Side view RMC 6107.M0 4 / 19

Side view
Cable box(rear side)
Cable test bushing(upper side)

All parts of the main circuit is inside SF6 tank except cables and CTs.
Provision for cable termination is made through seal off bushings at the bottom of switchgear
on the same height, parallel , on equal distance as from the ground and is accessible from the rear of
the RMU and protected by cable box covers. Ring type CTs to be assembled on the seal off bushings.
Features - Operating panel RMC 6107.M0 5 / 19

Operating panel

Voltage indicator
Red led blinks if high voltage present at main bushing
Capacitive voltage divider in bushings supply the power of voltage indicator
Installed on every operating panel

Phase comparison test unit


There are 2 plugs on phase comparison test unit
Connect each plug to the circuit where need to be tested.
If operator need to check A phase on circuit 2 and A phase
on circuit 3, connect one of the phase comparison test plug to Voltage indicator
phase A and on 2nd circuit and connect other plug to phase A on circuit 3.
If operator checks on same phase to test, test unit does not work.
If phases are different, test unit lamp start to blink.
Test unit still blinks even if pressurized.
Operation - Definition of Status RMC 6107.M0 6 / 19

Definition of Status
There are 3 status of RMU.
1. Close status: Busings and common bus bar is connected electrically.
2. Open status: Busings and common bus bar is disconnected electrically.
3. Earth status: Busings and earth bushing is connected electrically.

CLOSE state OPEN state EARTH state


Service condition Isolated condition Test condition

CB: Circuit Breaker


DS: 3 position off-load disconnector switch

Interlock
DS cannot operated when CB is ON position.
To operate DS, CB must be OFF position first.

Cable Box and Cable test bushing interlock


Cable box cover and the cover of the cable test bushings can be operated
when DS is EARTH and CB is ON position.

Operating procedure summary


Close Operation: DS-ON(only when CB is OFF position) and then CB-ON
Open Operation: CB-OFF first and then DS-OFF.
Cable Test: DS-EARTH first(only when CB is OFF position) and then CB-ON
Operation - CB operation RMC 6107.M0 7 / 19

CB operation
CB can be operated by manual push button after spring charging completed.
1. Spring Charge: rotate handle clockwise until indicator is turn to "Spring charged".
2. Close: Press "I" button. CB indication will change to Close.
3. Open: Press "O" button. CB indication will change to Open.
Open operation still can be done when spring charge is released condition.

Spring discharged(Green) → Spring charging(handle) → Spring charged(Red)

CLOSE: Push Red "I" button

Spring charging handle

OPEN: Push Green "O" button


Operation - DS operation RMC 6107.M0 8 / 19

DS operation
DS can be operated only in the CB OFF position. (Push down the interlock lever and insert th DS handle)
Rotate the operating handle in accordance with the arrow direction on the front panel.
In order to make DS switch on after Earth off, the handle has to be taken out and reinserted to operate.

OFF-DS

CW CW

CC CC

* Inserting direction of the handle


for Earth operation & DS
EARTH-DS operation is different. ON-DS

DS handle
Operation - Cable box open RMC 6107.M0 9 / 19

Cable box open


The cable box cover can be opened only when DS is EARTH position and CB is ON status.
CB OFF → DS EARTH → CB ON → Cable box cover remove
Lift and pull away the cable box cover from the RMU.

To return to service state


Cable box cover reinstall - CB OFF - DS OFF- DS- ON - CB ON
CB can not be open when the cable box door is open.

CB OFF DS EARTH CB ON

Cable box
lift up the cable box
and separate from RMU

* CB can be open when cable box door is close.


Operation - Cable Test RMC 6107.M0 10 / 19

Cable Test
Can be only operated when DS is EARTH position and CB is ON status.
CB OFF → DS EARTH → CB ON
Cover open and disconnect bus bar.

Cable test bushing cover attached status

Cable test bushing cover open status

Busbar disconnect and do the cable test

After cable testing and assembly bolts

* CB can be open when cable test bushing cover is close.


Terminal block - Control box RMC 6107.M0 11 / 19

Terminal blocks in control box


Terminal block - PT & Pilot cable RMC 6107.M0 12 / 19

Terminal blocks for PT

Terminal block for Pilot cable


MCB - Main Control Board RMC 6107.M0 13 / 19

Main Control Board MCB_Terminal Block (BR-762K-12)


1 : Remote control com
2 : Remote control close
3 : Remote control open
4 : Auxiliary contact of circuit breaker (com)
5 : Auxiliary contact of circuit breaker (close)
6 : Auxiliary contact of circuit breaker (open)
7 : Auxiliary contact of earthing switch (com)
8 : Auxiliary contact of earthing switch (close)
9 : Auxiliary contact of earthing switch (open)
10 : Auxiliary contact of disconnector switch (com)
11 : Auxiliary contact of disconnector switch (close)
12 : Auxiliary contact of disconnector switch (open)

FCN2 (YW396-4) FCN1 (HIF3BA-10) CN1 (Molex 5566-14) PCN1 (YW396-8)


1 : +24V 1 : +24V 1 : Control for open 1 : +24V
2 : DS open lamp 2 : +24V 2 : +24V 2 : +24V
3 : ES open lamp 3 : Local control 3 : N/C
4 : GND 4 : N/C 4 : Local control
5 : Control for open 5 : Remote control
6 : Control for close 6 : GND
7 : Open lamp 7 : GND
8 : Close lamp 8 : GND
9 : GND
10 : GND
MCB - Main Control Board RMC 6107.M0 14 / 19

Main Control Board

CN5 (Molex 5566-6) CN4 (Molex 5566-8) CN3 (YW396-7)


1 : DS1C (COM) 1 : MS1C(MS1 COM) 1 : + Motor
2 : DS1A 2 : MS1A 2 : - Motor
3 : DS1B 3 : MS1B 3 : + Close coil
4 : ES1C (COM) 4 : MS2C(MS2 COM) 4 : - Close coil
5 : ES1A 5 : MS1A 5 : + Trip coil
6 : ES1B 6 : MS1B 6 : - Trip coil
7 : SP MS COM 7 : N/C
8 : SP1B
PSM - Power supply module (DC-DC convertor) RMC 6107.M0 15 / 19

Power supply module (DC-DC convertor)

CN1(Molex 5219-4) CN2 (YW396-6)


1 : Input DC 50V 1 : DC +24V
2 : Input DC 50V 2 : DC +24V
3 : GND 3 : N/C
4 : GND 4 : N/C
5 : DC -24V
6 : DC -24V
Installation - Dimension RMC 6107.M0 16 / 19

Dimension

Base detail
Installation - Base detail RMC 6107.M0 17 / 19

Base detail
Installation - Protection Pillars RMC 6107.M0 18 / 19

Protection Pillars

3000
1300

1250
625
650
4040

1250
1540
1500

NOTE:

1500 1500 PILLARS OF ITEM NO. 4 ARE OF DIAMETER 4",


2MM THICK, WITH AN OVERALL HEIGHT OF 1.5M. A STEEL
CAP IS USED TO COVER THE TOP AND THE PILLARS IS THE
FIXED BY A CONCRETE BASE.

PILLAR COLOR: PHOSPHORUS.


5 FOUNDATION FOR PILLAR 10
4 PROTECTION PILLAR 10
3 FLOOR LEVEL 1
2 RING MAIN UNIT TYPE EN12 1
1 FOUNDATION PLINTH 1
SR. PART DESCRIPTION QTY
Wiring Diagram RMC 6107.M0 19 / 19