Application for the extension of I/Os on s

SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

Description of the application

A SIPROTEC 4- or Compact-Protection device has to send a trip-command via Ethernet network to several
wind turbines. The LED 8 from the protection device is only intended to be set when the feed-back of all
circuit breakers is positive.
The Ethernet (Subnet) is arranged with optical/electrical switches in a linear way, and can (if supported by
the switches) be expanded to a redundant ring.
This optical (redundant) allocation of the telegrams ensures the fault-free transmission of a trip-command
from the protection device to the relay of the SICAM I/O-Units, even over large distances. .
The protection device with EN100-Ethernet interface, as well as the SICAM I/O-Units are connected to the
electrical interfaces of the switches via patch cables. For the purpose of initialization, the protection device
must be temporarily connected to the PC via the frontal USB interface.

Wind turbine n Wind turbine 2 Wind turbine 1 Substation

7SJ80x
Switch n Switch 2 Switch 1 Switch S SIEMENS
R S 900 RS 900 R S 900 RS 900
Pow er Power Pow er Power RUN
9 9 9 9
Alarm Link Alarm Link Alarm Link Alarm Link
Reset R eset Reset R eset ERROR

L1: 0A 12: 0.0kV


Tx Act. Tx Act. Tx Act. Tx Act. L2: 0A 12: 0.0kV
8
Rx
8
Rx
8
Rx
8
Rx L3: 0A 12: 0.0kV
E : 0A 12: 0.0kV
EE:
CB
f :

7
Tx
Rx
LWL cable 7
Tx
Rx 7
Tx
Rx 7
Tx
Rx
Esc Enter
6XV8100-xx
5 6 5 6 5 6 5 6

Anregung L1
3 4 3 4 3 4 3 4
Anregung L2
Anregung L3
Anregung E
1 2 1 2 1 2 1 2
Aus L1
Aus L2
RU GG EDC OM RUG G ED COM RU GG EDCO M RUG G EDCO M
Aus L3

Patch cable 1:1


SICAM 7KE6000-8G SICAM SICAM Trip SIEMENS
I/O-Unit n I/O-Unit 2 I/O-Unit 1 7SJ8031-5EB00-1HE0

J 1 J 1 J 1
Quit
12
P
2 12
P
2 12
P
2 Port B / EN100
11 3 11 3 11 3
10 4 10 4 10 4
9 5 9 5 9 5
8 6 8 6 8 6
H 7 H 7 H 7
7 7 7
6 8 6 8 6 8
5 9 5 9 5 9
4
3
N/-
L/+
10
11
12
4
3
N/-
L/ +
10
11
12
4
3
N/-
L/ +
10
11
12
D IG S I 4
2 2 2
1 N 1 N 1 N
SIEMENS SIEMENS SIE MENS

BI 1 BO 1 BI 1 BO 1 BI 1 BO 1

L+ L+ L+ Notebook or PC

CB CB CB

SICAM I/O-Unit n SICAM I/O-Unit 2 SICAM I/O-Unit 1

Note
This specification attempts to display the procedure of the implementation of this application in as much
detail as possible. Nevertheless, basic knowledge of the PC operational system, and DIGSI 4 with routing
matrix, CFC and the IEC 61850 system configurator is of advantage.
This document has been built by the use of DIGSI 4.88 and I/O-Unit V2.03. If other versions of DIGSI or
I/O-Units are used, pictures and handling could be different.
Further application descriptions are available under www.siprotec.com > Downloads > Accessories.
Note for SIPROTEC Compact protection devices:
Using Modbus UDP protocol, a binary in and output extension (with 2 I/O units up to 12 in/outputs) can be
applied to SIPROTEC Compact protection devices 7SJ80 and 7SK80 via the Ethernet service module on
port A. An applicable application description is available in the Internet SIPROTEC download pool under
www.siprotec.com > Downloads > Accessories.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 1 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

Index:
1 Planning the application ................................................................................................... 4
1.1 Overview of the planned application with 2 SICAM I/O-Units........................................................ 4
1.2 Setting IP-addresses of the devices in the subnet ........................................................................ 4
2 Changing the IP-addresses of the SICAM I/O-Units ......................................................... 5
2.1 Setting the IP-Address of the PC to the default subnet of the SICAM I/O-Units ............................ 5
2.2 Opening the Web-Server of the SICAM I/O-Unit in the Internet-Browser ...................................... 6
2.3 Setting IP-Addresses of the SICAM I/O-Units for a planned subnet .............................................. 7
2.4 Saving and activating the settings ............................................................................................... 8
2.5 Setting the IP-Address of the PC for a planned subnet ................................................................ 8
3 Creating a new project in DIGSI 4 .................................................................................... 9
3.1 Setting up a new protection device in DIGSI ................................................................................ 9
3.2 Selecting the protocol of the EN100-interface in DIGSI ................................................................ 9
3.3 Setting Ethernet-addresses of the EN100-interface in DIGSI ......................................................10
3.4 Initialising the protection device ..................................................................................................10
4 Setting logical in and outputs in the SIPROTEC device .................................................. 11
4.1 Setting logical linkages in the routing matrix ...............................................................................11
4.2 Setting logic linkages in CFC ......................................................................................................13
4.2.1 Linking logical inputs in CFC ..................................................................................................13
4.2.2 Linking the logical output in CFC ............................................................................................14
4.2.3 Setting the priority sequence in CFC ......................................................................................15
4.2.4 Compiling the CFC-chart ........................................................................................................16
5 Inserting the SICAM I/O-Units into the DIGSI-project...................................................... 17
5.1 “Downloading “Default-ICD-File from the SICAM I/O-Unit ...........................................................17
5.2 Applying device-specific ICD-Files..............................................................................................18
5.3 Integrating the SICAM I/O-Units into the DIGSI-Object ...............................................................20
5.4 Applying an IEC 61850 Station in the DIGSI-Object ....................................................................21
6 The System Configurator ................................................................................................ 22
6.1 Object Properties of the IEC61850 station ..................................................................................22
6.1.1 Selecting IEC61850 Edition ....................................................................................................22
6.1.2 Adding network participants to the configurator ......................................................................23
6.2 Opening the system configurator ................................................................................................24
6.3 Adding a new GOOSE-Application .............................................................................................25
6.4 Effecting the logical links ............................................................................................................26
6.5 Saving the configuration .............................................................................................................26
6.6 Updating the GOOSE-participants ..............................................................................................27
6.7 Exporting the SCD-File of the IEC61850 station .........................................................................28

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 2 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

7 Installing the mapping tool .............................................................................................. 29


8 Updating the parameter sets of the devices.................................................................... 30
8.1 Updating the parameter set of the protection device ...................................................................30
8.2 Updating the parameter set (Mapping) of the SICAM I/O-Units ...................................................31
8.2.1 Loading the SCD file into the mapping tool .............................................................................31
8.2.2 Generating the 1. Mapping-File ..............................................................................................32
8.2.3 Generating the 2. Mapping-File ..............................................................................................33
8.2.4 Loading the 1. Mapping-File into the SICAM I/O-Unit ..............................................................34
8.2.5 Loading the 2. Mapping-File into the SICAM I/O-Unit ..............................................................36
9 Configuring Inputs- and Outputs of the SICAM I/O-Units ................................................ 37
9.1 Binary inputs ..............................................................................................................................37
9.2 Binary outputs ............................................................................................................................38
9.3 Fault alarms ...............................................................................................................................39
9.4 LEDs ..........................................................................................................................................39
9.5 Saving the settings in the SICAM I/O unit. ..................................................................................40
9.6 Applying the setting of the second SICAM I/O-Unit .....................................................................40
10 Task and test of the application ...................................................................................... 40
10.1 Task of the application ...............................................................................................................40
10.2 Test of the application ................................................................................................................40

A practicable operations process for IEC 61850 and GOOSE applications with SIPROTEC and other
external devices may be derived from this index

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 3 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

1 Planning the application


1.1 Overview of the planned application with 2 SICAM I/O-Units

Extended Inputs and Outputs over Ethernet with IEC 61850 (GOOSE)

IP-Address 192.168.10.1
Subnet Mask 255.255.255.0 FO cable FO cable

Switch / Router 1 Switch 2 Switch 3

PORT 1 PORT 2 PORT 3 PORT 4 PORT 5 PORT 6 PORT 1 PORT 2 PORT 3 PORT 4 PORT 5 PORT 6 PORT 1 PORT 2 PORT 3 PORT 4 PORT 5 PORT 6

POWER POWER POWER

LAN LAN LAN


SIEMENS SIPROTEC Double shielded Patch Cables Double shielded Patch Cables
SIEMENS RUN ER ROR

RUN
L1 402,1A
L2 402,1A
Max450.1A
Max450.1A
I/O-Unit 1 I/O-Unit 2
ERROR
L3 402,1A Max450.1A
L1: 0A 12: 0.0kV E 00.0A J P J 1
P 1
L2: 0A 12: 0.0kV 2
L3: 0A 12: 0.0kV 12 2 12
E : 0A 12: 0.0kV 11 3
EE: 11 3
f :
4 10 4
Anr. L1 10
Browser Anr. L2
9
8
5
6
9
8
5
6
Esc Enter Anr. L3 H 7
+ DIGSI Anr. Erde
7
H 7
7
Automat 6 8 6 8
Anregung L1 5 9 5 9
N/- N /- 10
Anregung L2 10 4
4 L/ + L/ +
Anregung L3 3 11
Anregung E 3 11
12 2 12
Aus L1 2
Aus L2 1 N 1 N
SIEMENS SIEMEN S
Aus L3

6 BI 6 BI
6 BO 6 BO
SIEM EN S
Binary outputs for Binary outputs for
Station PC for the 7SJ8031-5 EB00-1HE0

Configuration of trip command and trip command and


SIPROTEC Device release signal release signal
all I/O Units and the
SIPROTEC Device with EN100 interface IP-Address 192.168.10.10 IP-Address 192.168.10.11
Subnet Mask 255.255.255.0 Subnet Mask 255.255.255.0
IP-Address 192.168.10.2 IP-Address 192.168.10.120 Gateway 192.168.10.1
Gateway 192.168.10.1
Subnet Mask 255.255.255.0 Subnet Mask 255.255.255.0
Gateway 192.168.10.1 Gateway 192.168.10.1

This application shows the distribution of the command ”Gen. Trip“ of a 7SJ80 with feed-back via binary
inputs of two SICAM I/O-Units that are connected via Ethernet,e.g. in distributed wind-turbines. .
This application applies representatively for all SIPROTEC devices with EN100 Ethernet module.
The three switches/routers are connected via F/O cables and may also be operated as a ring. The switch
has to support this function, and is not described here.
1.2 Setting IP-addresses of the devices in the subnet
When starting the project, it is advisable to set the IP addresses of the individual devices.

Device IED-name IP-address Subnet mask Gateway


Switch / Router 192.168.10.1 255.255.255.0
PC 192.168.10.2 255.255.255.0 192.168.10.1
Protection device 192.168.10.120 255.255.255.0 192.168.10.1
1. SICAM I/O-Unit S_IO_00001 192.168.10.10 255.255.255.0 192.168.10.1
2. SICAM I/O-Unit S_IO_00002 192.168.10.11 255.255.255.0 192.168.10.1

In networks, the IP-address of the PC is often allocated via DHCP. It may however not conflict with other IP
addresses in the same subnet.
The IEC 61850 IED-name of the SICAM I/O-Unit has to begin with “S_IO_“ and end with a 5 digit number.
Example: „S_IO_12345“, or as in this application “S_IO_00001“.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 4 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

2 Changing the IP-addresses of the SICAM I/O-Units


If all devices have to communicate within one subnet, all the IP addresses of all devices have to be located
within this subnet. To exclude a multiple allocation of the same IP addresses, a list should be compiled ,
which stipulates a clear allocation (see above).
The following steps are necessary for the setting of the SICAM I/O-Units.
2.1 Setting the IP-Address of the PC to the default subnet of the SICAM I/O-Units
The IP-address of the “configuration PC” may have a fixed IP address. It may also have been allocated as a
variable by a router via DHCP. During later operation, the IP address of the “System PC” should be fixed.
In order to change the default IP-address of the SICAM I/O-Units (192.168.0.55) the PC with its Ethernet
interface has to be located in the same subnet. To achieve this, the IP address of the PC must be changed
as follows:
Under “Control Panel \ All Control Panel Items \ Network and Sharing Centre” and LAN-Connection,
Properties, Internet Protocol Version 4 (TCP/IPV4) and Use the following IP address the IP address of
the PC is changed to “192.168.0.2” and saved.

Thereafter the SICAM I/O-Units are connected to the PC via a patch cable (1:1 or cross over) individually,
one after the other.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 5 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

2.2 Opening the Web-Server of the SICAM I/O-Unit in the Internet-Browser


The SICAM I/O-Unit has an integrated Web-Server which can be opened in an Internet browser
After a SICAM I/O-Unit has been connected to the PC via an Ethernet interface, an Internet browser, for
example the MS Internet Explorer is opened. The default address of the SICAM I/O unit “192.168.0.55“ is
entered as the URL. The window “Information“ with the content “Device Information“ is opened.

Here the Device Information such as the Order number (MLFB), Firmware Version or
Device Date and Time are displayed.
For the purpose of fault location or monitoring of events, various Message Logs can be opened and
analysed in the navigation column on the left.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 6 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

2.3 Setting IP-Addresses of the SICAM I/O-Units for a planned subnet


After choosing the tabs Configure and Communication Ethernet the Ethernet-addresses and the
communication protocol may be set. .
If IEC 61850 has been chosen as the Bus protocol IEC 61850, the desired Edition has to be selected
under Parameter.
If several SICAM I/O-Units have to be “cascaded” via the Ethernet interface, or if a further bus participant has
to be connected, the integrated Ethernet switch has to be activated. To connect one or more devices the
Ethernet-Adapter 7KE6000-8GD00-0BA2 always has to be applied.

The figure shows the settings for the first SICAM I/O-Unit without active switch
IP-Address (192.168.10.10), Subnet mask (255.255.255.0) and Default Gateway (192.168.10.1) are set
according to Subnet plan (see 1.2).
If the choice yes has been selected under Use settings from uploaded Subscriber configuration, the
settings of the IEC 61850 protocol are loaded from a still to be generated SCD file.
If all settings have been made, these are saved and activated in the SICAM I/O unit with the buttons Send
and Activation.
Using Download ICD file, a Default-ICD-File from one of the SICAM I/O units must be saved on a data
medium for the later incorporation of the SICAM I/O unit into the system configurator. This ICD file is not
device specific. It can however be adapted to a specific device, using a text editor. Alternatively, the required
changes can be made later in the system configurator.
Now the next SICAM I/O-Unit can be connected to the PC and the settings can be made.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 7 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

2.4 Saving and activating the settings


The settings have to finally be activated in the SICAM I/O unit, after saving the changes on each altered
page with the button Send.

Using Activation and entering the Password all changes are activated in the SICAM I/O unit under Finish
Configuration.
Now the second SICAM I/O-Unit with Default-IP-address (192.168.0.55) can be connected to the PC, and
set to IP-address 192.168.10.11.
Note: The connection from the PC to the SICAM I/O unit can only be re-established after the IP address of
the PC has been changed to the final subnet 192.168.10.x.
2.5 Setting the IP-Address of the PC for a planned subnet
With the next step, the IP address of the PC is again adapted to the planned subnet with a fixed IP address
(see 2.1). When all SICAM I/O-Units are connected via a switch/router, they can now be centrally operated
and set via the PC.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 8 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

3 Creating a new project in DIGSI 4


After creating a new DIGSI 4 project, all devices are applied, set or parameterised again, one after the other.
Thereafter, the desired couplings of functions of the devices amongst each other are applied in the system
configurator.

3.1 Setting up a new protection device in DIGSI


The protection device has to be set up in DIGSI 4 with the corresponding MLFB (not as Plug & Play).

3.2 Selecting the protocol of the EN100-interface in DIGSI


If the device has no EN100 interface according to the MLFB, this can as a rule be retro-fitted. It must then be
applied in DIGSI under Object Properties, Communication modules as:
1. Port B (button … Protocol and
2. Port B (button … IEC 61850, RJ45 with EN100

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 9 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

3.3 Setting Ethernet-addresses of the EN100-interface in DIGSI


For the system interface, the planned Ethernet addresses of the protection device are set under
communication parameters (192.168.10.120).

After the entries have been confirmed with OK the device must be initialised.

3.4 Initialising the protection device


For this purpose the device has to be connected via the frontal operations interface (USB or RS232)

When the initialising process of the protection device has been completed, it is connected to the
switch/router, and may now also be operated via the Ethernet network with DIGSI 4.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 10 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

4 Setting logical in and outputs in the SIPROTEC device


In this application the command Gen. Trip is to be put out to relays 1 and 2 of both SICAM I/O-Units. The
feed-back of both circuit-breakers is only to be output to the LED 8 of the SIPROTEC device via a binary
input of the specific SICAM I/O unit, when both feed-backs are pending.
The logic command Gen. Trip of the protection device is already pre-set to the IEC 61850 interface and may
be linked directly in the system configurator.
The feed-back indication of both circuit-breakers must be coupled with an “AND“ gate and indicated via
LED 8. For this purpose, an “AND” gate must be generated on the CFC of the device, and the required in
and outputs must be routed to the margins.
Initially however, the logic in and outputs of the routing matrix have to be re-set, clearly identified and routed.
.
4.1 Setting logical linkages in the routing matrix
To facilitate a better overview in the routing matrix of the protection device, a new group GOOSE is applied
using Insert Group. Using Insert Information … three new annunciations are applied.
Then two logical inputs ExSP (feed-backs Input 01 and Input 02) are obtained under Source from the
interface “S“ and forwarded to the “C” FC under Destination.
The group alarm Group trip (is later derived from the “AND-gate“ in the CFC) is obtained from the “C” FC
under Source and put out on the LED 8 under Destination without being saved.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 11 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

Using the right mouse-click, the dialog e.g. Object properties – Input 01 –ExSP is opened.
A unique name e.g. In01 is entered in the box CTRL/, which then also appears in the CFC as well as the
system configurator.
The management of the routing matrix in DIGSI 4 is explained in detail in the system manual SIPROTEC 4.

After closing all dialogs with OK and saving under File, Save the routing matrix may be closed.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 12 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

4.2 Setting logic linkages in CFC


The two feed-back signals are linked via an AND gate.
For this application, a new CFC chart is applied. From the library Status of Information select the module
ST_AND (AND – Gate) and drag and drop it into the chart.

4.2.1 Linking logical inputs in CFC


To route the signals Input 01 and Input 02 from the group GOOSE to the input of the AND gates X1 and
X2, use the Interconnection to Address … The completed routing is then displayed on the left margin.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 13 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

4.2.2 Linking the logical output in CFC


By clicking with the right mouse-button on the output of the Gate, a selection box is opened.
The output Y (group) of the AND gate can be linked to the signal with the name Group trip from the group
GOOSE, using the Interconnection to Address … The completed routing is then displayed in the right
margin.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 14 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

4.2.3 Setting the priority sequence in CFC


Various modules of the CFC are pre-set with a low priority to facilitate slower processing, may however be
shifted to a faster processing level.
Note: The processor load is increased when a large number of sequences are processed simultaneously,
which results in a race condition..

Under Edit and Open Run Sequence the selection box for the processing level is opened.

The CFC plan CFC-(1) has already been shifted to the faster processing level PLC_BEARB (Fast PLC) in
the figure above.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 15 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

4.2.4 Compiling the CFC-chart


Finally the CFC chart has to be compiled for transfer to a protection device.

The relevant program is compiled with Charts as Program … under Chart and Compile and correctly
executed with the following prompt.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 16 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

5 Inserting the SICAM I/O-Units into the DIGSI-project


The SICAM I/O units must be applied along with the protection devices in the DIGSI project. Device specific
ICD-Files have to be compiled for this purpose.
5.1 “Downloading “Default-ICD-File from the SICAM I/O-Unit
The SICAM I/O-Unit offers a default-ICD-File, which defines the logic in and outputs.

Under Configure, Administrative, Communication on the SICAM/IO unit web surface the ICD-File
7XV56731.icd can be saved on the PC, using Download ICD file.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 17 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

5.2 Applying device-specific ICD-Files


When the default ICD files both I/O units are incorporated into the system configurator, a number of
confusing fault messages are displayed, as the IED names, the IP addresses and the virtual MAC addresses
of both (ICD-Files) are the same.
Applying device specific ICD files in a text editor is easier and more transparent.
The default ICD-file has to be opened on the PC 7XV56731.icd using the Windows text-editor. It then has to
be adapted to the individual SICAM I/O-unit and saved as device specific file.

The required alterations in the mapping file for two SICAM I/O units are displayed in the figure above.
The IED-name ”TEMPLATE“ has to be altered in S_IO_0000x.icd twice.
The corresponding IP-addresses are adapted to the corresponding SICAM I/O-Unit.
The virtual MAC-addresses for the GOOSE_Inputs and GOOSE_Outputs all have to vary, and may not
overlap with those of other devices (e.g. protection devices).

These changes may also be done later in the system configurator.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 18 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

These figures show successfully edited files for both SICAM I/O-units.

After editing, both files are saved with a specific name, e.g. 7XV5673_00001.icd and 7XV5673_00002.icd.

Note: The file extension “icd “is not displayed by the standard settings of the explorer.
It may however be activated in the settings of the explorer.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 19 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

5.3 Integrating the SICAM I/O-Units into the DIGSI-Object

A selection box is opened by clicking on the empty window with the right mouse button.
Under Insert New Object and Other IEC61850 communicator the window Import device is opened, and
the first SICAM I/O unit is selected and imported into the device list with 7XV5673_0001.icd.
The same process is repeated with the file 7XV5673_0002.icd to apply the second SICAM I/O-unit,.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 20 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

5.4 Applying an IEC 61850 Station in the DIGSI-Object

A selection box is opened by clicking into the empty window with the right mouse button.
An IEC61850 station is inserted into the device list under Insert New Object and IEC61850 station.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 21 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

6 The System Configurator


The system configurator serves the administration of all network participants and their IEC61850-
communication amongst each other.
6.1 Object Properties of the IEC61850 station

The Object Properties of the IEC61850 station are opened on the IEC61850 station by clicking the right
mouse button.

6.1.1 Selecting IEC61850 Edition

The desired edition, here IEC61850 edition 1, is selected with the tab IEC61850 settings. The window is
then closed with OK.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 22 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

6.1.2 Adding network participants to the configurator

The devices to be added are marked under the tab Communicator, and then added to the configurator with
the button Add.

The window is then closed with OK.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 23 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

6.2 Opening the system configurator


Before opening the system configurator, “SIPROTEC” protection devices must have been opened and
initialised once in the “offline mode” in DIGSI.

Both SICAM I/O-Units S_IO_00001 and S_IO_00002 are dragged from Subnet W01 in the window Network
and dropped into the subnet of the protection device NONE.

The subnet W01 may thereafter be deleted and the subnet NONE can be renamed under Identification,
Name in Appl_IO.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 24 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

6.3 Adding a new GOOSE-Application

Under Insert a new GOOSE application is inserted in the window GOOSE.

The trip command Protection/Total/OFF or PTRC1 Tr (Trip), routed to the Ethernet interface of the
protection device, is available under Source catalogue in this GOOSE application.
The logical inputs SPCS01-06 of both SICAM I/O units are available in the Destination catalogue.
The logic signals of the protection device are linked to these logical binary inputs of the SICAM I/O-Unit and
output to the corresponding relays.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 25 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

6.4 Effecting the logical links

The logical links are carried out by dragging the objects from the Source- / Destination catalogue to the
GOOSE messages. Objects such SPCS01, which have already been routed, are marked with a red cross
and blocked for further links.
Detailed notes regarding the management of the system configurator may be found under DIGSI 5 help or
the IEC 61850 applications.

6.5 Saving the configuration


Finally the configuration must be saved with Save via the menu bar under Station.

The following note in the figure above once again points out that after a change in the IEC61850 station, all
affected GOOSE applications have to be actualized.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 26 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

6.6 Updating the GOOSE-participants


After each change of the GOOSE application, the settings of all affected participants (devices) must be
updated in DIGSI!!!!

The tab Update in Object Properties … of


the IEC61850 station displays all GOOSE
participants. Should the devices that were
affected by the last change be known, these
may individually be marked and updated
with OK.
In the case of one not being sure, it is
recommended to use the button
Update all parameter sets
.
Note: The SICAM I/O-Units cannot be
updated here. This has to be done
separately (see 8.2.)

The results of the update are displayed in the window Report.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 27 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

6.7 Exporting the SCD-File of the IEC61850 station

Using Export IEC61850 station under Object Properties … of the IEC61850 station, the SCD file is saved
on the PC.

The data file of the SCD-file may


be selected here.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 28 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

7 Installing the mapping tool


A device specific mapping file for a SICAM I/O unit is generated from the SCD file by the system configurator
by the mapping tool. After starting the file Setup.exe please follow the installation guide hereunder.

A choice as to where the mapping tool is to be installed and who is entitled to use it can be made here.

When the installation has been correctly executed, the window may be closed.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 29 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

8 Updating the parameter sets of the devices


8.1 Updating the parameter set of the protection device
After the parameter set of the device in DIGSI has been updated by the system configurator, the protection
device itself has to be updated. This can be done via the frontal interface or the rear EN100 Ethernet
interface.

For this purpose the device is opened in the DIGSI Manager / Offline.

Subsequently the parameter set is transferred to the protection device using Device / DIGSI -> Device.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 30 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

8.2 Updating the parameter set (Mapping) of the SICAM I/O-Units


Before the parameter set of the SICAM I/O units can be updated, a mapping file (*.MAP) has to be
generated from the final SCD file of the system configurator, using the mapping tool. Using this device
specific mapping file, the parameter set of the SICAM I/O unit is then updated (see figure below).

P J 1
2
12
11 3
4
10
9 5
8 6
H 7

Load the device specific mapping 7


6
5
8
9
Save the default ICD-File of the I/O-Unit
on the PC using a Web-Browser
N/ - 10

file (.MAP) into the I/O-Unit


4
L/+
3 11
2 12

using a Web-Browser.
1
SIEME NS
N
and then modify it for each device.
SICAM I/O-Unit

D IG S I 4
4 1 W eb
B row ser

3 2
PC with Mappingtool
and Web-Browser PC with Web-Browser

Load the SCD-File into the D IG S I 4 Drag the device specific ICD-File of the
Mapping Tool and create a I/O-Unit into the System Configurator
device specific mapping file (.MAP). and then export the SCD-File.

PC with DIGSI 4 and


System Configurator

Note: This process has to be repeated after every change in the GOOSE application!

8.2.1 Loading the SCD file into the mapping tool

After starting the mapping tool with Load the existing SCD file IED61850 station.scd is selected and loaded
with Open.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 31 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

8.2.2 Generating the 1. Mapping-File

Exactly this IED name under IED: S_IO_[00001] must be entered before generating the mapping files for
the SICAM I/O-Unit S_IO_00001 with Generate Mapping,

After the generation process the file is stored in the selected folder (here the ICD file). .

If the generation process was successful this is shown in the box with the path information.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 32 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

8.2.3 Generating the 2. Mapping-File


When generating the 2. Mapping file, the procedure regarding the 1. Mapping file is repeated. The IED name
and the file name 7XV5673_00002.MAP are correspondingly changed.

After creation of the 1. Mapping file, the SCD file is still loaded. After changing the IED name to S_IO_00002,
the 2. Mapping file may be generated, and saved under another name.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 33 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

8.2.4 Loading the 1. Mapping-File into the SICAM I/O-Unit

The mapping file is loaded into the SICAM I/O unit in the web browser. After opening the operating tool of the
first SICAM I/O unit (IP address 192.168.10.10) in the web browser, a list of the available mapping files is
displayed under the tab Configure using Upload Subscriber configuration.

The selection 7XV5673_00001.MAP is confirmed with Open.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 34 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

The path and the MAP file is displayed in the window Configure under Substation Subscriber
configuration. Using the button Open, the mapping file is loaded into the SICAM I/O unit
After the loading process the SICAM I/O-Unit is re-started and is operational after 30 seconds.

If the upload was successful, this is displayed at the bottom right with File opened successfully.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 35 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

8.2.5 Loading the 2. Mapping-File into the SICAM I/O-Unit


Repeat the procedure described in 8.2.4 to actualise the 2. SICAM I/O unit.

After opening the operating tool of the second SICAM I/O-Unit (IP-address 192.168.10.11) in the Web-
Browser, a list of available Mapping files is displayed with the tab Configure and Upload Subscriber-
Configuration. A selection 7XV5673_00002.MAP is made with Open.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 36 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

9 Configuring Inputs- and Outputs of the SICAM I/O-Units


As a last step, the in and outputs of the SICAM I/O-Units must be configured..
9.1 Binary inputs
After opening the operating tools of the first SICAM I/O-unit (IP-address 192.168.10.10) in the Web-Browser,
the settings of the primary inputs are applied with the tab Configure under Binary Inputs

To avoid triggering of the input by parallel lines or displaced voltages, the pick-up thresholds Threshold
voltage of the binary inputs for higher battery voltages may be adapted here. In addition, the filtering time
Software filter time can be increased for each input.
A transparent text for the selected function may be entered in the lines Binary input indication
The button Send only buffers the settings in this tab. After a change the word modified appears in red
writing in the top right corner.
Using Finish configuration and Activation the settings of all tabs of the SICAM I/O unit are confirmed.
Activation can also take place after processing of all tabs.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 37 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

9.2 Binary outputs


The settings of the binary outputs are applied under Binary Outputs in the tab Configure.

The logical source for the triggering of the output relay is selected under Source. In this application the trip
command Indication 1 from Remote, is obtained from the protection device via Ethernet IEC61850
(GOOSE).
The signal can be inverted or the Operating mode changed under the parameter Source inverted.
The operating mode Persistent means that the state of the relay permanently corresponds to the
corresponding input signal.

A logical source can be routed to as many relays as required for the purpose of contact multiplication.
Using the button Send causes the settings to be saved and finally with Finish configuration and Activation
applied to the SICAM I/O-Unit. Save the settings with the button Send.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 38 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

9.3 Fault alarms


The selection of routings to a relay also offers fault alarms.

In this example, relay 6 shuts down if the Ethernet connection to the SICAMI/O unit is faulty.
Save the settings with the button Send.

9.4 LEDs
A number of alarms can be allocated to the LEDs.

Using H1, the incoming trip command can be routed to the three allocatable LEDs. H2 is used to alarm the
incoming response of the circuit breaker at the 1st binary input. The Error alarms the interrupt of the Ethernet
connection.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 39 of 40 Kl.-D. Müller / EM DG PRO S PROM


Feb. 16, 2016
Application for the extension of I/Os on s
SIPROTEC 4 Devices via SICAM I/O-Unit 7XV5673

9.5 Saving the settings in the SICAM I/O unit.


Before closing the window in the browser, the settings of all tabs in the SICAM I/O unit must be saved with
Finish configuration and Activation.

9.6 Applying the setting of the second SICAM I/O-Unit


The process as described in 11.1 – 5 of the first SICAM I/O-Unit has to be repeated with the second
SICAM I/O-Unit (IP-address 192.168.10.11).

10 Task and test of the application


10.1 Task of the application
This application facilitates the distribution of the command “Gen. Trip“ of a 7SJ80 (or another SIPROTEC 4-
device) with feed-back via binary inputs of two SICAM I/O units via Ethernet, e.g. in distributed wind turbines
in wind parks.
10.2 Test of the application
To test this application, a general trip is produced in the protection device by the application of an “over-
current”. This trip command is transmitted to both SICAM I/O units via GOOSE. The LEDs H1 are set in both
units, and the contacts of relay 1 on the terminals N1-N2 are interrupted.
If the binary inputs of both SICAM I/O units are now triggered on the terminals N8-N9 with an auxiliary
voltage corresponding to the pick-up value via the corresponding relay contacts N1-N2, the condition of the
binary inputs (e.g. the responses of the circuit breaker) are displayed on the corresponding LEDs H2, and
transmitted to the protection device. LED8 is set in the protection device via the AND gate in the CFC.

If the connection to one of the two binary inputs is interrupted, the LED 8 on the protection device turns off.

7XV5673_APP_IO-UNIT_SIP4_GOOSE_A2_EN.DOCX Page 40 of 40 Kl.-D. Müller / EM DG PRO S PROM