NOTE PE PLAN NOTES ON THE PLAN

W2a EXTERIOR WALL ON SUB-CONSTRUCTION U=0,22 W/m2K TECHNICAL BUILDING - Refrigeration eng. Room
PERETE EXTERIORA PE SUBSTRUCTURA F3d CLADIREA TEHNICA - CAMERA REFRIGERARE
CONDITII MINIME PENTRU CARE COMPARTIMENTUL DE INCEDNIU ESTE INCADRAT IN MINIMUM CONDITIONS FOR WHICH THE INQUIRY COMPARTMENT IS CONTAINED IN SANDWICH PANEL - MINERAL WOOL CORE (Λ= 0,044 W/mK) ON PANOU SANDWICH - VATA MINERALA (Λ= 0,044 20 cm 0,3 mm
GRADUL II DE REZISTENTA LA FOC: THE SECOND DEGREE OF RESISTANCE TO FIRE: SUB-CONSTRUCTION* W/mK) PE SUBSTRUCTURA EPOXY RESIN FINISHING FINISAJ RASINA EPOXIDICA
*for refrigeration eng.: panels perforated from inside REINFORCED CONCRETE SLAB PLACA BETON ARMAT 15 cm

· stalpi, coloane pereti portanti - clasa de combustibilitate C0 cu rezistenta la foc 120 · Pillars, columns bearing walls - fuel class C0 with fire resistance 120 minutes; FOUNDATION WALL 2 x PE FOIL 2 x FOLIE PE
W2i WALL ON SUB-CONSTRUCTION - HIGHBAY WAREHOUSE U=0,09 W/m2K COMPACTED GRAVEL Proctor 98% PIETRIS COMPACTAT 20 cm
minute; · Non-load-bearing interior walls - fuel grade C1 with 30 minutes fire resistance; PERETE PE SUBSTRUCTURA HIGH-BAY
· pereti interiori neportanti - clasa de combustibilitate C1 cu rezistenta la foc 30 minute; · External non-loadable walls - fuel grade C1 with 15 minutes fire resistance; SANDWICH PANELS WITH FOAM CORE (Λ= 0,018 W/mK) ON STEEL PANOU SANDWICH PIR (Λ= 0,018 W/mK) PE IMPROVED SOIL PAMANT IMBUNATATIT
20 cm
· pereti exteriori neportanti - clasa de combustibilitate C1 cu rezistenta la foc 15 minute; · Beams, planes, ribs, terrace roofs - fuel class C0 with fire resistance 45 minutes; SUBSTRUCTURE SUBSTRUCTURA METALICA
F5 FLOOR - Bridge PARDOSEALA - PASARELA MARFA
air coolers mounted on sub-construction acc. to PF air coolers mounted on sub-construction acc. to PF · grinzi, plansee, nervuri, acoperisuri terasa - clasa de combustibilitate C0 cu rezistenta la · Self-supporting roofs without bridge (incl. Overhangs), roofless roofless roofing - C1 W2f EXTERIOR WALL - TECHNICAL BUILDING PERETE EXTERIOR - CLADIRE TEHNICA CONCRETE SREED 12 cm
BETON DE PANTA
foc 45 minute; with fire resistance 30 minutes; PANOU SANDWICH -VATA MINERALA - PE 0,3 mm
steel purlins, acc. to PC stee frame acc. to PC SANDWICH PANEL - MINERAL WOOL CORE ON SUB-CONSTRUCTION 20 cm 2 x PE FOIL 2x FOLIE PE
· acoperisuri autoportante fara pod (inclusiv contravantuirile), sarpanata acoperisurilor fara · Cladding panels and continuous fuel cell support - Fuel grade C1. SUBSTRUCTURA METALICA
roof flashings with sealings, acc. to suppliers system roof flashings with sealings, acc. to suppliers system ceiling fire class C0/A1 : REI 60 distance acc. to First floor layout pod - C1 cu rezistenta la foc 30 minute; PIR BOARD 100 (Λ= 0,022 W/mK) PLACI TERMOIZOLANTE PIR 100 (Λ= 0,022 W/mK) 10 cm
AERATED CONCRETE BLOCKS (Λ= 0,16 W/mK) /reinforced concrete wall 30 cm
BCA (Λ= 0,16 W/mK)/ PERETE BETON ARMAT
· panouri de invelitoare si suportul continuu al invelitorii combustibile - clasa de · ANTI-FIRE WALL 2 x PE FOIL 0,3 mm
gutter with flashings and snow guards, acc. to suppliers system R6 10% 10% R6 gutter with flashings and snow guards, acc. to suppliers system combustibilitate C1. · The fire wall shall be entirely made of components with the fire reaction class C0 / A1 / INTERIOR PLASTER TENCUIALA INTERIOARA 1,5 cm 2x FOLIE PE
WALL PAINT VOPSEA INTERIOARA <0,1 cm
A2s1d0; REINFORCED CONCRETE SLAB
PLACA BETON ARMAT
20cm
PERETE ANTIFOC · All wall elements will have fire resistance on the fire wall;
W3c parapet WALL OFFICE BUILDING PARAPET / ATIC - CLADIREA DE BIROURI
technical area technical area · peretele antifoc va fi realizat integral din componente cu clasa de reactie la foc · For the firewall design, special solutions and specials recommended by the system
Fire protection cladding board on structural steel frame; REI60 ROOFING MEMBRANE- mechanical fastening 0,15 cm R1* FLAT ROOF OFFICE BUILDING (RF 60) ACOPERIS TERASA RF60
C0/A1/A2s1d0; vendor will be used to check and guarantee the proper wall construction; MEMBRAMA HIDROIZOLANTA -fixare mecanica
stee frame acc. to PC STEEL SHEET 0,15 cm
MEMBRAMA HIDROIZOLANTA-protejata cu sapa
BRIDGE PRODUCTION DELIVERY CORRIDOR +6.90 · toate elementele componente ale peretelui vor avea rezistenta la foc a peretelui antifoc; · The concrete structure to which the wall is fixed will have fire resistance of the fire wall; PLACA METALICA ROOFING MEMBRANE- protected by a cement armed layer armata de ciment
BRIDGE
CORRIDOR Fire protection cladding board on structural steel frame; REI60 · pentru realizarea peretelui antifoc se vor folosi solutii si detalii speciale recomandate de · The joints between the fire walls and the inner and / or outer walls, the roof is sealed HARD WOOL BOARD PLACI DE VATA MINERALA RIGIDA 5 cm
STONE WOOL WEDGES VATA MINERALA DE PANTA 2/20 cm
W2a PRODUCTION DELIVERY CORRIDOR CORRIDOR
W2a W2a I2a W2a catre furnizorul de sistem care va verifica si garanta executia corecta a peretelui; with materials with the reaction class C0 / A1 / A2s1d0 and which provide a fire resistance of at SUBSTRUCTURE - PARAPET POSTS FILLED WITH WOOL SUBSTRUCTURA PARAPET - UMPLUTA CU VATA 15 cm
least 90 minutes; MINERALA STONE WOOL 20 cm + STONE WOOL HARD 5 cm VATA MINERALA + VATA MINERALA RIGIDA 20 + 5 cm
· structura din beton de care se fixeaza peretele va avea rezistenta la foc a peretelui antifoc;
I2a

330
· rosturile dintre peretii antifoc si pereti interiori si/sau exteriori, acoperis se etanseaza cu · The gaps around the metallic elements that stand against the fire wall shall be NON- IGNITABLE OSB BOARD x3
PLACA OSB x3 - IGNIFUGAT
6 cm
0,2 mm
PRODUCTION materiale cu clasa de reactie la foc C0/A1/A2s1d0 si care sa asigure o rezistenta la foc cel designed so as to allow their expansion and shall be sealed with materials from the fire
ALUMINIUM FACADE POSTS FILLED WITH WOOL BATTING STRUCTURA ALUMINIU FATADA CORTINA - 15 cm
VAPOUR STOP
REINFORCED CONCRETE SLAB
BARIERA DE VAPORI
PLACA BETON ARMAT 15 cm
perimeter isolation strip perimeter isolation strip perimeter isolation strip perimeter isolation strip putin 90 minute; resistance class C0 / A1 / A2s1d0 resistant to fire for 90 minutes; UMPLUTA CU VATA MINERALA
DELIVERY CORRIDOR · golurile din jurul elementelor metalice care stapung peretele antifoc se vor realiza astfel · The free spaces around the pipes, cables and conductors (including those in the SPANDREL PANEL PANOU OPAC SUSPENDED CEILING PLAFON SUSPENDAT
F5 +3,60
F5 F5 F5 +3,60 = 65.10 m a.s.l. incat sa permita dilatarea acestora si se etanseaza cu materiale din clasa de reactie la foc channels) are closed with C0 / A1 / A2s1d0 materials with fire resistance equal to that of the
dripl flashing on suport profile, acc. to suppliers system drip flashing on suport profile, acc. to suppliers system dripl flashing on suport profile, acc. to suppliers system drip flashing on suport profile, acc. to suppliers system I2a INTERIOR WALL PERETE INTERIOR
C0/A1/A2s1d0 rezistente la foc 90 minute; wall; R3 FLAT ROOF TECHNICAL BUILDING
ACOPERIS TERASA - CLADIRE TEHNICA
· spatiile libere din jurul conductelor, cablurilor si conductoarelor electrice (inclusiv cele · When passing ventilation ducts (if applicable) the prescriptions should be observed. WALL PAINT/ GRESS TILES
VOPSEA INTERIOARA / PLACAJ CERAMIC
0,1-1,5 cm
ROOFING MEMBRANE - mechanical fastening 0,15 cm
+2,73 = 64,28 m a.s.l. MEMBRAMA HIDROIZOLANTA-fixare mecanica

65
+3.23 pozate in canale) se inchid cu materiale C0/A1/A2s1d0 cu rezistenta la foc egala cu cea a 2 x PLASTER BOARD 2,5 cm
2 x PLACA GIPSCARTON
peretelui; GENERAL CONDITIONS STONE WOOL WEDGES
VATA MINERALA DE PANTA 2/20 cm
+2.58 · Fire protection building elements will be executed according to the manufacturer's STONE WOOL ON STUDS 10 cm
· la trecerea canalelor de ventilare (daca este cazul) se vor respecta prescriptiile din VATA MINERALA IN STRUCTURA STONE WOOL 20 cm + STONE WOOL HARD 5 cm VATA MINERALA + VATA MINERALA RIGIDA 20 + 5 cm
beams and slab acc. to PC foudations/beams and slab acc. to PC 306 306.5 normativ. prescriptions that will provide the execution details and will verify and guarantee the correct 2 x PLASTER BOARD 2 x PLACA GIPSCARTON 2,5 cm VAPOUR STOP BARIERA DE VAPORI 0,2 mm
execution of the wall; WALL PAINT/ GRESS TILES VOPSEA INTERIOARA / PLACAJ CERAMIC 0,1-1,5 cm REINFORCED CONCRETE SLAB PLACA DE BETON ARMAT 15cm

281
CONDITII GENERALE
Sluice acc. to PL; OUT OF SCOPE RA RB RC NOTE: INTERIOR WALL - SOCIAL & TECHNICAL B./MARSHALING & HIGHBAY PERETE INTERIOR - SOCIAL SI TEHNIC / LIVRARE INSIDE PLASTER
TENCUIALA INTERIOARA 1,5 cm
· elementele de constructie cu rol de protectie la foc vor fi executate conform cu prescriptiile
I1b WAREHOUSE MARFA SI HIGH-BAY
producatorului care va furniza detaliile de executie si va verifica si garanta executia Information on the "fire safety" performance of the building is detailed in the FIRE SAFETY
HBW ±0,00 = 61,50 m a.s.l. HBW ±0,00 = 61,50 m a.s.l. WALL PAINT VOPSEA INTERIOARA <0,1 cm R6 FLAT ROOF ACOPERIS
ROAD LEVEL -0,46 = 61,27 m a.s.l. corecta a peretelui; SCENARIO, an integral part of the Executing / Approval / Authorization Documents (Technical
MINERAL WOOL SANDWICH PANEL PANOU SANDWICH DE ACOPERIS - VATA MINERALA 20 cm
Design, DTAC, Execution Details), where all the Compliance Components are detailed building INSIDE PLASTER TENCUIALA INTERIOARA 1,5 cm
STEEL SUBSTRUCTURE STRUCTURA METALICA
NOTA: fire (walls, planes, beams, stairs, etc.). Both the Written Parts and the Architectural Space Parts AERATED CONCRETE BLOCKS (Λ= 0,16 W/mK)/REINFORCED CONCRETE BCA (Λ= 0,16 W/mK) / PERETE BETON ARMAT 30 cm
Informatiile referitoare la performantele privind "securitatea la incendiu" ale cladirii sunt will be read together with the Fire Safety Scenario (stamped unchanged by the ISU Advisor). ETICS SYSTEM - MINERAL WOOL BOARD ETICS SISTEM- VATA MINERALA BORD 10 cm
detaliate in SCENARIU DE SECURITATE LA INCENDIU, parte integranta a documentatiilor The Executor has the obligation to know both the written and written part of the required NON VENTILATED VOID GOL NEVENTILAT 45 cm
de execiutie/avizare/autorizare (proiect tehnic, DTAC, detalii de executie), unde sunt execution and the Fire Safety Scenario.
foudations acc. to PC road layers acc. to PR detaliate toate elementele de conformare la foc ale constructiei (pereti, plansee, grinzi, TECHNICAL BUILDING - Refrigeration eng. Room
F3d CLADIREA TEHNICA - CAMERA REFRIGERARE
306.5 306.5 scari etc). Atat Partile scrise cat si Partile desenate aferente spacialitatii Arhitectura se 0,3 mm
RC RB RA vor citi obligatoriu impreuna cu Scenariu de securitate la incendiu (stamplilat spre EPOXY RESIN FINISHING FINISAJ RASINA EPOXIDICA

SECTION E1-E1 SECTION E2-E2 neschimbare de catre avizator ISU). Executantul are obligatia sa cunoasca atat partea
desenata si scrisa necesara executie cat si Scenariu de securitate la incendiu.
REINFORCED CONCRETE SLAB
2 x PE FOIL
PLACA BETON ARMAT
2 x FOLIE PE
15 cm

COMPACTED GRAVEL Proctor 98% PIETRIS COMPACTAT 20 cm


IMPROVED SOIL PAMANT IMBUNATATIT

F5 FLOOR - Bridge PARDOSEALA - PASARELA MARFA


Inel etansare trecere teava CONCRETE SREED BETON DE PANTA 12 cm

E1

E2
Flashing on pipe passthrough acc. to suppliers system PLACA / CEILING - C0/A1 : REI 60 : min 6.00m 2 x PE FOIL 2x FOLIE PE 0,3 mm
placă fără găuri iar hidro trebuie protejat de un strat armat cu ciment (material C0) PIR BOARD 100 (Λ= 0,022 W/mK) PLACI TERMOIZOLANTE PIR 100 (Λ= 0,022 W/mK) 10 cm
slab without holes and the hidro must be protected by a cement armed layer (C0 material) Flasing tabla cu sigilant montat pe panoul termoizolant
flashing/ termination bar with sealing mounted to elevation panels 2 x PE FOIL 0,3 mm
600 2x FOLIE PE
Flashing / profil ( cu posibilitate de dilatare) / flashing / termination bar
Flasing tabla cu sigilant montat pe panoul termoizolant REINFORCED CONCRETE SLAB 20cm
providing movement compensation Flashing tabla atic PLACA BETON ARMAT
flashing/ termination bar with sealing mounted to HBW elevation panels roof flashings with sealings
Flashing tabla pe suport REMARKS:
Echipament climatizare refrigeration piping on sub-construction - indicative schemFlasing tabla montat pe suport Platbanda / profil suport
flashing on suport profile 1. The site is located in the seismic area described by the ground acceleration ag=0,20g and corner period Tc=0,7 s,
Kondensator acc. to PF parapet wall flashing on suport flat bar flatbar support according to P100-1/2013.
2. Tender design documentation contains information for tender purpose only. It can not be used to conduct execution
Flashing tabla conf. furnizor
W2i works. Before execution, drawings must be multidisciplinary recoordinated.
Vata minerala 5cm sidel flashing with sealings, acc. to suppliers system 3. This documentation is protected by International Copyright Law. It is forbidden to distribute this study and the parts
3 2 1 mineral wool 5 cm protectie la foc a structurii metalice thereof outside the scope of distribution specified in the agreement with the designer, to store this study in database
3% +9.45 sistem ancoraj impotriva caderii Vata minerala
Flashing tabla conf. furnizor Fire protection cladding board on structural steel frame; REI60 mineral wool 5 cm systems without the author's permission, to transfer this study in any form, including electronic copies, photocopies and
horizontal fall protection +8.96 reproductions, and to introduce any changes to this study without the consent of the author.
sidel flashing with sealings, acc. to suppliers system Sealing membrane
W6 R1* flashing / termination bar providing movement compensation Panouri invelitoare C0/A1 REI 60 4. Building systems and materials trade names used in the project are not mandatory. It is acceptable to use equivalent
Flashing cu sigilare ( cu posibilitate de dilatare) W3c +8.48 sigilant membrana
3% R3 R6
ceiling fire class C0/A1 : REI 60; distance acc. to First floor layout Gap flashing with movement compnsation solutions and technology. Prior to committing to alternative solution GC is required to submit data sheets, drawings and
flashing providing movement compensation 3% documents for relevant replacements confirming solution equivalency and request and obtain DESIGNER's and
Flashing tabla inchidere gol ( cu posibilitate de dilatare)
CLIENT's approval.
PLACA / CEILING - C0/A1 : REI 60 : min 6.00m PAF C0/A1 REI180 (ANTIFIREWALL)
5. As far as fire safety is concerned it is mandatory to follow Romanian Fire Regulations (They are followed the "Fire
+7.79 +7.79 safetyNorms for buildingsP118-99"), but protection is to be no lower than marked on the drawings. All expansion joints
I1b
technical area Platforma ridicatoare paleti and connections in walls made of different technologies in the fire separation area must be sealed using approved
+7.34 solutions. It is recommended to pay attention to the connection of non-bearing walls to the ceiling above.
CORIDOR LIVRARE MARFA / PRODUCTION DELIVERY CORRIDOR pallets elewator acc. to PL; OUT OF SCOPE
Usa frigo rapida - EI90-C 6. All dimensions are to be verified in Execution Design and on site by the General Contractor prior to ordering
deep-freeze rapid action, fire safety door acc. to PL; OUT OF SCOPE I1a elements that are to be mounted.
PAF C0/A1 - REI180 (ANTIFIREWALL) SLUICE - OUT OF SCOPE 7. Brick and reinforced concrete walls joints or brick walls disjointed with each other must be sealed with flexible mass such
Pasarela mentenanta Cordon izolator Parapet flashing with movement compensation e.g. acrylic.
PAF (ANTIFIREWALL) + ANTIEX REI180
(resistant to explosure)
Maintenance pass through - Walk Over Plates acc. to PL; OUT OF SCOPE isolation strip Flashing tabla inchidere gol ( cu posibilitate de dilatare) 8. Openings in reinforced concrete elements (floors, walls) must be made according to the Structural Execution Design DRAWING KEY: N
Spuma poliuretanica Banda transportoare - in scopul GC-logistic cordon izolator perimetral drawings. Only openings of 100mm diameter or less may be done by drilling, all remaining openings are to be prepared
C0/A1 - REI 180 Reinforced concrete
Polyurethane foam conveyor lines - scope of general contractor of logistic perimeter isolation strip in formwork.
+4.10 +4.18 9. Penetrations and openings in the walls and ceilings of the fire separation must be sealed to the EI resistance of the Calcium silicate block Silka
Sealing membrane partition, higher or equal to EI60. Sandwich panel GENERAL REMARK:
F5 +3.60 F5 F5 +3.60 08.0+ sigilant membrana
50

10. All technological and installation openings in structural elements are to be adjusted and coordinated by GC in Execution G-K board These drawing is for Refrigeration Functional Tender purposes only.
Design, after the selection of supplier, according to manufacturer specifications of relevant equipment . Drawing shows only the functional layout of the building. Detailed solutions will be defined in further design stages.
11. Door and window openings are given in gross size (rough openings), installation openings in architectural drawings are EI 120 Fire resistance value
PRUCTION FLOOR LEVEL = 64,30 m a.s.l.
Fire rated wall
Please do not consider the drawing as a final version.
VENTILATED VOID

given in rough size and located by geometric axis. Please refer to discipline designs for net dimensions.

65
+3.18 +3.23 ROMANIAN NAME
I1b 12. The project defines the windows openings dimensions according to following rules: Designed floor level GENERAL DESIGNER INWESTOR
+2.83 XPS board expansion joint filling
+2.58 · above the line: horizontal dimension of the rough opening +6,00 Designed level of parapet wall
W2f · below the line: the vertical dimension of the rough opening
Flasing tabla cu sigilant montat pe panoul termoizolant REFRIGERATION · below the opening: sill finishing level height to the floor finishing near the wall.
+6,00 leb Lower edge of the beam ul. Skarbowców 23a, bud. A1
53 - 025 Wrocław
flashing/ termination bar with sealing mounted to HBW elevation panels ENGINEERING
In case of doubt, ask the designer to clarify the project purpose on the building site. A Section line Poland
Pietris / piatra sparta - drenaj

281
13. Before placing an order for door and window joinery, the GC is required to verify opening dimensions on site and assure tel: +48 (0) 71 786 41 12
drain rock/gravel Axis name www.metroplan.com.pl
+0,50

G
Pavaj conf. PD Pavaj conf. PD Fundatie B.A. conf. PS doors and windows of required net clear width and height can be mounted. If any discrepancy is discovered between the
I4b F3d F3d
Pavement acc. to PR Pavement acc. to PR foudations acc. to PC project and the actual state, the GC is required to notify the CLIENT and Metroplan.
DESIGN TEAM BUILDING QUALIFICATIONS NO.
HBW ±0,00 = 61,50 m a.s.l. -0,05 HBW ±0,00 = 61,50 m a.s.l. HBW ±0,00 = 61,50 m a.s.l. 14. Before placing an order for building materials, finishing and equipment, which are to be used for construction, the GC is Room tag: SIGNATURE
ROAD LEVEL -0,23 = 61,27 m a.s.l.
required to request and obtain CLIENT's approval. - Building name shortcut MAIN DESIGNER:
I4c 15. Supporting structures for technical equipment must be prepared strictly according to the device manufacturer - Room no.
Fundatie B.A. conf. PS BAK
Birou livrare
B.0.18
arch. SWERHUN-BIENIEK Aleksandra -

ARCHITECTURE
foudations acc. to PC guidelines. Delivery check - Room name
-1,10
16. The space between the electrical meter boxes and the ceiling on the ground floor level should be enclosed in the #####m2 VERIFING DESIGNER:
plasterboard system. - Room net floor area [m²]
- Height of room
arch. DROGA Barbara -
Fundatie B.A. conf. PS Fundatie B.A. conf. PS Fundatie B.A. conf. PS Fundatie B.A. conf. PS 17. The openings of ventilation ducts should be extended 5 cm on each side. The angle iron must be attached to the steel
F4a DESIGNER:
-2,25 foudations acc. to PC foudations acc. to PC foudations acc. to PC foudations acc. to PC ceilings to protect the opening. W1 Building partition layers designation
3 3' 2 1 R7 R6 R5 R4 R3 R2 R1 -
18. GC is required to deliver immovable equipment and fixed furniture of kitchenette and lockers in lockers rooms. Movable arch. HRISULIDIS Kostas
E1

E2
equipment, like office furniture, is outside the scope of GC contract. Green elements out of scope of General Contractor DATE
folie PEHD 19. Locations and size of all shafts and roof perforations are indicative. The GC is responsible for the collision coordination PROJECT
in all disciplines before erection. All costs must be included in bid.
dimpled foil NEW PLANT AND WAREHOUSE FOR CONTROLLED TEMPERATURE
201 469 570 75 635.5 800.5 635 692 45 232.5 20. All openings, sizes and dimensions of technological equipment and ductwork are indicative only. Buffers for
technological installations are to be prepared. Coordination between technological, TB installations and structural PRODUCTS IN THE REGION OF TULCEA, ROMANIA 06.2019
elements is solely in General Contractors scope of Executive Design and responsibility and subject to Investors

SECTION E-E approval. All costs related are to be included in tender bid.
21. During execution openings and sillings for technological instalations are to be made acc. to technology supplier
PF scope
CLIENT LIDAS SRL
cabluri incalzire + circuit rezerva
guidelines. And where located in fire partitions acc. to relevant Romanian fire protection regulations.
ACCORDING TO:
Mineri, Brailei Street 28; 827211 Tulcea, Romania DRAWING SCALE
H1 22. Lightning protection acc. to electrical documentation.
heating cables - main + emergency loop; acc. PE G.C. GENERAL CONTRACTOR
23. Service paths and walkways on the roof is to be provided to all roof mounted equipment acc. to specification in PIV PROJECT'S VENTILATION INSTALATION DOCUMENTATION
DRAWING HIGH BAY
Performance Description Part C. Prior to construction GC is required to present pathway layout and request CLIENTS
DEPOZIT HIGH-BAY CLADIRE SOCIALA - CLADIRE TEHNICA PASARELA TRANSPORT MARFA PRODUCTIE PATISERIE - PANIFICATIE / approval
PC PROJECT'S CONSTRUCTION DOCUMENTATION BRIDGE SECTION E-E, E1-E1, E2-E2 1:100
PIS PROJECT'S SANITARY INSTALATION DOCUMENTATION
HIGHBAY WAREHOUSE SOCIAL - TECHNICAL PRODUCT DELIVERY BRIDGE PRODUCTION PASTRY 24. Location , safety barriers, bumpers and safety bollards is indicative. Exact location should protect all TBA equipment PE PROJECT'S ELECTRIC INSTALATION DOCUMENTATION
STAGE REFRIGERATION FUNCTIONAL TENDER
and building components which might be exposed to mechanical damage during building use. PIT PROJECT'S TELETECHNIC INSTALATION DOCUMENTATION
25. The rain water roof drainage and catchment areas dimensions and size, are to be adjusted according to the relevant PR PROJECT'S ROAD DOCUMENTATION
instalation Execution Design. The position and dimensioning of inlets and other relevant equipment are to be adjusted PF PROJECT'S INSTALLATION OF FREEZ DOCUMENTATION INVESTMENT ADDRESS COM. FRECATEI , DRAWING NO.
INTRAVILAN SAT CATALOI,
in GC Execution Design after the selection of supplier, according to manufacturers specifications. PL PROJECT'S LOGISTICS DOCUMENTATION JUDETUL TULCEA , T44, A705,L659,A703
26. Architectural drawings are to be considered together with descriptions and other branch designs. NR. CADASTRAL 35121, 35122, 35123
LI_HBY_AS_TD_02r