PROJECT : DIFC DATE

AHU / FAHU STATUS 28/08/2019

FLOOR
SL.NO SYSTEM REFERENCE ZONE CATEGORY DESCRIPTION LOCATION REMARKS / SNAGS / COMMENTS
LEVEL

Main performance found within allowable tolerance.


1 AHU-CP-SL-02 RMCP AHU B1 Air Handling Unit Plant Room
Less flow in first floor terminals due to leakage.

Main performance found within allowable tolerance.


2 AHU-CP-SL-03 RMCP AHU B1 Air Handling Unit Plant Room Less flow in terminals due to leakage.
Grill installation not complete
Main performance found within allowable tolerance.
Grill Installation not complete
3 AHU-CP-SL-04 RMCP AHU B1 Air Handling Unit Plant Room
Less flow in ground floor terminals due to leakage
No access to check high level terminals
Main performance found within allowable tolerance.
4 AHU-CP-SL-05 RMCP AHU B1 Air Handling Unit Plant Room Less flow in terminal due leakage
Need VCD access for balancing

Main performance found within allowable tolerance.


5 AHU-MS-RF-01 RMCP AHU ROOF Air Handling Unit Mosque Roof
No access to check terminals due to high level

No access for checking main performance


6 AHU-CP-GF-01 RMCP AHU B1 Air Handling Unit
Less flow in terminals due to leakage

7 AHU-CP-L1-01 RMCP AHU B1 Air Handling Unit Return duct installation not complete

No Power
8 AHU-AN1-LG-01 NODE1 AHU GF Air Handling Unit Plant Area
Grill installation not proper. Has leakage in plenum boxes

No access for checking main performance


9 AHU-AN1-LG-02 NODE1 AHU GF Air Handling Unit Plant Area Less flow in terminals
Need access for VCD balancing
No access for checking main performance
10 AHU-AN1-L1-01 NODE1 AHU L1 Air Handling Unit Plant Area No access to check high level terminals
Grill installation not complete

No access for checking main performance


11 AHU-AN1-L1-02 NODE1 AHU L1 Air Handling Unit Plant Area
No access to check high level terminals

Main performance found within allowable tolerance.


12 FAHU-CP-TL-03 RMCP FAHU B2 Fresh Air Handling Unit Plant Room

Main performance found within allowable tolerance.


13 FAHU-CP-SL-06 RMCP FAHU B1 Fresh Air Handling Unit Plant Room
No access for checking terminals.

Main performance found within allowable tolerance.


14 FAHU-CP-SL-08 RMCP FAHU B1 Fresh Air Handling Unit Plant Room No access for checking terminals
Need VCD to balance the branches

No Power
15 FAHU-CP-SL-09 RMCP FAHU B1 Fresh Air Handling Unit Plant Room
Duct installation not complete

No Power
16 FAHU-MS-RF-01 RMCP FAHU ROOFFresh Air Handling UnitMosque Roof
Duct installation not complete

17 FAHU-CP-SL-01 NODE1 FAHU B1 Fresh Air Handling Unit Plant Area Fresh air duct installation not complete.

Main performance of fresh air found with allowable tolerance


18 FAHU-CP-SL-02 NODE1 FAHU B1 Fresh Air Handling Unit Plant Area
Electrical issue for Exhaust motor (tripping)
PROJECT : DIFC DATE

FCU STATUS 28/08/2019

FLOOR
SL.NO SYSTEM REFERENCE ZONE CATEGORY DESCRIPTION REMARKS / SNAGS / COMMENTS
LEVEL
No Power
1 FCU-CP-GF-01 RMCP FCU GF Fan Coil Unit
Duct installation not complete
No Power
2 FCU-CP-GF-02 RMCP FCU GF Fan Coil Unit
Duct installation not complete

3 FCU-CP-GF-03 RMCP FCU GF Fan Coil Unit No Power

No Power
4 FCU-CP-GF-04 RMCP FCU GF Fan Coil Unit
Duct installation not complete

5 FCU-CP-GF-06 RMCP FCU GF Fan Coil Unit No Power

6 FCU-CP-GF-08 RMCP FCU GF Fan Coil Unit FCU not working

7 FCU-CP-GF-09 RMCP FCU GF Fan Coil Unit FCU not working

8 FCU-CP-GF-10 RMCP FCU GF Fan Coil Unit FCU not working

9 FCU-CP-GF-11 RMCP FCU GF Fan Coil Unit No Power

No Power
10 FCU-CP-GF-12 RMCP FCU GF Fan Coil Unit
Duct installation not complete
No Power
11 FCU-CP-GF-12B RMCP FCU GF Fan Coil Unit
Duct installation not complete
No Power
12 FCU-CP-GF-13B RMCP FCU GF Fan Coil Unit
Duct installation not complete
No Power
13 FCU-CP-GF-13C RMCP FCU GF Fan Coil Unit
Duct installation not complete
No Power
14 FCU-CP-GF-13D RMCP FCU GF Fan Coil Unit
Duct installation not complete
No Power
15 FCU-CP-GF-13E RMCP FCU GF Fan Coil Unit
Duct installation not complete
No Power
16 FCU-CP-GF-13F RMCP FCU GF Fan Coil Unit
Duct installation not complete
No Power
17 FCU-CP-GF-13G RMCP FCU GF Fan Coil Unit
Duct installation not complete
No Power
18 FCU-CP-GF-13H RMCP FCU GF Fan Coil Unit
Duct installation not complete
No Power
19 FCU-CP-GF-14A RMCP FCU GF Fan Coil Unit
Duct installation not complete
No Power
20 FCU-CP-GF-14B RMCP FCU GF Fan Coil Unit
Duct installation not complete

21 FCU-CP-GF-14C RMCP FCU GF Fan Coil Unit No Power

22 FCU-CP-GF-15 RMCP FCU GF Fan Coil Unit No Power

23 FCU-CP-GF-16 RMCP FCU GF Fan Coil Unit FCU not installed

No Power
24 FCU-CP-GF-17A RMCP FCU GF Fan Coil Unit
Duct installation not complete

25 FCU-CP-GF-17B RMCP FCU GF Fan Coil Unit No Power

No Power
26 FCU-CP-GF-17C RMCP FCU GF Fan Coil Unit
Duct installation not complete

27 FCU-CP-GF-17D RMCP FCU GF Fan Coil Unit FCU not installed

28 FCU-CP-GF-17E RMCP FCU GF Fan Coil Unit FCU not installed

FCU not working


29 FCU-CP-GF-18 RMCP FCU GF Fan Coil Unit
Duct installation not complete
FCU not working
30 FCU-CP-GF-19 RMCP FCU GF Fan Coil Unit
Duct installation not complete
FCU not working
31 FCU-CP-GF-21 RMCP FCU GF Fan Coil Unit
Duct installation not complete
FCU not working
32 FCU-CP-GF-22 RMCP FCU GF Fan Coil Unit
Duct installation not complete
PROJECT : DIFC DATE

FCU STATUS 28/08/2019

FLOOR
SL.NO SYSTEM REFERENCE ZONE CATEGORY DESCRIPTION REMARKS / SNAGS / COMMENTS
LEVEL

33 FCU-CP-GF-26 RMCP FCU GF Fan Coil Unit FCU not working

34 FCU-CP-GF-27 RMCP FCU GF Fan Coil Unit FCU not working

35 FCU-CP-GF-28 RMCP FCU GF Fan Coil Unit FCU not working

36 FCU-CP-GF-29 RMCP FCU GF Fan Coil Unit FCU not working

37 FCU-CP-GF-30 RMCP FCU GF Fan Coil Unit FCU not working

38 FCU-CP-GF-31 RMCP FCU GF Fan Coil Unit FCU not working

39 FCU-CP-FF-21A RMCP FCU GF Fan Coil Unit FCU not installed

No Power
40 FCU-CP-L1-01 RMCP FCU L1 Fan Coil Unit
Duct installation not complete

41 FCU-CP-L1-02 RMCP FCU L1 Fan Coil Unit FCU not installed

FCU not working


42 FCU-CP-L1-04 RMCP FCU L1 Fan Coil Unit
Duct installation not complete

43 FCU-CP-L1-05 RMCP FCU L1 Fan Coil Unit No Power

44 FCU-CP-L1-06 RMCP FCU L1 Fan Coil Unit No Power

No Power
45 FCU-CP-L1-08 RMCP FCU L1 Fan Coil Unit
Duct installation not complete

46 FCU-CP-L1-09 RMCP FCU L1 Fan Coil Unit FCU not working

No Power
47 FCU-CP-L1-10 RMCP FCU L1 Fan Coil Unit
Diffuser installation not complete

48 FCU-CP-L1-11 RMCP FCU L1 Fan Coil Unit FCU not working

49 FCU-CP-L1-12 RMCP FCU L1 Fan Coil Unit No Power

No Power
50 FCU-CP-L1-13 RMCP FCU L1 Fan Coil Unit
Duct installation not complete
No Power
51 FCU-CP-L1-14 RMCP FCU L1 Fan Coil Unit
Duct installation not complete
No Power
52 FCU-CP-L1-14A RMCP FCU L2 Fan Coil Unit
Duct installation not complete
No Power
53 FCU-CP-L1-15A RMCP FCU L1 Fan Coil Unit
Duct installation not complete

54 FCU-CP-L1-16 RMCP FCU L1 Fan Coil Unit FCU not working

No Power
55 FCU-CP-L1-17A RMCP FCU L1 Fan Coil Unit
Duct installation not complete
No Power
56 FCU-CP-L1-17B RMCP FCU L1 Fan Coil Unit
Duct installation not complete
No Power
57 FCU-CP-L1-17C RMCP FCU L1 Fan Coil Unit
Duct installation not complete
No Power
58 FCU-CP-L1-17D RMCP FCU L1 Fan Coil Unit
Duct installation not complete
No Power
59 FCU-CP-L1-17E RMCP FCU L1 Fan Coil Unit
Duct installation not complete
No Power
60 FCU-CP-L1-17F RMCP FCU L1 Fan Coil Unit
Duct installation not complete

61 FCU-CP-L1-18 RMCP FCU L1 Fan Coil Unit No Power

No Power
62 FCU-CP-L1-19 RMCP FCU L1 Fan Coil Unit
Duct installation not complete
No Power
63 FCU-CP-L1-20 RMCP FCU L1 Fan Coil Unit
Duct installation not complete

64 FCU-CP-L1-22 RMCP FCU L1 Fan Coil Unit No power


PROJECT : DIFC DATE

FCU STATUS 28/08/2019

FLOOR
SL.NO SYSTEM REFERENCE ZONE CATEGORY DESCRIPTION REMARKS / SNAGS / COMMENTS
LEVEL
No Power
65 FCU-CP-L1-24 RMCP FCU L1 Fan Coil Unit
Duct installation not complete

66 FCU-CP-SL-19 RMCP FCU B1 Fan Coil Unit No Power

67 FCU-CP-SL-20 RMCP FCU B1 Fan Coil Unit No Power

68 FCU-CP-SL-21 RMCP FCU B1 Fan Coil Unit No Power

69 FCU-CP-SL-22 RMCP FCU B1 Fan Coil Unit No Power

70 FCU-CP-SL-23 RMCP FCU B2 Fan Coil Unit No Power

71 FCU-CP-SL-24 RMCP FCU B1 Fan Coil Unit No Power

72 FCU-CP-SL-25 RMCP FCU B1 Fan Coil Unit No Power

73 FCU-CP-SL-27 RMCP FCU B1 Fan Coil Unit No Power

74 FCU-CP-SL-28 RMCP FCU B1 Fan Coil Unit No Power

75 FCU-CP-SL-29 RMCP FCU B1 Fan Coil Unit No Power

No Power
76 FCU-CP-TL-12 RMCP FCU B2 Fan Coil Unit
Duct installation not complete
No Power
77 FCU-CP-TL-14 RMCP FCU B2 Fan Coil Unit
Duct installation not complete
No Power
78 FCU-CP-TL-15 RMCP FCU B2 Fan Coil Unit
Duct installation not complete
No Power
79 FCU-CP-TL-16 RMCP FCU B2 Fan Coil Unit
Duct installation not complete
No Power
80 FCU-CP-TL-17 RMCP FCU B2 Fan Coil Unit
Duct installation not complete
Less flow in terminals. 32% only
81 FCU-GF-01 MOS FCU GF Fan Coil Unit
Need to add flexible to terminal

82 FCU-GF-01.1 MOS FCU GF Fan Coil Unit No Power

83 FCU-GF-03 MOS FCU GF Fan Coil Unit No Power

84 FCU-GF-02 MOS FCU GF Fan Coil Unit No Power

85 FCU-GF-04 MOS FCU GF Fan Coil Unit No Power

86 FCU-GF-05 MOS FCU GF Fan Coil Unit No Power

87 FCU-GF-06 MOS FCU GF Fan Coil Unit No Power

88 FCU-GF-07 MOS FCU GF Fan Coil Unit No Power

89 FCU-GF-07 MOS FCU GF Fan Coil Unit No Power

90 FCU-GF-08 MOS FCU GF Fan Coil Unit No Power

91 FCU-1F-01 MOS FCU L1 Fan Coil Unit Fcu not running

92 FCU-1F-02 MOS FCU L1 Fan Coil Unit Less flow in terminals. 32% only

Grill installation not complete


93 FCU-1F-03 MOS FCU L1 Fan Coil Unit
No access for VCD balancing

94 FCU-1F-04 MOS FCU L1 Fan Coil Unit No access for balancing

Less flow in terminals. 30% only


95 FCU-1F-05 MOS FCU L1 Fan Coil Unit
No access for VCD balancing
Less flow in terminals. 30% only
96 FCU-1F-06 MOS FCU L1 Fan Coil Unit
No access for VCD balancing
PROJECT : DIFC DATE

FCU STATUS 28/08/2019

FLOOR
SL.NO SYSTEM REFERENCE ZONE CATEGORY DESCRIPTION REMARKS / SNAGS / COMMENTS
LEVEL

97 FCU-2F-08 MOS FCU L2 Fan Coil Unit Balancing complete

Less flow in terminals. 41% only


98 FCU-2F-10 MOS FCU L2 Fan Coil Unit
No access for VCD balancing

99 FCU-2F-07 MOS FCU L2 Fan Coil Unit Balancing complete

100 FCU-2F-01 MOS FCU L2 Fan Coil Unit No access for balancing

101 FCU-2F-01.1 MOS FCU L2 Fan Coil Unit No access for balancing

102 FCU-2F-03 MOS FCU L2 Fan Coil Unit Balancing complete

103 FCU-2F-09 MOS FCU L2 Fan Coil Unit OBD closed and stuck for the grill

Less flow in terminals. 48% only


104 FCU-2F-11 MOS FCU L2 Fan Coil Unit
Flexible connection not proper

105 FCU-2F-04 MOS FCU L2 Fan Coil Unit Balancing complete

Less flow in terminals. 49% only


106 FCU-2F-05 MOS FCU L2 Fan Coil Unit
No access for VCD balancing
Less flow in terminals. 47% only
107 FCU-2F-02 MOS FCU L2 Fan Coil Unit
No access for VCD balancing

108 FCU-GF-PB-01 RMPB FCU GF Fan Coil Unit No Power