Acoustic Calculation of Ventilation Systems

Octave Band Center Frequency (Hz)


63 125 250 500 1,000 2,000 4,000
1 Sound Power Fan 102 99 98 98 97 95 86
2 Safety Factors 3 3 3 3 3 3 3
10 Room and terminal effect -5 -5 -5 -5 -5 -5 -5
11 Allowance for end reflection -12 -8 -4 -1 0 0 0
12 Ductwork attenuation -17 -17 -9 -5 -5 -5 -5
13 Elbow attentuation 0 0 -7 -15 -25 -25 -29
14 Power level split, branch to terminals -6 -6 -6 -6 -6 -6 -6
15 Power level split, main duct to branch duct -10 -10 -10 -10 -10 -10 -10
0 0 0 0 0 0 0
0 0 0 0 0 0 0
0 0 0 0 0 0 0
0 0 0 0 0 0 0
20 Resulting Sound Power Fan 55 56 60 59 49 47 34
21 Sound Pressure Criterion 59 48 40 34 30 27 25
22 Silencer Requirements -4 8 20 25 19 20 9

Acoustic Calculation of Ventilation System

120

1 Sound Power Fan