Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
October 3, 2017
E
Prepared for:
L
ABC
P
City, State
A M Prepared by:
S
John D. Aeiker, PE, CSP
Consultant
CONTENTS
Arc Flash Study Overview
Incident Energy Summary Report
Equipment Evaluation Report
PPE Poster
Arc Flash Model Drawing
October 3, 2017
The current version (v7.0) of SKM Power Tools Arc Flash modeling, equipment evaluation, short circuit current
E
analysis and over current device coordination software programs were used to determine Arc Flash incident
energy levels for this project. IEEE Standard 1584 modeling software and NFPA 70E
L
2018 edition was used for verification.
We have documented the results of the calculations and models on two (2) drawings based on the facility
P
distribution system. The calculations have been based on data collected during my on-site visit on January 17-
18, 2017.
The results contained in this report are based on the design and information available at the time this report
was completed. Any changes made to equipment settings or system configuration will invalidate the results
M
contained in this report and may result in a more hazardous condition thus, necessitating a follow-up review of
this arc flash study.
A
The Incident Energy Summary Report and Equipment Evaluation Report provide the detailed results however;
the six (6) highlights of this Arc Flash Study are summarized as follows:
S
1) Utility Fault Current Contribution
The site-specific short circuit fault current available at the primary incoming bus for the incoming
utility service to the ABC facility in City was made available from the local utility for this Arc Flash Study
by email from Dan Somebody dated January 25, 2017.
2) Plant Electric Room and Compressor Room Main Buses @ DANGEROUS Level
Operation of the 3000A Main Fused Disconnects fed from utility transformers is indicated as
DANGEROUS (>40 calories/cm2). This is not unusual for protective devices located on the secondary
of transformers fed from a utility or at the incoming main lugs of a power distribution center as the
transformer significantly increases the response time of the upstream protective device.
Also, operation of all the protective devices connected to both the Plant Electric Room Main Bus and
the Compressor Room Main Bus is indicated as DANGEROUS (>40 calories/cm2). These DANGEROUS
levels may be mitigated by increasing the working distance to enable the use of AF PPE Category 4. See
the notes on the arc flash model drawing for details. Handle extensions may be available to achieve
this increased working distance. Remote operation of the switches or circuit breakers may also be an
option to consider.
3) System Miscoordination
The Incident Energy Summary Report indicates a few areas of over current device miscoordination, see
the (*N5) notations in the arc flash summary report. In a few cases, subpanel branch breakers are
coordinated to the bus duct fused disconnects bypassing the subpanel main breakers.
In an industrial power system, miscoordination is not an uncommon situation to find and it typically
works in your favor relative to arc flash as the speed of the upstream protective device reduces the
incident energy exposure. These upstream protective devices function in this manner only in an
E
overload condition. As we understand the system is reliable and functions well, our recommendation
is to leave these devices and their settings in their current state. While a detailed system analysis
L
could be considered, it should be noted that this power system device coordination analysis could
consume significant engineering and field monitoring cost.
4) Equipment Evaluation Report
The Equipment Evaluation Report indicates a few failures or marginal ratings. These are primarily in
P
two areas of over current device ratings in the Device Evaluation Summary Reports. One area is the
Short Circuit Current Available ratings for a device > 80% SCCA ratings and the other is related to
connected load to the device > 80% for continuous load ratings.
M
a. In the case of the available short circuit current ratings, these devices are continuous duty
rated and thus they are suitable for the service as designed and intended. This is a software
default value based on the NEC and in this case is not applicable to your system.
A
b. The second area is relative to connected load greater than 80% and 100%. The software
cannot determine the real horsepower of a particular motor and assumes it to be 100%loaded.
It cannot determine true loading of multiple motors operated in a lead / lag configuration. It
S
calculates to 100% load on every device connected. It cannot calculate diversity of loads per
the NEC. This is the only reason you will find a marginal rating on a device due to loading > 80%
or a failure rating on a device due to loading > 100%.
5) Equipment Labeling
The switchboard and motor control center (MCC) sections will be labeled to the actual incident energy
levels per the requirements of IEEE 1584 and NFPA 70E for testing, troubleshooting and interacting
with the device with exposed energized parts. All disconnects that could require maintenance, testing
or troubleshooting will be labeled to the requirements of NFPA 70E 130.5(H); extracted text from
provided next.
Exception: Labels applied prior to September 30, 2011 are acceptable if they contain the available
incident energy or required level of PPE.
The method of calculating and the data to support the information for the label shall be documented.
Where the review of the arc flash hazard risk assessment identifies a change that renders the label
E
inaccurate, the label shall be updated.
The owner of the electrical equipment shall be responsible for the documentation, installation, and
L
maintenance of the field-marked label.
P
6) Operation of Electrical Equipment
The motor control centers and distribution panels are typical lockout points. The calculated energy
levels as indicated on the drawings are often in excess of 1.2 calories/cm2 and as such would require
M
some level of arc rated PPE.
A
(a) Energized Work
(4) Normal Operation. Normal operation of electric equipment shall be permitted where all of the
following conditions are satisfied:
S
1) The equipment is properly installed.
2) The equipment is properly maintained.
3) The equipment doors are closed and secured.
4) All equipment covers are in place and secured.
5) There is no evidence of impending failure.
Informational Note: The phrase properly installed means that the equipment is installed in accordance
with applicable industry codes and standards and the manufacturer’s recommendations. The phrase
properly maintained means that the equipment has been maintained in accordance with the
manufacturer’s recommendations and applicable industry codes and standards. The phrase evidence of
impending failure means that there is evidence such as arcing, overheating, loose or bound equipment
parts, visible damage, or deterioration.
Arc Flash
Task Equipment Condition*
PPE Required
…
Normal operation of a circuit All of the following:
breaker (CB), switch, contactor,
E
or starter The equipment is properly installed
The equipment is properly maintained No
All equipment doors are closed and secured
L
All equipment covers are in place and secured
There is no evidence of impending failure
One or more of the following:
P
The equipment is not properly installed The
equipment is not properly maintained
Yes
Equipment doors are open or not secured
Equipment covers are off or not secured
M
There is evidence of impending failure
NFPA 70E makes it very clear the determination of this condition can only be made by the responsible
person in charge of the facility. If the facility has evidence and documentation as per the requirements
A
of NFPA 70E 205.3, 205.4 and 210.5 that all five conditions are met, then no arc rated PPE would be
required to operate disconnects with the doors properly closed and latched. "In our experience, it is
very rare that equipment is maintained to the exact specifications of the manufacturer”. For
S
reference see NFPA extracts listed below.
A safer approach could be taken. Other facilities with similar situations provide an appropriate Arc
Rated switchers coat, face shield and leather gloves in each of the MCC rooms and then instruct the
task qualified workers when performing the lock out procedure to wear the coat, hard hat, face shield
and gloves to interact with the disconnect in question. If this approach is taken, the under layer
clothing shall be 100% natural fiber non-melting clothing per NFPA 70E. After the disconnect switch is
operated to the “off” position, then lock out procedures can be performed without any arc rated PPE.
Informational Note: Common industry practice is to apply test or calibration decals to equipment to
indicate the test or calibration date and overall condition of equipment that has been tested and
maintained in the field. These decals provide the employee immediate indication of last maintenance
date and if the tested device or system was found acceptable on the date of test. This local information
can assist the employee in the assessment of overall electrical equipment maintenance status.
205.4 Overcurrent Protective Devices. Overcurrent protective devices shall be maintained in accordance
with the manufacturers’ instructions or industry consensus standards. Maintenance, tests, and inspections
shall be documented.
210.5 Protective Devices. Protective devices shall be maintained to adequately withstand or interrupt
available fault current.
Informational Note: Improper or inadequate maintenance can result in increased opening time of the
overcurrent protective device, thus increasing the incident energy.
E
The calculations in this study and resultant incident energy levels are based upon the overcurrent devices
(overcurrent relays, circuit breakers, and fused disconnects) operating as designed and being properly
L
maintained. Maintenance intervals should be based on the manufacturer’s recommendations or industry
consensus testing standards. This is typically a 3 to 5 year interval based on the conditions of the equipment.
The InterNational Electrical Testing Association (NETA) provides guidance documents for adjusting these
P
intervals based on location conditions.
It is important to note that in many cases, changing the trip settings of the equipment in place in the facility is
relatively simple to do. Full-function circuit breakers and time overcurrent relay devices often have adjustable
M
long-time, short-time and instantaneous (LSI) trip units that provide the unique ability to modify or change the
trip settings with a small screwdriver. As any changes to the equipment settings may have a significant impact
on the incident energy levels found in the electrical system, the facility should have a change management
process in place to maintain the settings as found for this Arc Flash Study. Any change to the site distribution
A
system or a change by the utility relative to your incoming service fault current could necessitate a review of
this arc flash study.
S
Annex H of NFPA 70E provides guidance for a clothing system to 12 calories/cm2 and as such on all the model
drawings anytime there is a PPE Category 3 situation it will be indicated as such with the specific calories/cm2
exposure. This can help you if your clothing supplier is providing 12 calories/cm2 clothing. This needs to be
verified to what level of protection your PPE uniform clothing provides. This can be your decision after
verification of the ATPV of the clothing supplied, documented and communicated to the affected personnel.
Layering of Arc rated clothing is allowed as long as it has been tested as a system. This information is available
on the clothing manufacturers’ websites as well as on ArcWear.com. As an example, Westex has tested their
Indura Ultrasoft shirt with their T-shirt (typical rental company provided material) and the combination
achieves 20 calories/cm2. Tyndale’s 9 calories/cm2 shirt has been tested with various other 4 calories/cm2 T-
shirts achieving slightly higher overall results when used together.
Any exposures greater than PPE Category 1 (> 4 calories/cm2) requires the use of an arc rated
face shield and balaclava or an arc rated face shield hood assembly.
NFPA 70E requires the arc flash study to be reviewed every five years. If the utility contacts you for a service
interruption, ask the question for what purpose. If they are upgrading the transmission line or transmission /
distribution transformers, this is your indication to find out what the change will be to your incoming fault
current and relay clearing times which can affect the arc flash calculations.
If the utility has not changed anything relative to your incoming service fault current and you have not changed
anything in your distribution system on site, then the review can be a very simple process of noting this fact
every 5 years. A verification from the utility of the utility information found on the arc flash study document
and also contained on the USB drive is all that would be required.
NFPA 70E requires initial qualified training and re-training every three years for your qualified electrical
workers. We typically recommend electrical safety training after the labeling activity as this can provide a
customized session for your specific equipment and what the labels require as far as proper work practices.
E
Within the documentation binder for this study are copies of all the associated information; this summary
report, the one-line drawings from SKM, the Incident Energy Summary Report, and the Equipment Evaluation
L
Report. All of the relative files in PDF, native Microsoft Office format and native SKM format are provided on
an USB drive for file retention. It is recommended that these files be retained in a secure location within your
organization. e-Hazard also retains the files backed up to a “secured cloud service”.
P
I keep an exact duplicate of the documentation binder in my office so if there is ever a question, we can both
look at the exact same piece of information at any time in the future. If I should be traveling,
I have all the files on my laptop with me.
M
Please call John Aeiker, 251-581-1492 for any additional clarification relative to this report.
Thank you,
S A
john.aeiker@e-hazard.com
A B C D E F G H I J K L M N O P
Bus Name Protective Bus Bus Bus Prot Dev Prot Dev Trip/ Breaker Ground Equip Gap Arc Working Incident PPE Level
E
1
2 Device kV Bolted Arcing Bolted Arcing Delay Opening Type (mm) Flash Distance Energy
3 Name Fault Fault Fault Fault Time Time/Tol Boundary (in) (cal/cm2)
L
Bus 1 - End Plant Elec - Bus 1 0.48 15.76 9.67 15.76 9.67 0.025 0.000 Yes PNL 25 14 18 0.80 Level 0
6
Bus 10 - Begin Plant Elec - Bus 10 0.48 35.03 19.14 35.03 19.14 0.025 0.000 Yes PNL 25 22 18 1.7 Level 1
7
Bus 10 - End Plant Elec - Bus 10 0.48 27.32 15.47 27.32 15.47 0.025 0.000 Yes PNL 25 19 18 1.3 Level 1
8
Bus 2 - Begin Plant Elec - Bus 2 0.48 32.38 17.89 32.38 17.89 0.025 0.000 Yes PNL 25 21 18 1.6 Level 1
9
P
Bus 2 - End Plant Elec - Bus 2 0.48 17.66 10.66 17.66 10.66 0.025 0.000 Yes PNL 25 15 18 0.89 Level 0
10
Bus 3 - Begin Plant Elec - Bus 3 0.48 26.90 15.27 26.90 15.27 0.025 0.000 Yes PNL 25 19 18 1.3 Level 1
11
Bus 3 - End Plant Elec - Bus 3 0.48 16.94 10.29 16.94 10.29 0.025 0.000 Yes PNL 25 15 18 0.86 Level 0
12
Bus 4 - Begin Plant Elec - Bus 4 0.48 24.32 14.01 24.32 14.01 0.025 0.000 Yes PNL 25 18 18 1.2 Level 0
13
Bus 4 - End Plant Elec - Bus 4 0.48 14.79 9.16 14.79 9.16 0.025 0.000 Yes PNL 25 14 18 0.75 Level 0
14
Bus 5 - Begin Plant Elec - Bus 5 0.48 21.51 12.62 21.51 12.62 0.025 0.000 Yes PNL 25 17 18 1.1 Level 0
15
M
Bus 5 - End Plant Elec - Bus 5 0.48 12.87 8.14 12.87 8.14 0.025 0.000 Yes PNL 25 13 18 0.66 Level 0
16
Bus 6 - Begin Plant Elec - Bus 6 0.48 19.24 11.47 19.24 11.47 0.025 0.000 Yes PNL 25 16 18 0.96 Level 0
17
Bus 6 - End Plant Elec - Bus 6 0.48 15.30 9.43 15.30 9.43 0.025 0.000 Yes PNL 25 14 18 0.78 Level 0
18
Bus 7 - Begin Plant Elec - Bus 7 0.48 17.92 10.79 17.92 10.79 0.025 0.000 Yes PNL 25 15 18 0.90 Level 0
19
Bus 7 - End Plant Elec - Bus 7 0.48 11.47 7.37 11.47 7.37 0.025 0.000 Yes PNL 25 12 18 0.60 Level 0
A
20
Bus 8 - Begin Plant Elec - Bus 8 0.48 17.92 10.79 17.92 10.79 0.025 0.000 Yes PNL 25 15 18 0.90 Level 0
21
Bus 8 - End Plant Elec - Bus 8 0.48 14.00 8.74 14.00 8.74 0.025 0.000 Yes PNL 25 13 18 0.72 Level 0
22
Bus 9 - Begin Plant Elec - Bus 9 0.48 17.07 10.36 17.07 10.36 0.025 0.000 Yes PNL 25 15 18 0.86 Level 0
23
Bus 9 - End Plant Elec - Bus 9 0.48 11.11 7.18 11.11 7.18 0.025 0.000 Yes PNL 25 12 18 0.58 Level 0
24
S
BUS-0003 Compressor Room Utility 22.86 22.95 22.95 22.94 22.94 0.017 0.000 Yes SWG 153 76 36 5.4 Level 2 (*N11) (*N21)
25 Cutout
Comp. Room - Typ Comp. Room - Typ 0.48 24.36 14.03 24.36 14.03 0.025 0.000 Yes PNL 25 18 18 1.2 Level 0
26 125A/150A Bus 125A/150A CB
Comp. Room - Typ Comp. Room - Typ 0.48 18.63 11.16 18.63 11.16 0.025 0.000 Yes PNL 25 15 18 0.93 Level 0
27 30A/80A Bus 30A/80A CB
Compressor Room Main Compressor Room Utility 0.48 39.77 18.13 39.24 17.88 2 0.000 Yes PNL 25 306 18 125 Dangerous! (*N3)
28 Bus Cutout (*N5) (*N9) (*N21)
Compressor Room Main Compressor Room Utility 0.48 39.95 18.20 39.42 17.96 2 0.000 Yes PNL 25 307 18 125 Dangerous! (*N3)
29 FD Bus Cutout (*N9) (*N21)
Furnace 701 Bus Plant Elec - Furnace 701 0.48 20.04 11.87 19.19 11.37 0.025 0.000 Yes PNL 25 16 18 1.00 Level 0
30 CB
Furnace 702 Bus Plant Elec - Furnace 702 0.48 17.28 10.46 16.44 9.96 0.025 0.000 Yes PNL 25 15 18 0.87 Level 0
31 CB
Furnance 701 Heater Plant Elec - Furnace 701 0.24 12.09 5.23 11.58 5.01 2 0.000 Yes PNL 25 135 18 33 Level 4 (*N9)
32 CB
Furnance 702 Heater Plant Elec - Furnace 702 0.24 11.55 5.06 10.99 4.82 2 0.000 Yes PNL 25 132 18 31 Level 4 (*N9)
33 CB
Plant Electric Main FD Plant Electric Utility 0.48 38.11 20.56 36.38 19.63 1.838 0.000 Yes PNL 25 310 18 128 Dangerous! (*N21)
34 Bus Cutouts
Plant Electric Room Plant Electric Utility 0.48 37.95 20.49 36.22 19.55 1.856 0.000 Yes PNL 25 311 18 128 Dangerous! (*N5)
35 Main Bus Cutouts (*N21)
Page 1 of 5
October 3, 2017 ABC e-Hazard
Incident Energy Summary Report J.D. Aeiker
A B C D E F G H I J K L M N O P
Bus Name Protective Bus Bus Bus Prot Dev Prot Dev Trip/ Breaker Ground Equip Gap Arc Working Incident PPE Level
E
1
2 Device kV Bolted Arcing Bolted Arcing Delay Opening Type (mm) Flash Distance Energy
3 Name Fault Fault Fault Fault Time Time/Tol Boundary (in) (cal/cm2)
L
36 Compressor CB
Typ 100A Load - Bus 1 Typ 100A FD - Bus 1 0.48 10.48 6.83 10.48 6.83 0.004 0.000 Yes PNL 25 4 18 0.09 Level 0
37
Typ 100A Load - Bus 10 Typ 100A FD - Bus 10 0.48 15.03 9.29 15.03 9.29 0.004 0.000 Yes PNL 25 5 18 0.13 Level 0
38
P
Typ 100A Load - Bus 2 Typ 100A FD - Bus 2 0.48 11.35 7.31 11.35 7.31 0.004 0.000 Yes PNL 25 4 18 0.10 Level 0
39
Typ 100A Load - Bus 3 Typ 100A FD - Bus 3 0.48 11.01 7.12 11.01 7.12 0.004 0.000 Yes PNL 25 4 18 0.10 Level 0
40
Typ 100A Load - Bus 4 Typ 100A FD - Bus 4 0.48 10.02 6.57 10.02 6.57 0.004 0.000 Yes PNL 25 4 18 0.09 Level 0
41
Typ 100A Load - Bus 5 Typ 100A FD - Bus 5 0.48 9.08 5.13 9.08 5.13 0.008 0.000 Yes PNL 25 5 18 0.13 Level 0 (*N3)
M
42
Typ 100A Load - Bus 6 Typ 100A FD - Bus 6 0.48 10.22 6.68 10.22 6.68 0.004 0.000 Yes PNL 25 4 18 0.09 Level 0
43
Typ 100A Load - Bus 7 Typ 100A FD - Bus 7 0.48 8.35 4.78 8.35 4.78 0.008 0.000 Yes PNL 25 5 18 0.12 Level 0 (*N3)
44
Typ 100A Load - Bus 8 Typ 100A FD - Bus 8 0.48 9.62 6.34 9.62 6.34 0.004 0.000 Yes PNL 25 4 18 0.08 Level 0
A
45
Typ 100A Load - Bus 9 Typ 100A FD - Bus 9 0.48 8.15 4.68 8.15 4.68 0.008 0.000 Yes PNL 25 4 18 0.12 Level 0 (*N3)
46
Typ 200A Load - Bus 1 Typ 200A FD - Bus 1 0.48 12.92 8.16 12.92 8.16 0.008 0.000 Yes PNL 25 6 18 0.22 Level 0
47
S
Typ 200A Load - Bus 10 Typ 200A FD - Bus 10 0.48 20.16 11.93 20.16 11.93 0.004 0.000 Yes PNL 25 5 18 0.17 Level 0
48
Typ 200A Load - Bus 2 Typ 200A FD - Bus 2 0.48 14.20 8.85 14.20 8.85 0.008 0.000 Yes PNL 25 7 18 0.24 Level 0
49
Typ 200A Load - Bus 3 Typ 200A FD - Bus 3 0.48 13.71 8.59 13.71 8.59 0.008 0.000 Yes PNL 25 7 18 0.23 Level 0
50
Typ 200A Load - Bus 4 Typ 200A FD - Bus 4 0.48 12.25 7.80 12.25 7.80 0.008 0.000 Yes PNL 25 6 18 0.21 Level 0
51
Typ 200A Load - Bus 5 Typ 200A FD - Bus 5 0.48 10.89 7.05 10.89 7.05 0.008 0.000 Yes PNL 25 6 18 0.19 Level 0
52
Typ 200A Load - Bus 6 Typ 200A FD - Bus 6 0.48 12.59 7.98 12.59 7.98 0.008 0.000 Yes PNL 25 6 18 0.22 Level 0
53
Typ 200A Load - Bus 7 Typ 200A FD - Bus 7 0.48 9.87 6.48 9.87 6.48 0.008 0.000 Yes PNL 25 6 18 0.17 Level 0
54
Typ 200A Load - Bus 8 Typ 200A FD - Bus 8 0.48 11.69 7.49 11.69 7.49 0.008 0.000 Yes PNL 25 6 18 0.20 Level 0
55
Typ 200A Load - Bus 9 Typ 200A FD - Bus 9 0.48 9.60 6.33 9.60 6.33 0.008 0.000 Yes PNL 25 5 18 0.17 Level 0
56
Typ 208V Panel - Bus 1 Typ 208V XFMR FD - 0.208 1.54 1.17 1.54 1.17 0.458 0.000 Yes PNL 25 18 18 1.2 Level 0 (*N15)
57 Bus 1
Typ 208V Panel - Bus Typ 208V XFMR FD - 0.208 1.57 1.19 1.57 1.19 0.426 0.000 Yes PNL 25 18 18 1.2 Level 0 (*N15)
58 10 Bus 10
Page 2 of 5
October 3, 2017 ABC e-Hazard
Incident Energy Summary Report J.D. Aeiker
A B C D E F G H I J K L M N O P
Bus Name Protective Bus Bus Bus Prot Dev Prot Dev Trip/ Breaker Ground Equip Gap Arc Working Incident PPE Level
E
1
2 Device kV Bolted Arcing Bolted Arcing Delay Opening Type (mm) Flash Distance Energy
3 Name Fault Fault Fault Fault Time Time/Tol Boundary (in) (cal/cm2)
L
59 Bus 2
Typ 208V Panel - Bus 3 Typ 208V XFMR FD - 0.208 1.55 1.17 1.55 1.17 0.453 0.000 Yes PNL 25 18 18 1.2 Level 0 (*N15)
60 Bus 3
Typ 208V Panel - Bus 4 Typ 208V XFMR FD - 0.208 1.54 1.17 1.54 1.17 0.463 0.000 Yes PNL 25 18 18 1.2 Level 0 (*N15)
61 Bus 4
P
Typ 208V Panel - Bus 5 Typ 208V XFMR FD - 0.208 1.53 1.16 1.53 1.16 0.475 0.000 Yes PNL 25 18 18 1.2 Level 0 (*N15)
62 Bus 5
Typ 208V Panel - Bus 6 Typ 208V XFMR FD - 0.208 1.54 1.17 1.54 1.17 0.46 0.000 Yes PNL 25 18 18 1.2 Level 0 (*N15)
63 Bus 6
Typ 208V Panel - Bus 7 Typ 208V XFMR FD - 0.208 1.52 1.16 1.52 1.16 0.487 0.000 Yes PNL 25 18 18 1.2 Level 0 (*N15)
64 Bus 7
Typ 208V Panel - Bus 8 Typ 208V XFMR FD - 0.208 1.54 1.17 1.54 1.17 0.468 0.000 Yes PNL 25 18 18 1.2 Level 0 (*N15)
M
65 Bus 8
Typ 208V Panel - Bus 9 Typ 208V XFMR FD - 0.208 1.52 1.16 1.52 1.16 0.491 0.000 Yes PNL 25 18 18 1.2 Level 0 (*N15)
66 Bus 9
Typ 240V Panel - Bus 1 Typ 240V XFMR FD - 0.24 1.34 0.91 1.34 0.91 0.861 0.000 Yes PNL 25 18 18 1.2 Level 0 (*N3) (*N15)
67 Bus 1
Typ 240V Panel - Bus Typ 240V XFMR FD - 0.24 1.36 0.92 1.36 0.92 0.799 0.000 Yes PNL 25 18 18 1.2 Level 0 (*N3) (*N15)
A
68 10 Bus 10
Typ 240V Panel - Bus 2 Typ 240V XFMR FD - 0.24 1.34 0.91 1.34 0.91 0.846 0.000 Yes PNL 25 18 18 1.2 Level 0 (*N3) (*N15)
69 Bus 2
Typ 240V Panel - Bus 3 Typ 240V XFMR FD - 0.24 1.34 0.91 1.34 0.91 0.851 0.000 Yes PNL 25 18 18 1.2 Level 0 (*N3) (*N15)
70 Bus 3
S
Typ 240V Panel - Bus 4 Typ 240V XFMR FD - 0.24 1.34 0.91 1.34 0.91 0.871 0.000 Yes PNL 25 18 18 1.2 Level 0 (*N3) (*N15)
71 Bus 4
Typ 240V Panel - Bus 5 Typ 240V XFMR FD - 0.24 1.33 0.91 1.33 0.91 0.894 0.000 Yes PNL 25 18 18 1.2 Level 0 (*N3) (*N15)
72 Bus 5
Typ 240V Panel - Bus 6 Typ 240V XFMR FD - 0.24 1.34 0.91 1.34 0.91 0.864 0.000 Yes PNL 25 18 18 1.2 Level 0 (*N3) (*N15)
73 Bus 6
Typ 240V Panel - Bus 7 Typ 240V XFMR FD - 0.24 1.32 0.90 1.32 0.90 0.916 0.000 Yes PNL 25 18 18 1.2 Level 0 (*N3) (*N15)
74 Bus 7
Typ 240V Panel - Bus 8 Typ 240V XFMR FD - 0.24 1.33 0.91 1.33 0.91 0.879 0.000 Yes PNL 25 18 18 1.2 Level 0 (*N3) (*N15)
75 Bus 8
Typ 240V Panel - Bus 9 Typ 240V XFMR FD - 0.24 1.32 0.90 1.32 0.90 0.923 0.000 Yes PNL 25 18 18 1.2 Level 0 (*N3) (*N15)
76 Bus 9
Typ 30A Load - Bus 1 Typ 30A FD - Bus 1 0.48 5.19 3.74 5.19 3.74 0.004 0.000 Yes PNL 25 3 18 0.05 Level 0
77
Typ 30A Load - Bus 10 Typ 30A FD - Bus 10 0.48 6.02 4.25 6.02 4.25 0.004 0.000 Yes PNL 25 3 18 0.05 Level 0
78
Typ 30A Load - Bus 2 Typ 30A FD - Bus 2 0.48 5.38 3.86 5.38 3.86 0.004 0.000 Yes PNL 25 3 18 0.05 Level 0
79
Typ 30A Load - Bus 3 Typ 30A FD - Bus 3 0.48 5.30 3.81 5.30 3.81 0.004 0.000 Yes PNL 25 3 18 0.05 Level 0
80
Typ 30A Load - Bus 4 Typ 30A FD - Bus 4 0.48 5.08 3.68 5.08 3.68 0.004 0.000 Yes PNL 25 3 18 0.05 Level 0
81
Typ 30A Load - Bus 5 Typ 30A FD - Bus 5 0.48 4.84 3.53 4.84 3.53 0.004 0.000 Yes PNL 25 2 18 0.04 Level 0
82
Typ 30A Load - Bus 6 Typ 30A FD - Bus 6 0.48 5.11 3.69 5.11 3.69 0.004 0.000 Yes PNL 25 3 18 0.05 Level 0
83
Typ 30A Load - Bus 7 Typ 30A FD - Bus 7 0.48 4.64 3.40 4.64 3.40 0.004 0.000 Yes PNL 25 2 18 0.04 Level 0
84
Page 3 of 5
October 3, 2017 ABC e-Hazard
Incident Energy Summary Report J.D. Aeiker
A B C D E F G H I J K L M N O P
Bus Name Protective Bus Bus Bus Prot Dev Prot Dev Trip/ Breaker Ground Equip Gap Arc Working Incident PPE Level
E
1
2 Device kV Bolted Arcing Bolted Arcing Delay Opening Type (mm) Flash Distance Energy
3 Name Fault Fault Fault Fault Time Time/Tol Boundary (in) (cal/cm2)
L
Typ 30A Load - Bus 9 Typ 30A FD - Bus 9 0.48 4.58 3.36 4.58 3.36 0.004 0.000 Yes PNL 25 2 18 0.04 Level 0
86
Typ PP Panels & Field Typical LL Panel Branch 0.208 1.79 1.30 1.79 1.30 1.834 0.000 Yes PNL 25 18 18 1.2 Level 0 (*N15) (*N21)
87 Devices CB
Typical LL Panel Field Typical LL Panel Branch 0.48 18.19 10.93 18.19 10.93 0.018 0.000 Yes PNL 25 13 18 0.66 Level 0 (*N21)
88 Device CB
P
Level 0: Nonmelting or 0.0 - 1.2 cal/cm^2 #Level 0 = 71 (*N11) - Out of IEEE
Untreated Fiber with 1584 Range, Lee
Weight >= 4.5 oz/sq yd Equation Used.
Applicable for Open
Air only. Existing
Equipment type is not
89 Open Air!
M
Level 1: Arc-rated shirt 1.2 - 4.0 cal/cm^2 #Level 1 = 6 (*N3) - Arcing Current
& pants or arc-rated Low Tolerances Used
90 coverall
Level 2: Arc-rated shirt 4.0 - 8.0 cal/cm^2 #Level 2 = 1 (*N5) -
& pants or arc-rated Miscoordinated,
coverall Upstream Device
Tripped
A
91
Level 3: Arc-rated shirt 8.0 - 25.0 cal/cm^2 #Level 3 = 0 (*N9) - Max Arcing
& pants + arc-rated Duration Reached
coverall + arc-rated arc
flash suit
92
S
Level 4: Arc-rated shirt 25.0 - 40.0 cal/cm^2 #Level 4 = 2 (*N15) - Report as
& pants + arc-rated category 0 if fed by
coverall + arc-rated arc one transformer size
flash suit < 125 kVA
93
Level Dangerous!: DO 40.0 - 999.0 cal/cm^2 #Danger = 4 (*N21) - Equipment
NOT WORK ON LIVE! Evaluation Failed,
OVERDUTIED
EQUIPMENT
FOUND -
Inappropriate to
provide arc-flash
94 hazard results.
For additional information refer to NFPA 70 E, Standard for NFPA 70E 2012 Annex D.7 - IEEE 1584 Bus Report ( - 80% Cleared
Electrical Safety in the Workplace. Fault Threshold, include Ind. Motors for 5.0 Cycles), mis-coordination
checked
95
Level 0: Nonmelting or Untreated Fiber with Weight >= 4.5 oz/sq yd, Safety Glasses or Goggles + Ear Canal Inserts, Leather Gloves, Safety glasses, Non-melting or untreated natural fiber (cotton/wool/rayon/silk > 4.5 oz/sq
yd), shirt (long-sleeve), pants (long)., > 50V voltage rated tools + Class 0 (minimum) gloves, Dielectric shoes or insulating mat (step and touch potential).
96
Level 1: Arc-rated shirt & pants or arc-rated coverall , Hardhat + Arc-rated hard hat liner + Safety Glasses or Goggles + Ear Canal Inserts, Leather Gloves, Leather work shoes, Safety glasses, electrically rated hard hat with
hood and face shield., 4 cal/sq cm, Arc-rated shirt (long-sleeve) plus Arc-rated pants (long), or Arc-rated coverall, plus arc-rated face shield or arc flash suit hood, Arc-rated rainwear as needed., > 50V voltage rated tools +
Class 0 (minimum) gloves and leather protectors (flash) as needed., Leather shoes (flash) as needed. Dielectric shoes or insulating mat (step and touch potential).
97
Page 4 of 5
October 3, 2017 ABC e-Hazard
Incident Energy Summary Report J.D. Aeiker
A B C D E F G H I J K L M N O P
Bus Name Protective Bus Bus Bus Prot Dev Prot Dev Trip/ Breaker Ground Equip Gap Arc Working Incident PPE Level
E
1
2 Device kV Bolted Arcing Bolted Arcing Delay Opening Type (mm) Flash Distance Energy
3 Name Fault Fault Fault Fault Time Time/Tol Boundary (in) (cal/cm2)
L
hood and face shield. Hearing protection., 8 cal/sq cm, Arc-rated shirt (long-sleeve) plus Arc-rated pants (long), or Arc-rated coverall, plus arc-rated flash suit hood or arc-rated face shield and arc rated balaclava, Arc-rated
rainwear as needed., > 50V voltage rated tools + Class 0 (minimum) gloves and leather protectors (flash)., Leather shoes (flash) as needed. Dielectric shoes or insulating mat (step and touch potential).
98
Level 3: Arc-rated shirt & pants + arc-rated coverall + arc-rated arc flash suit , Hardhat + Arc-rated hard hat liner + Safety Glasses or Goggles + Ear Canal Inserts, Arc-rated Gloves, Leather work shoes, Safety glasses,
electrically rated hard hat with hood and face shield. Hearing protection., 25 cal/sq cm, Arc-rated shirt (long-sleeve) plus Arc-rated pants (long) plus Arc-rated coverall, plus arc rated arc flash suit jacket, pants, & hood, Arc-
rated rainwear as needed., > 50V voltage rated tools + Class 0 (minimum) gloves and leather protectors (flash)., Leather shoes (flash) as needed. Dielectric shoes or insulating mat (step and touch potential).
P
99
Level 4: Arc-rated shirt & pants + arc-rated coverall + arc-rated arc flash suit , Hardhat + Arc-rated hard hat liner + Safety Glasses or Goggles + Ear Canal Inserts, Arc-rated Gloves, Leather work shoes, Safety glasses,
electrically rated hard hat with hood and face shield. Hearing protection., 40 cal/sq cm, Arc-rated shirt (long-sleeve) plus Arc-rated pants (long) plus Arc-rated coverall, plus arc rated arc flash suit jacket, pants, & hood, Arc-
rated rainwear as needed., > 50V voltage rated tools + Class 0 (minimum) gloves and leather protectors (flash)., Leather shoes (flash) as needed. Dielectric shoes or insulating mat (step and touch potential).
100
Level Dangerous!: DO NOT WORK ON LIVE!, DO NOT WORK ON LIVE!, DO NOT WORK ON LIVE!, DO NOT WORK ON LIVE!, DO NOT WORK ON LIVE!, No FR Category Found
M
101
S A
Page 5 of 5
October 3, 2017 ABC e-Hazard
Equipment Evaluation Report J.D. Aeiker
A B C D E F G
1 Device/Bus Status Description Voltage (V) Continuous Amps INT kA Rating%
3 Comp. Room - Compressor CB Pass SFLA, Spectra RMS 480 90.69 41.95 (*N1) 100.00
5 GE SFLA 36.28
6
7 Comp. Room - Typ 125A/150A CB Pass SFLA, Spectra RMS 480 0.00 41.95 (*N1) 100.00
9 GE SFLA 0.00
10
11 Comp. Room - Typ 30A/80A CB Pass SELA, Spectra RMS 480 0.00 41.95 (*N1) 100.00
E
12 Compressor Room Main Bus 15-150A 480 80.00 65.00 64.54
13 GE SELA 0.00
14
L
15 Compressor Room Main FD Pass A4BY, 600V Class L 480 90.69 42.44 (*N1) 80.00
P
18
19 Compressor Room Main SW Pass TPS Power Break 480 90.69 42.44 (*N1) 100.00
20 Compressor Room Main FD Bus LSI, 3000A 480 3000.00 100.00 42.44
21 GE TPS 3.02
M
22
23 Compressor Room Utility Cutout Fail SM-4, 25kV E-Rated 22860 1.90 *25.74 99.39
A
26
27 Plant Elec - Bus 1 Pass SGLA, Spectra RMS 480 0.00 41.95 (*N1) 100.00
S
29 GE SGLA 0.00
30
31 Plant Elec - Bus 10 Pass SGLA, Spectra RMS 480 0.00 40.17 (*N1) 100.00
32 Plant Electric Room Main Bus 125-600A 480 400.00 65.00 61.80
33 GE SGLA 0.00
34
35 Plant Elec - Bus 2 Pass SGLA, Spectra RMS 480 0.00 41.95 (*N1) 100.00
37 GE SGLA 0.00
38
39 Plant Elec - Bus 3 Pass SGLA, Spectra RMS 480 0.00 41.95 (*N1) 100.00
41 GE SGLA 0.00
42
43 Plant Elec - Bus 4 Pass SGLA, Spectra RMS 480 0.00 41.95 (*N1) 100.00
45 GE SGLA 0.00
46
47 Plant Elec - Bus 5 Pass SGLA, Spectra RMS 480 0.00 41.95 (*N1) 100.00
49 GE SGLA 0.00
50
51 Plant Elec - Bus 6 Pass SGLA, Spectra RMS 480 0.00 41.95 (*N1) 100.00
53 GE SGLA 0.00
Page 1 of 6
October 3, 2017 ABC e-Hazard
Equipment Evaluation Report J.D. Aeiker
A B C D E F G
1 Device/Bus Status Description Voltage (V) Continuous Amps INT kA Rating%
54
55 Plant Elec - Bus 7 Pass SGLA, Spectra RMS 480 0.00 40.17 (*N1) 100.00
56 Plant Electric Room Main Bus 125-600A 480 400.00 65.00 61.80
57 GE SGLA 0.00
58
59 Plant Elec - Bus 8 Pass SGLA, Spectra RMS 480 0.00 40.17 (*N1) 100.00
60 Plant Electric Room Main Bus 125-600A 480 400.00 65.00 61.80
61 GE SGLA 0.00
E
62
63 Plant Elec - Bus 9 Pass SGLA, Spectra RMS 480 0.00 40.17 (*N1) 100.00
64 Plant Electric Room Main Bus 125-600A 480 400.00 65.00 61.80
65 GE SGLA 0.00
L
66
67 Plant Elec - Furnace 701 CB Pass SGLA, Spectra RMS 480 152.28 40.17 (*N1) 100.00
68 Plant Electric Room Main Bus 125-600A 480 500.00 65.00 61.80
P
69 GE SGLA 30.46
70
71 Plant Elec - Furnace 702 CB Pass SGLA, Spectra RMS 480 152.48 40.17 (*N1) 100.00
72 Plant Electric Room Main Bus 125-600A 480 500.00 65.00 61.80
M
73 GE SGLA 30.50
74
75 Plant Electric Room Main FD Pass A4BY, 600V Class L 480 304.76 40.59 (*N1) 80.00
A
77 GOULD SHAWMUT A4BY 10.16
78
79 Plant Electric Room Main SW Pass TPS Power Break 480 304.76 40.59 (*N1) 100.00
S
80 Plant Electric Main FD Bus LSI, 3000A 480 3000.00 100.00 40.59
81 GE TPS 10.16
82
83 Plant Electric Utility Cutouts Fail SM-4, 25kV E-Rated 22860 6.40 *24.33 99.39
86
87 Typ 100A FD - Bus 1 Pass FRS-R, 600V Class RK5 480 0.00 15.76 80.00
90
91 Typ 100A FD - Bus 10 Pass FRS-R, 600V Class RK5 480 0.00 27.32 80.00
94
95 Typ 100A FD - Bus 2 Pass FRS-R, 600V Class RK5 480 0.00 17.66 80.00
98
99 Typ 100A FD - Bus 3 Pass FRS-R, 600V Class RK5 480 0.00 16.94 80.00
102
103 Typ 100A FD - Bus 4 Pass FRS-R, 600V Class RK5 480 0.00 14.79 80.00
Page 2 of 6
October 3, 2017 ABC e-Hazard
Equipment Evaluation Report J.D. Aeiker
A B C D E F G
1 Device/Bus Status Description Voltage (V) Continuous Amps INT kA Rating%
106
107 Typ 100A FD - Bus 5 Pass FRS-R, 600V Class RK5 480 0.00 12.87 80.00
110
111 Typ 100A FD - Bus 6 Pass FRS-R, 600V Class RK5 480 0.00 15.30 80.00
E
114
115 Typ 100A FD - Bus 7 Pass FRS-R, 600V Class RK5 480 0.00 11.47 80.00
L
117 BUSSMANN FRS-R 0.00
118
119 Typ 100A FD - Bus 8 Pass FRS-R, 600V Class RK5 480 0.00 14.00 80.00
P
120 Bus 8 - End 1-600A 600 100.00 200.00 7.00
122
123 Typ 100A FD - Bus 9 Pass FRS-R, 600V Class RK5 480 0.00 11.11 80.00
M
124 Bus 9 - End 1-600A 600 100.00 200.00 5.56
126
127 Typ 200A FD - Bus 1 Pass FRS-R, 600V Class RK5 480 0.00 15.76 80.00
A
128 Bus 1 - End 1-600A 600 200.00 200.00 7.88
130
S
131 Typ 200A FD - Bus 10 Pass FRS-R, 600V Class RK5 480 0.00 27.32 80.00
134
135 Typ 200A FD - Bus 2 Pass FRS-R, 600V Class RK5 480 0.00 17.66 80.00
138
139 Typ 200A FD - Bus 3 Pass FRS-R, 600V Class RK5 480 0.00 16.94 80.00
142
143 Typ 200A FD - Bus 4 Pass FRS-R, 600V Class RK5 480 0.00 14.79 80.00
146
147 Typ 200A FD - Bus 5 Pass FRS-R, 600V Class RK5 480 0.00 12.87 80.00
150
151 Typ 200A FD - Bus 6 Pass FRS-R, 600V Class RK5 480 0.00 15.30 80.00
154
155 Typ 200A FD - Bus 7 Pass FRS-R, 600V Class RK5 480 0.00 11.47 80.00
Page 3 of 6
October 3, 2017 ABC e-Hazard
Equipment Evaluation Report J.D. Aeiker
A B C D E F G
1 Device/Bus Status Description Voltage (V) Continuous Amps INT kA Rating%
158
159 Typ 200A FD - Bus 8 Pass FRS-R, 600V Class RK5 480 0.00 14.00 80.00
162
163 Typ 200A FD - Bus 9 Pass FRS-R, 600V Class RK5 480 0.00 11.11 80.00
E
165 BUSSMANN FRS-R 0.00
166
167 Typ 208V XFMR FD - Bus 1 Pass FRS-R, 600V Class RK5 480 0.00 15.76 80.00
L
168 Bus 1 - End 1-600A 600 100.00 200.00 7.88
170
P
171 Typ 208V XFMR FD - Bus 10 Pass FRS-R, 600V Class RK5 480 0.00 27.32 80.00
174
M
175 Typ 208V XFMR FD - Bus 2 Pass FRS-R, 600V Class RK5 480 0.00 17.66 80.00
178
A
179 Typ 208V XFMR FD - Bus 3 Pass FRS-R, 600V Class RK5 480 0.00 16.94 80.00
S
182
183 Typ 208V XFMR FD - Bus 4 Pass FRS-R, 600V Class RK5 480 0.00 14.79 80.00
186
187 Typ 208V XFMR FD - Bus 5 Pass FRS-R, 600V Class RK5 480 0.00 12.87 80.00
190
191 Typ 208V XFMR FD - Bus 6 Pass FRS-R, 600V Class RK5 480 0.00 15.30 80.00
194
195 Typ 208V XFMR FD - Bus 7 Pass FRS-R, 600V Class RK5 480 0.00 11.47 80.00
198
199 Typ 208V XFMR FD - Bus 8 Pass FRS-R, 600V Class RK5 480 0.00 14.00 80.00
202
203 Typ 208V XFMR FD - Bus 9 Pass FRS-R, 600V Class RK5 480 0.00 11.11 80.00
206
Page 4 of 6
October 3, 2017 ABC e-Hazard
Equipment Evaluation Report J.D. Aeiker
A B C D E F G
1 Device/Bus Status Description Voltage (V) Continuous Amps INT kA Rating%
207 Typ 240V XFMR FD - Bus 1 Pass FRS-R, 600V Class RK5 480 0.00 15.76 80.00
210
211 Typ 240V XFMR FD - Bus 10 Pass FRS-R, 600V Class RK5 480 0.00 27.32 80.00
214
215 Typ 240V XFMR FD - Bus 2 Pass FRS-R, 600V Class RK5 480 0.00 17.66 80.00
E
216 Bus 2 - End 1-600A 600 100.00 200.00 8.83
218
L
219 Typ 240V XFMR FD - Bus 3 Pass FRS-R, 600V Class RK5 480 0.00 16.94 80.00
P
222
223 Typ 240V XFMR FD - Bus 4 Pass FRS-R, 600V Class RK5 480 0.00 14.79 80.00
M
226
227 Typ 240V XFMR FD - Bus 5 Pass FRS-R, 600V Class RK5 480 0.00 12.87 80.00
A
230
231 Typ 240V XFMR FD - Bus 6 Pass FRS-R, 600V Class RK5 480 0.00 15.30 80.00
S
233 BUSSMANN FRS-R 0.00
234
235 Typ 240V XFMR FD - Bus 7 Pass FRS-R, 600V Class RK5 480 0.00 11.47 80.00
238
239 Typ 240V XFMR FD - Bus 8 Pass FRS-R, 600V Class RK5 480 0.00 14.00 80.00
242
243 Typ 240V XFMR FD - Bus 9 Pass FRS-R, 600V Class RK5 480 0.00 11.11 80.00
246
247 Typ 30A FD - Bus 1 Pass FRS-R, 600V Class RK5 480 0.00 15.76 80.00
250
251 Typ 30A FD - Bus 10 Pass FRS-R, 600V Class RK5 480 0.00 27.32 80.00
254
255 Typ 30A FD - Bus 2 Pass FRS-R, 600V Class RK5 480 0.00 17.66 80.00
Page 5 of 6
October 3, 2017 ABC e-Hazard
Equipment Evaluation Report J.D. Aeiker
A B C D E F G
1 Device/Bus Status Description Voltage (V) Continuous Amps INT kA Rating%
258
259 Typ 30A FD - Bus 3 Pass FRS-R, 600V Class RK5 480 0.00 16.94 80.00
262
263 Typ 30A FD - Bus 4 Pass FRS-R, 600V Class RK5 480 0.00 14.79 80.00
E
266
267 Typ 30A FD - Bus 5 Pass FRS-R, 600V Class RK5 480 0.00 12.87 80.00
L
270
271 Typ 30A FD - Bus 6 Pass FRS-R, 600V Class RK5 480 0.00 15.30 80.00
P
273 BUSSMANN FRS-R 0.00
274
275 Typ 30A FD - Bus 7 Pass FRS-R, 600V Class RK5 480 0.00 11.47 80.00
M
277 BUSSMANN FRS-R 0.00
278
279 Typ 30A FD - Bus 8 Pass FRS-R, 600V Class RK5 480 0.00 14.00 80.00
A
281 BUSSMANN FRS-R 0.00
282
283 Typ 30A FD - Bus 9 Pass FRS-R, 600V Class RK5 480 0.00 11.11 80.00
S
284 Bus 9 - End 1-600A 600 100.00 200.00 5.56
286
287 Typical LL Panel Branch CB Fail TED (E-100 Line) 480 0.00 *24.36 100.00
288 Comp. Room - Typ 125A/150A Bus 15-100A, 2-3 Pole 480 50.00 14.00 *174.00
290
291
292 (*N1) System X/R higher than Test X/R, Calc INT kA modified based on low voltage factor.
293 (*Calc INT kA) Device did not pass. Device is either Marginal (90%) or Failed (100%) of the device library interrupting rating.
294 (*Calc C-L kA) Device did not pass. Device is either Marginal (90%) or Failed (100%) of the device library close-latch / momentary rating.
Page 6 of 6
Best Practices
40 cal/cm2 25 cal/cm2 8 cal/cm2 4 cal/cm2
PPE Min. Arc Rating PPE Min. Arc Rating PPE Min. Arc Rating PPE Min. Arc Rating for
Exposure
up to:
1cal/cm
.2 2
Rated Face Shield Rated Face Shield
E
with Rated Balaclava or
or
Rated Flash Hood
Head
L
Hard Hat Eye and Hearing
Protection
Safety Glasses/Goggles
Hearing Protection
P
Rated long sleeve Shirt Long sleeve Shirt
2
& Rated Pants 2 Long Pants
40Rating
cal/cm
25Rating
cal/cm
Undergarments
Body
Arc or Arc
Rated Coverall ALL Clothing Made
M
of Nonmelting or
or Untreated Natural
Rated Arc Flash Suit Fiber
Heavy Duty Heavy Duty
A
Leather Gloves Leather Gloves
Hands
Rated Gloves
or or
Rubber Insulating Gloves
with Leather Protectors
S
EH Leather Work
Feet
P ersonal
Required by NFPA 70E
sure correct
d
be
e
Required, Choices Available
As Needed
Check to
you h
ave
-R at
Recommended Best Practice
Arc P rotective Taking the Flash Out of Electrical Safety
Someplace, S T
Settings
The DANGEROUS Level may be mitigated by increasing the 100 Amps
working distance from 18" to 38". This increase in working distance Plant Electric Main FD Bus Plant Electric Main FD Bus
would reduce the Incident Energy from 128 cal/cm2 to 37 cal/cm2 and
Voltage 480.0 V
enable the use of AF PPE Level 4 for operation of the Plant Electric Isc 3P 38106.89 A
Room Main Fused Disconnect. The AFB remains the same in either AF_TripTime 1.838 s
AF_IncidentEnergy 127.67 Cal/cm^2
case. AF_PPE Category Dangerous!
CBL-0003
(1) 2/0 AWG 300.0 ft
AF_Boundary 310.13 inches
Installation Direct Buried
AF_ArcingFault 20.561 kA
Ampacity 288.3 A
3 Labels
E
Plant Electric Room Main FD P
L
Interrupt Rating 9.4 kA either case.
Trip 100.0 A
Settings CBL-0002
100 Amps (1) 3000 AWG 10.0 ft
Installation Sandwich
Ampacity 3000.0 A
Plant Electric Room Main Bus - MDP-2 Plant Electric Room Main Bus - MPD-2 Plant Electric Room Main Bus
CBL-0016 Voltage 480.0 V
(1) 2/0 AWG 300.0 ft Isc 3P 37951.39 A
Installation Direct Buried AF_TripTime 1.856 s
Plant Elec - Bus 7 Plant Elec - Bus 8 Plant Elec - Bus 9 Plant Elec - Bus 10 Plant Elec - Furnace 701 CB Plant Elec - Furnace 702 CB AF_IncidentEnergy 128.41 Cal/cm^2
Ampacity 288.3 A GE Model SGLA GE Model SGLA GE Model SGLA GE Model SGLA GE Model SGLA GE Model SGLA AF_PPE Category Dangerous!
Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V AF_Boundary 311.22 inches
Rated Current 400.0 A Rated Current 400.0 A Rated Current 400.0 A Rated Current 400.0 A Rated Current 600.0 A Rated Current 600.0 A AF_ArcingFault 20.490 kA
Interrupt Rating 65.0 kA Interrupt Rating 65.0 kA Interrupt Rating 65.0 kA Interrupt Rating 65.0 kA Interrupt Rating 65.0 kA Interrupt Rating 65.0 kA
Trip 400.0 A Trip 400.0 A Trip 400.0 A Trip 400.0 A Trip 500.0 A Trip 500.0 A
P
Plug 0.0 A Plug 0.0 A Plug 0.0 A Plug 0.0 A Plug 0.0 A Plug 0.0 A 3 Labels
XFMR - Compressor Room
S Settings Settings Settings Settings Settings Settings
Nominal kVA 2000.0 kVA
MAX MAX MAX MAX MAX MAX
Pri RatedVoltage 22860 V
P
Sec RatedVoltage 480 V
Z% 5.7000 %
Ampacity 58.1 A
Ampacity Sec 2766.5 A
CBL-0014 CBL-0012 CBL-0010 CBL-0008 CBL-0004 CBL-0005
(2) 4/0 AWG 230.0 ft (2) 4/0 AWG 230.0 ft (2) 4/0 AWG 250.0 ft (2) 4/0 AWG 20.0 ft (2) 350 AWG 240.0 ft (2) 350 AWG 320.0 ft
Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit
CBL-0017 Ampacity 520.0 A Ampacity 520.0 A Ampacity 520.0 A Ampacity 520.0 A Ampacity 700.0 A Ampacity 700.0 A
NOTE #3: DANGEROUS!! VERY HIGH INCIDENT ENERGY
(6) 500 AWG 25.0 ft
Installation Conduit Operation of the Compressor Room Main Fused Disconnect
Ampacity 2580.0 A is Dangerous; >40 calories/cm2. Furnace 701 Furnace 702
Bus 7 - Begin Bus 8 - Begin Bus 9 - Begin Bus 10 - Begin Furnace 701 Bus Furnace 702 Bus
Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V
The DANGEROUS Level may be mitigated by increasing the Isc 3P 17922.24 A Isc 3P 17922.24 A Isc 3P 17073.52 A Isc 3P 35031.27 A Isc 3P 20035.59 A Isc 3P 17281.47 A
working distance from 18" to 38". This increase in working distance AF_TripTime 0.025 s AF_TripTime 0.025 s AF_TripTime 0.025 s AF_TripTime 0.025 s AF_TripTime 0.025 s AF_TripTime 0.025 s
Compressor Room Main FD Bus AF_IncidentEnergy 0.9 Cal/cm^2 AF_IncidentEnergy 0.9 Cal/cm^2 AF_IncidentEnergy 0.86 Cal/cm^2 AF_IncidentEnergy 1.67 Cal/cm^2 AF_IncidentEnergy 1 Cal/cm^2 AF_IncidentEnergy 0.87 Cal/cm^2
would reduce the Incident Energy from 125 cal/cm2 to 37 cal/cm2 and P P
Voltage 480.0 V AF_PPE Category 0 AF_PPE Category 0 AF_PPE Category 0 AF_PPE Category 1 Furnance 701 XFMR AF_PPE Category 0 Furnance 702 XFMR AF_PPE Category 0
Isc 3P 39951.63 A enable the use of AF PPE Level 4 for operation of the Compressor AF_Boundary 15.16 inches AF_Boundary 15.16 inches AF_Boundary 14.75 inches AF_Boundary 22.1 inches S
Nominal kVA 150.0 kVA AF_Boundary 16.14 inches S
Nominal kVA 150.0 kVA AF_Boundary 14.85 inches
AF_TripTime 2.000 s Room Main Fused Disconnect. The AFB remains the same in either AF_ArcingFault 10.794 kA AF_ArcingFault 10.794 kA AF_ArcingFault 10.356 kA AF_ArcingFault 19.135 kA Pri RatedVoltage 480 V AF_ArcingFault 11.873 kA Pri RatedVoltage 480 V AF_ArcingFault 10.464 kA
AF_IncidentEnergy 125.32 Cal/cm^2 Sec RatedVoltage 240 V Sec RatedVoltage 240 V
AF_PPE Category Dangerous! case.
Z% 2.0000 % 2 Labels Z% 2.0000 % 2 Labels
AF_Boundary 306.64 inches Ampacity 180.4 A Ampacity 180.4 A
AF_ArcingFault 18.197 kA Ampacity Sec 360.8 A Ampacity Sec 360.8 A
CBL-0015 CBL-0013 CBL-0011 CBL-0009
3 Labels (1) 400 AWG 210.0 ft (1) 400 AWG 105.0 ft (1) 400 AWG 210.0 ft (1) 400 AWG 60.0 ft Furnance 701 Drive Furnance 702 Drive
Installation Sandwich Installation Sandwich Installation Sandwich Installation Sandwich Rated HP 125.0 hp Rated HP 125.0 hp
CBL-0006 RatedVoltage 480 V CBL-0007 RatedVoltage 480 V
Ampacity 400.0 A Ampacity 400.0 A Ampacity 400.0 A Ampacity 400.0 A (2) 4/0 AWG 10.0 ft (2) 4/0 AWG 10.0 ft
M
Compressor Room Main FD RatedAmps 150.8 A RatedAmps 150.8 A
Installation Conduit Installation Conduit
GOULD SHAWMUT Model A4BY Ampacity 520.0 A Ampacity 520.0 A
Voltage 480.0 V
Rated Current 3000.0 A
Interrupt Rating 200.0 kA
Trip 3000.0 A
NOTE #2: DANGEROUS!! VERY HIGH INCIDENT ENERGY Bus 7 - End Bus 8 - End Bus 9 - End Bus 10 - End Furnance 701 Heater Furnance 702 Heater
Operation of protective devices on the Compressor Room Main Bus Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Voltage 240.0 V Voltage 240.0 V
Compressor Room Main SW is Dangerous; >40 calories/cm2. Isc 3P 11472.62 A Isc 3P 13997.60 A Isc 3P 11112.18 A Isc 3P 27320.87 A Isc 3P 12093.86 A Isc 3P 11548.70 A
GE Model TPS AF_TripTime 0.025 s AF_TripTime 0.025 s AF_TripTime 0.025 s AF_TripTime 0.025 s AF_TripTime 2.000 s AF_TripTime 2.000 s
Voltage 480.0 V AF_IncidentEnergy 0.6 Cal/cm^2 AF_IncidentEnergy 0.72 Cal/cm^2 AF_IncidentEnergy 0.58 Cal/cm^2 AF_IncidentEnergy 1.33 Cal/cm^2 AF_IncidentEnergy 32.57 Cal/cm^2 AF_IncidentEnergy 31.34 Cal/cm^2
Rated Current 3000.0 A The DANGEROUS Level may be mitigated by increasing the AF_PPE Category 0 AF_PPE Category 0 AF_PPE Category 0 AF_PPE Category 1 AF_PPE Category 4 AF_PPE Category 4
Interrupt Rating 100.0 kA working distance from 18" to 38". This increase in working distance AF_Boundary 11.79 inches AF_Boundary 13.19 inches AF_Boundary 11.58 inches AF_Boundary 19.22 inches AF_Boundary 134.89 inches AF_Boundary 131.78 inches
Trip 3000.0 A AF_ArcingFault 7.374 kA AF_ArcingFault 8.740 kA AF_ArcingFault 7.176 kA AF_ArcingFault 15.474 kA AF_ArcingFault 5.235 kA AF_ArcingFault 5.064 kA
Plug 0.0 A
would reduce the Incident Energy from 125 cal/cm2 to 37 cal/cm2 and
enable the use of AF PPE Level 4 for operation of protective devices 2 Labels 2 Labels
on the Compressor Room Main Bus. The AFB remains the same in
either case.
CBL-0018
(1) 3000 AWG 10.0 ft
A
Installation Sandwich
Ampacity 3000.0 A
Compressor Room Main Bus Compressor Room Main Bus Compressor Room Main Bus
Voltage 480.0 V
Isc 3P 39768.70 A
AF_TripTime 2.000 s
AF_IncidentEnergy 124.79 Cal/cm^2
Plant Elec - Bus 1 Plant Elec - Bus 2 Plant Elec - Bus 3 Plant Elec - Bus 4 Plant Elec - Bus 5 Plant Elec - Bus 6 Comp. Room - Compressor CB Comp. Room - Typ 125A/150A CB Comp. Room - Typ 30A/80A CB
AF_PPE Category Dangerous!
GE Model SGLA GE Model SGLA GE Model SGLA GE Model SGLA GE Model SGLA GE Model SGLA GE Model SFLA GE Model SFLA GE Model SELA
AF_Boundary 305.84 inches
Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V
AF_ArcingFault 18.126 kA
Rated Current 400.0 A Rated Current 400.0 A Rated Current 400.0 A Rated Current 400.0 A Rated Current 400.0 A Rated Current 400.0 A Rated Current 250.0 A Rated Current 250.0 A Rated Current 80.0 A
Interrupt Rating 65.0 kA Interrupt Rating 65.0 kA Interrupt Rating 65.0 kA Interrupt Rating 65.0 kA Interrupt Rating 65.0 kA Interrupt Rating 65.0 kA Interrupt Rating 65.0 kA Interrupt Rating 65.0 kA Interrupt Rating 65.0 kA
Trip 400.0 A Trip 400.0 A Trip 400.0 A Trip 400.0 A Trip 400.0 A Trip 250.0 A Trip 150.0 A Trip 80.0 A 6 Labels
Trip 400.0 A
Plug 0.0 A Plug 0.0 A Plug 0.0 A Plug 0.0 A Plug 0.0 A Plug 0.0 A Plug 0.0 A Plug 0.0 A Plug 0.0 A
Settings Settings Settings Settings Settings Settings Settings Settings Settings
MAX MAX MAX MAX MAX MAX MAX MAX MAX
S
CBL-0025 CBL-0023 CBL-0021 CBL-0019 CBL-0029 CBL-0027 CBL-0031 CBL-0032 CBL-0035
(2) 4/0 AWG 100.0 ft (2) 4/0 AWG 50.0 ft (2) 4/0 AWG 100.0 ft (2) 4/0 AWG 130.0 ft (2) 4/0 AWG 170.0 ft (2) 4/0 AWG 210.0 ft (1) 250 AWG 40.0 ft (1) 2/0 AWG 50.0 ft (1) 2 AWG 50.0 ft
Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit
Ampacity 520.0 A Ampacity 520.0 A Ampacity 520.0 A Ampacity 520.0 A Ampacity 520.0 A Ampacity 520.0 A Ampacity 290.0 A Ampacity 195.0 A Ampacity 130.0 A
Bus 1 - Begin Bus 2 - Begin Bus 3 - Begin Bus 4 - Begin Bus 5 - Begin Bus 6 - Begin SSR Compressors Comp. Room - Typ 125A/150A Bus Comp. Room - Typ 30A/80A Bu s
Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V
Isc 3P 26901.03 A Isc 3P 32382.34 A Isc 3P 26901.03 A Isc 3P 24324.63 A Isc 3P 21512.10 A Isc 3P 19244.61 A Isc 3P 29538.68 A Isc 3P 24359.97 A Isc 3P 18629.10 A
AF_TripTime 0.025 s AF_TripTime 0.025 s AF_TripTime 0.025 s AF_TripTime 0.025 s AF_TripTime 0.025 s AF_TripTime 0.025 s AF_TripTime 0.025 s AF_TripTime 0.025 s AF_TripTime 0.025 s
AF_IncidentEnergy 1.31 Cal/cm^2 AF_IncidentEnergy 1.56 Cal/cm^2 AF_IncidentEnergy 1.31 Cal/cm^2 AF_IncidentEnergy 1.2 Cal/cm^2 AF_IncidentEnergy 1.07 Cal/cm^2 AF_IncidentEnergy 0.96 Cal/cm^2 AF_IncidentEnergy 1.43 Cal/cm^2 AF_IncidentEnergy 1.2 Cal/cm^2 AF_IncidentEnergy 0.93 Cal/cm^2
AF_PPE Category 1 AF_PPE Category 1 AF_PPE Category 1 AF_PPE Category 0 AF_PPE Category 0 AF_PPE Category 0 AF_PPE Category 1 AF_PPE Category 0 AF_PPE Category 0
AF_Boundary 19.05 inches AF_Boundary 21.14 inches AF_Boundary 19.05 inches AF_Boundary 18 inches AF_Boundary 16.8 inches AF_Boundary 15.78 inches AF_Boundary 20.08 inches AF_Boundary 18.01 inches AF_Boundary 15.49 inches
AF_ArcingFault 15.271 kA AF_ArcingFault 17.892 kA AF_ArcingFault 15.271 kA AF_ArcingFault 14.012 kA AF_ArcingFault 12.616 kA AF_ArcingFault 11.471 kA AF_ArcingFault 16.541 kA AF_ArcingFault 14.030 kA AF_ArcingFault 11.157 kA
CBL-0033
(1) 6 AWG 10.0 ft
Installation Conduit
Ampacity 75.0 A
ABC SUBSIDARYCORPORATION
Voltage 480.0 V Voltage 480.0 V
Isc 3P 15757.15 A Isc 3P 17661.64 A
Typ 208V XFMR FD - Bus 1 Typ 240V XFMR FD - Bus 1 Typ 30A FD - Bu s 1 Typ 100A FD - Bus 1 Typ 200A FD - Bus 1 AF_TripTime 0.025 s Typ 208V XFMR FD - Bus 2 Typ 240V XFMR FD - Bus 2 Typ 30A FD - Bu s 2 Typ 100A FD - Bus 2 Typ 200A FD - Bus 2 AF_TripTime 0.025 s
BUSSMANN Model FRS-R BUSSMANN Model FRS-R BUSSMANN Model FRS-R BUSSMANN Model FRS-R BUSSMANN Model FRS-R AF_IncidentEnergy 0.8 Cal/cm^2 BUSSMANN Model FRS-R BUSSMANN Model FRS-R BUSSMANN Model FRS-R BUSSMANN Model FRS-R BUSSMANN Model FRS-R AF_IncidentEnergy 0.89 Cal/cm^2
Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V AF_PPE Category 0 Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V AF_PPE Category 0
Rated Current 100.0 A Rated Current 45.0 A Rated Current 30.0 A Rated Current 100.0 A Rated Current 200.0 A AF_Boundary 14.1 inches Rated Current 100.0 A Rated Current 100.0 A Rated Current 100.0 A Rated Current 100.0 A Rated Current 200.0 A AF_Boundary 15.03 inches
Interrupt Rating 200.0 kA Interrupt Rating 200.0 kA Interrupt Rating 200.0 kA Interrupt Rating 200.0 kA Interrupt Rating 200.0 kA AF_ArcingFault 9.670 kA Interrupt Rating 200.0 kA Interrupt Rating 200.0 kA Interrupt Rating 200.0 kA Interrupt Rating 200.0 kA Interrupt Rating 200.0 kA AF_ArcingFault 10.660 kA
SOMEPLACE, ST
Trip 45.0 A Trip 45.0 A Trip 30.0 A Trip 100.0 A Trip 200.0 A Trip 45.0 A Trip 45.0 A Trip 30.0 A Trip 100.0 A Trip 200.0 A
CBL-0050 CBL-0049 CBL-0048 CBL-0047 CBL-0046 CBL-0055 CBL-0054 CBL-0053 CBL-0052 CBL-0051
(1) 6 AWG 50.0 ft (1) 6 AWG 50.0 ft (1) 8 AWG 50.0 ft (1) 2 AWG 50.0 ft (1) 4/0 AWG 50.0 ft (1) 6 AWG 50.0 ft (1) 6 AWG 50.0 ft (1) 8 AWG 50.0 ft (1) 2 AWG 50.0 ft (1) 4/0 AWG 50.0 ft
Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit
Ampacity 75.0 A Ampacity 75.0 A Ampacity 55.0 A Ampacity 130.0 A Ampacity 260.0 A Ampacity 75.0 A Ampacity 75.0 A Ampacity 55.0 A Ampacity 130.0 A Ampacity 260.0 A
E
P P P P
Typ 208V XFMR - Bus 1 Typ 240V XFMR - Bus 1 Typ 30A Load - Bus 1 Typ 100A Lo ad - Bus 1 Typ 200A Load - Bus 1 Typ 208V XFMR - Bus 2 Typ 240V XFMR - Bus 2 Typ 30A Load - Bus 2 Typ 100A Load - Bus 2 Typ 200A Load - Bu s 2
S S S S
Nominal kVA 30.0 kVA Nominal kVA 30.0 kVA Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Nominal kVA 30.0 kVA Nominal kVA 30.0 kVA Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V
Pri RatedVoltage 480 V Pri RatedVoltage 480 V Isc 3P 5189.64 A Isc 3P 10483.92 A Isc 3P 12918.83 A Pri RatedVoltage 480 V Pri RatedVoltage 480 V Isc 3P 5384.08 A Isc 3P 11351.27 A Isc 3P 14204.44 A
Sec RatedVoltage 208 V Sec RatedVoltage 240 V AF_TripTime 0.004 s AF_TripTime 0.004 s AF_TripTime 0.008 s Sec RatedVoltage 208 V Sec RatedVoltage 240 V AF_TripTime 0.004 s AF_TripTime 0.004 s AF_TripTime 0.008 s
Z% 5.0000 % Z% 5.0000 % AF_IncidentEnergy 0.05 Cal/cm^2 AF_IncidentEnergy 0.09 Cal/cm^2 AF_IncidentEnergy 0.22 Cal/cm^2 Z% 5.0000 % Z% 5.0000 % AF_IncidentEnergy 0.05 Cal/cm^2 AF_IncidentEnergy 0.1 Cal/cm^2 AF_IncidentEnergy 0.24 Cal/cm^2
Ampacity 36.1 A Ampacity 36.1 A AF_PPE Category 0 AF_PPE Category 0 AF_PPE Category 0 Ampacity 36.1 A Ampacity 36.1 A AF_PPE Category 0 AF_PPE Category 0 AF_PPE Category 0
Ampacity Sec 83.3 A Ampacity Sec 72.2 A AF_Boundary 2.53 inches AF_Boundary 3.76 inches AF_Boundary 6.45 inches Ampacity Sec 83.3 A Ampacity Sec 72.2 A AF_Boundary 2.59 inches AF_Boundary 3.93 inches AF_Boundary 6.81 inches
AF_ArcingFault 3.745 kA AF_ArcingFault 6.828 kA AF_ArcingFault 8.161 kA AF_ArcingFault 3.864 kA AF_ArcingFault 7.307 kA AF_ArcingFault 8.850 kA
Typ 208V Panel - Bus 1 Typ 240V Panel - Bus 1 Typ 208V Panel - Bus 2 Typ 240V Panel - Bus 2
Typical for: Typical for: Typical for: Typical for: Typical for: Typical for:
Voltage 208.0 V Voltage 240.0 V Voltage 208.0 V Voltage 240.0 V
Isc 3P 1544.69 A Isc 3P 1338.73 A 15A to 60A 70A to 125A 150A to 400A Isc 3P 1551.37 A Isc 3P 1344.52 A 15A to 60A 70A to 125A 150A to 400A
AF_TripTime 0.458 s AF_TripTime 0.861 s Bus Loads Bus Loads Bus Loads AF_TripTime 0.450 s AF_TripTime 0.846 s Bus Loads Bus Loads Bus Loads
AF_IncidentEnergy 1.2 Cal/cm^2 AF_IncidentEnergy 1.2 Cal/cm^2 AF_IncidentEnergy 1.2 Cal/cm^2 AF_IncidentEnergy 1.2 Cal/cm^2
AF_PPE Category 0 AF_PPE Category 0 AF_PPE Category 0 AF_PPE Category 0
AF_Boundary 18.04 inches AF_Boundary 18.04 inches AF_Boundary 18.04 inches AF_Boundary 18.04 inches
L
AF_ArcingFault 1.172 kA AF_ArcingFault 0.912 kA AF_ArcingFault 1.175 kA AF_ArcingFault 0.915 kA
Typical for all 208V Panels Typical for all 240V Panels Typical for all 208V Panels Typical for all 240V Panels
fed by transformers less fed by transformers less fed by transformers less fed by transformers less
than 125KVA than 125KVA than 125KVA than 125KVA
P
Bus 3 - End Bus 4 - End Bus 5 - End
Voltage 480.0 V Voltage 480.0 V
Voltage 480.0 V Isc 3P 14789.36 A Isc 3P 12873.32 A
Typ 208V XFMR FD - Bus 3 Typ 240V XFMR FD - Bus 3 Typ 30A FD - Bu s 3 Typ 100A FD - Bus 3 Typ 200A FD - Bus 3 Isc 3P 16942.03 A Typ 208V XFMR FD - Bus 4 Typ 240V XFMR FD - Bus 4 Typ 30A FD - Bu s 4 Typ 100A FD - Bus 4 Typ 200A FD - Bus 4 AF_TripTime 0.025 s Typ 208V XFMR FD - Bus 5 Typ 240V XFMR FD - Bus 5 Typ 30A FD - Bu s 5 Typ 100A FD - Bus 5 Typ 200A FD - Bus 5 AF_TripTime 0.025 s
BUSSMANN Model FRS-R BUSSMANN Model FRS-R BUSSMANN Model FRS-R BUSSMANN Model FRS-R BUSSMANN Model FRS-R AF_TripTime 0.025 s BUSSMANN Model FRS-R BUSSMANN Model FRS-R BUSSMANN Model FRS-R BUSSMANN Model FRS-R BUSSMANN Model FRS-R AF_IncidentEnergy 0.75 Cal/cm^2 BUSSMANN Model FRS-R BUSSMANN Model FRS-R BUSSMANN Model FRS-R BUSSMANN Model FRS-R BUSSMANN Model FRS-R AF_IncidentEnergy 0.66 Cal/cm^2
Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V AF_IncidentEnergy 0.86 Cal/cm^2 Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V AF_PPE Category 0 Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V AF_PPE Category 0
Rated Current 100.0 A Rated Current 100.0 A Rated Current 100.0 A Rated Current 100.0 A Rated Current 100.0 A AF_PPE Category 0 Rated Current 100.0 A Rated Current 100.0 A Rated Current 100.0 A Rated Current 100.0 A Rated Current 100.0 A AF_Boundary 13.6 inches Rated Current 100.0 A Rated Current 100.0 A Rated Current 100.0 A Rated Current 100.0 A Rated Current 100.0 A AF_Boundary 12.58 inches
Interrupt Rating 200.0 kA Interrupt Rating 200.0 kA Interrupt Rating 200.0 kA Interrupt Rating 200.0 kA Interrupt Rating 200.0 kA AF_Boundary 14.69 inches Interrupt Rating 200.0 kA Interrupt Rating 200.0 kA Interrupt Rating 200.0 kA Interrupt Rating 200.0 kA Interrupt Rating 200.0 kA AF_ArcingFault 9.160 kA Interrupt Rating 200.0 kA Interrupt Rating 200.0 kA Interrupt Rating 200.0 kA Interrupt Rating 200.0 kA Interrupt Rating 200.0 kA AF_ArcingFault 8.137 kA
Trip 45.0 A Trip 45.0 A Trip 30.0 A Trip 100.0 A Trip 200.0 A AF_ArcingFault 10.288 kA Trip 45.0 A Trip 45.0 A Trip 30.0 A Trip 100.0 A Trip 200.0 A Trip 45.0 A Trip 45.0 A Trip 30.0 A Trip 100.0 A Trip 200.0 A
CBL-0060 CBL-0059 CBL-0058 CBL-0057 CBL-0056 CBL-0065 CBL-0064 CBL-0063 CBL-0062 CBL-0061 CBL-0070 CBL-0069 CBL-0068 CBL-0067 CBL-0066
(1) 6 AWG 50.0 ft (1) 6 AWG 50.0 ft (1) 8 AWG 50.0 ft (1) 2 AWG 50.0 ft (1) 4/0 AWG 50.0 ft (1) 6 AWG 50.0 ft (1) 6 AWG 50.0 ft (1) 8 AWG 50.0 ft (1) 2 AWG 50.0 ft (1) 4/0 AWG 50.0 ft (1) 6 AWG 50.0 ft (1) 6 AWG 50.0 ft (1) 8 AWG 50.0 ft (1) 2 AWG 50.0 ft (1) 4/0 AWG 50.0 ft
Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit
Ampacity 75.0 A Ampacity 75.0 A Ampacity 55.0 A Ampacity 130.0 A Ampacity 260.0 A Ampacity 75.0 A Ampacity 75.0 A Ampacity 55.0 A Ampacity 130.0 A Ampacity 260.0 A Ampacity 75.0 A Ampacity 75.0 A Ampacity 55.0 A Ampacity 130.0 A Ampacity 260.0 A
P P P P P P
Typ 208V XFMR - Bus 3 Typ 240V XFMR - Bus 3 Typ 30A Load - Bus 3 Typ 100A Lo ad - Bus 3 Typ 200A Load - Bus 3 Typ 208V XFMR - Bus 4 Typ 240V XFMR - Bus 4 Typ 30A Load - Bus 4 Typ 100A Load - Bus 4 Typ 200A Load - Bus 4 Typ 208V XFMR - Bus 5 Typ 240V XFMR - Bus 5 Typ 30A Load - Bus 5 Typ 100A Load - Bus 5 Typ 200A Load - Bu s 5
S S S S S S
Nominal kVA 30.0 kVA Nominal kVA 30.0 kVA Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Nominal kVA 30.0 kVA Nominal kVA 30.0 kVA Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Nominal kVA 30.0 kVA Nominal kVA 30.0 kVA Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V
Pri RatedVoltage 480 V Pri RatedVoltage 480 V Isc 3P 5301.79 A Isc 3P 11005.59 A Isc 3P 13714.21 A Pri RatedVoltage 480 V Pri RatedVoltage 480 V Isc 3P 5079.26 A Isc 3P 10024.20 A Isc 3P 12249.57 A Pri RatedVoltage 480 V Pri RatedVoltage 480 V Isc 3P 4840.28 A Isc 3P 9081.61 A Isc 3P 10892.26 A
Sec RatedVoltage 208 V Sec RatedVoltage 240 V AF_TripTime 0.004 s AF_TripTime 0.004 s AF_TripTime 0.008 s Sec RatedVoltage 208 V Sec RatedVoltage 240 V AF_TripTime 0.004 s AF_TripTime 0.004 s AF_TripTime 0.008 s Sec RatedVoltage 208 V Sec RatedVoltage 240 V AF_TripTime 0.004 s AF_TripTime 0.008 s AF_TripTime 0.008 s
Z% 5.0000 % Z% 5.0000 % AF_IncidentEnergy 0.05 Cal/cm^2 AF_IncidentEnergy 0.1 Cal/cm^2 AF_IncidentEnergy 0.23 Cal/cm^2 Z% 5.0000 % Z% 5.0000 % AF_IncidentEnergy 0.05 Cal/cm^2 AF_IncidentEnergy 0.09 Cal/cm^2 AF_IncidentEnergy 0.21 Cal/cm^2 Z% 5.0000 % Z% 5.0000 % AF_IncidentEnergy 0.04 Cal/cm^2 AF_IncidentEnergy 0.13 Cal/cm^2 AF_IncidentEnergy 0.19 Cal/cm^2
Ampacity 36.1 A Ampacity 36.1 A AF_PPE Category 0 AF_PPE Category 0 AF_PPE Category 0 Ampacity 36.1 A Ampacity 36.1 A AF_PPE Category 0 AF_PPE Category 0 AF_PPE Category 0 Ampacity 36.1 A Ampacity 36.1 A AF_PPE Category 0 AF_PPE Category 0 AF_PPE Category 0
Ampacity Sec 83.3 A Ampacity Sec 72.2 A AF_Boundary 2.56 inches AF_Boundary 3.87 inches AF_Boundary 6.68 inches Ampacity Sec 83.3 A Ampacity Sec 72.2 A AF_Boundary 2.5 inches AF_Boundary 3.67 inches AF_Boundary 6.26 inches Ampacity Sec 83.3 A Ampacity Sec 72.2 A AF_Boundary 2.44 inches AF_Boundary 4.76 inches AF_Boundary 5.86 inches
AF_ArcingFault 3.814 kA AF_ArcingFault 7.117 kA AF_ArcingFault 8.588 kA AF_ArcingFault 3.676 kA AF_ArcingFault 6.571 kA AF_ArcingFault 7.799 kA AF_ArcingFault 3.528 kA AF_ArcingFault 5.134 kA AF_ArcingFault 7.054 kA
M
Typ 208V Panel - Bus 3 Typ 240V Panel - Bus 3 Typ 208V Panel - Bus 4 Typ 240V Panel - Bus 4 Typ 208V Panel - Bus 5 Typ 240V Panel - Bus 5
Typical for: Typical for: Typical for: Typical for: Typical for: Typical for: Typical for: Typical for: Typical for:
Voltage 208.0 V Voltage 240.0 V Voltage 208.0 V Voltage 240.0 V Voltage 208.0 V Voltage 240.0 V
Isc 3P 1549.10 A Isc 3P 1342.56 A 15A to 60A 70A to 125A 150A to 400A Isc 3P 1540.71 A Isc 3P 1335.28 A 15A to 60A 70A to 125A 150A to 400A Isc 3P 1531.09 A Isc 3P 1326.94 A 15A to 60A 70A to 125A 150A to 400A
AF_TripTime 0.453 s AF_TripTime 0.851 s Bus Loads Bus Loads Bus Loads AF_TripTime 0.463 s AF_TripTime 0.871 s Bus Loads Bus Loads Bus Loads AF_TripTime 0.475 s AF_TripTime 0.894 s Bus Loads Bus Loads Bus Loads
AF_IncidentEnergy 1.2 Cal/cm^2 AF_IncidentEnergy 1.2 Cal/cm^2 AF_IncidentEnergy 1.2 Cal/cm^2 AF_IncidentEnergy 1.2 Cal/cm^2 AF_IncidentEnergy 1.2 Cal/cm^2 AF_IncidentEnergy 1.2 Cal/cm^2
AF_PPE Category 0 AF_PPE Category 0 AF_PPE Category 0 AF_PPE Category 0 AF_PPE Category 0 AF_PPE Category 0
AF_Boundary 18.04 inches AF_Boundary 18.04 inches AF_Boundary 18.04 inches AF_Boundary 18.04 inches AF_Boundary 18.04 inches AF_Boundary 18.04 inches
AF_ArcingFault 1.174 kA AF_ArcingFault 0.914 kA AF_ArcingFault 1.170 kA AF_ArcingFault 0.910 kA AF_ArcingFault 1.165 kA AF_ArcingFault 0.906 kA
Typical for all 208V Panels Typical for all 240V Panels Typical for all 208V Panels Typical for all 240V Panels Typical for all 208V Panels Typical for all 240V Panels
fed by transformers less fed by transformers less fed by transformers less fed by transformers less fed by transformers less fed by transformers less
than 125KVA than 125KVA than 125KVA than 125KVA than 125KVA than 125KVA
A
Bus 6 Bus 6 Bus 6 - End Bus 7 Bus 7 Bus 7 - End
Bus 8 Bus 8 Bus 8 - End
Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V
Isc 3P 15301.50 A Isc 3P 11472.62 A Isc 3P 13997.60 A
Typ 208V XFMR FD - Bus 6 Typ 240V XFMR FD - Bus 6 Typ 30A FD - Bu s 6 Typ 100A FD - Bus 6 Typ 200A FD - Bus 6 AF_TripTime 0.025 s Typ 208V XFMR FD - Bus 7 Typ 240V XFMR FD - Bus 7 Typ 30A FD - Bu s 7 Typ 100A FD - Bus 7 Typ 200A FD - Bus 7 AF_TripTime 0.025 s Typ 208V XFMR FD - Bus 8 Typ 240V XFMR FD - Bus 8 Typ 30A FD - Bu s 8 Typ 100A FD - Bus 8 Typ 200A FD - Bus 8 AF_TripTime 0.025 s
BUSSMANN Model FRS-R BUSSMANN Model FRS-R BUSSMANN Model FRS-R BUSSMANN Model FRS-R BUSSMANN Model FRS-R AF_IncidentEnergy 0.78 Cal/cm^2 BUSSMANN Model FRS-R BUSSMANN Model FRS-R BUSSMANN Model FRS-R BUSSMANN Model FRS-R BUSSMANN Model FRS-R AF_IncidentEnergy 0.6 Cal/cm^2 BUSSMANN Model FRS-R BUSSMANN Model FRS-R BUSSMANN Model FRS-R BUSSMANN Model FRS-R BUSSMANN Model FRS-R AF_IncidentEnergy 0.72 Cal/cm^2
Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V AF_PPE Category 0 Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V AF_PPE Category 0 Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V AF_PPE Category 0
Rated Current 100.0 A Rated Current 100.0 A Rated Current 100.0 A Rated Current 100.0 A Rated Current 100.0 A AF_Boundary 13.87 inches Rated Current 100.0 A Rated Current 100.0 A Rated Current 100.0 A Rated Current 100.0 A Rated Current 100.0 A AF_Boundary 11.79 inches Rated Current 100.0 A Rated Current 100.0 A Rated Current 100.0 A Rated Current 100.0 A Rated Current 100.0 A AF_Boundary 13.19 inches
Interrupt Rating 200.0 kA Interrupt Rating 200.0 kA Interrupt Rating 200.0 kA Interrupt Rating 200.0 kA Interrupt Rating 200.0 kA AF_ArcingFault 9.431 kA Interrupt Rating 200.0 kA Interrupt Rating 200.0 kA Interrupt Rating 200.0 kA Interrupt Rating 200.0 kA Interrupt Rating 200.0 kA AF_ArcingFault 7.374 kA Interrupt Rating 200.0 kA Interrupt Rating 200.0 kA Interrupt Rating 200.0 kA Interrupt Rating 200.0 kA Interrupt Rating 200.0 kA AF_ArcingFault 8.740 kA
Trip 45.0 A Trip 45.0 A Trip 30.0 A Trip 100.0 A Trip 200.0 A Trip 45.0 A Trip 45.0 A Trip 30.0 A Trip 100.0 A Trip 200.0 A Trip 45.0 A Trip 45.0 A Trip 30.0 A Trip 100.0 A Trip 200.0 A
CBL-0075 CBL-0074 CBL-0073 CBL-0072 CBL-0071 CBL-0080 CBL-0079 CBL-0078 CBL-0077 CBL-0076 CBL-0085 CBL-0084 CBL-0083 CBL-0082 CBL-0081
(1) 6 AWG 50.0 ft (1) 6 AWG 50.0 ft (1) 8 AWG 50.0 ft (1) 2 AWG 50.0 ft (1) 4/0 AWG 50.0 ft (1) 6 AWG 50.0 ft (1) 6 AWG 50.0 ft (1) 8 AWG 50.0 ft (1) 2 AWG 50.0 ft (1) 4/0 AWG 50.0 ft (1) 6 AWG 50.0 ft (1) 6 AWG 50.0 ft (1) 8 AWG 50.0 ft (1) 2 AWG 50.0 ft (1) 4/0 AWG 50.0 ft
Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit
S
Ampacity 75.0 A Ampacity 75.0 A Ampacity 55.0 A Ampacity 130.0 A Ampacity 260.0 A Ampacity 75.0 A Ampacity 75.0 A Ampacity 55.0 A Ampacity 130.0 A Ampacity 260.0 A Ampacity 75.0 A Ampacity 75.0 A Ampacity 55.0 A Ampacity 130.0 A Ampacity 260.0 A
P P P P P P
Typ 208V XFMR - Bus 6 Typ 240V XFMR - Bus 6 Typ 30A Load - Bus 6 Typ 100A Lo ad - Bus 6 Typ 200A Load - Bus 6 Typ 208V XFMR - Bus 7 Typ 240V XFMR - Bus 7 Typ 30A Load - Bus 7 Typ 100A Load - Bus 7 Typ 200A Load - Bus 7 Typ 208V XFMR - Bus 8 Typ 240V XFMR - Bus 8 Typ 30A Load - Bus 8 Typ 100A Load - Bus 8 Typ 200A Load - Bu s 8
S S S S S S
Nominal kVA 30.0 kVA Nominal kVA 30.0 kVA Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Nominal kVA 30.0 kVA Nominal kVA 30.0 kVA Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V Nominal kVA 30.0 kVA Nominal kVA 30.0 kVA Voltage 480.0 V Voltage 480.0 V Voltage 480.0 V
Pri RatedVoltage 480 V Pri RatedVoltage 480 V Isc 3P 5107.94 A Isc 3P 10216.63 A Isc 3P 12586.98 A Pri RatedVoltage 480 V Pri RatedVoltage 480 V Isc 3P 4637.96 A Isc 3P 8350.50 A Isc 3P 9866.26 A Pri RatedVoltage 480 V Pri RatedVoltage 480 V Isc 3P 4971.63 A Isc 3P 9621.31 A Isc 3P 11688.11 A
Sec RatedVoltage 208 V Sec RatedVoltage 240 V AF_TripTime 0.004 s AF_TripTime 0.004 s AF_TripTime 0.008 s Sec RatedVoltage 208 V Sec RatedVoltage 240 V AF_TripTime 0.004 s AF_TripTime 0.008 s AF_TripTime 0.008 s Sec RatedVoltage 208 V Sec RatedVoltage 240 V AF_TripTime 0.004 s AF_TripTime 0.004 s AF_TripTime 0.008 s
Z% 5.0000 % Z% 5.0000 % AF_IncidentEnergy 0.05 Cal/cm^2 AF_IncidentEnergy 0.09 Cal/cm^2 AF_IncidentEnergy 0.22 Cal/cm^2 Z% 5.0000 % Z% 5.0000 % AF_IncidentEnergy 0.04 Cal/cm^2 AF_IncidentEnergy 0.12 Cal/cm^2 AF_IncidentEnergy 0.17 Cal/cm^2 Z% 5.0000 % Z% 5.0000 % AF_IncidentEnergy 0.05 Cal/cm^2 AF_IncidentEnergy 0.08 Cal/cm^2 AF_IncidentEnergy 0.2 Cal/cm^2
Ampacity 36.1 A Ampacity 36.1 A AF_PPE Category 0 AF_PPE Category 0 AF_PPE Category 0 Ampacity 36.1 A Ampacity 36.1 A AF_PPE Category 0 AF_PPE Category 0 AF_PPE Category 0 Ampacity 36.1 A Ampacity 36.1 A AF_PPE Category 0 AF_PPE Category 0 AF_PPE Category 0
Ampacity Sec 83.3 A Ampacity Sec 72.2 A AF_Boundary 2.51 inches AF_Boundary 3.71 inches AF_Boundary 6.36 inches Ampacity Sec 83.3 A Ampacity Sec 72.2 A AF_Boundary 2.38 inches AF_Boundary 4.54 inches AF_Boundary 5.55 inches Ampacity Sec 83.3 A Ampacity Sec 72.2 A AF_Boundary 2.47 inches AF_Boundary 3.58 inches AF_Boundary 6.1 inches
AF_ArcingFault 3.694 kA AF_ArcingFault 6.679 kA AF_ArcingFault 7.982 kA AF_ArcingFault 3.402 kA AF_ArcingFault 4.778 kA AF_ArcingFault 6.483 kA AF_ArcingFault 3.610 kA AF_ArcingFault 6.345 kA AF_ArcingFault 7.492 kA
Typ 208V Panel - Bus 6 Typ 240V Panel - Bus 6 Typ 208V Panel - Bus 7 Typ 240V Panel - Bus 7 Typ 208V Panel - Bus 8 Typ 240V Panel - Bus 8
Typical for: Typical for: Typical for: Typical for: Typical for: Typical for: Typical for: Typical for: Typical for:
Voltage 208.0 V Voltage 240.0 V Voltage 208.0 V Voltage 240.0 V Voltage 208.0 V Voltage 240.0 V
Isc 3P 1543.25 A Isc 3P 1337.48 A 15A to 60A 70A to 125A 150A to 400A Isc 3P 1522.11 A Isc 3P 1319.16 A 15A to 60A 70A to 125A 150A to 400A Isc 3P 1537.23 A Isc 3P 1332.27 A 15A to 60A 70A to 125A 150A to 400A
AF_TripTime 0.460 s AF_TripTime 0.864 s Bus Loads Bus Loads Bus Loads AF_TripTime 0.487 s AF_TripTime 0.916 s Bus Loads Bus Loads Bus Loads AF_TripTime 0.468 s AF_TripTime 0.879 s Bus Loads Bus Loads Bus Loads
AF_IncidentEnergy 1.2 Cal/cm^2 AF_IncidentEnergy 1.2 Cal/cm^2 AF_IncidentEnergy 1.2 Cal/cm^2 AF_IncidentEnergy 1.2 Cal/cm^2 AF_IncidentEnergy 1.2 Cal/cm^2 AF_IncidentEnergy 1.2 Cal/cm^2
AF_PPE Category 0 AF_PPE Category 0 AF_PPE Category 0 AF_PPE Category 0 AF_PPE Category 0 AF_PPE Category 0
AF_Boundary 18.04 inches AF_Boundary 18.04 inches AF_Boundary 18.04 inches AF_Boundary 18.04 inches AF_Boundary 18.04 inches AF_Boundary 18.04 inches
AF_ArcingFault 1.171 kA AF_ArcingFault 0.911 kA AF_ArcingFault 1.160 kA AF_ArcingFault 0.902 kA AF_ArcingFault 1.168 kA AF_ArcingFault 0.909 kA
Typical for all 208V Panels Typical for all 240V Panels Typical for all 208V Panels Typical for all 240V Panels Typical for all 208V Panels Typical for all 240V Panels
fed by transformers less fed by transformers less fed by transformers less fed by transformers less fed by transformers less fed by transformers less
than 125KVA than 125KVA than 125KVA than 125KVA than 125KVA than 125KVA
CBL-0090 CBL-0089 CBL-0088 CBL-0087 CBL-0086 CBL-0095 CBL-0094 CBL-0093 CBL-0092 CBL-0091
(1) 6 AWG 50.0 ft (1) 6 AWG 50.0 ft (1) 8 AWG 50.0 ft (1) 2 AWG 50.0 ft (1) 4/0 AWG 50.0 ft (1) 6 AWG 50.0 ft (1) 6 AWG 50.0 ft (1) 8 AWG 50.0 ft (1) 2 AWG 50.0 ft (1) 4/0 AWG 50.0 ft
Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit Installation Conduit
Ampacity 75.0 A Ampacity 75.0 A Ampacity 55.0 A Ampacity 130.0 A Ampacity 260.0 A Ampacity 75.0 A Ampacity 75.0 A Ampacity 55.0 A Ampacity 130.0 A Ampacity 260.0 A
P P P P
Typ 208V XFMR - Bus 9 Typ 240V XFMR - Bus 9 Typ 30A Load - Bus 9 Typ 100A Lo ad - Bus 9 Typ 200A Load - Bus 9 Typ 208V XFMR - Bus 10 Typ 240V XFMR - Bus 10 Typ 30A Load - Bus 10 Typ 100A Load - Bus 10 Typ 200A Load - Bus 10
Typical for all 208V Panels Typical for all 240V Panels Typical for all 208V Panels Typical for all 240V Panels
fed by transformers less fed by transformers less fed by transformers less fed by transformers less
than 125KVA than 125KVA than 125KVA than 125KVA