Sei sulla pagina 1di 124

1.

General description

2. Operating instructions

3. Alarms and
troubleshooting

4. Installation and start up

5. Technical information -
Service and maintenance

6. Function diagrams
Electrical diagrams

7. Spare parts list

8. Technical data

9. Appendices
Preface
This manual provides the information needed to install the WRO Chem,
operate the WRO Chem, to carry out maintenance on it and to identify and
remedy faults that may occur.

This manual is valid for program version: RC9701..

Publication no. Denomination


HCEN9315 rev. 05. 04 Service & Operator´s manual

The complete manual, HCEN9315, consists of following chapters:


HCEN9315 rev. 10. 00 General description WRO Chem
HCEN9315 rev. 10. 00 Operating instructions
HCEN9315 rev. 10. 00 Alarms and troubleshooting
HCEN9315 rev. 10. 00 Installation and start up
HCEN9315 rev. 10. 00 Technical information- Service and maintenance
HCEN9315 rev. 05. 04 Function diagrams & Electrical diagrams
HCEN9315 rev. 10. 00 Spare parts list
HCEN9315 rev. 10. 00 Technical data
HCEN9315 rev. 10. 00 Appendices

All rights reserved


© Copyright Gambro AB, Sweden 1996

Caution: At delivery the system is filled with a combined preservation and


anti-freeze solution, containing 1% formaldehyde and 20% glycerine. This
solution must be thoroughly rinsed out before the system is put into normal
operation.
Check that no residual formaldehyde can be detected before connecting
patients.

Caution: The WRO Chem includes intentionally initiated programmes for


chemical disinfection with Dialox of the piping system downstream the
reverse osmosis unit.The operator is therefore responsible to insure
that no disinfection solution is present in the dialysis fluid before
dialysis is initiated.

Caution: The disinfection mode Central chemical disinfection has only


been validated together with the Gambro AK95, AK100 (prom version 3:60
or later), AK 100 ULTRA (prom version 4.xx or later), AK200 and
AK200 Ultra dialysis machines.

Caution: Dialysis machines that are to be connected to the loop supplied


with water from Gambro CWP 100 Systems, must comply with IEC 60601-
2-16.
0. Definitions, general warnings & cautions

Is used to alert the user/operator not to take a


certain action, which if taken can cause a potential
hazard and result in a serious adverse reaction,
Warning injury or death. A warning may also be used to alert
the user/operator to take a certain action to avoid
the potential hazard as above.

Is used to alert the user/operator to take a certain


action to protect against a potential hazard which, if
ignored, could have an adverse effect on the patient
Caution or the device. A caution may also be used to alert the
user/operator not to take a certain action to avoid
the potential hazard as above.

A reminder to the user/operator on normal treatment


activity and on what is a suitable action in a
Note particular situation.

HCEN9315 Rev. 10. 00 0:1


Unauthorized modifications, alterations or repair of the
CWP 100, model WRO Chem, may result in
Warning malfunctioning or have other serious consequences for the
safe operation of the equipment.

1. The CWP 100, model WRO Chem, may only be


Caution operated by persons trained in this equipment and who
have studied the instructions in this manual. If the CWP
100 does not perform as described in this manual, it
should not be used until the condition is rectified.

2. When unpacking, check the equipment for any signs of


damage. If the equipment is in any way damaged, proper
operation can not be assured.

3. The installation and start up of CWP 100, model WRO


Chem, must be made by authorized personnel.

4. At delivery the system is filled with a combined


preservation and anti-freeze solution, containing 1%
formaldehyde and 20% glycerine. This solution must be
thoroughly rinsed out before the system is put into
normal operation. Verify that no residual formaldehyde
can be detected before connecting patients.

5. The use of mobile telephones or communication


equipment in the vicinity of the CWP 100, model WRO
Chem could adversely influence the performance of the
machine.

6. The CWP 100, model WRO Chem, will perform as


designed only if it is used and maintained in accordance
with Gambro’s instructions. Any warranties made by
Gambro with respect to the CWP 100, model WRO Chem,
are void if the equipment is not used in accordance with
the instructions provided. Gambro will not accept
responsibility for any damage or injury resulting from
improper use or maintenance or unauthorized repair.

7. The user must verify the quality of the protective earth


in the installation.

8. When used as a medical device, Federal law restricts


this device to sale by or on the order of a physician.

0:2 HCEN9315 Rev 10. 00


CE-marking
This product is CE marked in accordance with the re-
quirements in EC Council Directive 93/42/EEC of 14
June 1993 concerning medical devices.

Notified body is: British Standards Institution (BSI) with


the notified body number 0086.

The symbol means: Year of manufacturing.

The CE-marking of this manual is only valid if the device


which it describes is CE-marked.

Manufacturer:
Gambro Lundia AB, Monitor Division,
Box 10101, SE-220 10 LUND, Sweden.
Phone +46 46 16 90 00.

HCEN9315 Rev. 10. 00 0:3


Symbol description
Note: All symbols in this list may not be represented on this product.

Symbol Description

∼ Alternating current

Protective earth (ground)

Attention, consult ACCOMPANYING DOCUMENTS

Off (power, disconnection from the mains)

On (power, connection to the mains)

TYPE B APPLIED PART

Handle with care

This way up

Keep dry

Input / Output

Year of manufacturing

Heater power supply outlet

0:4 HCEN9315 Rev 10. 00


Symbol description
Note: All symbols in this list may not be represented on this product.

Symbol Description

Conforms to requirements in EC Council Directive


93/42/EEC concerning medical devices.
0086 identifies BSI, British Standards Institution,
as Notified Body

CSA approved for Canada

CSA approved for Canada and USA

CSA-listed Manufacturer

HCEN9315 Rev. 10. 00 0:5


This page is intentionally left blank

0:6 HCEN9315 Rev 10. 00


1. General description WRO Chem

Contents

Introduction ........................................................................... 2

The quality of dialysis fluid - general aspects ..................... 3


Microbiological quality ............................................. 3
Chemical quality ....................................................... 3

Description of reverse osmosis ............................................. 4

Description of WRO Chem .................................................... 5


General description .................................................. 5
Conductivity monitoring .......................................... 5
Flow monitoring ........................................................ 5
Chemical disinfection ............................................... 5

Flow diagram ......................................................................... 6

Component list ....................................................................... 7

Exploded view of WRO Chem - front .................................... 8

Exploded view of WRO Chem - right side ............................ 9

Main components ................................................................. 10

The MAC operator´s panel .................................................. 11


Function of the different buttons ........................... 11
CWP INFO .............................................................. 13

Chemical disinfection .......................................................... 16


Disinfection programs ............................................ 16
Required disinfection frequency ............................ 16
Disinfection solution ............................................... 16
Information about peracetic acid ........................... 16
Residual testing of Dialox ...................................... 16

Disinfection of WRO ............................................................ 17

Disinfection of the distribution system .............................. 18

Rinse of the dialysis monitors ............................................. 21

Remote control (option) ....................................................... 22

External indication (option) ................................................ 22

HCEN9315 Rev. 10. 00


1:1
Introduction

Intended use
The Gambro water treatment system CWP 100, In addition, the WRO Chem has been designed
model WRO Chem, produces water of high to reduce water consumption by automatically
quality, chemically and microbiologically and adjusting the reject flow to the actual
with adequate flow, provided that the feed water consumption of pure water.
complies with existing standards for drinking
water and has been properly pre-treated by Caution: WRO Chem utilizes chemical
softening, charcoal filtration and particle filt- disinfectants for the disinfection of the WRO
ration to minimum 10 µm. and the distribution system in the clinic. A test
for residual chemicals must therefore be perfor-
med before initiation of a dialysis treatment.
Introduction WRO Chem comes in four different sizes:
The water used in the dialysis setting is a very WRO111, WRO112, WRO113 and WRO114.
important factor in achieving and maintaining
an adequate quality of the dialysis fluid. The
chemical and microbiological quality of the water
depends not only on technical parameters of
membranes (such as retention rate, rejection
rate, chemical composition, and pore size), but
also to a large extent on the condition of, and
proper maintenance of, equipment and distribu-
tion system.

WRO Chem is a member of Gambro´s central


water treatment system CWP 100. It has been
specially designed to meet the unique
requirements of the dialysis clinic. When proper-
ly maintained it will produce water of high
quality both from a chemical and microbiological
standpoint, provided that the inlet water
complies with normal standards for drinking
water and has been properly pretreated.

CWP 100, model WRO Chem, operates under


the principle of reverse osmosis (RO) which is
the preferred method for the purification of
water for dialysis. This system removes 95 - 98%
of total dissolved salts (based on conductivity)
and more than 99% of the bacteria and
endotoxins from the inlet water.

In order to ensure that the microbiological


quality will be maintained, the system has:

• Hygienic design with smooth surfaces and a


minimum of stagnant zones.

• Automatic flushing programs at preset inter-


vals when the system is not in use.

• Built-in automized disinfection and cleaning Fig. 1. CWP 100, model WRO Chem.
programs that enable integrated chemical
disinfection of the WRO and all parts of the
piping system downstream the WRO.

HCEN9315 Rev. 10. 00


1:2
The quality of dialysis fluid - general aspects
Microbiological quality Chemical quality

The microbiological quality of the dialysis fluid The conductivity, i. e. the ability of the water to
is a function of a number of factors. Neglecting conduct a current, is a measure of the amount of
only one of these could result in a poor quality. dissolved salts in water. It is therefore used to
These factors are: indicate the quality of the water and the perfor-
mance of different water treatment processes,
• Acceptable quality of the inlet water to the such as reverse osmosis.
water treatment system, i.e. in accordance
with standards for drinking water. The conductivity in water is normally expressed
in microsiemens per cm (µS/cm).
• High capacity of reduction of microorganisms
and endotoxins in the water treatment The amount of dissolved salts in tap water
system. This requires both the necessary varies significantly from place to place and may
purification steps (e.g. RO) as well as also change over time due to seasonal varia-
hygienic design and correct maintenance tions. As reverse osmosis removes a percentage
including regular cleaning and disinfection. of the salts (appr. 95%) it is obvious that the
pure water conductivity also will vary
• Hygienic design of the distribution system of depending on the quality of the inlet water.
treated water to the dialysis clinic with
smooth surfaces and with a minimum of The conductivity of the water is not always a
joints and stagnant zones. good indicator of the suitability of the water for
dialysis. Aluminium, for example, may be pre-
• Frequent disinfection of the distribution sent in concentrations well exeeding recommen-
system. ded standards without affecting the conductivity.

• Hygienic design and regular cleaning and The quality of dialysis water should therefore
disinfection of the dialysis machines. always be verified by regular water analyses.

• High quality and proper handling of bicarbo- The conductivity should mainly be used as an
nate concentrates. indicator of the performance of the reverse
osmosis system.
• Correct arrangement of the drain connections
from the dialysis machines i.e. air gap to The regulations and guidelines on the quality
avoid microbial contamination from the requirements for dialysis water varies in diffe-
drainage system. rent countries.

• Regular sampling to verify that the quality is


maintaned.

HCEN9315 Rev. 10. 00


1:3
Description of reverse osmosis
Reverse osmosis is a membrane process and is The membrane that is used in this system will
today the most widely used technique for the retain at least 95 % of dissolved salts (based on
production of water for dialysis. The membrane conductivity) in the water and about 99 % of the
that is used is semipermeable, i.e. it allows contents of bacteria, endotoxins and substances
passage of water but retains most of the dissolved exceeding 200 Dalton in molecular weight.
salts, particles, bacteria and endotoxins *). The pure water from the reverse osmosis process
is also called permeate.
Principle: If two solutions of different concentra-
tion of salts are separated by a semipermeable Part of the water, normally 30-50 %, containing
membrane, water will pass through the membra- the retained contaminants is continously diver-
ne from the weaker to the stronger solution in an ted to drain (reject water) via a needle valve.
effort to equalize the difference in concentration.
This is called OSMOSIS. The required operating pressure in a reverse
osmosis system generally ranges from 10 to 60
By applying a pressure on the more concentrated bar, depending on application. The maximum
solution, this transport of water will go in the pressure in the RO-unit in this system is
opposite direction, i.e. from the stronger to the approximately 18 bar.
weaker solution. This process is called REVER-
SE OSMOSIS. (Fig 2).

*) cell fragments of gram negative bacteria with


pyrogenic properties

semipermeable
membrane pure water
(permeate)

water inlet

pump

reject recirculation

reject to
drain

Fig. 2. Reverse osmosis

HCEN9315 Rev. 10. 00


1:4
Description of the WRO Chem
General description Conductivity monitoring

Refer to fig 3, 4 and 5! The conductivity on the inlet water and pure
water are continously monitored by two
(The components in the system are marked with conductivity cells (32 and 35). The pure water
the numbers within parenthesis below.) conductivity is continously displayed on the
operator´s panel during operation. The inlet
After pretreatment (preferably in carbon filter, water conductivity is displayed on request by
softener and 5 µm particle filters) the water pressing MAIN MENU. Refer to page 1:14
enters an inlet water tank (4) with an air gap
via a solenoid valve (1). A booster pump (33) Conductivity cell (144) in the return line from
then creates the pressure that is required for the clinic is used to monitor the loop disinfection
the reverse osmosis process (12 - 18 bar). procedure by indicating when disinfectant has
reached that part of the system.
The pure water from the WRO-unit is distribu-
ted directly to the clinics distribution system via Flow monitoring
solenoid valves (48) and (136). Excess pure
water that has not been used in the clinic is The flow rates are measured at the following
recirculated back to the inlet water tank via places (fig. 3):
solenoid valve 106.
Flow pos
The reject flow leaving the reverse osmosis
module is split into two streams. One part is
• Reject flow from RO-unit (F2) 42
recirculated back to the inlet side of the main
• Pure water flow from RO-unit (F6) 121
pump via valve (71) (preset from factory) in
• Return flow from the loop (F4) 51
order to maintain a high flow velocity over the
membrane surface. The other part is the reject
These flow rates are used to calculate:
flow rate which is set with needle valve (41).
• Actual water consumption F5 = F6 - F4
To save water, a three way motor valve is
• Inlet water flow F1 = F2 + (F6 - F4)
installed in the reject line downstream reject
valve (41). This valve directs part of the reject
All flow rates are presented on the operator´s
water back to the inlet tank during periods of
panel on request by pressing MAIN MENU.
low water consumption.
Refer to page 1:14.
The pure water line in the WRO has a solenoid
valve (36) for automatic flushing to drain at
start up, in conductivity alarm situations, at
Chemical disinfection
regular intervals when the system is in stand
by mode and at rinse during disinfection WRO Chem offers the possibility to perform
different chemical desinfection programs.
The outlet pure water line has two solenoid For this purpose the WRO has one (models 111,
valves in series. Valve 48 is a normal shut off 112) or two (models 113, 114) proportioning
valve. Valve 136 has a special design and pump(s) (45) for the addition of Dialox to the
functions as a restrictor when it is in closed system. The WRO has enough internal space to
position. It is used to reduce the outlet flow rate hold Dialox containers up to 30 liters of volume.
during intake of Dialox during loop disinfection, The proportioning pump(s) and the Dialox
thereby increasing the concentration of Dialox. container is completely disconnected from the
Valve operates parallel to valve 48 in all other fluid path of the WRO during normal operation.
modes of operation. Refer to page 1:16 for more information about
chemical disinfection.
The WRO-unit has an overflow valve on the pure
water side (64) to control pressure and to relieve
pressure peaks. This overflow valve is set at
approx. 7 bar at delivery.

HCEN9315 Rev. 10. 00


1:5
1:6
144
32 106
1 µS
µS 52 51

5
54
4
64

132 35
6 53
33 µS 48 136
110 P1 P2 121 ( 130
34 (
131
36
71
122 132

41
WRO Chem - flow diagram

138
132
111
45
43
44
134
46
47 42

62
61

Fig. 3

HCEN9315 Rev. 10. 00


HCEN9315 Rev. 10. 00
1 inlet solenoid valve 53 dosing connector sensor, pos. for disinf. WRO
4 inlet water tank 54 solenoid valve, return line to drain
5 float valve 61 collecting tray
6 level switch inlet water tank 62 level switch for collecting tray
32 conductivity cell inlet water 64 overflow valve RO pure water
33 main pump RO 71 needle valve for recirculation of RO-reject
34 RO-modules (1-4 pcs) 106 solenoid valve return line inlet water tank
35 conductivity cell pure water 110 dosing connector, pos. for disinf. of WRO
36 solenoid valve, pure water flush line 111 dosing connector, operating positio
41 needle valve RO-reject 121 flow meter probe outlet pure water
42 flow meter probe RO-reject 122 flow control
WRO Chem - component list

43 injection valve 130 dosing connector sensor, pos. for disinf. loop
44 dosing connector sensor, operating position 131 dosing connector, pos. for disinf. loop
45 proportioning pump disinfectant 132 dosing connector, female part
46 container for Dialox 134 funnel
47 pick-up tube+level switch for disinfectant 136 solenoid valve with drilled hole
48 solenoid valve outlet pure water 138 motor valve
51 flow meter probe, pure water return 144 conductivity cell, pure water return
52 overflow valve pure water return Presure measuring points 1/4" female thread:
P1 RO pump pressure
P2 outlet pressure RO

1:7
WRO Chem -
front view

P1
P2

111
45
130

110

131
53

134
44

42
43, 132

63
34
33
40

41
71

32
62

47
1

61
Fig. 4.

HCEN9315 Rev. 10. 00


1:8
64
WRO Chem -
view from right
121

48
106
35
54

52

136

36

122

Fig. 5.

HCEN9315 Rev. 10. 00


1:9
Main components
Refer to figures 3, 4 and 5!

Inlet water tank (4) Special solenoid valve (136)


The inlet water tank in the RO-unit separates The solenoid valve 136 is mounted in series with
the system from the mains water supply system valve 48 in the outlet pure water line. It has a
by an air gap. The water level is regulated by drilled hole which allows passage of water also in
means of a float valve (5). The tank also contains closed position. It operates identical to valve 48
a low level switch (6) which stops the system if except from during Dialox intake period during
the water supply is inadequate. loop disinfection when it is closed. The purpose is
to reduce the outlet pure water flow and
Main pump module (33) pressure during intake of Dialox, thereby
A pump module consists of a fiberglass reinforced increasing the concentration of Dialox.
pressure vessel containing a multistage
centrifugal pump made of stainless steel. Both Operator´s panel
ends are closed by plastic o-ring sealed end The Operator´s panel on the front is used for all
plugs. The module is connected to the upper and communication between operator and the WRO.
lower stainless steel frames through the plastic Refer to page 1:12.
end plugs and sealed by o-rings.
Electrical control cabinet WRO
RO-modules (34) The electrical components is mounted behind
An RO-module consists of a fiberglass reinforced the upper front cover of the WRO-unit (behind
pressure vessel which encases two membrane the operator´s panel). This cabinet contains
elements. Both ends are closed by o-ring sealed equipment such as programmable controller
plastic end plugs. The modules are connected to (PLC), signal converters, relays and fuses. For
the upper and lower stainless steel frames access (trained personnel only), release the two
through the end plugs and sealed by o-rings. locking screws.

Dosing pump (45) Collecting tray (61)


Magnetic membrane dosing pump. One or two The collecting tray at the bottom of the unit is
pumps are included depending on size of WRO. connected to drain and will lead away small
The output of the pump is regulated by changing amounts of water, such as spillage and conden-
the stroke frequency with a graduated knob. The sate. The tray has a level switch (62) which will
membrane in the pump is made of teflon stop the unit and shut off the water supply in
The pump have non-return valves on both inlet case of a larger internal leak by closing the inlet
and outlet of the pump head and in the dosing water solenoid valve (1).
connector.
The pump has a suction tube with a built-in low Cover
level switch. The container plug has adjustable The system is enclosed in a painted steel plate
diameter and a built-in aeration valve. cover. The internal parts are accessible through
three doors: one on the front, one on the left and
Dosing connector (132) one on the right side of the unit.
During operation the (female) dosing connector
for the disinfectant must be positioned in the Caution: Those parts of the cover that are
position OPERATION (44). The dosing pump fastened with screws may only be opened by
and disinfection container is then completely trained technical personne
isolated from the fluid system in the WRO.
At initiation of disinfection the dosing connector
is manually moved to either DISINF WRO (53)
or DISINF LOOP (131), depending on which
disinfection program that is selected.
It then has to be moved back to OPERATION
before the WRO can be put back into operation
again. All three positions have sensors to verify
correct position of the connector.

HCEN9315 Rev. 10. 00


1:10
Motor valve (138)
The purpose of this three-way valve is to reduce
the overall water consumption. The valve is
mounted in the reject line (fig. 3, 4) and is
controlled by the PLC. It will recirculate part of
the reject water to the inlet tank during periods
when less water is used.
Function: The reject flow rate leaving the
RO- module(s) is constant and is set with
needle valve 41 with fully open motor valve to
the value recommended in the Installation and
Service and maintenance sections.
When the consumption of pure water goes down,
valve 138 gradually closes, thereby leading a
larger part of the reject water back to the inlet
tank. (4). The Water Conversion Factor =

WCF (%) = pure water consumption x 100


inlet water flow
will therefore remain constant during operation,
independent of product water consumption.

Note: The part of the product water that is not


used in the clinic will also be recirculated to the
inlet tank. The quality of the product water will
remain unchanged, regardless of the degree of
recirculation of reject.

HCEN9315 Rev. 10. 00


1:11
The MAC operator´s panel

- Operation
2 µS/cm

DISINF CLEAR
START STOP
WRO 7 8 9

DISINF ALARM
STATUS C LOOP 4 5 6 ACK

ALARM MAIN
LIST MENU 1 2 3 i
- 0 . ENTER

Fig. 6.
The operator´s panel on the front of the RO-unit is used for the operation of the system. It is also
used for alarm information and for setting purposes.
The display shows information about the operational status of the system. More detailed informa-
tion on the display can be obtained by keeping the STATUS-button pressed until the display
changes (approx. 5 seconds). Revert to normal display by again pressing STATUS for 5 seconds.
The curser in the upper left corner of the display is used when searching for information. It is
moved by pushing the four arrow buttons.
" >" in the upper right corner of the display indicates that the fast stepping function has been
selected. Refer to 2. on page 5:3 for more information.
" * " in the upper right corner indicates that the alarm list includes an active alarm in the WRO
that has been reset. Refer to section 3, Alarms and trouble shooting for more information.

Below please find the basic information about the panel which is required for the daily operation.
The detailed information is contained in section 5, Technical information.

Text on display
Button to start the WRO. When START is pressed, a
flush to drain first takes place for a few minutes, -
START
followed by a conductivity check which lasts for 30 START UP .... MIN
seconds. If the conductivity is approved, the system goes .....µS/cm
into normal operation. If a restart is done within 10 minutes after a
stop, the system will skip the start-up flush and directly enter the -
conductivity check. OPERATION ... µS/cm
The flush to drain can be speeded up by keeping START depressed
during the flush. "rapid" will then appear on the display and the
minutes count down to 0 in seconds. This function should not be - rapid
used in the routine operation of the WRO. START UP .... MIN
The START button can also be used to initiate forced rinse during .....µS/cm
disinfection. To do this, first press STOP and then keep START
depressed for minimum 5 seconds, until rinse starts.

-
Pressing this button stops the system and puts it into STAND BY
STOP Stand by.
During stand by the WRO will perform a flush at regular
intervals, either to drain or including the distribution -
system (selectable, refer to section 5). Rinse is shown on the display STAND BY
during this flush. Rinse

HCEN9315 Rev. 10. 00


1:12
DISINF
Button to initiate disinfection of the WRO. Note: A code (code 1) is also
WRO required to initiate and terminate the disinfection procedure.

Button to initiate disinfection of the distribution system. The dialysis


DISINF machines and the WRO can also be included in this procedure.
LOOP
Note: A code (code 1) is also required to initiate and terminate the
disinfection procedure.
The DISINF LOOP button can also be used to restart the intake phase. The
program must then be in intake or contact mode.

1: Return to normal status display: You can at any time return to


STATUS display of status by just pressing this button.
Exception: If you are in TIME CHANNELS, refer to section 5.
2: Alter between normal/detailed display: Press the button for five
seconds to change between normal and detailed display. Refer to section 5.

This button is only used for as confirmation button in certain technical


+ setting procedures. It is nonfunctional in all other situations.

These buttons are used for handling of alarms in alarm situations. Refer to
ALARM ALARM
LIST ACK
section 4, Alarms and trouble shooting.

Pressing this button will bring up CWP INFO where present information
MAIN about the status of the WRO can be obtained, see below. It is also the
MENU
entrance to the technical information levels of the system. Refer to section 5.

The numbered buttons are used to dial the different codes and when
 ' programming the time channels. Refer to Programming of TIME
CHANNELS.

The arrow buttons are used to move the curser to desired position on the
display.

Clear The Clear - button is used during programming to clear unwanted digits or
signs.

Enter The Enter - button is used as confirmation when entering information into
the system.

The information button is used to bring up time information on the alarm


list and setting ranges for different parameters during technical calibration.

This button is not used in this model.

HCEN9315 Rev. 10. 00


1:13
CWP INFO / MAIN MENU
Pressing MAIN MENU gives access to 6. Consumption ... l/min
information about the present status of the Actual pure water consumption. The dis-
WRO. played value is updated every 4 seconds.

Use the arrow buttons to move through the list. 7. Cond.in < .... µS/cm
The conductivity of the inlet water to the
1. Day, date, time WRO. Alternatively, the conductivity in the
loop return line can be checked.To do this,
2. Inlet water ...l/min put the cursor on < and press ENTER. The
3. Pure water ...l/min display changes to Cond. ret.
4. RO reject ...l/min The display reverts to inlet conductivity after
5. Return flow ...l/min 30 seconds.
6. Consumption ...l/min
7. Cond.in < µS/cm 8. Cond.out .... µS/cm
8. Cond. out µS/cm Conductivity of the pure water.
9. Recovery rate ...%
10. Rejection rate ...% 9. Recovery rate ... %
Actual recovery rate of water, i.e. the portion
11. Mode LOCAL if the inlet water that is converted to pure
12. Start/Stop MAN water.
13. =>Technician info
14. Test operat.WRO no/yes 10. Rejection rate ...%
15. Test/Circ. LOOP no/yes Actual rejection of dissolved salts in %. The
16. WS-control: value is calculated with the formula:
17. 0 AUT (aut)
(1 - cond out) x 100
Fig. 7. MAIN MENU cond in

1. Present date and time. 11.Mode LOCAL/REMOTE


Information about mode of operation.
Note: the time has to be adjusted for summer- LOCAL: operation from the panel.
and winter time, Refer to 3, 4 on page 5:4. REMOTE: operation from an external key
switch control (optional). Refer to page 5:4 for
2. Inlet water ... l/min more information.
Present inlet water flow rate. The displayed
value is updated every 4 seconds. 12.Start/Stop MAN/AUT
This value is calculated, refer to page 1:5. If LOCAL operation has been selected, the
WRO can be programmed for manual or
3. Pure water ... l/min automatic start and/or stop of operation.
Present pure water flow rate. The displayed The present setting is displayed here.
value is updated every 4 seconds. Refer to Technician info level 2 (page 5:4) for
more infromation and instructions.
4. RO - reject ... l/min Note: When in REMOTE control, automatic or
Present reject flow rate to drain. The dis-
manual start/stop is determined by the position
played value is updated every 4 seconds.
of the external key switch. The selection in this
position then has no meaning.
5. Return flow ... l/min
Return pure water flow rate from the loop.
The displayed value is updated every 4
seconds.

HCEN9315 Rev. 10. 00


1:14
13. ->Technician info
Here you enter the level Technician info.
Place the curser at the arrow and press
ENTER. See Refer to section 5, Technical
informaton, for more information.

14.Test operat.WRO (no/yes)


This function is used if you want to operate
the WRO for testing purposes. All pure water
will be diverted to drain via valve 36.
To start test operation: Put the curser at
no and press ENTER. The display will then
change to TEST OPERATION WRO.
To stop test operation: press STOP.

15.Test/Circ. LOOP (no/yes)


This function is used if you want to operate
the WRO to the loop during testing.

To start test operation:


Put the curser at no and press ENTER.
The display changes to:
TEST OPERATION LOOP.
To stop test operation: press STOP.

16.WS -control
Indication of the status of the water saving
control system:

AUT - Normal position. The water saving


control system follows what is set in the
technical level, Refer to Service and
maintenance for more information.
MAN - The water saving control system is
disenganged and the CWP is operated with
the motor valve 138 fully open to drain.

To disengage the water saving function:

Note: Disengaging the wter saving function


cannot be performed when the CWP is in Stand-
by mode.

1. Move the cursor to line 17 with the down


arrow button.
2. Enter the operator´s code and then press
ENTER (>>>> appears on line 17).
3. Place the cursor at AUT (right arrow button)
and press ENTER. The text then changes to
MAN and the motor valve opens fully to
drain.

HCEN9315 Rev. 10. 00


1:15
Chemical disinfection
Disinfection programs
Disinfection must be performed on a regular Caution: Do not use any other disinfectant
basis to ensure consistent microbiological quality than Dialox without consulting Gambro.
of the pure water. WRO Chem therefore has Other peracetic based disinfectants may
automized disinfection programs to simplify the require other dilution ratios than Dialox.
disinfection procedure: The use of other peracetic acid based
disinfection solutions has not been validated.
1. DISINF WRO The use of chlorine based disinfectants such
Disinfection of the WRO alone according to as sodium hypochlorite will rapidly destroy
page 1:17. the reverse osmosis membranes.
Formalin will be insufficiently rinsed out
2. DISINF LOOP with the rinse programs intended for Dialox.
Disinfection of the distribution system of pure
water downstream the WRO according to
pages 1:18 -1:20. Information about peracetic acid
Depending on preferences, this disinfection Peracetic acid is a chemical disinfectant consis-
program may include: ting of a mixture of hydrogen peroxide (H2O2),
acetic acid (CH3COOH) and water. Peracetic
A. Only the distribution system acid is formed when mixing these ingredients :
B. The distribution system + the WRO
C. The distribution system + the WRO + H2O2 + CH3COOH ⁄ CH3 COOOH +H2O
dialysis machines type Gambro. hydrogen acetic acid peracetic acid water
This mode is also referred to as Central peroxide
chemical disinfection
Peracetic acid has strong oxidizing properties. It
Caution: The mode Central chemical attacks proteins in the cellullar membranes of
disinfection has only been validated with the microorganisms, penetrates into the cells
Gambro dialysis machines AK 90, AK 100 and oxidizes the enzymatic system. After reaction
(prom version 3:60 or later), it decomposes to water, oxygen and acetate.
AK 100 ULTRA (prom version 4.xx or
later), AK 95, AK 200 and AK 200 ULTRA. The recommended concentration of Dialox in the
disinfectant solution is 2-4 %, which corresponds
to a dilution ratio of 1:25 - 1:50.
Required disinfection frequency Refer to Users Manual for Dialox for more
The required frequency of disinfection depends information regarding Dialox.
on factors such as inlet water quality and opera-
tion schedule and must therefore be determined Caution: Too high concentrations of Dialox may
by regular microbiological testing. cause irreversible damage to the reverse osmosis
Weekly disinfection should however be regarded membrane. Damage will also occur if the
as a minimum. temperature of the disinfection solution in the
system exceeds 25 °C (max. feed water temp. =
20°C, refer to Technical data in section 6).
Disinfection solution Consult Gambro if any doubts exist!
The disinfectant to be used is Dialox, which is a
peracetic acid based agent.

Caution: Peracetic acid concentrates are Residual testing of Dialox


corrosive and may cause damage to eyes and Potassium Iodine test strips are used to test for
skin. Study the safety instructions prior to use. residual chemicals, e.g. Merck Peroxide test
Use protective glasses! strips (sensitivity 0.5 mg/l of H2O2), Gambro
Exposed skin will be irritated and white spots order no 113 004 078.
may appear which will disappear after 1-2
hours. In case of spillage, flush with plenty of
water.

HCEN9315 Rev. 10. 00


1:16
1. Disinfection of WRO
Refer to the function diagram
106
in section 6. 1

54

Phase 1. 53 33 48
Disinfectant intake
36
The dosing connector is put in
DISINF WRO (110) and
138
DISINF WRO is initiated.
45
Dialox is pumped into the
WRO and circulated within
the unit.

Fig. 8.

106
1

54
Phase 2. Contact period
53 33 48
To allow for sufficient contact
time of the Dialox. 36

The main pump runs


intermittently. 138

45

Fig. 9.

106
1

54
Phase 3. Rinse
53 33 48
The Dialox is rinsed out of
the WRO. 36

138

45

Fig. 10.

HCEN9315 Rev. 10. 00


1:17
2. Disinfection of the distribution system
Also refer to Operating instructions and function diagram (section 6)
Disinfectant intake - phase 1.
Filling up the distribution system

The dosing connector is put in DISINF LOOP (130) and DISINF


LOOP is initiated (see operating instructions).
The dosing pump first starts and, after 40 seconds, the main pump
also starts and feeds the disinfection solution into the loop (fig.11)

106
1

54

33 48 136
130

36

45
138

Fig. 11.

Disinfectant intake - phase 2.


Filling up AK dialysis machines and WRO
1: Central chem is manually initiated on all Gambro dialysis
machines that have this feature.
2: AK90: The fill phase of the chemical disinfection program is
manually initiated. Duration: Approx. 7 minutes per AK 90.
3: Solenoid valve 54 closes and 106 opens at a preset time to feed
disinfection solution back to the WRO.
106
1

54

33 48 136
130

36

45
138

Fig. 12.

HCEN9315 Rev. 10. 00


1:18
Contact period

To allow for sufficient contact time of Dialox.

During the contact time the WRO is programmed to flush to


drain intermittently to flush out Dialox.

106
1

54

33 48 136
130

36

45
138

Fig. 13.

Rinse - phase 1. Rinse WRO+loop


Rinse of WRO and distribution system

The WRO and the loop is rinsed out. The pure water- and return flow
are monitored during this phase. If they differ to much, an alarm is
issued. Also, a conductivity test is performed during the last period of
the rinse phase to check that the main part of the disinfectant has been
rinsed out.
106
1

54

33 48 136
130

36

138
45

Fig. 14.

HCEN9315 Rev. 10. 00


1:19
Rinse - phase 2. Final rinse WRO

2.1. Rinse of return line to WRO

Solenoid valve 54 closes and valve 106 opens for 20 seconds to


allow for rinse of the return line to WRO.

106
1

54

33 48 136
130

36

138
45

Fig. 15.

2:2. Final rinse of WRO

The outlet valve to the loop is closed and the WRO is rinsed out.

106
1

54

33 48 136
130

36

138
45

Fig. 16.

HCEN9315 Rev. 10. 00


1:20
Rinse of dialysis monitors
A. Automatic rinse of the monitors

Alternative 1: Rinse of the dialysis The WRO is then programmed to start some
monitors should follow immediately after minutes prior to this time and run for a preset
final rinse of WRO period to enable rinse of the dialysis monitors.
This mode is called RINSE CIRCULATION,
The WRO program offers the possibility to add a see fig. 16. Refer to TIME CHANNELS in
rinse period immediately after rinse of the WRO section 5 for more information.
and the loop has been completed. This mode is Refer to autorinse mode in the operating
called Rinse monitors and is suitable to use to instructions for AK100.
perform automatic rinse of AK 90, see fig. 16.
Note: The WRO Chem is still in disinfection
Note: The WRO will still be in disinfection mode mode when rinse circulation is activated.
during this rinse period. It then will stop and
cannot be put into operation until the Note: When using the autorinse feature in the
disinfection procedure has been completed by AK 100 you enter the desired ready time. This
entering the operator´s code. must be programmed into the AK 100 before
the central chem program is activated. If
Caution: The dwell time for the dialysis not, a manual rinse will be required.
monitors must be programmed so that the rinse
cycle of the WRO will overlap the rinse cycles of
the dialysis monitors. B. Manual rinse of the monitors

If the desire is to perform the rinse of the


Alternative 2: Rinse of the dialysis
monitors manually, this is done after finishing
monitors is programmed to take place at a
the disinfection the normal way and then
fixed, preset time, e.g. one hour before
starting the WRO in normal operation.
start of dialysis.

This rinse mode can only be used if the dialysis


monitors have a real time clock and an
autorinse mode, enabling automatic rinse at a
fixed, preset time.

106
1

54

33 48 136 130

36

45
138

Fig. 17. Rinse monitors alt.


RINSE CIRCULATION

HCEN9315 Rev. 10. 00


1:21
Remote control (option) External indication (option)
As an option, a key selector (fig. 18) can also be The CWP is prepared for the connection of an
fitted if external control is desired. This box external operation and alarm indication panel
should be placed in a suitable location in the and a separate buzzer unit.
dialysis clinic. It is then used to select mode of
operation of the system. The indication unit gives information about the
present status of the CWP and should be placed
in a suitable location with good visibility in the
MAN AUT clinic. It contains four lamps:

0 DIS
Green Normal operation

Fig.18. Key selector box White Not in operation

When the WRO is in Remote mode, the key Orange B- alarm


selector´s functions are as follows:
Red A-alarm
0: The WRO will go to stand by when turned to
this position, dialysis can not be carried out.
Fig. 19. Lamp indication unit
Note: The key selector must be in 0 position if
the desire is to change from Remote to Local Green light
mode or reversed. Blinking light:
The CWP is in start up mode, conductivity
MAN: The CWP is forced to go to normal opera- monitoring is bypassed during the start up
tion, bypassing time channel settings. Refer to sequence.
AUT below. Steady light:
The CWP is in operation, i . e. supplies pure
AUT: Normal position during remote control of water to the clinic.
the system. The machine starts/ stops according
to what is set in the time channels. Please refer White light
to section 5.
Steady light:
The CWP is not in operation, e.g during disinfec-
DIS: Disinfection can be initiated from the
tion and stand by.
operator´s panel on the CWP only when the key
Blinking:
switch is in this position. Alarm will otherwise
The CWP is in start up mode, conductivity
occur.
monitoring is bypassed during the start up
sequence.
Note: Disinfection can also be performed if the
key switch is in 0 position, provided that the
machine is in Local mode. Please refer to
Orange light
section 5. Blinking light:
An alarm type B has occurred . Refer to Alarm
section.
Steady light:
The B-alarm has been acknowledged, but the
cause of the alarm still remains.

Red light
Blinking light:
An alarm type A has occurred. Refer to Alarm
section.
Steady light:
The A-alarm has been acknowledged, but the
cause of the alarm still remains.

HCEN9315 Rev. 10. 00


1:22
2. Operating instructions

Contents
Morning when no disinfection of the WRO or the loop has been performed .................. 2

Evening when no disinfection of the WRO or the loop is to be performed ..................... 2

Operating instructions - central chemical disinfection ................................................... 3

Evening for central chemical disinfection ........................................................... 3

Morning after central chemical disinfection ....................................................... 3

If the display does not show TEST WRO after loop disinfection .................................... 4

Operator´s block diagram ................................................................................................. 5

HCEN9315 Rev. 10. 00


2:1
Operating instructions - Days with no disinfection
Morning when no disinfection procedure Evening when no disinfection of the
has been performed: WRO or the loop is to be performed:

1. The display on the WRO shows Stand by. 1. Press STOP.


The display changes to STAND BY.
2. If flushing is in progress: Press STOP.
A flush is performed at regular intervals during
stand by (flushing on the display).

3. To start operation: Press START.


The WRO starts with a short flush to drain
(START UP) and then goes into OPERATION.

HCEN9315 Rev.10. 00
2:2
Operating instructions - Central chemical disinfection
Evening for central chemical disinfection: Morning after chemical disinfection:

In the dialysis unit: In the water treatment room:


1. Finish dialysis according to normal routines. 1. The display should now show "TEST WRO".
Regarding programming and actions for the
dialysis machines, see separate information. Warning: If the display does not show "Test
WRO", go to page 2:4 for more information before
In the water treatment room: any more actions are taken!
2. Stop the WRO by pressing STOP.
3. Dial code 1 and press ENTER. Testing for residues in the WRO:
4. Press DISINF LOOP twice acc. to the dis- 2. Press START.
play. 3. When "wait" changes to "test water":
Collect a water sample in the funnel on the
Caution: Read the safety instructions for the right hand side of the WRO.
disinfection chemical. Use protective glasses! 4. Verify with a peroxide test strip that no
disinfectant can be detected in the sample.
5. Open the door on the WRO. 5. If no residues are detected*, press STOP.
6. Check that there is sufficient amount of Dialox Then enter code 1 and press ENTER. The
for one loop disinfection procedure. If not, display will then change to "TEST LOOP".
replace the container with a filled one. * If residues are detected, continue test opera-
7. Move the dosing connector to DISINF. LOOP. tion until the WRO is free from residues.
Make sure that the connector is securely fixed
in the disinfection position. Testing for residues in the loop:
8. Press DISINF LOOP. 6. Press START.
7. When "wait" changes to "test water":
In the dialysis unit: Collect a water sample in the last tap on
9. Perform the required actions on the dialysis the loop, close to the WRO (= return water
machines according to separate information in from the loop).
section 9, Appendices. 8. Verify with a peroxide test strip that no
disinfectant can be detected in the sample.
Caution: Put a label on all machines & taps 9. If no residues are detected*, press STOP.
stating that chemical disinfection is in progress. Then enter code 1 and press ENTER. The
display then goes to "STAND BY ".
In the water treatment room: * If residues are detected, continue test opera-
10.When the disinfectant intake phase is finished tion until the loop is free from residues.
the dosing pump(s) stop(s) and "Move dos. 10. Press START. The WRO now starts with a
conn." appears on the display. Then open the extended flush to drain, also including a flush
door on the WRO and do the following: of the loop ("START UP" on the display) and
then goes into OPERATION.
a: Within 10 minutes(to avoid alarm): 11. Perform the required actions on the dialysis
Return the dosing connector in the WRO to machines according to separate information.
OPERATION. This will eliminate the risk of
Dialox being drawn into the fluid system. Warning: Do not initiate dialysis until a test for
residual disinfectant has been performed at the
b: Check that the correct amount of Dialox has outlet on all dialysis machines.
been consumed during the disinfectant intake.
12. When all residual tests has been performed,
11. Make a mark at the fluid level in the remove all labels indicating the chemical
disinfectant container with a permanent pen. disinfection procedure.

Caution: Insure that correct amount of Dialox


has been used. Otherwise, the disinfection of the
dialysis machines will be inadequate.

12.Close the door on the WRO.


HCEN9315 Rev. 10. 00
2:3
If the display does not show "TEST WRO" after loop disinfection

If an alarm is displayed:

1. If the alarm can be found in the list on


page 3:5:
- Perform the recommended actions for that
specific alarm.

2. If the alarm can NOT be found in the list


on page 3:5:
- Call for technical service.

3. If the alarm cannot be rectified:


- Continue according to local regulations

4. If the bypass connection is going to be


used:
- Continue according to local routines
concerning the use of bypass water.

After opening the bypass valve:

- Open the LAST tap in the distribution system,


placed in the return line from the clinic, close to
the WRO Chem.

- Flush for 5 minutes to drain through this valve.

- Make a test for residual disinfectant in the


water from the last tap.

If any residuals can be detected:

- Perform an additional rinse cycle on the dialysis


machines.

- Make a test for residual chemicals on the


dialysis machines before initiating dialysis

Warning: Do not initiate dialysis until a test for


residual disinfectant has been perfomed on the
dialysis machines!

HCEN9315 Rev.10. 00
2:4
WRO Chem - Operator´s block diagram

At regular intervals
STAND BY STAND BY
DISINFECTION: FLUSHING
Dial code 1

STOP
.... START ENTER

START UP ... MIN


....uS/cm XXX > > > > > > > > >
STAND BY

OPERATION ...uS/cm
DISINF
DISINF LOOP STOP
WRO

DISINF. WRO??? DISINF. LOOP???


No=press STOP No=press STOP
Yes=press DIS. WRO Yes=press DIS LOOP
DISINF DISINF
WRO LOOP
DISINF. WRO??? DISINF. LOOP???
Move dos connector Move dos connector
to WRO and press to LOOP and press
DISINF. WRO Move the DISINF. LOOP Move the
connector connector
DISINF DISINF
DISINF. WRO ...MIN WRO DISINF. LOOP ...MIN LOOP

If dos. connector already has If dos. connector has NOT Programmed circulation of
Flushing of WRO and been moved to OPERATION been moved to OPERATION water in the loop to enable
loop at regular intervals (ALARM issued on display): autorinse of dialysis machines
ALARM
Flushing Move the Rinse circulation
DISINF. FINISHED DISINF. FINISHED connector DISINF. FINISHED DISINF. FINISHED
TEST WRO to OP, Move dos.connector
Test op.=press START reset alarm to OP. - Test water

START

Residual
test
TEST OPERATION TEST OPERATION
TEST WRO
WRO WRO STOP
Test=press START
Wait ..uS Test water ...uS
Accept=dial code
Accept = press STOP
START
STOP
Dial
code 1
ENTER

Residual
TEST OPERATION TEST OPERATION test
DISINF FINISHED START LOOP LOOP TEST LOOP
STOP
TEST LOOP Wait ...uS Test water ...uS Test=press START
Test op.=press START Accept=press STOP Accept=dial code

START Dial
code 1
ENTER

HCEN9315 Rev. 10. 00


2:5
This page is intentionally left blank

HCEN9315 Rev.10. 00
2:6
3. Alarms and trouble shooting guide

Contents

Alarms .................................................................................... 2
Symbols found in the alarm list ........................................ 2
External alarm indication ................................................. 2
Power failure ...................................................................... 2
Water supply interruption ................................................. 2

Alarm list ................................................................................ 3

Operator´s action is case of an alarm .................................... 4

Alarms that can be handled by the operator ........................ 5

Trouble shooting guide .......................................................... 7


1. Low level inlet .............................................................. 8
3. Drain valve ................................................................... 9
4. Dos.connector ............................................................. 10
5. Warning cond ............................................................. 12
6. High cond. .................................................................. 13
7. Motorprotect WRO ..................................................... 14
8. Low flow F6 ................................................................ 15
9. Low level chem ........................................................... 16
10. Leakage ...................................................................... 17
17. Low flow F2 ................................................................ 18
19. Loop leakage .............................................................. 19
21. Cond.rinse.hi. C4 ....................................................... 20
22. Cond. test. C4 ............................................................. 21
23. Cond. intake. lo C2 ..................................................... 22
24. Cond. intake. lo C4 ..................................................... 23
25. Operat.indicat ............................................................ 24
26. Remote control ........................................................... 25
27. Low battery PLC ........................................................ 25
28. Disinf. time ................................................................. 26
30. WS control .................................................................. 27
31. Cond. test. C2 ............................................................. 28

Internal alarms in the MAC terminal

Comm. ERROR .......................................................... 29


System ERROR .......................................................... 30
Batt. Low .................................................................... 30

HCEN9315 Rev. 10. 00


3:1
Alarms
In alarm situations, ALARM will be displayed in External alarm indication
the upper right corner of the display. Action:
The WRO can be connected to an external alarm
1. Press ALARM LIST. A list of the alarms that device via a potential-free contact in the
have occurred (max. 32) will then appear with electrical control box in the WRO. Refer to
the latest alarm at the top. The time at the section 4, Installation and section 6, Electri-
bottom of the display is the time that the cal diagrams, for more info.
alarm that the cursor points at occurred .
(If no time is displayed: Press ) Power failure

2. Resetting of alarm: Press ALARM ACK to If a power failure occurs, the WRO will stop and
reset the alarm that the cursor points at. the display on the operator´s panel goes blank.
Then press STATUS for normal reading. An alarm will, however, be issued on the exter-
nal alarm contact.
List of alarms
During operation: The WRO will restart
The Alarm list on next page shows all alarms
automatically and return to operation after 45
that can occur in the system. Alarms that are
seconds (cond. check) when the power returns.
easy to correct are listed in "Alarms that can
be handled by the operator". Other alarms
During stand by or disinfection: The system
normally requires technical assistance and can
will restart from where it was before the power
be found in the Trouble shooting guide below.
failure occurred as soon as the power returns.
Alarm no 28, Disinf time, will be issued in case
Symbols found in the alarm list of a longer power failure.
All relevant data will be retained in the
memory during the power failure.
Symbol in Meaning
front of alarm Alarm that have been reset will be deleted
from the alarm list in case of a power failure.
* Active alarm that has not
been reset in the alarm list Water supply interruption
Active alarm that has been
Refer to page 3:8 for more information!
reset in the alarm list (the
cause of the alarm remains).
During operation: The WRO will stop and
This is also indicated att all
issue alarm no 1. It will then make up to 4
times by a * in the upper
attempts to restart. If a restart attempt is
right corner of the display.
successful, the WRO will return to operation.
The alarm(s) will, however, remain in the alarm
Alarm that is no longer
list and has to be reset manually.
$ active but has not been
If all four restart attempts fail the WRO will
reset in the alarm list (the
stop. It then has to be restarted manually after
cause of the alarm is cleared)
correction of the cause of the alarm.
Old alarms that are no
During Stand by flushing: No alarm is
longer active and that has
no issued. The flushing will be interrupted. A new
been reset. These alarms do
symbol flushing period will be initiated after set time,
not affect the performance of
provided that there is water in the inlet tank.
the WRO anymore
During disinfection: Alarm no 1 will be
issued. The WRO will try to start at prepro-
grammed intervals.

3:2 HCEN9315 Rev. 10. 00


Alarm list
Nb. Display text in Reason Sensor in flow -
ALARM LIST and el. diagrams

1 Low level inlet Low level inlet water tank 6

3 Drain valve Drain valve error (motor valve 138) 138

4 Dos.connector Wrong position dosing connector 44, 53, 130

5 Warning cond. Warning signal pure water conductivity 35

6 High cond. High pure water conductivity 35

7 Motorprotect WRO 1: Motor protector for pump in WRO F1


2: Unauthorized use of fast-stepping

8 Low flow F6 Low pure water flow during rinse (F6) 121

9 Low level chem. Low level in container for Dialox 47

10 Leakage Leakage (water on collecting tray) 62

17 Low flow F2 Low reject drain flow (F2) 42

19 Loop leakage Leakage in the loop -

21 Cond. rinse. H C4 High conductivity in the return line during 144


end phase of rinse program

22 Cond. test C4 Error in conductivity cell in the return line 144

23 Cond. intake. lo C2 Low conductivity in return line during 144


disinf intake

24 Cond. intake. lo C4 Low pure water conductivity during 35


disinf intake

25 Operat.indicat. Error in external operation indication K14

26 Remote control Error in the remote control system -

27 Low battery PLC PLC Battery voltage is less than 3 V -

28 Disinf. time Time deviation during disinf too large -

30 WS control Error in the water saving system 138

31 Cond. test. C2 Error in pure water conductivity cell 35

HCEN9315 Rev. 10. 00


3:3
Operator´s action in case of an alarm
If an alarm occurs on the CWP, the external alarm lamp (if installed) will light up
and ALARM will be displayed in the upper right corner of operator´s panel display.
The enclosed alarms list "Alarm list for nurses" covers the alarms that can be
handled by the nurses. Other alarms requires technical personnel.

Actions:
ALARM
LIST
1. On CWP 100: Press . A list of alarms that have occurred will be displayed
with the latest alarm at the top of the list. " * " in front of the alarm indicates an
active alarm that has not been reset. The time when the alarm that the cursor
points at occurred is shown at the bottom of the display.
(If no time is shown, press the I-button .)

2. Acknowledgement of the alarm: Insure that the small arrow on the alarm list
points at the alarm to be acknowledged ( " * " in front of the alarm). If not move
the arrow with the arrow buttons. Then press . " * " will then disappear.
ALARM
ACK

If " - " is shown after acknowledgement, the cause still remains .


A "$" indicates an alarm that is no longer active but has not been reset.

3. If the alarm is included in the enclosed list, follow recommended actions to cor-
rect the fault. If not, call for technical assistance. For complete alarm list and
trouble shooting guide, please refer to the Trouble shooting section of the
manual.

4. In some cases consecutive alarms may occur. It is then important to acknowledge


all alarms. Use the arrow buttons to find all alarms and then reset them.

5. When the fault has been rectified: Press STATUS to return to normal display
reading.
START
If operation is to be resumed: press ()*+) .

If the alarm has occurred during a disinfection cycle and this is to be contin-

ued, press DISINF


,-(-./
. If disinfection is to be finished as soon as possible, keep START
()*+)

depressed for more than 5 seconds. Rinse will then be initiated. When the rinse is
completed, finish disinfection according to normal routines. Then perform a rinse
of the dialysis machines before testing for residual disinfectants.

Warning: Do not initiate dialysis until all dialysis machines have been tested for
residual disinfectant!

3:4 HCEN9315 Rev. 10. 00


Alarms that can be handled by the operator
No Cause Action
1. "Low level inlet." Operation: The CWP will reset the alarm (indicated by $
Low level in the inlet in the alarm list) and make up to 4 restart attempts. If an
water tank inside the attempt is successful the CWP will continue in operation.
CWP. This alarm may be During restart attempts, check that the inlet pressure to
caused by plugged the CWP is minimum 2,5 bar (35 psi). Call for technical
prefilters or insufficient assistance to investigate the cause of the alarm.
water supply. Loop disinfection: The CWP will try to restart at regular
intervals (factory set at 10 minutes). If the disinfection
program is delayed more than a certain time (factory set
at 15 minutes ), alarm 28. Disinf. time will also be is-
sued.
After correction of the fault: Let disinfection go to
completion. An extra rinse of the dialysis machines is then
mandatory before performing test for residual chemicals.
4. "Dos. conn. error" Operation: Open the front door of the CWP and check the
The disinfectant connec- position of the dosing connector. Make sure that is firmly
tor sensors indicate in Operation position. Call for technical assistance if the
incorrect position. The alarm cannot be rectified.
sensor must be returned Loop disinfection: Follow the normal procedure to finish
to Operation after the disinfection of the CWP and the loop. An extra rinse of the
intake phase, otherwise dialysis machines is then mandatory before performing
this alarm will occur. test for residual chemicals.
5. Warning cond.
The CWP will continue in operation. Call for technical
The product water con-
assistance to find out the reason for the alarm.
ductivity is elevated.
6. High cond. The CWP goes into divert-to drain mode and the dialysis
The high conductivity machines will stop because of insufficient water supply.
alarm limit has been Immediately call for technical assistance to investigate
exceeded. The alarm can the cause of the alarm.
not be cleared until the Operation will be resumed automatically if the conductiv-
conductivity again is ity goes below 50% of the set limit for high conductivity.
below the alarm limit.

9. "Low level chem" At the initiation of a disinfection cycle: Replace the


The level of disinfectant is empty container with a filled one
below the level switch in During a loop disinfection cycle: The CWP and the
the disinfectant container. dialysis machines will stop. Replace the empty container
Always insure that there with a filled one within 30 minutes! Then restart the
is sufficient amount of disinfection programme.
disinfectant at the initia- After a disinfection cycle: Perform an extra disinfection
tion of a disinfection cycle! of the dialysis machines before initiating dialysis.

27. "Battery low PLC" This alarm is technical and does not effect the dialysis
The battery in the PLC treatments. Proceed according to normal routines but
is losing its power. immediately call for technical assistance to investigate the
cause of the alarm.

28. "Disinf. time" Follow the normal procedure to finish disinfection of the
The disinfection cycle in CWP and the loop. Then perform an extra rinse of the
the CWP has been de- dialysis machines before performing test for residual
layed more than allowed. chemicals.

HCEN9315 Rev. 10. 00


3:5
This page is intentionally left blank.

3:6 HCEN9315 Rev. 10. 00


Trouble shooting guide
This trouble shooting guide is intended to be used to identify the cause of issued alarms and to help
correct the fault causing the alarm.

HCEN9315 Rev. 10. 00


3:7
1.Low level inlet
Reason:
The level switch 6 in the inlet water tank 4 has indicated low water level.

Possible causes:
1: Inadequate water supply
2: Plugged prefilters
3: Faulty level switch

WRO action:
During operation: The WRO will stop and issue this alarm. It will then make up to four
restart attempts with one minute intervals (preset under Tec.info level 2).
If a restart attempt is successful the WRO will return to operation. For information pur-
pose the alarm(s) will remain in the alarm list (" $ " in front of the alarm) and must be reset
manually. They will, however, not affect the operation of the WRO .
If all four restart attempts fail the WRO will stop. It then has to be restarted manually
after correction of the cause of the alarm.

During stand by flushing: The flushing will be interrupted but no alarm is issued.
"low level" will appear on the operator´s panel to inform why the WRO has stopped. The WRO
will try to restart at preprogrammed intervals (standard setting 30 minutes, set under Tech-
nician info level 2) if there is sufficient water level in the inlet tank.

Note: Every time the level switch 6 indicates low level in the inlet tank, this will be regis-
tered under Technician info, subtitle "no of low level", for future records (refer to Service
and maintenance).

During disinfection: The WRO will stop and issue Low level inlet alarm. "STOPPED" and
"low level" will appear on the display.
The WRO will try to restart at preprogrammed intervals (standard setting 10 minutes, set
under Technician info level 2) if there is sufficient water level in the inlet tank.

Corrective action:
1. Is the water supply sufficient according to Technical data?
The accumulated number of low level alarms is registered under Nb. low level (4. in Techni-
cian info, page 5:2). Keep record of this number to find out if interruptions in the water
supply occurs on a regular basis.
A temporary drop in pressure may occur if backwashing or regeneration of different pretreat-
ment filters takes place when the WRO is in operation.

2. Check of prefilters: Start the WRO and check the pressure before and after the prefilters.
The pressure drop during operation should be max. 0,5 bar and the pressure after the
prefilters should be min. 3.0 bar.
Exchange prefilter filter cartridges if necessary.

3. Check the function of the level switch (6) (output X13 on PLC). It should be lit when there is
water in the tank and go out when the tank goes empty. Replace if faulty.

3:8 HCEN9315 Rev. 10. 00


3.Drain valve
Reason:
Motor valve 138 on the drain and recirculation line is equipped with a microswitch which senses
the position of the valve when it is in closed position, i.e. full recirculation of the reject back to
the inlet water tank 4.

This alarm is issued, after a short delay, if the input signal X15 from the sensor is not on when
the output signal Y15 is activated.

Possible causes:
1: Malfunction of motor valve 138
2: Malfunction of the microswitch

WRO action:
The CWP stops and cannot be restarted again until the cause of the alarm is rectified.

Corrective action:
Valve 138 is powered from the output Y15 via solid state relay K32. This output is powered
during the intake and recirculation periods of the disinfection program to divert the solution back
to the inlet tank.

1. Put the motor valve in manual position (refer to Technical info level 2) . Try to open/close the
valve and check that the LED´s on the out put and solid state relays K31 and K32 lights up
correctly.

2. Check if the valve is closed (the pointer for the valve shall point at 0). If not, try to close it manu-
ally (remove the black rubber cap on the motor valve) by using an Allen (hexagon) key. Turn
counter clockwise to close the valve.

3. Check the function of the microswitch. LED for X15 shall be on when the valve is closed.

HCEN9315 Rev. 10. 00


3:9
4. Dos.connector
Reason:
This alarm is issued if any of the three sensors 53, 11 and 130 for the dosing connector indicate
that the connector is incorrectly positioned for the present mode of operation. The sensor must be
located in the hole in the square metal part surrounding the connector. The connector must be
in the correct position and must not be in any other position. Otherwise, this alarm will be issued.
A red light can be seen at the back of the sensor (behind the panel) when the sensor is active.

Possible causes:
The dosing connector must be positioned as follows:

MODE OF OPERATION CONNECTOR POSITION


1. operation or stand by OPERATION (44)
2. loop disinfection, disinfectant intake DISINF. LOOP (53)
3. loop disinfection, contact and rinse periods OPERATION (44)
4. disinfection of the WRO DISINF. WRO (110)

WRO action:
1. DURING OPERATION AND STAND BY:
The WRO will stop and cannot be restarted until the cause of the alarm is rectified.

2. DURING THE INTAKE PHASE OF THE LOOP DISINFECTION PROGRAM:


a. The dosing pump(s) and main pump will stop. As a consequence, all dialysis machines that
have not finished their intake phase will issue alarm for insufficient water supply.
b. WRO time counting will freeze .
c. If the STOP button is pressed within 30 minutes, the disinfection program will be put
on hold until further action is taken.
d. If no action is taken within 30 minutes, the disinfection program will start from
where it was before the alarm occurred. All pumps will, however, stay switched off
during the remaining part of the intake period.

3. DURING CONTACT AND RINSE PHASES IN THE LOOP DISINFECTION PROGRAM:


When the intake phase has ended, the connector MUST be moved back to OPERATION
to eliminate the risk of disinfectant being introduced into the system during the subsequent
rinse sequences. If the connector is not returned to OPERATION within 10 minutes , this
alarm will be issued. The disinfection program will, however continue and go to completion.

Warning: If this alarm occurs, an extra loop test and rinse of the dialysis machines must be
performed before initiation of dialysis. To indicate this, LOOP TEST REQUIRED will flash on
the display and the WRO will operate intermittent until the test has been verified by entering the
operator´s code + ENTER

4: DURING DISINFECTION OF WRO


Alarm will be issued but the disinfection programme will continue. The dosing pump(s) will,
however, remain switched off.

3:10 HCEN9315 Rev. 10. 00


4. Dos.conn. cont´d
Corrective action:
1. DURING OPERATION AND STAND BY:
Check that the connector is firmly in place in the OPERATION position. After reset, press
START to resume operation (if in operation). If the alarm is still not cleared, check the sensor.

2. DURING THE INTAKE PHASE OF THE LOOP DISINFECTION PROGRAM:


Insure that the connector is firmly in place in the LOOP DISINFECTION position. Then restart
disinfection by pressing LOOP DISINF.

Warning: If this alarm occurs during the intake phase of central chemical disinfection and is not
rectified within 30 minutes, the dialysis machines may not have been properly disinfected. An
extra disinfection of the dialysis machines is therefore mandatory before dialysis is initiated.

3. DURING CONTACT AND RINSE PHASES IN THE LOOP DISINFECTION PROGRAM:


a: The connector must be firmly attached in the OPERATION position.
b: Perform an extra loop test and rinse of the dialysis machines before initiation of dialysis. To
insure that this is done, LOOP TEST REQUIRED will flash on the display and the WRO will
operate intermittently to make initiation of dialysis impossible until the test has been verified
by entering the operator´s code + ENTER

If the connector is correctly positioned and the alarm still persists after reset, call for technical
service to check the function of the sensor.

HCEN9315 Rev. 10. 00


3:11
5.Warning cond.
Reason:
The purpose of the warning limit for pure water conductivity is to alert the operator that the
conductivity for some reason is elevated.
The warning limit should be set at 2 x the normal pure water conductivity, however minimum
30µS/cm. Factory setting: 50 µS/cm

Possible causes:
1. The inlet water conductivity is for some reason elevated. The reason could be:
- insufficiently rinsed softeners in the pretreatment equipment
- increased conductivity in the raw water that is used
2. Incorrect calibration of the pure water conductivity.
3. Internal leakage in the pure water conductivity cell (35).
4. Insufficient rinse times in the disinfection program.
5. Fouled RO-membranes.
6. Internal leakage in the reverse osmosis module(s).
7. Faulty conductivity transmitter CX2.
8. Irreversible damaged RO-membranes because of elevated chlorine levels in the inlet water to
the WRO or excessive temperatures (>25°C) during disinfection with peracetic acid.

WRO action:
During operation: The system will issue this alarm after some delay but continue in operation.
During disinfection and cleaning: No alarm will be issued.
During rinse circulation: No alarm will be issued.
During stand by flush: The pure water will be diverted to drain, independent of WRO setting.

Corrective action:
1. Check that the inlet water conductivity is normal (is displayed under MAIN MENU). If not,
check the function of the softeners and, if necessary, perform an extra rinse.
Also check the inlet conductivity with a conductivity reference meter.
2. Calibrate the inlet conductivity according to section 5.
3. Remove the rubber cap on the conductivity cell (35) and remove humidity that may be present.
4. If the rinse times are too short, the conductivity will continue to decrease during flushing until
the conductivity is below the alarm limit.
5. Perform cleaning according to section 5 in this manual. If the cleaning procedure does not
result in sufficient improvement, continue with 6. and 7.
6. Disassemble the membrane modules and change the internal o-rings. Refer to spare parts.
7. Replace the conductivity transmitter CX2, spare part no 25-11029.
8. Contact Gambro if the problem cannot be resolved.

3:12 HCEN9315 Rev. 10. 00


6. High cond.
Reason:
The purpose of the high conductivity limit for pure water is to alert the operator that the
maximum allowable conductivity has been exceeded.
The high conductivity limit should be based upon the initial feed water analysis and initial rejec-
tion characeristics of the reverse osmosis unit and shall correspond to the lowest conductivity at
which any contaminant reaches an unacceptable limit, i.e. outside the valid standard.
Factory setting: 100 µS/cm.
Normally a high conductivity alarm is preceded by a warning alarm (alarm no 5).

Possible causes:
1. The inlet water conductivity is for some reason elevated. The reason could be:
- insufficiently rinsed softeners in the pretreatment equipment
- increased conductivity in the raw water that is used
2. Incorrect calibration of the pure water conductivity.
3. Internal leakage in the pure water conductivity cell (35).
4. Insufficient rinse times in the disinfection program.
5. Fouled RO-membranes.
6. Internal leakage in the reverse osmosis module(s).
7. Faulty conductivity transmitter CX2.
8. Irreversible damaged RO-membranes because of elevated chlorine levels in the inlet water to
the WRO or excessive temperatures (>25°C) during disinfection with peracetic acid.

WRO action:
During operation: The system will issue this alarm and switch to flush to drain.
If the high cond.alarm is activated during start up the WRO will continue to flush to drain until
the quality goes below the limit or until the flushing is manually interrupted.
During disinfection and cleaning: Alarm will be issued after termination of the rinse cycle.
During rinse circulation: No alarm will be issued.
During stand by flush: The pure water will be diverted to drain, independent of WRO setting.

Corrective action:
1. Check that the inlet water conductivity is normal (is displayed under MAIN MENU). If not,
check the function of the softeners and, if necessary, perform an extra rinse.
Also check the inlet conductivity with a conductivity reference meter.
2. Calibrate the inlet conductivity according to section 5.
3. Remove the rubber cap on the conductivity cell (35) and remove humidity that may be present.
4. If the rinse times are too short, the conductivity will continue to decrease during flushing until
the conductivity is below the alarm limit.
5. Perform cleaning according to section 5 in this manual. If the cleaning procedure does not
result in sufficient improvement, continue with 6. and 7.
6. Disassemble the membrane modules and change the internal o-rings. Refer to spare parts.
7. Replace the conductivity transmitter CX2, spare part no 25-11029.
8. Contact Gambro if the problem cannot be resolved.

HCEN9315 Rev. 10. 00


3:13
7. Motorprotect WRO
Reason:
This alarm is issued in the following two situations with a delay time of 10 seconds:

1: You have tried to use the fast stepping function without first selecting it under Technician
info level 2.
2: The motor protector F1 for the main pump 33 has released.

Possible causes:
2a: Incorrect setting of the motor protector
2b:The main pump is consuming too much current on any of the phases
2c: The pump operates with only two of the three phases connected

CWP action:
Input X7 on the PLC lights up and the unit stops.

Corrective action:
1: Reset the alarm and then select fast stepping. When selected, an arrow appears in the top
right corner of the display. Deactivate after use (resets itself after 30 minutes).

2a. The motor protector (thermal relay F1 in the electrical diagrams) is placed in the electrical
control cabinet of the CWP. Check that the setting of the motor protector correspond to the motor
sign of the main pump (attached to the outside of the pump).
Reset the motor protector before restarting the unit.

2b, c. Trouble shooting of three-phase pumps


- Reset the motor protector.
- Measure the current on all three phases. The difference between the phases should be
maximum 10 %.
- If the current does not differ but is higher on all three phases than what is stated on the
mark sign of the motor, this indicates problems with the pump, i.e. it is working harder than it
should.
- If the current consumption on the three phases differs, check that all the electrical phases are
correctly connected. Measure the voltages between terminals L1, L2 and L3 to check that the
incoming voltage is correct. If this is the case, disconnect the cable to the motor and measure the
voltage between all three phases when the contactor is on. (The reason for disconnecting the
motor is that if it is connected, you will have voltage on all three phases even if you feed the
motor with only one phase, as the windings in the motor will induce voltage on the other two.)
- If you have correct voltage supplied to the motor and the current between the phases differs,
you probably have some electrical problems with the motor. Then do the following:
- Check that there is no damage to the motor cable.
- Measure the windings in the motor. The resistance (measured with a DC-instrument) between
two wires in the motor cable should not differ more than maximum 10% between the windings.
Normal value for a SP2A-pump is 10 - 20 Ω.
- Measure the insulation between each phase connection and earth with an insulation tester.
It must exceed 1 M Ω.

Note: The fast stepping function and motor protector alarm is connected to the same PLC input
(X7), fast stepping will automatically occur in case of a motor protector alarm if fast stepping has
been selected. A loop test will therefore be required in these situations.

3:14 HCEN9315 Rev. 10. 00


8. Low flow F6
Reason:
The pure water flow rate during rinse is supervised by a magnetic, pulse-giving impeller flow
meter (121) to insure sufficient rinse of the WRO and the loop. The WRO will stop and issue this
alarm if the flow rate is less than the set alarm limit for more than two consecutive minutes.
The alarm limit varies depending of model size and is set under Technician info level 2, refer to
23. on page 5:6. The following alarm limits are recommended:

WRO 111: 3 l/min


WRO 112: 6 l/min
WRO 113: 9 l/min
WRO 114: 9 l/min

Possible causes:
1. Flow control 122 on the pure water flush line is blocked by foreign material.
2. Any of the solenoid valves 36, 48, 54, 106 or 136 does not open properly.
3. The flow meter probe 121 is not functioning properly.
4. The flow transmitter FX1 in the electrical control box is not functioning properly.

WRO action:
The WRO will stop and issue this alarm. The WRO can be restarted after reset of the alarm.
It will stop again after two minutes if the flow rate still is below the alarm limit.

Corrective action:
Reset the alarm and restart the system in rinse mode. The function diagrams in section 6 gives
information about the function of the different components in the different rinse modes.

1. Check the Pure water flow rate on the display (MAIN MENU) and compare with the set
alarm limit. Also make a visual check in the flush funnel at the right hand side of the WRO.
2. Check the flow control (122) on the drain line for any obstructions.
3. Check input LED X0 on the PLC (should be flashing).
4. If the display shows 0 l/min and there is no pure water rinse flow to drain in the funnel, check
solenoid valves 36, 48, 54, 106 or 136 and their respective LED output on the PLC.
5. Check the function of the flow transmitter FX2 by measuring there is:
- 12 V DC between terminals 5 and 6
- 24 V DC between terminals 3 and 4
- a pulse signal between terminals 6 and 7
- a pulse signal between terminals 2 and 3
6. If there is no pulse signal between 6 and 7, check the flow meter probe 121.
7. If input X0 is flashing and the display shows 0 l/min, the PLC is probably faulty.
8. Both the flow transmitters (FX1, FX2 and FX3) and the flow meter probes (42, 121 and 51) are
identical and may be switched to check the function.
9. Contact Gambro if the fault cannot be rectified.

HCEN9315 Rev. 10. 00


3:15
9. Low level chem
Reason:
The level switch (47) in the Dialox container indicates low level of Dialox.

Possible causes:
- The level in the container is below the level switch.
- Faulty level switch.

WRO action:
At initiation of any disinfection programme:
Disinfection cannot be initiated until the empty container has been replaced with a new container
with sufficient amount of disinfectant.
During loop disinfection:
1. The dosing pump(s) and main pump will stop. As a consequence, all dialysis machines that
have not finished their intake phase will issue alarm for insufficient water supply.
2. WRO time counting will freeze .
3. If the STOP button is pressed (within 30 minutes) the disinfection programme will be put
on hold until further action is taken.
4. If no action is taken, the disinfection programme will start after 30 minutes from where it
was before the alarm occurred. All pumps will, however, remain switched off during the
remaining time of the intake period.
During disinfection of WRO:
Alarm will be issued but the disinfection programme will continue. The dosing pump(s) will,
however, remain switched off.
After disinfection: The alarm can be reset after disinfection. It will, however, reoccur if a disin-
fection cycle is to be initiated without exchanging the empty container with a filled one.

Corrective action:
1. If the container is empty: Immediately replace the empty Dialox container with a filled
one. The alarm is rectified and the programme is manually restarted by pressing DISINF LOOP.

2. If this alarm is issued and the container still contains Dialox: Check the level switch.
Replace it if faulty.

Caution: Always make sure that there is sufficient amount of Dialox when initiating disinfection.

3:16 HCEN9315 Rev. 10. 00


10. Leakage
Reason:
The level switch 62 indicates that water has collected on the tray beneath the WRO.

Possible causes:
- Internal leakage in the WRO which has caused the water level on the tray to rise above the
level switch.
- Faulty level switch.

WRO action:
The CWP stops and the inlet solenoid valve 1 closes to avoid flooding.

Corrective action:
Check for leaks. If the leak is small the level sensor 62 can be temporarily lifted so that the alarm
goes out. The water that leaks out will be diverted to drain via the overflow drain connection from
the tray. The fault can then be corrected when no dialysis takes place.
For larger leaks that can not be corrected within reasonable time, discontinue operation. If
dialysis has to be continued, bypass the system.

HCEN9315 Rev. 10. 00


3:17
17. Low flow F2
Reason:
A certain flow to drain must be maintained whenever the CWP is in operation to avoid fouling of
the membranes. Therefore, if the reject flow (measured by a magnetic, pulse-giving impeller flow
meter 42) goes below a certain set minimum value for a certain time, this alarm is issued.
During normal operation: If the flow goes below 0,2 l/min for more than four consecutive
minutes, MV138 opens fully to drain. If the flow still remains below 0,2 l/min for another 2
minutes, alarm no 17 will be issued and the machine will stop after additional 10 minutes.
During disinfection: Alarm no 17 will be issued if the flow rate goes below set alarm limit
(Tech. info level 2) for more than two consecutive minutes.

Possible causes:
1. The needle valve 41 on the reject line is incorrectly adjusted or blocked by some debris.
2. The motor valve MV138 is not functioning properly.
3. The inlet flow measuring circuit is not functioning properly.

CWP action:
The WRO can be restarted after reset of the alarm. It will stop again after two minutes if the flow
rate still is below the alarm limit.
The flow alarm function may be deactivated to enable operation and to simplify trouble shooting,
refer to 8. on page 5:4. Do not, however, forget to activate the alarm after correction of the fault.

Caution: Operation with insufficient reject flow for longer periods will damage the reverse
osmosis membranes!

Corrective action:
Reset the alarm and restart the unit.
1. Select CWP INFO. Check that the RO reject flow rate is correctly set (refer to page 4:12).
Adjust with valve 41.
2. If the display shows 0 l/min in reject flow rate, visually check in the drainage receptacle
during operation that there is a flow. If not, check the function of motor valve 138 by opening it
and closing it, refer to WS- control under Technical info level 2 for more information.
The motor valve can also be manually operated with an Allen (hexagon) key by removing the
black cylindrical cover on the motor valve. If required exchanged the motor valve.
3. Checking the reject flow measuring circuit:
Input X14 on the PLC should flash when the CWP is running.
If input X14 is not flashing:
Check the function of the flow transmitter FX2 by measuring that there is:
- 12 V DC between terminals 5 and 6
- minimum 20 V DC between terminals 3 and 4
- a pulse signal between terminals 6 and 7 (from flow sensor)
- a pulse signal between terminals 2 and 3 (to PLC)
If there is no pulse signal between 6 and 7, check the flow meter sensor 42 including electrical
connections.
If input X0 is flashing and the display shows 0 l/min:
- Check that there is minimum 20 Volt on the 24 V terminal on the PLC. If the voltage is lower
investigate the reason.
- If the voltage is ok, the PLC is probably faulty.
All flow transmitters FX and the flow meter probes 42 and 51 are identical. They may
therefore be switched to check the function.

3:18 HCEN9315 Rev. 10. 00


19. Loop leakage
Reason:
During rinse loop and stand-by operation, the pure water flow (121) and return flow (51) are
measured. This alarm is issued if comparisation between these two values differ more than set
alarm limit.

Possible causes:
1. A leak has occured in the distribution system.
2. Flow meter (51) in the return line and/or flow meter (121) on the pure water side is malfunc-
tioning.
3. Too narrow setting of the leakage alarm limit.
4. Consumption in the clinic.

WRO action:
The WRO will stop when this alarm is issued, can be restarted when the cause of the alarm has
been rectified.

Corrective action:
1. Check for leaks in the distribution system
2. Check functionality of flow meter 51 and 121, replace if faulty.
3. Check alarm limit setting (Leak, Tech.info.level 2).
4. Check if there is any consumption on the loop, e.g dialysis machine in rinse mode.

HCEN9315 Rev. 10. 00


3:19
21. Cond. rinse. H C4
Reason:
The conductivity in the return line from the clinic is measured by conductivity cell 144 during
rinse of loop. This alarm is issued if the conductivity is higher than set alarm limit during the last
two minutes of the rinse of the loop (WRO + Loop).

Possible causes:
- Incomplete rinse-out of disinfectant from the loop.
- Error in the conductivity measurement system.
- Incorrect calibration of the conductivity reading.
- Malfunctioning relay K28

WRO action:
The WRO will continue until started program is completed. The alarm will remain to inform the
operator.

Corrective action:
1. Acknowledge the alarm and follow normal routines for test after loop disinfection.
2. Check the function of conductivity cell 144, using an external reference instrument, refer to
Alarm no 22.
3. Check that the LED on relay K28 lights up when alternating between cond. in and cond. ret.
on the display.

3:20 HCEN9315 Rev. 10. 00


22. Cond. test. C4
Reason:
Dynamic test of the conductivity cell (144) in the return line from the clinic. During the first
minute of disinfection intake of the loop disinfection programme, the conductivity must be below
set limit. If not, this alarm will be issued.

Possible causes:
- The pure water conductivity in the return line is for some reason elevated.
- Malfunctioning conductivity transmitter CX1
- Malfunctioning conductivity cell 144
- Too narrow setting of alarm limit
- Faulty relay K28

WRO action:
The WRO will continue in operation, but the alarm will remain to inform the operator.

Corrective action:
1. Measure the conductivity from the last tap on the loop with an external reference instrument.
2. Check the conductivity transmitter CX1 by measuring there is:
- minimum 20 V between terminals 3 and 4
- connect a restistance of 1kΩ between terminals 7 and 8. The display should then read about
400 µS/cm (provided that the calibration factor is set at 100%, refer to Conductivity calibra-
tion in Service and maintenance.
3. Check the functionality of conductivity cell 144 in the return line.
4. Check the function of relay K28 by alternating between cond. in and cond. ret on the display.
When alternating, check that the LED on the relay lights up when cond. ret. is selected.

HCEN9315 Rev. 10. 00


3:21
23. Cond. intake. lo C2
Reason:
The pure water conductivity is continiously monitored during disinfection of the loop. This alarm is
issued if set alarm limit, based on conductivity, not is exceeded during the first period of the intake
phase of chemical disinfectant. This to verify that chemical disinfectant is present in the entire WRO.

Possible causes:
- Malfunctioning conductivity cell 35.
- Malfunctioning transmitter CX2.
- Malfunctioning dosing pump.

WRO action:
The WRO will continue until disinfection is completed, but the alarm will remain to inform the
operator.

Corrective action:
1. Check the functionality of the conductivity cell 35, using an external reference conductivity
meter.
2. Check if there is fluid present inside the conductivity cell (leakage along the pins).
3. Check the functionality of the conductivity transmitter CX2.
4. Check that the dosing pump is working properly.

3:22 HCEN9315 Rev. 10. 00


24. Cond. intake. lo C4
Reason:
The conductivity in the return line is continiously monitored during disinfection of the loop. This
alarm is issued if set alarm limit, based on conductivity, not is exceeded during the first period of the
intake phase of chemical disinfectant. This to verify that chemical disinfectant is present in the
entire distribution system.

Possible causes:
- Malfunctioning conductivity cell 144.
- Malfunctioning transmitter CX1.
- Malfunctioning dosing pump.
- Faulty relay K28.

WRO action:
The WRO will continue until disinfection is completed, but the alarm will remain to inform the
operator.

Corrective action:
1. Check the functionality of the conductivity cell 144, using an external reference conductivity
meter.
2. Check if there is fluid present inside the conductivity cell (leakage along the pins).
3. Check the functionality of the conductivity transmitter CX1. Refer to Electrical diagrams.
4. Check that the dosing pump is working properly.
5. Check the function of relay K28 by alternating between cond. in and cond. ret on the display.
When alternating, check that the LED on the relay lights up when cond. ret. is selected.

HCEN9315 Rev. 10. 00


3:23
25. Operat.indicat.
Reason:
In order to insure that the (optional) external operation indication lamp is not lit in other occasions
than when the WRO really is in operation, the operation signal is supervised by a relay (K21) and
an answer signal to the PLC. If the signal status does not correspond to that of the PLC-programme,
this alarm is issued and the WRO will stopped. Refer to section 6,Electrical diagrams.

Possible causes:
- Relay K21 is not functioning properly
- Poor connection between the PLC and relay K21
- Input X10 or output Y11 on the PLC is not functioning properly

WRO action:
The WRO will stop and cannot be operated until the problem has been rectified.

Corrective action:
1. Check relay K21.
2. Check the connections between relay K21 and the PLC.
3. Check the function of the PLC.

3:24 HCEN9315 Rev. 10. 00


26. Remote control
Reason:
This alarm is issued if there is an error in the remote key system (optional) to the CWP 100. Refer
to Electrical diagrams for more information.

Possible causes:
The PLC registers no signal or signal on more than one input connected to the remote key
switch. Remote key is in incorrect position. When the WRO is in Local mode, i.e. operated from
the operator´s panel, the remote key must be positioned at 0.

WRO action:
The WRO will stop and the remote control option cannot be used.

Corrective action:
1. Turn the remote key to position 0.
2. Acknowledge the alarm. If this cannot be done, check the electrical connections.
3. Go to Technician info level 2 and deactivate the remote control option if possible (see section 5).

27. Low battery PLC


Reason:
Insufficient voltage from the battery in the PLC.

Possible causes:
The battery voltage in the PLC battery has dropped below 3,0 Volt.

WRO action:
The WRO will issue this alarm at start up. The alarm can be reset but will occur again at the next
start up of the WRO.
If the battery is not changed within approx. one month, the operation of the WRO will be blocked.

Corrective action:
Exchange the battery according to the procedure on page 5:18.

HCEN9315 Rev. 10. 00


3:25
28.Disinf. time
Reason:
This alarm will be issued when there is a time deviation in loop disinfection programme that
may result in insufficient rinse of the dialysis machines.

Possible causes:
A: The loop disinfection procedure has been initiated so late that the time channel "Rinse circu-
lation" is entered before the rinse phase "final rinse WRO" has gone to completion.
B. The set maximum delay time (see below) of the disinfection program has been exceeded.

The delay may be caused by:


- Water supply or power interruptions.
- Manual interruptions of the disinfection cycle.
- Manual restart of the disinfection intake period.

The max. delay time is set under Tec. info level 2 (Max. time delay). Preset: 15 minutes.

WRO action:
A: The WRO will issue the alarm when the preset Rinse circulation period should have been
entered. The disinfection procedure will, however, be finished according to the program.
The WRO will then enter the remaining part of the preset Rinse circulation period.
B: The alarm will be issued but the disinfection procedure will continue according to the program

Corrective action:
1. Reset the alarm.
2. Perform the normal tests after disinfection of the WRO and the loop.
3. Perform an extra rinse procedure of the dialysis machines.
4. After rinse: Perform a test for residual disinfectants on all dialysis machines according to
normal routines.

3:26 HCEN9315 Rev. 10. 00


30.WS control
Reason:
The regulation of the reject flow rate is unstable and has not managed to find a stable condition
after one hour.

Possible causes:
1. Incorrect setting of the needle valve 41 on the reject line.
2. Error in the reject flow measuring system.
3. Malfunction of motor valve 138.
4. Incorrect parameter setting for the motor valve 138.
5. Error in the PLC or control relay.

WRO action:
If the reject flow has been below set minimum limit for more than 4 minutes, the motor valve will
get a signal to open fully to drain. Then the following can happen:

A: If the flow despite this does not exceed the warning limit within 2 minutes, flow alarm 17 will
be issued and the CWP will stop.
B: If the flow still is ok after 10 minutes the regulation system of the motor valve is activated
again. If scenario B is repeated 4 times, alarm 30 is issued.

Corrective action:
Go to MAIN MENU and switch off the water saving system by selecting MAN. The motor valve
will then open fully to drain, provided that the PLC and the control relay is functioning properly.
If the valve does not open when MAN is selected, it can be opened manually with an Allen (hexa-
gon) key. The screw is positioned behind the black rubber cap on side of the motor valve.
Then check if the drain flow is correct and adjust if necessary with needle valve 41.

Contact Gambro.

HCEN9315 Rev. 10. 00


3:27
31. Cond. test. C2
Reason:
When a reverse osmosis unit is left standing for some time, dissolved salts will
migrate through the membrane and thus gradually increase the salt concentration on the pure
water side. At next start up, these salts will cause a momentary increase in the pure water
conductivity at start up.
This fact is used to check that the conductivity measurement system is responding.
In order to pass this test, the conductivity has to exceed the limit set at Test at some time during
the start up phase (provided that the CWP has been stopped for more than 10 minutes).
Otherwise alarm no 31. Cond. test. C2 will be issued the moment the RO unit switches to
operation.

Possible causes:
1. Incorrect setting of alarm limit. (Test, Technician info level 2)
1. Malfunctioning conductivity cell 35.
2. Malfunctioning conductivity transmitter.
3. Faulty relay K28

WRO action:
The WRO will continue in operation, but the alarm will remain to inform the operator.

Corrective action:
1. Check Test setting under Technician info level 2.
1. Check the functionality of conductivity cell 35 in pure water outlet, using an external conduc-
tivity reference meter, replace if faulty.
2. Check the function of the transmitter, refer to electrical diagrams.
3. Check the function of relay K28 by alternating between cond. in and cond. ret on the dis-
play. When alternating, check that the LED on the relay lights up when cond. ret. is selected.

3:28 HCEN9315 Rev. 10. 00


Internal alarms in the MAC terminal
You can also get error messages issued directly on the MAC operator´s terminal. These messages
appear in the upper left corner of the display and have no number. They inform about internal errors
in the MAC terminal and in the communication between the MAC and the PLC.

Comm Error
Reason
The communication with the PLC has failed.

Possible causes
1. Interruption in the cable between the MAC and the PLC.
2. Malfunction in the PLC.
3. Error in the communication port in the MAC or PLC.

CWP action
If the problem is in the MAC, in the cable or in the communication ports, the CWP will continue in
operation. All safety functions are controlled by the PLC. You can, however, probably not get any
information about the operation or operate the CWP from the MAC terminal.

Corrective action
1. Check the communication cable between the MAC and the PLC, including the connections.

2. Check that the PLC is functioning. Normal indication of the LED´s on the PLC is:

POWER ON
RUN ON
Batt.V OFF
PROG.E/CPU.EOFF

3. Try to switch off the power supply to the CWP and then switch it on again. If the communication
error message remains, you probably have to replace either the MAC or the PLC.

Note: If you need to stop the CWP and the STOP button does not work you have to switch off the
switch for the power supply on the wall.

HCEN9315 Rev. 10. 00


3:29
SYSTEM ERROR
Reason
An error has occurred in the MAC terminal which makes it impossible for it to function correctly.

Possible cause
Read the additional information that is shown under the text SYSTEM ERROR on the display.

CWP action
If the problem is in the MAC terminal, the cable or in the communication ports, the CWP will
continue in operation. All safety functions are controlled by the PLC. You can, however, probably
not get any information about the operation or operate the CWP from the MAC terminal.

Corrective action
1. Note down the additional text on the display.
2. Check the communication cable between the MAC and the PLC, including the connections.
3. Check that the PLC is functioning. Normal indication of the LED´s on the PLC is:

POWER ON
RUN ON
Batt.V OFF
PROG.E/CPU.E OFF

4. Press ENTER
5. Try to switch off the power supply to the CWP and then switch it on again. If the system error
message remains, you probably have to replace either the MAC or the PLC.

Note: If you need to stop the CWP and the STOP button does not work you have to switch off
the switch for the power supply on the wall.

Batt. Low
Reason
Low battery voltage in the MAC terminal.

Possible cause
The battery has not been changed within the specified time range. Life expectancy is 5 years.

CWP action
1. In the beginning the alarm does not effect the function of the CWP.
2. If the battery is not changed within approximately one month you may lose the memory content
next time the power to the CWP is interrupted. The CWP can not be restarted again until you
reload the program in the MAC terminal.

Corrective action
Exchange the battery according to the procedure in the Service and Maintenance section of this
manual.

3:30 HCEN9315 Rev. 10. 00


4. Installation and start up
Caution: This section is intended for trained technicians only

Contents

Installation ................................................................................2
1.1 General ..........................................................................2
1.2 Piping connections ........................................................2
1.3 Electrical installation .................................................... 3
1.4 Electrical connections ...................................................3
1.4.1 Separate control voltage .............................................3
1.5 Connection of external signals ......................................4
1.5.1 Start of booster pump ................................................. 4
1.5.2 Extrenal alarm ...........................................................4
1.5.3 Extrenal blocking of operation ...................................4
1.5.4 External lamp indication unit and buzzer .................4
1.5.5 Connection of remote control unit ............................ 4

Start up after installation .........................................................5


Rinsing out the preservation solution .................................5
Checking the electrical phase sequence ..............................5
Test for residual formaldehyde ............................................5
Flushing the distribution system .........................................5

Settings at installation ..............................................................6


Delivery settings ..................................................................6
Settings at installation .........................................................6
Operation settings ................................................................ 6
Disinfection of WRO - setting of parameters .......................6
Disinfection of loop - setting of parameters ........................7
Initial setting of dosing pump .............................................. 7
Setting of disinfectant intake ...............................................7
Integration of WRO in the disinfection ............................... 8
Integration of dialysis machine in the disinfection ............. 8
Example ................................................................................9
Setting of contact time .........................................................9
Setting of rinse .....................................................................9

Setting table ............................................................................ 10

Table for setting of time channels and autorinse .............. 11

HCEN9315 Rev. 10. 00 4:1


1. Installation
Caution: The person starting up the CWP 100 The drain lines must be installed without any
must be trained and well informed about the incline to a floor drain close to the unit (Fig.1).
function of this machine and how to use the Also, air gaps must be arranged to avoid micro-
operator´s panel. bial contamination from the drainage system.

1.1. General
1.2. Piping connections
The hydraulic installation must be made in
accordance with Technical data, fig 1 , 2 and The piping connections on the right side of the
the valid process flow sheet. Pipe and valve CWP 100 is shown in fig. 2:
material shall always be stainless steel or plastic Inlet: PVC female, fits to pipe OD 25 mm
and resist a pressure of 10 bar. Drain: PVC female union, fits to pipe OD 32 mm
Drain from tray: 1/2" female thread
When placing the CWP 100, allow 500 mm on Pure water outlet & return: PVC female
the right hand side and 400 mm behind the union, fits to pipe OD 25mm
system to simplify service work in the future.

The feed water must be properly pretreated by


carbon filtration and softening, followed by 5 µm
filtration.

isolation switch
RO unit

Back
of
WRO

pure water
outlet


 !
"

pure water
return
%+&

#+&
inlet
,-./!0" 1"

/!0" *+&
*%&

)&

drain from #$
drain from tray
%&
'%&
RO -unit ((&

Fig. 1. Installation Fig. 2. Piping connections (mm)

HCEN9315 Rev. 10. 00


4:2
Distribution system 1.4.1. Separate control voltage

Caution: The loop must be designed as a direct At delivery, the control voltage is taken from the
feed system with no intermediate pure water main supply according to fig. 4:
tank. Also, special emphasis must be put on
Main Power supply
avoiding dead ends and stagnant zones that
would prolong the required rinse time. X1 L1 L2 L3 N

X1.1
1.3 Electrical installation
X1.2 Control
voltage
The electrical supply must be installed three
phase and fused according to Technical data
and local regulations.
Refer to fig. 3 and Electrical diagrams in Fig 4. Control voltage - delivery connection
section 6 for more information.
The CWP can, however, also be connected to a
Isolation separate control voltage. To do this, remove the
switch links, shown in fig. 4, between:

X1.
X1.L1 and X1.1
X1.N and X1.2
L1 L1
L2 L2 Power Then connect the external control voltage supply
L3 L3 supply according to fig. 5 and fig. 6, i.e:.
N N

L to X1.1, and
N to X1.2

Fig 3. Main power supply


External control
The supply must have an lockable isolation Main Power supply voltage supply
switch according to IEC947-3 and IEC204-01 or
X1 L1 L2 L3 N L N
local regulations, mounted on the wall close to
the system (fig.1).
Isolating
switch
Note: Ensure that the electrical phase sequence
is correct, refer to Start up after installation
X1.1 Control
following this section. Incorrect sequence
X1.2 voltage
results in insufficient pure water flow.
Fig. 5. External control voltage supply.
1.4. Electrical connections
Connect external
The mains power supply is connected to the CWP X1 control voltage here
through cable glands on the right hand side of
the electrical control cabinet (fig 1).
L N
N1
F11
L1
L2
L3

1 2
N

Remove links before


you connect external
voltage

Fig. 6. Connection of external voltage supply.

HCEN9315 Rev. 10. 00 4:3


1.5. Connection of external signals 1 2
5 3 4
External signals can be connected to the 1 5 2
interface relays in the upper right corner inside 3 4
the CWP electrical control cabinet. (fig 7).
Max rating for the contacts: Fig.8. 1 pol. interface relay
5A, 250V resistive load
2A, 250V inductive load 5 7 6
1
8
4 2 3

1 5 2 7
X4
4 3 5 6

K11
K12 Fig.9. 2 pol. interface relay
K13
K14 4 3 5
K15 2 1

K21
3
5 1
K22 4
2 External contact
K23
K24 X4.1
K27
Fig. 10. External blocking of operation.

Fig. 7. Interface relays.

1.5.4. Connection of external lamp


indication unit and buzzer
1.5.1. Start of booster pump
The external lamp indicaton unit gives
Connect to relay K27 (fig. 9), terminal 6 and 5 operational status information about the CWP
Relay is activated when the unit need water 100 and should therefore be placed at a visible
supply. place in the clinic, together with the buzzer unit.
The lamp indication unit is connected to relays
1.5.2. External alarm K21 - K24 according to the information on page
E1308 in the Electrical diagrams and fig. 8 and
Connect to relay K22 (fig. 8), terminals 3 & 4 or fig. 9.
terminals 3 & 2.
The relay K22 is activated during normal 1.5.5. Connection of remote control unit
conditions. It is deactivated in case of an A-
alarm or loss of power. The CWP 100 can be fitted with an optional
remote control device, consisting of a key
The relay contact is open between terminals 3 selector box (refer to General description).
and 4 and closed between terminals 3 and 2 This box should be installed at a suitable location
when an A-alarm is issued. in the clinic, such as in the head nurses office.
The remote control unit is connected to relays
1.5.3. External blocking of operation K12 - K15 according to the information on page
E1307 in the Electrical diagrams.
Connect an external switch to terminal X4.1 and
terminal 5 on relay K11 ( fig.10). Note: The remote control option also requires
Start of operation is blocked if an external switch the external lamp indication unit and buzzer
is closed between these terminals. which is described above.

HCEN9315 Rev. 10. 00


4:4
Start up after installation
Rinsing out the preservation solution Checking the electrical phase sequence

Caution: At delivery the system is filled with a Note: If the electrical phases are not correctly
combined preservation and anti-freeze solution, mounted, the pump will rotate in the reverse
containing 1% formaldehyde and 20% glycerine. direction, resulting in low pressure and insuffi-
This solution must be thoroughly rinsed out cient product water flow.
before the system is put into normal operation.
Check that no residual formaldehyde can be 4. To check the electrical phase sequence, check
detected before connecting patients. that the reject flow rate during rinse
corresponds to what is stated on page 5:14. If
At delivery, the WRO Chem is in pause mode considerably lower, stop the unit, switch off
in the cleaning programme, refer to function the isolation switch and change two of the
diagram for Cleaning of WRO (section 6). phases. Then restart and check again.

Initiation of rinse: Test for residual formaldehyde


1. Open the inlet water valve and turn on the 5. Collect a water sample in the funnel on the
electrical isolation switch for the RO unit. right hand side of the WRO and, using a test
The display will within 10 seconds show: kit for residual formaldehyde, verify that
there is no formaldehyde present.

CLEANING WRO XX MIN 6. Follow the operating instructions on page 2:3


to finish disinfection.
Press DIS WRO

Flushing the distribution system


2. Press DISINF WRO.
7. Disconnect the return line from the dialysis
3. The system will start after a one minute unit from the WRO and divert it to drain.
delay (to allow fill-up of the inlet tank) and
perform a complete internal rinse cycle which 8. Start the WRO by pressing START.
will last 100 minutes (preset at delivery).
9. Flush the distribution system for 1 - 2 hours.
During the flushing, check for leaks at all
connections in the loop.

10. Stop the WRO by pressing STOP and then


reconnect the return line to the WRO.

11. Restart the WRO and check for leaks once


more. Also check the pressure in the distribu-
tion system.
The pressure should be approx. 3 bar at the
outlet from the WRO when no consumption
takes place. Adjust if required with overflow
valve 52 (refer to fig. 3 and 5 in section 1).
At nominal capacity the pressure should be
minimum 1,5 bar at the last tap.

12. Put a container of Dialox on the tray in the


WRO and insert the pick up tube and level
switch into the container. Adapt the plug so
it fits into the hole in the container.

HCEN9315 Rev. 10. 00 4:5


Settings at installation
Delivery settings Disinfection of the WRO -
setting of parameters
Caution: First study this manual in detail before
attempting to change any of the set values in the Refer to page 5:11 and Function diagram for
program. disinfection of WRO in section 6.
The WRO is programmed at delivery according to The presets for disinfection of WRO has been
what is stated in the setting table on page 4:10. programmed from factory and does normally not
need to be changed, unless the setting of the
Also refer to section 5, Technical information
dosing pump is altered. Check that the
and the function diagrams in section 6.
consumption of Dialox for disinfection of the
WRO alone corresponds to the values in table 1.
The values marked * on page 4:10 are program-
med as follows: Fig. 11 shows the capacity of the dosing pump as
Reject and Pure water are set according to size a function of the outlet pure water pressure from
of the WRO. Refer to 22. and 23. on page 5:6. the CWP pressure.

CALIBRATION COND: The inlet and pure


water conductivities are calibrated at delivery
and the valid values are stored in the program. size: WRO111 WRO112 WRO113 WRO114
Refer to section 5 for more information about
conductivity calibration. Dialox 0,6 l 0,75 l 0,9 l 1,1 l

Settings at installation Table 1. Required amounts of Dialox


when performing disinfection of WRO alone
Certain values have to be set in the WRO to
enable safe and optimal operation for the
individual dialysis unit.
The function diagrams in section 6 for the
different modes of operation shows all the
presetteable values.
HI JHJ0"

Operation settings
*' '$$
Refer to pos. 30 - 34 on page 5:7 and to function
diagram for operation in section 6!
+
These set values does normally not need to be
changed at installation. *$$

$ * ' ( ) K!

Fig. 11. Capacity of the dosing pump as a


function of the outlet pressure from the CWP.

HCEN9315 Rev. 10. 00


4:6
Disinfection of the loop -
Setting of parameters Setting of disinfectant intake

The loop disinfection program must be adapted 1. Select detailed display by keeping STATUS
for the specific dialysis unit. Below you will find pressed for 5 seconds.
a step-by-step instruction to determine the
required total injection time for Dialox. Please 2. Initiate the loop disinfection programme.
also read the example that follows after the (DISINF LOOP).
instruction.
Refer to the function diagram in section 6 and Note: Record the starting time!
fig. 11 - fig. 14 on pages 1:18 - 1:20!
The display will show DISINF. INTAKE. The
Initial setting of dosing pump dosing pump will first start and 40 seconds
later the main pump will start and feed the
In order to obtain optimum concentration of disinfection solution into the loop. The return
Dialox in the disinfection solution, the outlet flow from the loop will go to drain via the
pure water flow is reduced during the funnel on the right side of the WRO. The
disinfectant intake phase. The outlet pressure injection phase is set to 10 minutes at delivery.
from the WRO then also will drop. The
approximate outlet flow rates for the different 3. Recording fill-up time for the loop:
model sizes during disinf intake are shown in Use peroxide test strips in the funnel to
table 2 below. determine when disinfection solution can be
detected in the return line. This time is the
Table 2 is used as a guideline for the initial required time to fill the loop with disinfection
setting of the dosing pump to obtain a dilution solution. Record this time.
ratio of 1:30 - 1:40, provided that the output of
the WRO during disinfectant intake (Pure water 4. Checking the output from the WRO
under MAIN MENU) is in accordance with the during the intake phase:
table and that the counter pressure in the loop Press MAIN MENU and record the pure
during the intake phase does not exceed 2,5 water output from the display. Compare to the
bar. table below.
Fig. 11 shows the capacity of the dosing pump as
a function of the outlet pressure in the loop. Disinfection of only the loop
Caution: The dosing pump may provide insuffi- 5a. Add 1 - 2 minutes to the time that you
cient capacity if the pressure in the pure water recorded at step 3. above. Then set this time
outlet exceeds 2,5 bar during intake of Dialox. at Return from loop to drain in the
setting menu, refer to Block Diagram for
Technician and Function Diagram for
Loop Disinfection in section 6!

5b. Set Return from loop to WRO to 0 min.

RO -unit Dosing pump


Model size Hole diam. in Appr. output No of Setting Output at 2,5 bar
valve 136 (mm) at 10 °C (l/min) pumps % (ml/min)

WRO111 2,5 4 1 50 80 - 90

WRO112 2,5 7 1 100 160 - 180

WRO113 3,0 10 2 75 240 - 270

WRO114 3,0 12 2 100 320 - 360

Table 2.
HCEN9315 Rev. 10. 00 4:7
Integration of WRO in the disinfection

6a. Set Return loop to drain to the minimum 7b. Divide the total fill volume you have
value (1 minute). obtained at 7a. with the nominal output of
the WRO during the intake phase (refer to
6b. Add the fill-up time for the loop that you 4.). This will give you the additional time
recorded under 3. above to the fill-up time that is required to fill up the dialysis
for the WRO according to table 3: machines.

Size fill-up time 7c. Add this time to the time that you have set
at step 6c.
WRO111 8 minutes
WRO112 6 minutes 8. Estimation of required time for filling
WRO113 5 minutes up the dialysis machines:
WRO114 4 minutes Summarize the time for each dialysis
machine according to table 4.
Table 3. Required fill time for the WRO
during loop disinfection. Caution: The total time for injection of Dialox
must not be lower than the required time to
6c. Set the sum that you thereby obtain at complete the fill phase on all dialysis machines.
Return loop to WRO in the setting menu.

Integration of Gambro dialysis machines


in the disinfection

7a. Calculate the approximate total fill volume


of the dialysis machines. This is done by
multiplying the fill volume with the number
of machines for each type according to table 4.

Machine fill-up volume fill-up time

AK 90 0,85 litres 7- 8 minutes


AK 95 1,35 litres* 7- 8 minutes
AK 100 2 litres 3 minutes
AK 100 Ultra 2,8-3 litres 7- 8 minutes
AK 200 2,8-3 litres 3 minutes
AK 200 Ultra 2,8-3 litres 7- 8 minutes

* UFD kit included

Table 4. Required fill-up volume and fill-up


time for Gambro´s different dialysis machines.

HCEN9315 Rev. 10. 00


4:8
Example Setting of rinse

9a. A dialysis unit that is equipped with six Caution: Verify with peroxide test strips during
AK100 and four AK90 dialysis machines. the rinse procedures below that set times are
The WRO is a WRO112. sufficient to obtain complete rinse of the piping
system and WRO.
9b. The required time to fill the loop according
to step 3. above was 3 minutes. "Total time"

9c. The WRO will be included in the procedure.


Add 6 minutes according to 6.

9d. The total fill volume for the AK100 dialysis


machines will be 12 liters and for the AK90´s "Rinse WRO+loop" "Rinse monitors"
12 liters. Total fill-up volume is then 24 "Final Rinse WRO"
liters. If the installed WRO has an output of
7 liters/minute during disinf. intake, the Fig. 8. Rinse sequence for the WRO, loop and
extra running time required to fill up the dialysis monitors type AK 90.
machines will be 24:7 ³ 4 minutes .
Refer to fig. 8 above and to pages 1:16 - 1:19!
9e. The total required time will be:
3 + 6 + 4 minutes = 13 minutes

9f. Enter this time into DISINF LOOP;


DISINF INTAKE; Return from loop to
WRO.

9g. Set Return from loop to drain to 1 min-


ute.

Setting of Contact time

Extended contact time may be desired for opti-


mum disinfection of the distribution system. The
contact time can therefore be extended up to
9999 minutes. The membranes in the WRO
does. however, not withstand extended periods
of exposure to Dialox, refer to the caution below.
Therefore, regular flushing of the WRO alone
is mandatory. Minimum flushing intervals that
can be set is 3 minutes every 60 minutes during
the contact period, see 11. below.

Caution: Membrane life expectancy may be


reduced if the total contact time per week
exceeds one hour.

10. Setting the contact time:


The available contact time is the time until
the rinse seqence has to be initiated (see
below) in order to get the WRO and the loop
rinsed out to allow for rinse of the AK100´s.
Set this time at CONTACT, Total time.

11. Setting Pause - Run:


Recommended settings:
Pause: 30 minutes
Run: 3 minutes
HCEN9315 Rev. 10. 00 4:9
WRO Chem no Setting table Name of Hospital.......................................................

SETTING OBJECT Del. setting Install:Date / Sign Rev:Date / Sign

LIMIT VALUES / -2000 / -2000


Conductivity:
cond.out (C2)
-Warning µS/cm 50
-High µS/cm 100
-Intake:Low µS/cm 100
-Test µS/cm 10
cond.return (C4)
-Intake: Low µS/cm 500
-Rinse: High µS/cm 50
-Test µS/cm 100
Flow:
-Reject l/min *
-Pure l/min *
-Leak. l/min 2,0
delay min 2

CALIBRATION COND
Inlet water % *
Ret. water % *
Pure water % *

COUNTERS
Start up min 3
Ret. to drain min 10
SB pause min 120
SB operat. min 10
Disinfection:
Restart min 10
Max time dev. min 15
Move dos.conn min 10
Operation:
Restart sec 60
Delay RO-pump sec 10.0

DISINF LOOP:
DISINF. INTAKE
Return from loop to drain min 10
Return from loop to WRO min 5

CONTACT
Total time min 10
Pause min 10
Run min 3

RINSE
Rinse WRO+loop min 240
Final rinse WRO min 30
Rinse monitors min 30

DISINF WRO:
DISINF.INTAKE min 5
CONTACT min 5
RINSE min 100

HCEN9315 Rev. 10. 00


4:10
sign / date
WRO Chem Setting of TIME CHANNELS and AUTORINSE Name of Hospital....................................................

HCEN9315 Rev. 10. 00


DAY OF AUTOSTART AUTORINSE DIALYSIS
DIALYSIS HOURS
WEEK START UP 1 START UP 2 RINSE CIRC. 1 RINSE CIRC. 2 MACHINE
FROM TO
ON OFF ON OFF ON OFF ON OFF READY TIME

Monday

Tuesday

Wednesday

Thursday

Friday

Saturday

Sunday

4:11
This page is intentionally left blank

HCEN9315 Rev. 10. 00


4:12
5. Technical information -
Service and maintenance WRO Chem
Note:The information in this section is intended for technicians only

Contents

Operator´s panel .......................................................................2


Technician info level 1 ........................................................2
Technician info level 2 ........................................................3

Time channels ..........................................................................8

Disinfection displays ............................................................... 11

Helpful hints in service situations ......................................... 12


Total stop ........................................................................... 12
Fast stepping of program .................................................. 12

Loop test ................................................................................. 12

Conductivity monitoring ........................................................ 13


General .............................................................................. 13
Calibration of conductivity reading ................................... 13

Maintenance ........................................................................... 14
Changing container for disinfectant ................................. 14
Checking the proportioning pump .................................... 14
Change of battery in operator´s panel and PLC ............... 14
Checking the reject flow rate ........................................... 14
Setting of recirculation flow rate ...................................... 15
Checking sensor functions ................................................ 15

Cleaning .................................................................................. 16

Preservation ........................................................................... 17

Programmable control unit ................................................... 18

Water saving control .............................................................. 19


Water save- setting level .................................................. 20
Water saving- advanced setting level ............................... 22

HCEN9315 Rev. 10. 00


5:1
Technician info level 1
Refer to Block Diagrams for Technicians ! 8. ->PLC-info
This position is used to get access to internal
To enter Technician info, press MAIN programming data.
MENU, move the curser to Technician info
and press ENTER. 9. Progr.version MAC
Use the arrow buttons to move through the list. Information about present program version in
the MAC operator´s panel.
1. ->Level 2
To enter Technician info level 2, move the 10.Progr. version PLC
curser to -> and press ENTER. Then dial code Information about present program version in
2 (technician´s code) and press ENTER again. the PLC.
Refer to page 5:3.

2. Rej. STARTUP
Reject flow in litres per minute during the TECHNICIAN INFO
most recent STARTUP period (motor valve
1. -> Level 2
fully open to drain). This value can therefore
be used for logging purposes and (setting of 2. Rej.START UP l/min
needle valve 41). 3. Running time ...h
4. Inlet water ....m3
3. Running time 5. Disinf. cycles ...
Running time meter for the RO-unit. 6. Low level alarm ...
7. ->PROGR.DISINF
4. Inlet water 8. ->PLC-info
Approximative accumulated consumption of
9. Progr. version MAC
inlet water in cubic metres (m3).
RCXXXXXX
5. Disinf. cycles 10. Progr. version PLC
Registration of number of disinfection cycles RCXXXXXX
that have been performed. Fig.1. Technician info display

6. Low level alarm


Registration of number of instances that the
system has stopped because of low level in the
inlet water tank (4).
Low level occurs if the water pressure is
insufficient or if the water supply is
interrupted. Refer to section 3, Alarm and
trouble shooting, for more information.

7. ->PROGR.DISINF.
Here you check the presets and make
modifications in the disinfection program.
Place the curser at -> and press ENTER.
Please refer to page 5:11, Disinfection
displays, for more information.

HCEN9315 Rev. 10. 00


5:2
Technician info, level 2 1. Total stop:
Link 69-70 and
Technician info, level 2, is used for setting of press STOP
general parameters (see below). A special 2. Fast stepping on/off
code, code 2, is required to get access to this 3. Date: xxx
level. This code is handed over to the 4. Time: xxx
responsible technician at the installation. Code 5. Day: xxx
2 can also be obtained from your Gambro 6. ->TIME CHANNELS
representative. CHOICE
7. Stand by to loop no/yes
Entering Technician info level 2: 8. Flow alarm in OP no/yes
- Press MAIN MENU 9. Loop leak. alarm no/yes
- Go to ->Technician info and press ENTER. 10. Mode LOCAL/REMOTE
- Go to ->Level 2 and press ENTER. 11. Local Start/Stop AUT/MAN
- Dial code 2 and press ENTER. 12. Ext. ind. on/off
13. Ext. sign. test no/yes
1. Total stop (Press DISINF.WRO!!)
A total stop will reset the PLC-programme. 14. Cleaning no/yes
It is useful in service situations, i.e. to interrupt LIMIT VALUES
a disinfection cycle. Refer to page 5:12 for info. Conductivity:
cond.out (C2)
To perform a total stop: 15. -Warning ...µS
- Enter Technician info, level 2. 16. -High ...µS
- Open the electrical control box on the WRO. 17. -Intake:Low ...µS
- Connect a jumper between terminals 69 and 70 18. -Test ...µS
(input X7 lights up) cond.return (C4)
- Press STOP. 19. -Intake: Low ...µS
- Remove the jumper. 20. -Rinse: High ...µS
21. -Test ...µS
Caution: The normal safety functions will be Flow:
overruled when a total stop is performed. The 22. -Reject l/min
person who has performed the total stop is 23. -Pure l/min
therefore responsible for ensuring, by separate 24. -Leak. l/min
testing, that no chemicals remain in the system. 25. delay m
Refer to Loop test. CALIBRATION COND
26. Inlet water ...%
2. Fast stepping 27. Ret. water ...%
Fast stepping is helpful in service situations. 28. Pure water ...%
When using this function the sequence times in Inlet< xxx Pure xxx
the program decrease by a factor of 60. 29. ->WS control
COUNTERS
Activation of the fast stepping function: 30. Start up ...m
- Put the curser at off and press ENTER. 31. Ret. to drain ...m
32. SB pause ...m
An arrow will appear in the upper right corner of 33. SB operat. ...m
the display to indicate that the fast stepping Disinfection:
function has been activated. 34. Restart ...m
Refer to page 5:12 for more information about 35. Max time dev. ...m
how and when to use this function. 36. Move dos.conn ...m
Operation:
Caution: The normal safety functions will be 37. Restart ...s
overruled when fast stepping is performed. The 38. Delay RO-pump ...s
person who has performed the total stop is 39. Reload old values
therefore responsible for ensuring, by separate no/yes
testing, that no chemicals remain in the system. 40. Save new values no/yes
Refer to Loop test. 41. GSS on/off

Fig. 2. Technician info level 2 - display

HCEN9315 Rev. 10. 00


5:3
Technician info level 2, continued
3, 4. Date; Time The flow alarm function is set at yes at delivery.
Setting of correct time. Move the curser to the It can however be temporarily inactivated if
digit to be changed, enter new digit and then required, such as if a flow meter is out of func-
press ENTER. Programmed digits will not be tion or in certain service situations.
accepted until ENTER is pressed. To inactivate the flow alarm: Place the
curser at yes and press ENTER.
5. Day To reactivate the flow alarm: Place the
The weekday appears when date & time is set. curser at no and press ENTER.

Note: Adjustment for summer/winter time is Caution: To avoid potential damage to the
required. system, this alarm must only be bypassed for
shorter periods of time.

6. TIME CHANNELS Caution: If the reason for the alarm is a faulty


The time channels are used for setting time flow meter, insure that there is flow through the
and time periods for the following purposes: drain lines, e. g. by opening the motor valve
Function 1: AUTOMATIC START UP (138) fully to drain before bypassing the flow
Automatic start of operation at a preselected alarm.
point of time of day.
Function 2: AUTOMATIC STOP 9. Loop leak. alarm
Automatic stop of operation at a preselected point
Selection between activating/deactivating alarm
of time of day.
no 19. Loop leakage.
Function 3: RINSE CIRCULATION
Activate: Move cursor to no, press ENTER.
To set start and duration of circulation of water
Deactivate: Move cursor to yes, press ENTER.
in the loop after integrated chemical disinfection
to enable rinse of the dialysis machines. Refer to
Time channels on page 5:8 for more information.
10. Mode LOCAL/REMOTE
Selection between operating the CWP in Local-
or Remote mode.
CHOICE (7-14) Local mode: The CWP is operated from the
operator´s panel on the CWP.
Remote mode: The CWP is operated from the
Note: A total stop does not affect Choice settings optional external key selector box.
(7-14).
Note: The external key selector must be in 0
7. Stand by to loop position when changing from Local- to Remote
To avoid extended stagnant periods during stand mode or reversed.
by, flushing will take place at regular intervals.
If the distribution system should be included in 11. Local Start/Stop AUT/MAN
the flush the display should read yes. Selection between manual or automatic start
To include the loop in the flush: Move the and/or stop of the system. Refer to Time
curser to no and press ENTER. channels, 6. above and on page 5:8.
To exclude the loop: reverse the procedure. To select auto function: Put the curser at MAN
and press ENTER.
Note: The stand by flush will always include the AUT: The CWP start/stops according to what is
loop after a loop disinfection has been performed set under 6. Time Channels settings.
MAN: The CWP is operated from the operator´s
8. Flow alarm in OP panel.
Some of the flow rates are monitored during the
operation of the system (refer to General de- Note: Automatic start cannot be obtained after
scription). Example: the reject flow from the disinfection has been performed.
unit must exceed 0.5 liter/minute during rinse
and 0.2 liter/minute during operation. If not, the Note: This feature is bypassed if the CWP is in
CWP will stop and issue this alarm. Remote mode, refer to 10. above.

HCEN9315 Rev. 10. 00


5:4
12. Ext. ind on/off also start to blink. The CWP continues to flush
Position to turn on/off the external lamp to drain until STOP is pressed or the
indication unit (optional). conductivity again goes below the high
To activate: conductivity limit.
Place the cursor at off and press ENTER. Recommended setting: should be based upon
To deactivate: the initial feed water analysis and initial
Place the cursor at on and press ENTER. rejection characeristics of the reverse osmosis
unit and shall correspond to the lowest
13. Ext. sign. test no/yes conductivity at which any contaminant reaches
an unacceptable limit, i.e. outside the valid
Test of external signal to lamp indication unit
standard.
is made from this position. When this option is
Delivery setting: 100 µS/cm
activated, green, orange and red lamps on the
To change set value: Move the curser to the
indication unit (optional) light up. The white
limit value, enter new value and press ENTER.
lamp is not lit during this test.
Activate: Place cursor at no and press ENTER.
Deactivate: Place cursor at yes and press ENTER. 17. Intake Low.. µS (alarm no 23)
Display of set conductivity limit to confirm
that the WRO has been filled with disinfectant
14. Cleaning during the intake phase of the loop disinfection
The system has a special cleaning mode which is program. Alarm is issued if set limit has not
selected here. Refer to Cleaning. been exceeded at the end of the intake phase.
To change set value: Move the curser to the
LIMIT VALUES (15-25) limit value, enter new value and press ENTER.

Under this position, certain limit values are set. 18. Test... µS (alarm no 31)
The present set values are shown to the right, An increase of conductivity occurs at each start
while those within paranthesis are the most up when the WRO has been in stand by for some
recently saved values. Alarm will be issued if the time. This fact is used to check that the pure
limits values are triggered. Refer to section 3, water conductivity cell (35) is responding. Alarm
Alarms and trouble shooting. no 31 will be issued if set limit has not been
exceeded.
Conductivity, cond out (C2): Recommended setting: Depends on inlet water
conductivity. Stop the WRO for 10 minutes then
15. Warning ... µS (alarm no 5) start it again a couple of times. Record the peak
If, for some reason, the pure water conductivity conductivity values. Set the alarm limit 3-5µS/cm
should increase during operation and exceed the below lowest achieved peak value.
set warning limit, alarm no 5, "Warning cond." Delivery setting: 10 µS/cm
will be issued and the B-alarm lamp on the lamp To change set value: Move the curser to the
indication unit (optional) will start to blink to limit value, enter new value and press ENTER.
alert the operator. The CWP will, however,
continue in operation.
Recommended setting: 2 x normal Conductivity, cond. return (C4):
conductivity, however, minimum 10µS/cm 19. Intake Low... µS (alarm no 23)
Delivery setting: 50 µS/cm Display of set conductivity limit to confirm
To change set value: Move the curser to the that the loop has been filled with disinfectant
limit value, enter new value and press ENTER. during the intake phase of the loop disinfection
program. Alarm is issued if set limit has not
16. High ... µS (alarm no 6) been exceeded during the last two minutes of the
If a significant increase in the pure water intake phase of the loop disinfection program.
conductivity should occur during operation and Recommended setting: 500 µS/cm
exceed the set high conductivity alarm limit, the Delivery setting: 500 µS/cm
CWP will immediately switch to flush-to-drain To change set value: Move the curser to the
mode and issue alarm no 6, "High cond" (after a limit value, enter new value and press ENTER.
delay time of 30 seconds). The A-alarm lamp on
the external almp indication unit (optional) will

HCEN9315 Rev. 10. 00


5:5
Technician info level 2, continued
20. Rinse High... µS (alarm no 21) 24. -Leak ..l/min (alarm no 19)
During the last minutes of the rinse phase, the During rinse of loop and stand-by operation, the
conductivity in the return line has to be below pure water flow (121) as well as the return water
set limit. This is an indication that the main part flow (51) are monitored by the machine. Alarm
of the disinfectant has been rinsed out of the no 19 is issued, if these two values differ more
system. If not, alarm 21 "Cond rinse hi C4" will than set limit.
be issued. Recommended setting: 2.0 l/min
Recommended setting: Same as set warning Delivery setting: 2.0 l/min.
conductivity limit. To change setting: See Limit values above.
Delivery setting: 50 µS/cm
To change set value: Move the curser to the 25. delay ..min
limit value, enter new value and press ENTER. Display of set delay time between when the Loop
leakage alarm occurs and when it is displayed on
21. Test... µS (alarm no 22) the machine.
Dynamic test of the conductivity cell (144) in the Recommended setting: 2 minutes.
return line from the clinic. During the first Delivery setting: 2 minutes.
minute of disinfection intake, the conductivity To change setting: See Limit values above.
must be below set limit. Alarm 22 Cond test. C4
is issued if set limit is exceeded. CALIBR. COND.
Recommended setting: 100 µS/cm
Delivery setting: 100 µS/cm
To change set value: Move the curser to the
26. Inlet water .....%
limit value, enter new value and press ENTER. Position for calibration of the inlet water
conductivity. The present value is displayed to
simplify the setting procedure. Refer to
Flow: Conductivity monitoring on page 5:13.
22. Reject (alarm no 17)
The reject flow rate is supervised in all modes
of operation. Alarm no 17 is issued if the flow
27. Ret. water ......%
rate goes below set limit. The set flow limit Position for calibration of the return water
depends on model size and is displayed here. conductivity. The present value is displayed to
Recommended setting: See table 1 below! simplify the setting procedure. Refer to
Delivery setting: According to table. Conductivity monitoring on page 5:13.
To change set value: Move the curser to the
limit value, enter new value and press ENTER. 28.(16.) Pure water ......%
Position for calibration of the product water
Model 22. RO-reject 23. Pure water conductivity. The present value is displayed to
simplify the setting procedure.Refer to
WRO111 1 l/min 3 l/min Conductivity monitoring on page 5:13.
WRO112 2 " 6 "
WRO113 3 " 9 " 29. ->WS control
WRO114 4 " 9 " Position to enter Water saving control settings.
To enter, place the cursor on the arrow and
Table 1. Setting of flow limits. press ENTER. For more information refer to
Water saving in this chapter.
23. Pure (alarm no 8)
For safety reasons the pure water flow rate is COUNTERS
supervised during the rinse phase in the
disinfection or cleaning programme. Alarm no 8 Head line for positions 30 - 38.
is issued if the flow rate goes below set limit. The numbers within parenthesis refer to the
The set minimum allowed flow rate depends on numbers in the function diagram on page 6:3,
model size and is displayed here. WRO Chem - Operation
Recommended setting: See table 1 above! To change set value: Move the curser to the
Delivery setting: According to table 1 above. value, enter the new value and press ENTER.
To change setting: See Limit values above.

HCEN9315 Rev. 10. 00


5:6
Technician info level 2, continued
30. START UP (1) Delivery setting: 10 minutes.
Flush of the WRO to drain at start up. Setting range: 1-99 minutes
When a reverse osmosis system is switched off,
salts will migrate from the reject side to the pure Operation:
water side of the membrane. The conductivity
will therefore be elevated for a short while at
start up. The shorter the stop, the shorter time 37. Restart
is required until the conductivity reaches the Here you set the time in seconds between
normal operation value again. restart attempts after a water interruption when
Setting range: 2 - 30 minutes the WRO is in operation.
Delivery setting: 3 minutes Factory set at 60 seconds.

31. Ret. to drain (4) 38. Delay RO-pump


An extra flush of the loop to drain via valve 54 In this position you can alter delay time for
will take place after a disinfection or cleaning start of the main pump.
procedure has been performed. Factory set at 10 seconds
Setting range: 1 - 60 minutes Setting range: 5 - 60 seconds.
Delivery setting: 2 minutes
39. Reload old values
32. SB pause (6) This function is used if you have entered new
During stand by the system performs a flush at values in any of the positions 15 - 38 but want to
regular intervals to keep it in good condition. return to the old values (within parenthesis).
Here you set the time between flushes.
Setting range: 30 - 240 minutes To reload the old values:
Delivery setting: 120 minutes - Move the curser to no.
- Press ENTER.
33. SB operat. (7) - Press the red button marked with "C" .
Setting of the duration of the flushing period.
Setting range: 1 - 30 minutes 40. Save new values
Delivery setting: 10 minutes This function is used if you want to make any
changes that you have performed in positions
Disinfection: 15 - 38 permanent.

To save the new value(s):


34. Restart - Move the curser to no.
Here you set the time in minutes between the - Press ENTER.
restart attempts after a water interruption - Press the red button marked with "C" .
during disinfection or cleaning.
Factory set at 10 minutes. As a confirmation, the value within parenthesis
then changes to the new value.
35. Max time dev.
The central chemical disinfection program may
only be delayed a limited time in order to insure
41. GSS ON/OFF
This machine can be connected to Gambro
sufficient rinse of the dialysis machines,
Surveillance System GSS. If the function is
otherwise alarm no 28. Dis time dev., will be
activated, ON is shown in this position and the
issued. The desired delay time is set here.
MAC operator´s panel will send information
Factory set at 15 minutes.
every 30 seconds via the RS232 port on the back
Setting range: 1-99 minutes
of the panel. A converter (RS232 to RS 422) is
required when connecting the CWP 100 to GSS.
36. Move dos. conn To activate, place cursor at OFF and press
Display of set delay time for the operator to ENTER. To deactivate, reverse the procedure.
move the dosing connector. Alarm no
4. Dos.conn.error is issued if set value is
exceeded.

HCEN9315 Rev. 10. 00


5:7
TIME CHANNELS
4. Time: xxx 3: Rinse circulation
5. Day: xxx The time channels RINSE CIRC. can be used to
6. ->TIME CHANNELS initiate circulation of water in the loop after a
CHOICE: central chemical disinfection, thereby enabling
7. Stand by to loop no/yes automatic rinse of dialysis machines with auto
8. Flow alarm in OP no/yes rinse feature.
The WRO is still in disinfection and runs only for
the preset period of time.
The time channels are used for setting time
and time periods for the following purposes: Caution: Consult Gambro before activating the
1: START OPERATION 1 Automatic rinse feature.
Automatic start of operation at a preselected
point of time of day. Caution: The WRO and the distribution system
2: STOP OPERATION have not been tested for residual disinfectants
Automatic stop of operation at a preselected when the rinse circulation period is started.
point of time of day.
3: RINSE CIRCULATION
To set start and duration of circulation of water
in the loop after integrated chemical
disinfection to enable rinse of the dialysis
machines.

1: Automatic start of the WRO


The WRO can be programmed for automatic
start at a preselected time of day (11. page 5:4).
Desired starting time is set under any of the
time channels START OPERATION 1 or 2.

Note: Because of the way the time channels are


set up, you always have to enter a period, also
when using the autostart function. The period
should be very short (five minutes). The WRO
will then start at the initiation of the period.

Note: If disinfection has been performed, the


WRO will not start automatically although
the autostart function has been activated. The
reason for this is that a test for residual
disinfectant must always be performed before
the WRO is put into operation after disinfection.

2: Automatic stop of the WRO


The WRO can be programmed for automatic
stop at a preselected time of day (11. page 5:4).
Desired time is set under any of the time
channels STOP OPERATION 1 or 2.
Also here, a period has to be entered, refer to
note above.

HCEN9315 Rev. 10. 00


5:8
Programming instructions

1. Go to TIME CHANNELS, put the curser at


the arrow and press ENTER. The following
display will then appear:

START OPERATION 1
START OPERATION 2
STOP OPERATION 1
STOP OPERATION 2
RINCE CIRC. 1
RINCE CIRC. 2

2. Put the curser at the desired channel and


press ENTER. The following then appears:

EXIT
I 1:...................
I 2:...................
I 3:...................
I 4:...................

Under each of the channels you can thus pro-


gram up to 4 different periods, in total 8 periods
for each function, all with the same priority.

3. Enter desired time period according to the


information and examples on next page. A
period can be a specific time interval on one
day, a group of days or all days of the week.

4. Programming of weekdays:

To write Monday, press: 1

Tuesday: 2

Wednesday: 3

Thursday: 4

Friday: 5

Saturday: 6

Sunday: 7

Clear
To delete a sign:

Space:

5. To exit time channels:


- Place curser at EXIT.
- Press ENTER and then MAIN MENU.

HCEN9315 Rev. 10. 00


5:9
Programming example - autostart

1: The personnel normally arrives at 07:00 in 4. If programming is incorrectly performed:


the morning Monday to Friday. The text "INVALID DATA " will be displayed
2: On Saturdays, dialysis starts at 09:00. when you try to exit.
3: No dialysis takes place on Sundays.
4: Disinfection of the WRO is initiated every 5. Activation of autostart: Change Local
Thursday evening. Start/Stop (11 on page 5:4) from MAN to AUT.

- Monday - Thursday: The system should go 6. Return to normal reading:


into operation well before 07:00, for example - Place curser at EXIT.
at 06:40, to allow for sufficient flush of the - Press ENTER.
distribution system. - Press MAIN MENU.
- Friday: Autostart is not possible after a - Press STATUS.
chemical disinfection has been performed. You
can, however, enter the same starting time as Rinse circulation - example
for the other days (to simplify programming).
Autostart will then take place Friday morning In a unit equipped with AK 100 monitors, central
only if disinfection has not performed. chemical disinfection is going to be performed
- Saturday: Autostart at 08:40. Monday and Thursday nights on a weekly
- Sunday: No operation - no autostart. basis. The personnel arrives at 07:00 in the
morning the next day. The auto rinse should
Entering the data therefore be ready before that time, say 06:30.

1. Follow the instructions on previous page to Instructions:


enter TIME CHANNELS, START 1. Program the AK100 dialysis machines for
OPERATION 1 or 2. auto rinse the mornings after central
chemical disinfection, expected ready time
Then, at any free line, with the curser in 06:30 *). Refer to the manual for AK100.
the left position, write:
Monday to Friday 0640-0645: *) Because of the way the program is set up, the
AK100´s will go into auto rinse 25 min. earlier
1 5 than calculated time. This should be taken into
account when programming the AK 100´s, i.e.
0 6 4 0 the ready time should be set at 06:55

0 6 4 5 2. The rinse cycle in the auto rinse program in


AK100 will last 26 minutes. The WRO
2. Then, at any of the remaining 7 free lines, therefore has to start rinse circulation by
then write: Saturday 0840-0845: latest 06:00. A suitable rinse circulation period
would therefore be 05:50 - 06:50.
6
3. Enter any of the time channels Rinse
0 8 4 0 circulation according to the info above.

0 8 4 5 4. Then, at any free line, with the curser in


the left position, write: 1 space 0550-0650
(refer to the information for autostart above).
3. Checking the programming:
Exit TIME CHANNELS (see below) and then 5. At another line, write: 4 space 0550-0650.
reenter to check that the data is correct:

EXIT
I 1:Mo-Fr 0640-0645
I 2:Sa 0840-0845
I 3:...................
I 4:...................

HCEN9315 Rev. 10. 00


5:10
Disinfection displays
WRO + loop (11)
The disinfection displays are entered from The WRO and the loop are rinsed out to drain via
Technician info level 1, refer to page 5:2. valve 54.
Refer to section 1 in this manual and the Setting range: 1 - 240 minutes
respective function and block diagrams for Delivery setting: 240 minutes
more information.
final rinse WRO (14)
The numbers within parenthesis below refer to Valve 106 opens for a short while to flush the
the numbers in respective function diagram. return line from the loop to the WRO. The outlet
valve to the loop (48) then closes and the final
DISINF LOOP residues are rinsed out of the WRO via valve 36.
Change timers Setting range: 10 -30 minutes
Here you enter the level where you can change Delivery setting: 30 minutes
the preprogrammed time values. Put the curser
at the arrow and press ENTER. Then enter Monitors (15)
code 2 (technician´s code) and press ENTER. This mode of operation follows immediately after
final rinse WRO to enable automatic rinse of
DISINF INTAKE: dialysis machines.
Total time (1) Setting range: 0 - 240 minutes
Factory setting: 0 minutes
The total intake time of Dialox is made up of
the sum of 4 and 5 below.
Reload old values
Recall of old values (within parenthesis).
Return from loop to drain (4) Refer to 39 on page 5:7 for more information.
The disinfection solution is diverted to drain.
Setting range: 1 - 240 minutes
Delivery setting: 10 minutes Save new values
To save new values permanently.
Return from loop to WRO (5) Refer to 40 on page 5:7 for more information.
The disinfection solution is diverted back to the
WRO to integrate it in the disinfection cycle. DISINF WRO
Setting range: 1 - 240 minutes Change timers
Delivery setting: 5 minutes Refer to DISINF LOOP above.

CONTACT: DISINF INTAKE (1)


Total time (9) Setting range: 1 - 30 minutes
Set contact time of Dialox. Delivery setting: 5 minutes
Setting range: 1 -240 minutes
Delivery setting: 10 minutes CONTACT (4)
Setting range: 1 -240 minutes
Pause (10)/Run (11) Delivery setting: 10 minutes
During the contact period, you can have the
main pump to start at desired intervals to feed RINSE (8)
fresh disinfection solution into the loop. Setting range: 30 - 240 minutes
Setting range Pause: 1 - 240 minutes Delivery setting: 100 minutes
Setting range Run: 3 - 60 minutes
Delivery setting Pause / Run: 30/3 minutes
Reload old values
Recall of old values (within parenthesis).
RINSE Refer to 22 on page 5:5 for more information.
Total time (10)
The total rinse time is made up of 11, 14 and
Save new values
15 below.
To save new values permanently.
Refer to 40 on page 5:7 for more information.

HCEN9315 Rev. 10. 00


5:11
Helpful hints for service Loop test
Total stop and fast stepping are helpful tools The safety functions in the WRO Chem will be
for the technician when working on the WRO. overruled in the following situations:

Caution: A test of the water in the loop is 1: When a total stop has been performed.
required after a total stop has been performed or 2: After using the fast stepping function.
the fast stepping function has been used. It is
the responsibility of the technican to ensure that An extra test of the water in the loop will
no chemicals remain in the system. therefore always be necessary when these
Refer to loop test below. functions have been used, before the system can
be put into normal operation again.

1. Total stop The text "LOOP TEST REQUIRED!!" will flash


A Total stop will reset the PLC programme. It on the display until the test has been confirmed
is useful in certain service situations, i.e. to to remind about the need for an extra test of the
interrupt an ongoing disinfection cycle. water in the loop.

To perform a Total stop: The WRO will operate intermittently until


- Enter Technician info, level 2 (refer to 5:3). the test has been confirmed (four minutes to the
- Change from fast stepping no to yes loop, one minute to drain) to make use of the
- Open the electrical control box on the WRO. dialysis machines impossible.
- Connect a jumper between terminals 69 and 70
(input X7 lights up). Caution: It is the responsibility of the technician
- Press STOP and remove the jumper. to ensure, by testing, that no chemicals remain
in the WRO or in the loop.
2. Fast stepping of program
Using this function decreases the sequence
times in the program by a factor of 60, i.e. one
Performing the loop test
second equals one minute. To perform fast While the system is running, collect a water
stepping: sample in the last tap in the loop and verify by
testing that there are no residues of the
1. Activate the fast stepping function under disinfectant chemicals present in the water.
Technician info level 2 (refer to 2. on page
5:3). An arrow then appears in the upper Confirmation of the loop test
right corner of the display. The WRO is put into normal operation by
2. Open the electrical control box on the WRO. entering the operator´s code, followed by
3. Hold a jumper between terminals 69 and 70. ENTER.
The programme will run faster as long as the
jumper is connected. Note: Confirmation of the loop test has to be
done while the WRO is running.
Note: Only counters in the program will be
affected, not delays set with normal timers.

Note: Alarm no 7, Motorprotect.WRO will be


issued (after 10 seconds delay) if you try to use
the fast stepping function without first
activating it under Tec. info level 2.

Note: The fast stepping function will be


deactivated if not used for 30 minutes. It can also
be deactivated under Technician info level 2.

HCEN9315 Rev. 10. 00


5:12
Conductivity monitoring
General
The conductivity is measured at three positions pure water conductivity has stabilized (approx. 5
within the WRO Chem (refer to fig 3 & 4 in minutes).Then go to CALIBRATION COND.
chapter 1): under Technician info level 2 (page 5:6)

1. The inlet water conductivity (C1) is measured A) Calibration of inlet water reading
by conductivity cell 32. 1. Collect a sample of the inlet water in a clean
2. The pure water conductivity (C2) is measured container in a sample valve just before the
by conductivity cell 35. WRO.
3. The return water conductivity (C4) is 2. Measure the conductivity of the inlet water,
measured by conductivity cell 144. using an external reference conductivity
instrument.
Inlet water conductivity (C1)
The inlet water conductivity (C1) is displayed 3. Change the % value at 26. on page 5:6
under MAIN MENU (refer to section 1). The (Calibr. cond., Inlet water) until the new
conductivity values of the inlet and pure water reading (is displayed at the bottom of the
are used to calculate the salt removal effiency of display) corresponds with the reading on the
the reverse osmosis unit, the rejection rate, reference meter.
which is also displayed under MAIN MENU.
B) Calibration of pure water reading.
1. Collect a sample of the pure water in a clean
Pure water conductivity (C2)
container in the drain funnel on the right
The pure water conductivity (C2) is displayed
hand side of the WRO.
under MAIN MENU. It has a number of
functions concerning the operation of the CWP.
2. Measure the conductivity of the pure water
using an external reference conductivity
Return water conductivity (C4) instrument.
The return water conductivity (C4) is dis-
played under MAIN MENU. Move cursor to the 3. Change the % value at 28. on page 5:6
arrow right of cond. in and press ENTER, the (Calibr. cond., Pure water) until the new
display will change to cond. ret. It has a number reading (is displayed at the bottom of the
of functions concerning the operation of the display) corresponds with the reading on the
CWP. reference meter.
Calibration of conductivity reading Procedure C, return water
The conductivity depends on the temperature of Go to MAIN MENU and start test operation
the water and increases with approx. 2% per °C. LOOP. (refer to 15. on page 1:15). Wait until the
The conductivity measuring system is calibrated pure water conductivity has stabilized (approx. 5
at a temperature of 10°C at the factory. minutes).Then go to CALIBRATION COND.
Adjustment may therefore be required if the under Technician info level 2 (page 5:6)
actual water temperature differs significantly.
Conductivity calibration is done under C) Calibration of return water reading
CALIBRATION COND. in Tec. info level 2. 1. Collect a sample of the return water in a
Refer to page 5:6 for more information. clean container from the last tap on the
loop.
Required equipment
An external reference instrument, designed for 2. Measure the conductivity of the return water,
measurement of conductivity in water. using an external reference conductivity
Required measuring range: 1 - 2000 µS/cm. instrument.

Procedure A and B, inlet/ pure water 3. Change the % value at 27. on page 5:6
Go to MAIN MENU and start test operation (Calibr. cond., Ret. water) until the new
WRO. (refer to 14. on page 1:15). Wait until the reading (is displayed at the bottom of the
display) corresponds with the reading on the
reference meter.

HCEN9315 Rev. 10. 00


5:13
Maintenance
Changing container for disinfectant Checking the reject flow rate
If the level switch in the solution container The setting of valve 41 must be checked
indicates low level when a disinfection cycle is to regularly (motor valve open fully to drain).
be initiated, alarm no 9, Low level chem., will Incorrect reject flow setting may lead to
be issued. The cycle cannot be initiated until the increased fouling of the RO - membranes. Once a
empty container has been replaced with a filled week is recommended the first month. The
one. If the level goes low during a disinfection intervals can then be extended based upon
cycle an alarm will also be issued, but the pro- experience.
gram will continue as normal. The table below shows the required reject flow
rates for different sizes.
Caution: Before initiating a central chemical
disinfection including the dialysis machines, The higher values are applicable for water with
always make sure that there is sufficient amount high fouling properties or temperature. Adjust if
of disinfectant in the container. required with valve 41.

To change container: model reject flow rates, l/min


1. Open the door on the front. Lift up the level
switch/pick-up tube arrangement from the WRO 111 3-6
empty container. WRO 112 7 - 10
WRO 113 9 - 13
Caution: use protective glasses. WRO 114 12 - 15

2. Remove the empty container and replace it Adjusting the reject flow rate:
with a filled one. 1. Disengage the water saving control system.
3. Insert the cap with level switch/pick-up tube The motor valve then opens fully to drain.
into the new container and close the door. 2. Check the reject flow rate on the display.
3. If adjustment is necessary, first close the
Checking the proportioning pump valve to a lower value than the recommended
Accuracy: setting, then slowly adjust until the correct
The volume of Dialox that has been used during setting is obtained.
the disinfection cycle should be recorded by
making a mark on the container and compare it Note: After adjustment of needle valve (41),
with the normal consumption. This is an easy make sure that the locking nut is firmly
way to check the proportioning pump. attached.

Leakage: 4. Activate water saving control again.


Check the pressure line and the dosing
connectors every two months for leaks or cracks. Checking the pure water conductivity
Exchange if required. measurement system
The pure water conductivity measurement
Battery change in operator´panel & PLC system must be checked on a regular basis with
The batteries in the operator´s panel and the PLC a reference conductivity meter, intended for
should be changed every five years. measurement of conductivity in pure water. The
PLC-unit: refer to page 5:18 frequency of this conductivity control should be
Operator´s panel: the battery is placed behind based upon local rules.
the cover at the back of the terminal.
Checking the conductivity:
During operation, collect a pure water sample
from the first tap in the clinic. Measure the
conductivity with a reference meter and compare
with the value shown on the display. If the
values do not correspond, calibrate the pure
water reading on the CWP, see previous page.

HCEN9315 Rev. 10. 00


5:14
Setting of recirculation flow rate
Part of the reject flow is recirculated to the
suction side of the main pump in order to
maintain a high flow velocity in the reverse
osmosis membrane modules. The recirculation
flow is regulated with valve 71 according to the
following instructions.

Note: The recirculation valve 71 must always be


partly opened, at least half a turn.

1. Mount a 0 - 25 bar pressure gauge (spare part


no 25-10159) in the threaded connection on
the upper left hand side on the upper frame).
2. Start the RO -unit in operation.
3. Adjust the outlet pump pressure with valve 71
until it corresponds to the value in the table
below.

model pump pressure, bar

WRO 111 15-18


WRO 112 12-15
WRO 113 14-15
WRO 114 12-14

Checking sensor functions


A function check of the sensors in the system
should be performed every six months.

HCEN9315 Rev. 10. 00


5:15
Cleaning Cleaning procedure
Cleaning may be required on a periodic basis 1. Enter Technician info level 2 and go to
if the reverse osmosis membranes become fouled Cleaning (14. on page 5:5).
by contaminants in the water.
WRO Chem therefore has a special cleaning 2. Put the curser at no and press ENTER
programme. It is based on the disinfection PRESS DISINF WRO!! will then be
programme for the WRO and therefore the time displayed on the line above Cleaning.
settings are identical. Refer to Technician´s
block diagram 2 and the function diagram 3. Press DISINF WRO twice.
for cleaning in section 6.
4. Open the needle valve 41 on the RO-reject
Cleaning with citric acid is recommended if a line to improve the circulation flow.
significant increase in the pure water conduc- Reject recirculation valve 71 may also be
tivity should occur. This could be caused by opened to further increase the flow velocity in
mineral scaling, such as the carbonates of the membrane module(s).
calcium or magnesium.
Note: Readjustment of valve 71 after cleaning
Recommended amount of citric acid: requires a pressure gauge. Refer to section 5,
0,5 - 1,0 kg (depending of WRO size) of solid citric Setting of recirculation flow rate.
acid is slowly added directly into the inlet tank
of WRO at step 5 in the procedure below. 5. Press DISINF WRO again.
The main pump will now start and circulate
Cleaning with alcaline cleaning agents may water internally, back to the inlet water tank
be required if the inlet water contains high levels
of organic material. 6. Remove the cover on the inlet water tank and
slowly add the required amount of cleaning
Example of alcaline cleaning agents: agent. The main pump will now run
- 0,1 % solution of sodium hydroxide and the continously until the Contact period is
disodium salt of EDTA. Dissolve 20 (111), 25 finished. It will then stop and show: "Open
(112), 30 (113) or 35 (114) grams each of these the drain valve on WRO. Press DIS WRO".
salts in 2 liters of water. Slowly add this
solution to the WRO during step 5 in the 7. Press DISINF WRO to initiate rinse.
procedure below.
8. Readjust the reject flow rates to the normal
Caution: Sodium hydroxide is very corrosive. value with valves 41 and 70. Refer to p. 5:11
Read safety instructions before use!
9. Check the performance of the WRO. If
- Ultrasil 10 (Henkel) is an alternative alcaline necessary, perform another cleaning cycle
cleaning agent. Please contact Gambro. with an alternative cleaning agent.

HCEN9315 Rev. 10. 00


5:16
Preservation
If the system is to be taken out of operation for
shorter periods of time, i.e. up to one week, the
built-in intermediate flushing in combination
with weekly disinfection will keep the system in
good condition.

For even longer periods of no operation, preserva-


tion of the system with a 1% formaldehyde
solution should be performed.
If freezing may occur, glycerine should also be
added to the preservation solution.

Preservation solution

Caution: formaldehyde is highly toxic. Carefully


study safety instructions prior to use!

Model 37% formaldehyde glycerine,


size solution, liters liters

WRO 111 0,4 2,5


WRO 112 0,5 3,3
WRO 113 0,6 4,1
WRO 114 0,7 4,9

Preservation procedure

1. Initiate a cleaning cycle. Select detailed


display.

2. When the display shows DISINF INTAKE:


Remove the cover on the inlet water tank (4)
and slowly add the correct amount of
preservation solution.

3. After 5 - 10 minutes: Select fast stepping


function and fast-step the program until the
display shows "Open the drain valve on
WRO. Press DIS WRO".

4. Let the valve on the drain line stay closed.


Close the main inlet water valve and turn off
the electrical isolation switch on the wall.

Start up after preservation

Refer to Start up after installation.

HCEN9315 Rev. 10. 00


5:17
Programmable control unit
The electrical control cabinet in the RO-unit Maintenance
contains a programmable control unit (PLC),
type Mitsubishi FX, which monitors and controls No maintenance is normally required except
the different modes of operation of the system. exchange of a lithium battery with a life expectancy
The PLC-unit is preprogrammed at delivery. of five years.
Certain values must however be programmed
into the system at installation to adapt it for the Changing the battery in the PLC-unit:
specific clinic.
The present program version will be found under 1. Switch off mains supply with the isolation switch
Technician info. on the wall.

The left hand side of the base unit contains 2. Remove the cable connection on the front of the
LED's indicating the following conditions: PLC (going to the MAC operator´s panel)

POWER indicator 3. Remove the panel cover on the front of the PLC.
Lit LED indicates that power is on.
4. Remove the old battery from the holder.
RUN indicator
LED is lit during operation of the PLC. 5. Exchange the old battery for a new one within
30 seconds (spare part no 25 - 10048).
BATT.V voltage indicator (A capacitor in the unit will retain the memory
LED illuminates when battery voltage is low. during this period).
This will also be indicated on the MAC operator´s
panel (BATT. VOLT. LOW on the display). The 6. Reassemble the unit.
battery should then be changed as soon as
possible (see below).
If the battery is not changed within approx. one
The input connection block
month, the system will shut itself down and can be removed by loosening LED´s for
display BLOCKED. LOW BATT. VOLT PLC the two holding screws the inputs

PROG. E/CPU. E
LED´s will blink or show steady light if any of the
following conditions occur:
• programming error LED´s:
• battery voltage drop POWER
• check-sum error caused by noise RUN
interference BATT.V
• too high ambient temperature PROG.E
• CPU-error CPU.E
Inputs:
The inputs are denominated X0-X17 and X20 -
X23. The numbers are marked on the PLC-unit
and indicated by LED´s. The LED is lit when The output connection block LED´s for
can be removed by removing the outputs
corresponding input circuit is closed.
the two holding screws
Outputs:
The outputs are denominated Y0-Y17and Y20 - Fig. 3. The front of the PLC
Y23. The numbers are marked on the PLC-unit
and indicated by LED´s. The LED is lit when the
corresponding output is activated by the PLC-
program.

The functions and wiring of the in- and outputs


are listed and described in section 6; Function
and electrical diagrams.

HCEN9315 Rev. 10. 00


5:18
Water saving control
CWP100 has been equipped with water saving feature to optimize the water
usage. This equipment consists of a motor-operated three way valve on the
reject line according to the flow diagram in chapter 1. The motor valve is
denominated 138.
CWP INFO
Function
Day, date, time
During operation, the pure water consumption in the clinic is continuously Inlet water ...l/min
calculated by the PLC. At maximum consumption, the motor valve 138 is
Pure water ...l/min
fully open to drain. When the consumption goes down, it automatically
adjusts to return a portion of the reject water to the inlet tank (4). The RO reject ...l/min
lower the consumption, the more water is returned to the tank. Return flow ...l/min
Consumption ...l/min
The recovery rate or Water Conversion Factor (WCF, refer to definition Cond.in < µS/cm
below) will therefore remain constant during operation, independent of
Cond. out µS/cm
pure water consumption.
Recovery rate ...%
Recovery rate (%) = WCF = pure water consumption x 100 Rejection rate ...%
inlet water flow Mode LOCAL
Start/Stop MAN
The WCF is set under the setting level, refer to 4 on next page.
=>Technician info
The actual recovery rate is displayed under CWP INFO (press MAIN
MENU) Test operat.WRO no/yes
Test/Circ. LOOP no/yes
The reject flow rate leaving the reverse osmosis membrane modules is set WS-control:
during test operation or start up (motor valve fully open) with needle 0 AUT (aut)
valve 41 according to Maintenance in this chapter. It then stays constant.

Note: The reject flow rate at fully open motor valve must be checked on a
regular basis! Refer to Maintenance in this chapter.

A minimum reject flow to drain must always be maintained during periods of


low pure water consumption, to lead away heat that is produced by the pump.
This limit has been preset in the program, refer to Advanced settings.

HCEN9315 Rev. 10. 00


5:19
Water save - setting level

WATER SAVING CONTROL


Valve138 AUT F2.....
2
open close F5.....
F1- ..... F4 - ...... WCF..% 3
4 Recovery(WCF)set .....%
5 ->Controller set
6 ->Ret.techn.lev.2

Entering the setting and control level:


- Go to Technician info level 2 (refer to Technician info level 2 in this chapter).
- Move the cursor downwards with the arrow buttons to WS control.
- Put the cursor at -> and press ENTER.

1. Flow indication
In order to simplify setting and control of the water saving function, the actual flow rates are
continuously shown on the display:
F1 = Inlet water
F2 = Reject flow rate from the RO - unit
F4 = Return flow rate from the clinic.
F5 = Actual consumption of pure water in the clinic.

2. Control mode for the motor valve


a: Automatic control:
Normally the parameters that have been set in the program (refer to below) will automatically
control the operation of the motor valve. This is indicated by AUT on the display.
Signal for open or close from the PLC to the valve is indicated by a black square to the right of
resp. command.

b: Manual control:
1. Place the cursor at AUT .
2. Press ENTER. The text changes to MAN.
3. To open the valve: Put the cursor at open and press ENTER (open changes to OPEN).
The black square after OPEN confirms that a signal is issued from the PLC to the valve.
To deactivate the OPEN signal, put the cursor at OPEN and press ENTER. OPEN then
reverts to open and the valve remains in the present position.
4. To close the valve: Put the cursor at close and press ENTER (close changes to CLOSE).
The black square after CLOSE confirms that a signal is issued from the PLC to the valve.
To deactivate the CLOSE signal, put the cursor at CLOSE and press ENTER. CLOSE then
reverts to close and the valve remains in the present position.

3. WCF value
WCF is short for Water Conversion Factor. Actual WCF value is displayed here.

HCEN9315 Rev. 10. 00


5:20
4. Recovery (WCF) set
WCF is short for Water Conversion Factor and represents the percentage of the inlet water that is
converted to pure water. Here you set the desired WCF. The set value and actual value at 3. on
previous page should correspond during normal operation.
Factory set value WRO Chem: 67 %

Please contact Gambro before changing the water conversion factor.

Caution: Too high WCF will increase the risk for fouling of the membranes in the CWP.

5. Controller set: Entrance to the advanced setting level for the water saving function.

Note: This level is only intended for Gambro technicians.

To enter this level, put the curser at -> and press ENTER, enter Technician code 3 and press
ENTER again.
Please refer to next page for more information.

6. Ret.techn.lev.2: To return to Technician info level 2, place curser at -> and press ENTER. Enter
Technician code 2 and press ENTER again.

HCEN9315 Rev. 10. 00


5:21
Water saving - advanced setting level

WATER SAVING CONTROL


Level 3 settings
Min.flow V138 xx l/m
1
reset xx l/m
2 Hysteresis WCF ......%
3 P-factor .......
4 Pulse length .... s
5 Pulse cycle .... s
6 Start pulse ... s
7 ->Ret.to WS-lev.2

Caution: The information on this page is intended for Gambro techicians. The set values should
not be changed before consulting Gambro.

1. Min flow V138 During periods of low pure water consumption, the min. flow regulation
reset system will maintain the reject flow to drain between the flow rates set at
this position.

2. Hysteresis WCF Variation of the actual value (±) from the WCF set value inside which no
adjustments of the position of the value is made.
Recommended set value: 1%

3. P-factor The pulse from the regulation system to open or close the motor valve is
proportional to the deviation from the WCF set value. This proportional-
ity factor determines the size of the pulse increase when the deviation
increases.
Recommended set value: 1

4. Pulse length The minimum duration of a pulse (with no compensation for deviation and
p-factor).

5. Pulse cycle The time between pulses when the system is in regulating mode.
Recommended set value: 10 seconds

6. Start pulse The motor valve closes when the CWP is stopped. At start of operation, an
extended pulse is issued to open the valve into operating range. The dura-
tion of this pulse is set here.
Recommended set value: 5 seconds

7. ->Ret. to WS-lev.2 To return to Water Saving Control level 2, place cursor at -> and press
ENTER.

HCEN9315 Rev. 10. 00


5:22
6. Function diagrams
Electrical diagrams

Contents

Block diagrams for technicians


Block diagram for technicians:1 .................... 2
Block diagram for technicians:2 .................... 3

Function diagrams
Operation ....................................................... 4
Disinfection of the loop .................................. 5
Disinfection of the WRO ................................ 6
Cleaning of the WRO ..................................... 7

In- and outputs of PLC-unit .......................... 8

Data sheets:
Flow transmitter FX1000 .............................. 9
Conductivity transmitter CX200 ................. 10
Conductivity transmitter CX2000 ............... 11

Electrical diagrams ....................................... 13

HCEN9315 Rev. 05. 04


6:1
210
At regular intervals
210 Block diagram 1 for
STAND BY
DISINFECTION
STAND BY technicians
Dial code 1 flush loop/drain
From "Technician Info
200 210
level 2"
STOP ENTER
.. ....
START >>>>>>>>>
START UP ... MIN STAND BY DISINF
WRO
....uS/cm to loop/drain
STOP 250

205 CLEAN. WRO???


DISINF No=press STOP
LOOP
OPERATION ...uS/cm 250 YES=press DIS. WRO
DISINF
WRO 255
DISINF. LOOP???
DISINF
250 No=press STOP WRO
260
Yes=press DIS. LOOP
DISINF. WRO??? DISINF
LOOP CLEAN. WRO ..MIN
No=press STOP
255 Add cleaner ...M
YES=press DIS. WRO
DISINF. LOOP???
DISINF
255 WRO Move the Move dos connector 260

DISINF. WRO??? connector to LOOP and press


DISINF. LOOP CLEAN. WRO ...MIN
Moe dos connector Contact ....M
DISINF
to WRO and press LOOP 260
DISINF. WRO Move the 262
connector DISINF. LOOP ...MIN
260
Disinf. intake ....M CLEANING WRO ..MIN
DISINF
DISINF. WRO ...MIN WRO
Disinf. intake ...M 260 press DIS. WRO
260
260 DISINF
DISINF. LOOP ...MIN WRO
Contact ....M CLEAN. WRO ...MIN
DISINF. WRO ...MIN
Rinse ....M
Contact ....M
260
260
DISINF. LOOP ..MIN
DISINF. WRO ...MIN Rinse loop/WRO/monit ..M
Rinse ....M

Flushing of WRO and Programmed circulation of water


loop at regular intervals If dos. connector already has If dos. connector has NOT in the loop to enable autorinse of
265/272 been moved to OPERATION been moved to OPERATION dialysis machines
272 265/272
265
Flushing
Rinse circulation
DISINF. FINISHED
DISINF. FINISHED
265 Move the DISINF. FINISHED DISINF. FINISHED
TEST WRO connector Move dos.connector
Test op.=press START to OP. to OP. - Test water
272

START
CLEANING FINISHED
265
TEST WRO
270 270 Residual 271 Test op.=press START
TEST OPERATION test
TEST OPERATION
WRO WRO TEST WRO
STOP
Wait ...uS Test water ...uS Test=press START
Accept = press STOP Accept=dial code....
START
STOP
Dial code 1
ENTER

272
Residual
270 270 test 271

START TEST OPERATION TEST OPERATION


DISINF FINISHED LOOP LOOP
STOP TEST LOOP
TEST LOOP Wait ...uS Test water ...uS Test=press START
Test op.=press START Accept=press STOP Accept=dial code
START
Dial code 1
ENTER

HCEN9315 Rev. 05. 04


6:2
MAIN Day,date time
MENU
Inlet water
Pure water
...l/min
... l/min
Technician´s Block Diagram:2
Go to "Block
diagram 1 for RO reject ...l/min 810 811
technicians" Return flow ...l/min
--------DISINF WRO------ --------DISINF. LOOP-------
Consumption ...l/min
-> Change timers -> Change timers
Cond.in < ..µS/cm
DISINF.INTAKE DISINF. INTAKE
Cond. out ..µS/cm
Recovery rate ...% Total time ... m Total time ... m
Rejection rate ...% CONTACT Return from loop
Mode LOCAL/MAN Total time ... m to drain ... m
Start/Stop MAN/AUT ENTER
RINSE
ENTER
to WRO ... m
-> Technician info
Test operat. WRO no/yes Total time ... m CONTACT
Test/Circ. LOOP no/yes Total time ... m
WS-control -------------------------------- Pause ... m
ENTER 0 AUT (aut) Password: code 2 Run ... m
-------------------------------- RINSE
TECHNICIAN INFO Total time ... m
-> Level 2 Rinse WRO+loop ... m
Rej. START UP l/min ENTER
Final rinse WRO
Running time ...h 820
... m
Inlet water ...m3 ENTER
--------DISINF WRO------ Rinse monitors ... m
ENTER Disinf. cycles xx DISINF.INTAKE ENTER
Low level alarm xx Total time ( xx) ... m --------------------------------
-> PROGR.DISINF. ENTER CONTACT Password: code 2
-> PLC-info Total time ( xx) ... m --------------------------------
Progr.version MAC ENTER RINSE
RCXXXXXX Total time ( xx) ... m
Progr.version PLC ENTER
Reload old values
RCXXXXXX no/yes 821

Save new values no/yes --------DISINF. LOOP-------


--------------------------------
DISINF. INTAKE
Password: code 2
801 809 Total time ... m
--------------------------------
SELECT PROGRAMME Return from loop
ENTER -> Disinf. WRO to drain ( xx) ... m
Total stop: to WRO ( xx) ... m
Link 69-70 and -> Disinf. LOOP
press STOP CONTACT
Fast stepping on/off ENTER Total time ( xx) ... m
Date: xx:xx:xx
Time: xx:xx:xx
Pause ( xx) ... m
Day: .... Run ( xx) ... m
->TIME CHANNELS RINSE
CHOICE --------------------------------
Stand by to loop no/yes Total time ... m
Flow alarm in OP no/yes Password: code 2 WRO+loop ( xx) ... m
Loop leak. alarm no/yes -------------------------------- Final rinse
Mode LOCAL/REMOTE
Local Start/Stop AUT/MAN WRO ( xx) ... m
Ext. ind. on/off Monitors ( xx ... m
ENTER
Ext. sign. test no/yes
(Press DISINF.WRO!!)
------------------------------------
900
Cleaning no/yes Reload old values
LIMIT VALUES Change reg. values
no/yes
Conductivity: LOOK AT:
cond.out (C2) Save new values no/yes
Register D.......
-Warning ( ..) ...µS
-High ( ..) ...µS ENTER Value ...........
-Intake:Low ( ..) ...µS Timer T ........ --------------------------------
-Test ( ..) ...µS
Value ........... Password: code 3
cond.return (C4) --------------------------------
-Intake: Low ( ..) ...µS Counter C........
-Rinse: High ( ..) ...µS Value ...........
-Test ( ..) ...µS
Flow: T XXXXXXXXX ENTER
-Reject ( ..) l/min R XXXXXXXXX 901
-Pure ( ..) l/min PV XXXXXXXXX
-Leak. ( ..) l/min CHANGE VALUE:
delay ( ..) m reg. value new set
CALIBRATION COND
Inlet water ...% MAIN D...... ....... ....... no/yes
Ret. water ...% Pure water ...% MENU -------------------------------------
Inlet< xxx Pure xxx
->WS control
Test values no/yes
START OPERATION 1 Delivery values no/yes
COUNTERS
Start up ( ..) ...m START OPERATION 2
Ret. to drain ( ..) ...m STOP OPERATION 1
SB pause ( ..) ...m
STOP OPERATION 2
ENTER EXIT
SB operat. ( ..) ...m I 1: ..............
ENTER RINSE CIRC. 1
Disinfection:
Restart ( ..) ...m RINSE CIRC. 2
ENTER I 2: ..............
Max time dev. ( ..) ...m I 3: ..............
Move dos.conn ( ..) ...m
Operation:
I 4: ..............
Restart ( ..) ...s WATER SAVING CONTROL
Delay RO-pump ( ..) ...s Valve 138 AUT F2-XX
Reload old values WATER SAVING CONTROL
no/yes open close F5-XX Level 3 settings
Save new values no/yes F1-XX F4-XX WCF XX% Min. flow V138 xx l/min
GSS on/off
Recovery (WCF) set X% reset xx l/min
->Controller set ENTER
Hysteresis WCF ..%
-> Ret. tech.lev.2 P-factor ...
ENTER Start pulse ...
2000 10 01 /TW --------------------------------
-> Ret. to WS-lev.2
Password: code 3
--------------------------------

HCEN9315 Rev. 05. 04


6:3
6:4
Technician info level 2
Operation Valid for prom versions RC9701VX(PLC) and RC9701X (MAC)
Total stop:
Link 69-70 and
Pos. PLC press STOP
Object Start up Operation Stand by Test operation
no output Fast stepping on/off
flush of flush Date: xxx
pause run WRO to loop Time: xxx
WRO of loop
Day: xxx
Inlet water valve 1 Y6 ->TIME CHANNELS
CHOICE
Stand by to loop no/yes
Main pump RO-unit 2 33 Y1 Flow alarm in OP no/yes
Loop leak. alarm no/yes
5 8b Mode LOCAL/REMOTE
Pure water flush to drain 36 Y7 3
8a 3 Local Start/Stop AUT/MAN
Ext. ind. on/off
Ext. sign. test no/yes
Dosing pump 45 Y5 (Press DISINF.WRO!!)
Cleaning no/yes
Outlet valve to loop 48 Y4 3 9 LIMIT VALUES
8a Conductivity:
cond.out (C2)
Return from loop to drain 54 Y12 8a -Warning ( ...) ...µS
-High ( ...) ...µS
-Intake:Low ( ...) ...µS
Return from loop to WRO 106 Y13 -Test ( ...) ...µS
cond.return (C4)
Disinf. flow reducer 136 Y3 -Intake: Low ( ...) ...µS
8a
-Rinse: High ( ...) ...µS
-Test ( ...) ...µS
Ext.operat.indication Y11 Flow:
-Reject ( ...) ..l/min
External A-alarm signal 10 Y2 -Pure ( ...) ..l/min
-Leak. ( ...) ..l/min
Motor valve open to drain 138 Y14 delay ( ...) ..m
CALIBRATION COND
Motor valve close to drain 138 Y15 Inlet water ...%
Ret. water ...% Pure water ...%
Inlet< xxx Pure xxx
=Regulating ->WS control
1 4 6 7 COUNTERS
1. Initial flush to drain of the WRO. Setting range: 2 - 30 minutes. 1. Start up ( ...) ...m
4. Ret. to drain ( ...) ...m
In case of a short stop (< 10minutes), elapsed time will remain. 6. SB pause ( ...) ...m
2. Start of main pump is delayed at every start. Delay setting range: 5 - 60 seconds. Factory setting: 10 seconds. 7. SB operat. ( ...) ...m
3. Conductivity check.Valve 48 opens 30 seconds after the conductivity is approved (is below high cond. alarm limit). Disinfection:
Restart ( ...) ...m
4. Flush of loop to drain (1 - 60 minutes); This mode will be activated only if the unit has been in disinfection or cleaning mode.
Max time dev. ( ...) ...m
5. This valve is open for 2 minutes after the STOP button has been pressed. Move dos.conn ( ...) ...m
6. Pause time when unit is in stand by mode (30 - 240 minutes). Operation:
7. Intermediate flushing when unit is in stand by mode (1 - 30 minutes). Restart ( ...) ...s
2. Delay RO-pump ( ...) ...s
8a. If yes has been selected under "Stand by to loop", the water will go to the loop provided that the conductivity is approved. Reload old values
8b. If no has been selected under "Stand by to loop", the water will go to drain via valve 36. no/yes
9. The WRO starts with 30 seconds internal circulation before the outlet valves to the loop open. Save new values no/yes

HCEN9315 Rev. 05. 04


10. The alarm signal is activated by normal conditions, i.e. when no A-alarm is issued. 2000 10 01 / TW GSS on/off
WRO Chem - Disinfection of loop 9 Rinse 10 20
Object Pos. PLC Disinfectant Stand by Valid for prom versions
Contact WRO+ final, moni- Rinse Test Test RC9701VX(PLC) and
no output 1 intake loop

code
code
8 loop 11 WRO 14 tors 15 pause run circ. WRO
7 RC9701X (MAC)
Inlet water valve 1 Y6 18
-----DISINF. LOOP----

HCEN9315 Rev. 05. 04


Main pump RO-unit 33 Y1 2 13 1 DISINF.INTAKE
6
17 Total time ....m
Pure water flush to drain 36 Y7 12 16
delivery
Return from loop settings
4 to drain ( xx) .. m (10)
Dosing pump 45 Y5 6 19 19
5 to WRO ( xx) .. m (5)
22
Outlet valve to loop 48 Y4 8 CONTACT
Total time ( xx) ... m (10)
Return from loop to drain 54 Y12 4 Pause ( xx) ... m (5)
Return from loop to WRO 106 Y13 Run ( xx) ... m (3)
5
10 RINSE
Disinf. flow reducer 3 136 Y3 Total time ... m
11 WRO+loop ( xx) ... m (240)
External A-alarm signal Y2 21 Final rinse
14
Motor valve open to drain 138 Y14 23 WRO ( xx) ... m (30)
15 Monitors ( xx) ... m (0)
Motor valve close to drain 138 Y15 24 ................................................
Reload old values
1. Disinfectant intake. The disinfection solution is fed into the loop. Total time is the sum of times set under 4 and 5. no/yes (no)
2. At initiation of disinfection, the start of the main pump is delayed 40 seconds to allow the dosing pump to fill up the dosing line. Save new values no/yes (no)
The delay of the start of the pump is 10 seconds in all other cases.
3. Valve 136 has a drilled hole which allows a certain flow also when the valve is closed. It is closed during disinfectant intake to
reduce flow into the loop during this phase. The function of valve 136 is identical to valve 48 in all other modes of operation.
4. The return from the loop is diverted to drain via valve 54 during the time set here (1 - 240 minutes).
5. Integration of the WRO in the disinfection cycle by opening valve 106 (1 - 240 minutes).
6. If dos. conn. error or low level chem occurs during disinf. intake, main- and dosing pumps stop and time counting freezes. If the fault is not corrected or
STOP is not pushed within 30 min., the program restarts from where it was. The pumps will stay switched off during the remaining part of disinf. intake.
7. At the end of the intake period, valve 48 closes and valve 36 opens for 3 seconds to disinfect the drain line. Valve 36 then also closes but the main pump
continues to run for another 7 seconds to fill the overflow line in the WRO with disinfection solution.
8. Contact period for the loop (0 - 9999 minutes). To avoid excessive membrane contact times, the WRO can be set to run periodically to rinse out the
disinfectant solution from the WRO. The pause periods can be set between 10 - 60 minutes, run time between 3 - 10 minutes.
9. The intake period can be restarted during Disinf. intake or Contact by pressing DISINF LOOP for minimum 5 seconds. 36
10. Rinse. Total time is the sum of times set under 11, 14and 15. 48
11. Valve 54 is open during the first part of the rinse cycle (Rinse WRO+loop) to flush the loop (30 - 240 minutes).
12. Every minute valves 36 and 48 flip to reach the pure water drain and overflow lines in the WRO. Refer to the figure! 55s 3s 2s 55s
13. Main pumps stops for 10 seconds every 5 minutes.
14. Valves 48 and 106 first open for 20 seconds to flush the return line to the WRO. Valve 36 then opens for the final rinse of WRO (10 - 30 minutes),
15. Rinse phase (Monitors) to enable automatic rinse of the dialysis machines directly after rinse of WRO and loop (0-240 minutes).
16. Valve 36 closes for 3 seconds every minute.
17. The valves stay open for two minutes after a stop to relieve pressure in the system.
18. Intermittent flush of the system after loop disinfection. This flush always includes the loop, provided that the cond. is approved (see 19.).
19. Valves 48, 136 and 54 opens after 30 sec. if the cond. is below the high cond. alarm limit. If the cond. is above this limit, valve 36 stays open.
20. To enable rinse of dialysis machines during a preset time period after central chem. disinf. Time period is set under TIME CHANNELS.
21. The alarm signal is activated by normal conditions, i.e. when no A-alarm is issued.
22. The WRO starts with 30 seconds internal circulation before the outlet valves to the loop open. "wait" is displayed during this period.
23. Motor valve 138 open to drain for 10 seconds after each pump start.
24. Motor valve 138 closes to drain for 10 seconds after each pump start. 2000 10 01 / TW

6:5
6:6
Disinfection of WRO Valid for prom versions RC9701VX(PLC) and RC9701X (MAC)

Object Pos. PLC Disinf. Contact Rinse Test Test Stand

code
code
no output intake period WRO loop by
Inlet water valve 1 Y6 3 5

Main pump RO-unit 2 33 Y1 6 9


delivery
settings
Pure water flush to drain 36 3 7 10
Y7
(refer to block diagram
for technicians)
Dosing pump 45 Y5
-------DISINF WRO------
1. DISINF. INTAKE
Outlet valve to loop 48 Y4
Total time ( xx) ....m (5)
4. CONTACT
Return from loop to drain 54 Y12 Total time ( xx) ....m (10)
8. RINSE
Return from loop to WRO 106 Y13 Total time ( xx) ....m (100)
Reload old values
Y3 no/yes (no)
Disinf. flow reducer 136
Save new values no/yes (no)
Ext.operat.indication Y11

External A-alarm signal Y2 11

Motor valve open to drain 138 Y14 12 13


Motor valve close to drain 138 Y15 12 13

1 4 8

1. Disinfectant intake period. Setting range: 1 - 30 minutes.


2. Start of main pump is delayed at every start ( preset:10 seconds)
3. These valves open the first 2 minutes during disinfectant intake to improve distribution of disinfectant.
4. Contact period. Setting range: 1 - 240 minutes.
5. Opens 5 seconds every minute.
6. Cycles of 2 minutes of pause and 4 minutes of operation.
7. Opens for 2 seconds every minute
8. Rinse period. Setting range: 30 - 240 minutes.
9. Stops 10 seconds every 5 minutes.
10. Closes 5 seconds every minute. 2000 10 01 / TW
11. The alarm signal is activated by normal conditions, i.e. when no A-alarm is issued.
12. Valve 138 is opened to drain for 5 seconds after each pump start.
13. Valve 138 is closed to drain for 10 seconds after each pump start.

HCEN9315 Rev. 05. 04


DISINF Valid for prom versions RC9701VX(PLC)
WRO
Cleaning of WRO-unit and RC9701X (MAC)

Object Pos. PLC Adding Contact / Wait Rinse Test Test Stand delivery
settings

code
code
no output cleaner Circulation WRO loop by

HCEN9315 Rev. 05. 04


Inlet water valve 1 Y6 Refer to
block diagram for technicians.
Main pump RO-unit 2 33 Y1 6
-------DISINF WRO------
1. DISINF. INTAKE
Pure water flush to drain 36 Y7 7 8 Total time ( xx) ....m (5)
3. CONTACT
Dosing pump 45 Y5 10 Total time ( xx) ....m (10)
5. RINSE
Y4 Total time ( xx) ....m (100)
Outlet valve to loop 48
Reload old values
no/yes (no)
Return from loop to drain 54 Y12 Save new values no/yes
(no)
Return from loop to WRO 106 Y13

Disinf. flow reducer 136 Y3

Ext.operat.indication Y11

External A-alarm signal Y2 9

Motor valve open to drain 138 Y14

Motor valve close to drain 138 Y15 11

1 3 4 5
1. Time for adding cleaning solution to inlet tank. Setting range: 1 - 30 minutes.
2. Start of main pump is delayed at every start, preset at 10 seconds (delay time set under Tec. info 2 ).
3. Contact period. Setting range: 1 - 240 minutes.
4. The unit stops when contact period is completed. To continue, press DISINF WRO.
5. Rinse period. Setting range: 30 - 240 minutes.
6. Stops 10 seconds every 5 minutes.
7. Opening of valve 36 is delayed 5 minutes.
8. Closes 5 seconds every minute.
9. The alarm signal is activated by normal conditions, i.e. when no A-alarm is issued. 2000 10 01 / TW
10. This valve will stay open 2 minutes after stop.
11. Motor valve 138 is closed to drain for 10 seconds after each pump start.

6:7
PLC in - and outputs
(The numbers within parenthesis refer to the flow diagram in the Operator´s and Service manual)

Input Function

X0 Flow meter pure water (121)


X1 Flow meter pure water return line from clinic (51)
X2 Conductivity cell inlet water (32)
X3 Conductivity cell pure water (35)
X4 Dosing connector, loop disinfection position (130)
X5 Dosing connector, operating position (44)
X6 Solution connector, WRO disinfection position (53)
X7 1: Thermal relay (F1), motor protector main pump (33)
2: Fast stepping performed without being selected under Tec. info.
X10 Operation indication
X11 Level switch in Dialox container (47)
X12 Level switch collecting tray (62)
X13 Level switch inlet water tank (6)
X14 Flow meter RO-reject (42)
X15 "Closed to drain"-signal for motor valve 138
X16 External run signal
X17 External blocking of operation
X20 Remote control unit in pos. 0
X21 Remote control unit in pos. RUN
X22 Remote control unit in pos. AUT
X23 Remote control unit in pos. DIS

Output Function

Y1 Contactor K1, main pump RO-unit (33)


Y2 Relay K11, external A -alarm, activated by normal cond. (term. 55, 56 and 61, 62, 63)
Y3 Solenoid valve 136 with drilled hole, in series with valve 48
Y4 Solenoid valve outlet pure water (48)
Y5 Dosing pump Dialox (45)
Y6 Relay K13, solenoid valve inlet water (1). Start booster pump (term. 31 & 32 )
Y7 Solenoid valve in pure water flush line (36)
Y11 Relay K14, external operation indication (term. 29, 30 )
Y12 Solenoid valve for return from loop to drain (54)
Y13 Solenoid valve for return from loop to inlet tank (106)
Y14 Motor valve (138), signal to open
Y15 Motor valve (138), signal to close
Y16 Conductivity cell (144) in return line
Y20 External lamp indication unit, red lamp (A-alarm)
Y22 External lamp indication unit, orange lamp (B-alarm)

HCEN9315 Rev. 05. 04


6:8
HCEN9315 Rev. 05. 04
6:9
HCEN9315 Rev. 05. 04
6:10
HCEN9315 Rev. 05. 04
6:11
Electrical diagrams
Refer to separate documents for relevant voltage

HCEN9315 Rev. 05. 04


6:12
7. Spare parts list WRO Chem
This spare parts list covers mechanical and electromechanical components in WRO Chem.
For electrical components, please refer to the component list in the Electrical diagrams (section
6).

Contents
WRO Chem, view from right ................................... 2
WRO Chem, front view ............................................ 3
Spare parts list ......................................................... 4
Proportioning pump ................................................. 5
RO-module ............................................................... 6

HCEN9315 Rev. 10. 00


7:1
15

21

20

19

18

30
9
8

8 25
22
24
6
6
6
29

14 23,24,25

13 7

10 5

1 14

3 28

16 32

27
35

HCEN9315 Rev. 10. 00


7:2
33

32
16
16
32

36

17
32

34

31

HCEN9315 Rev. 10. 00


7:3
No Description Part no Pos. in Remarks
flow dia

1 Pick-up tube/level switch and plug 25-10174 47


- check valve in plug 25-10003
2 Needle valve 25-10009 41,71
3 Lower frame 25-10126 - WRO111 - 113
Lower frame 25-10127 - WRO114
5 Flow meter probe 25-10084 42,121,51 1,5 - 20 l/min
- o-ring large for d:o, silicone 25-10202 -
- o-ring small for d:o, silicone 25-10203 -
6 Inductive sensor 25-10012 44,53,130
7 Motor valve 230V 25-10509 138
8 Proportioning pump (s) 25-10260 45 see page 5!
9 Hose PE 6/4" 25-10385 1 meter
10 PVC hose 8/4" 25-10235 1 meter
13 RO-pump module, 50 Hz, complete 25-10758 33 SP2A-33, WRO 111-112
25-10744 33 SP3A-29, WRO 113-114
RO-pump module, 60 Hz, complete 25-10225 33 SP2A-21, WRO 111-112
25-10??? 33 SP3A-18, WRO 113-114
- o-ring set for pump module 25-10151
End plug for pump, top 25-10752
End plug for pump, bottom 25-10750
Pressure vessel for pump 25-10754 - WRO 111-114
14 RO-module, complete 25-10755 34 See below
15 Upper frame 25-10677 - WRO111-113; specify model
Upper frame 25-10678 - WRO114
16 Conductivity cell 25-10023 32,35,144
17 Overflow valve 3-50 psi 25-10025 52
18 Raw water tank PVC 25-10259 4
19 Float valve 25-10099 5
20 Cover 25-10038 -
21 Level switch raw water tank 25-10140 6
22 Solution connector, male 25-10130 110,111,131
- o-ring for d:o 25-10104 -
23 Solution connector female male thread 25-10256 132
24 PVC-connector for 25-10256 25-10257 -
25 Check valve in PVC-connector 25-10258 43
26 Connector panel 25-10261 - WRO111 - 113
Connector panel 25-10264 - WRO114
27 Shelf for container 25-10182 -
28 Level switch for collecting tray 25-10141 61
29 T-connector red/black 25-10142 -
30 Connector red/black 25-10143 -
31 Funnel 25-10157 134
32 Solenoid valve 25-10171 1,36,48,54,106 L131Z323D
- coil for d:o 25-10172 -
33 Overflow valve 50-150 psi 25-10024 52
34 Flow control 1,4 GPM 25-10108 122 WRO111
2,0 GPM 25-10109 122 WRO112
3,5 GPM 25-10110 122 WRO113, WRO114
35 Collecting tray 25-10265 - WRO111 - 113
Collecting tray 25-10266 - WRO114
36 Solenoid valve w. drilled hole Ø 2,5 mm 25-10360 136 WRO111, WRO112
Solenoid valve w. drilled hole Ø 3,0 mm 25-10361 136 WRO113, WRO114
- coil for d:o 25-10172

HCEN9315 Rev. 10. 00


7:4
Item Denomination Order no Remarks

Proportioning pump, complete 25-10260

1 nipple incl. nut, suction side 25-10221


2 o-ring 3/8" 25-10222
3 check valve incl. valve guide 25-10003
4 pump head for proportioning pump 25-10421
5 o-ring for pump head 25-10422
6 membrane for proportioning pump 25-10420
7 nipple incl. nut, pressure side 25-10263
8 Fuse 1A slow-blow 25-11001

2
3

4
6
5
3
2
8
1

HCEN9315 Rev. 10. 00


7:5
RO-module (LE) complete 25-10755

3 4 5 4 3

6 7

No Description Part no Remarks

2 pressure vessel 25-10747


3 locking ring (half moon shaped) 25-10748 4 required for complete module
4 end plug with o-rings 25-10749 incl. o-rings (2x25-10113, 4x25-10114)
- o-ring 89,1 x 5,7 25-10113
- o-ring 18,77 x 1,78 25-10114
5 bolt + washer + nut 25-10210 12 required for complete module
6 short LE- membrane 25-10495
7 long LE- membrane 25-10494
8 connector for RO-modules 25-10193
- o-ring set for one RO-module 25-10119 4 x 25-10113, 16 x 2510114

HCEN9315 Rev. 10. 00


7:6
8. Technical data WRO Chem
Pure water Connections
Minimum Capacity in l/min at a pure water Inlet: PVC female union, fits to pipe OD 25 mm
outlet pressure of 200 kPa: Drain: PVC female union, fits to pipe OD 32 mm
Drain from tray: 1/2" female thread
Temp 111 112 113 114 Pure water outlet & return: fits to pipe OD
+ 5°C 7 13 18 22 25mm
+10°C 8 15 20 24
+15°C 10 17 22 26 Membranes
+20°C 12 19 25 28 Membrane material: Modified polyamide,
thin film composite
Quality: Membrane configuration: Spiral wound
Depends on inlet water quality. If potable water is pH-tolerance: 2 - 11
used and the system is properly maintained, the
following rejection rates will be obtained:

Total dissolved salts: >95% Power Supply


Bacteria (CFU) & endotoxins (EU): >99% Mains voltage: 230/400 V, 50Hz, three-phase
Water Conversion Factor: max. 75% (five wires)
Power rating:1.8 kW WRO 111 - 112
2.5 kW WRO 113 - 114
Fuse: 10 AT (slow blow)
Water Supply
Model 111 112 113 114
Measuring Ranges
Min. input, l/min: 20 30 40 50
Temperature: 0 - 100 °C (±10%)
Min. input pressure, kPa:200 250 300 350
Maximum flow occurs during flushing.
Flow:
Pure water: 3 - 40 l/min (±10%)
Max. input pressure: 500 kPa (all models)
Reject flow: 0.2 - 15 l/min (±10%)
Temperature: +5°C to +25°C *
Return flow: 0.2 - 20 l/min (±10%)

Conductivity:
Quality:
Inlet water: 100 - 1000 µS/cm (±15%)
Potable water should be used. Additional
Pure water: 2 – 200 µS/cm (±15% or
pretreatment is normally necessary. Membrane and
±1,5 µS/cm if < 10 µS/cm)
machine life expectancy depends on inlet water
quality. It is recommended not to operate the CWP
outside the following limits:

Hardness <1 °dH


Iron < 0.1 mg/l
Manganese < 0.1 mg/l
Chloride < 100 mg/l
Silica < 25 mg/l
Total dissolved salts < 1500 mg/l
Chlorine < 0.1 mg/l
Fouling Index (S.D.I) 5 * Maximum +20°C if peracetic acid is used for disinfection
** Including handle, 40 mm

Drain Requirements
The information herein imay be subject to change without
Required capacity in l/min:
further notice

Model 111 112 113 114


20 30 40 50

HCEN9315 Rev. 10. 00


8:1
8. Technical data WRO Chem
Ambient temperature
Shipping and storage: -10°C to +40°C
Operation: +5°C to +35°C

Dimensions
Model D x W x H (mm)
111 - 113 : 670** x 700 x 2010
114 : 670** x 890 x 2010
500 mm space is required on both sides of the unit

Weight
Model 111 112 113 114
Unit (kg): 210 220 230 270
Unit + packing (kg): 340 350 360 420
Operation (kg): 225 240 255 300

Logging Interface
RS 232, 9 pin male
According to EIA 232 C
Max input Voltage: ± 15 VDC
High Level min output: + 5 VDC
Low level min output: - 5 VDC
Max Current: ± 5 mA

* Maximum +20°C if peracetic acid is used for disinfection


** Including handle, 40 mm

The information herein imay be subject to change without


further notice

HCEN9315 Rev. 10. 00


8:2
9. Appendices

Caution: This information is general. For full


information about the function of the different
dialysis machines, please refer to the respective
Operator´s and Service manuals.

Central Chemical disinfection

HCEN9315 Rev. 10. 00 9: Appendix


Central chemical disinfection
Integrating the dialysis machines in the loop disinfection procedure

General Central chemical disinfection in


AK 100, AK 200 and AK 200 ULTRA.
Caution: The information below is general. For
full information about the function of the differ- Caution: For full information about central
ent dialysis machines, please refer to the respec- chemical disinfection on AK 100, AK 100
tive Operator´s and Service manuals. ULTRA, AK 200 and AK 200 ULTRA, please
refer to the respective manuals!
The WRO Chem offers the possibility to inte-
grate the dialysis machines type Gambro in the These machines can be preset for central chem,
loop disinfection procedure. This is called cen- which means that the pick-up tube does not have
tral chemical disinfection or integrated to be extracted from the heating vessel during
chemical disinfection. This will also allow the intake phase.
disinfection of the connection hoses between the
loop and the dialysis machines. Three predefined disinfection programs can be
preset in the information display (shown when
Caution: The AK 90S does not support central pressing the disinfection button). By default, this
chemical disinfection. is Peracetic acid, Hypochlorite and Formaldehyde.
If presetting of the machine for Central disinfec-
The AK 90S can, however, still be run together tion is desired, one of the other programs must
with the WRO Chem in a mode that is described be removed and replaced by Central disinfection.
below.
Assume that Central disinfection is to be in-
AK 95, AK 100, AK 100 ULTRA, AK 200 and stalled in position three. Use external preset
AK 200 ULTRA all have a preset denominated and change the parameter S217. Default value is
Central Chem. They also have a ”real time 0 (Formaldehyde). Change this to 4 (Central
clock” and an ”auto rinse” feature which enables disinfection). The contact time for this position is
presetting of a desired ”ready time”, i.e. when defined in S219. Default is 20 minutes. This can
the machine should be rinsed out and ready for be changed to 1 minute since a contact time will
dialysis. be obtained during the flush of the CWP loop
anyway. Preset parameter S218 (Concentration
Caution: Only disinfectants based upon perace- of disinfectant) is not valid when Central disin-
tic acid are approved for use in the WRO Chem! fection is used in this position, so it may be left
The WRO Chem has been validated with Dialox, as it is.
which is a peracetic acid based disinfectant.
When the disinfectant intake phase has been
Warning: The dialysis machines must always initiated on the WRO Chem and the disinfectant
be tested before initiation of dialysis to verify has reached the first dialysis machine in the
that they are free from disinfectant ! loop, start this machine, press the Disinfectant
button, choose Central disinfection and then
Warning: If a dialysis machine is started while press the Disinfectant button for three seconds.
disinfectant is present in the loop, a complete The machine will now make a short drain and
rinse cycle with clean water must be performed then start the central disinfection program.
before using that machine for dialysis. When the fillup phase is completed (this takes
approx. three minutes for AK 100 and AK 200,
6-7 minutes for AK 100 ULTRA and AK 200
ULTRA ), the attention messages ”CENTRAL
CHEM DISINF. COMPLETED, Press Rinse/
Drain” will be issued.

9. Appendix HCEN9315 Rev. 10. 00


Central chemical disinfection mode in
AK 95
Two alternative actions can now be performed: As for AK 100 AK 200 and AK 200 ULTRA, the
AK 95 can also be preset to run ”central chemi-
Alternative 1. cal disinfection”:
1. Wait until the entire loop disinfection pro-
gram of the WRO Chem has been completed Set the preset ”Central chem” to TRUE in one
according to the Operation instructions for of the three different Chemical disinfection
the WRO Chem. positions (Alt 1, 2 or 3). The machine will then
take in the entire disinfectant agent through
2. After confirmation that the loop is free INVA. Set the corresponding Dwell time to
from residual disinfectant: "Forever". This will stop the machine after
Press the Rinse/Drain button.The machine fillup (approximately 3 minutes), when the
will then do a Post Chemical Rinse program. machine is put in logical OFF (unlit ON/OFF
button).
Alternative 2
Switch off the machine with the ON/OFF Also for the AK 95, two alternative actions can
button and let the machine do an AUTO now be performed:
RINSE procedure later on, i.e. when Rinse
circulation is in progress in the WRO Chem. Alternative 1.
Please refer to the manual for WRO Chem. 1. Wait until the entire loop disinfection pro-
gram of the WRO Chem has been completed
Note! If the second alternative is selected, make according to the Operation instructions for
sure that the AUTO RINSE function is set and the WRO Chem.
activated (AUTO RINSE button steady lit )
before starting the Central chemical disinfec- 2. After confirmation that the loop is free
tion program. Otherwise the program will not from residual disinfectant:
allow Auto rinse. Press the Rinse/Drain button.The machine
will then do a Post Chemical Rinse program.

Caution: Always perform a test to verify that Alternative 2


the dialysis fluid is free from residual chemicals Switch off the machine with the ON/OFF
before initiating dialysis. button and let the machine do an AUTO
RINSE procedure later on, i.e. when Rinse
circulation is in progress in the WRO Chem.
Please refer to the manual for WRO Chem.

This will switch off the machine after fill-up


(approx three minutes), when the machine is put
in logical OFF (unlit ON/OFF button).
Use the AUTO RINSE function to rinse out the
machine in the morning, when the CWP is ready
and delivering fresh water.

Note: After initiation of the disinfection program


of the AK 95, the operator has to wait for one
minute before putting the machine in logical
OFF. If the operator immediately switches the
machine to OFF, the machine might switch off
instead of running the complete fill-up.

Note! If the second alternative is selected, make


sure that the AUTO RINSE function is set and
activated (AUTO RINSE button steady lit).
before starting the Central chemical disinfec-
tion program. Otherwise the program will not
allow Auto rinse.

HCEN9315 Rev. 10. 00 9: Appendix


Information about AK 90S and
WRO Chem
Note: The procedure below is only used to clean
the tube between AK 90S and the wall, not to
disinfect the machine.

The AK 90S does not support central chemical


disinfection. However, in order to disinfect the
hose between the water distribution system and
the machine the following procedure can be used:

1. Start the AK 90S chemical disinfection pro-


gram, WITHOUT removing the B-concen-
trate intake. This will start the disinfection
program, but ”hold” the program for the
operator to remove the B-concentrate intake.
The concentrate preset should be set at
”Conc”, not ”Work” (in order to open INVA
during fill-up).

2. Initiate loop disinfection of the WRO


Chem. Wait until the disinfectant has reached
the first dialysis machine in the loop.

3. Disconnect the B-concentrate intake from the


AK 90S (remove the intake only the few
millimeters necessary for the machine to
detect that the pick-up tube has been discon-
nected). The machine will now begin to pull
disinfectant from the loop.

4. Wait until the fill-up phase is completed (7


minutes), and then reconnect the B-concen-
trate intake to the machine.

5. Correlate the dwell time of the AK 90S with


the program of the WRO Chem, in order to let
the CWP rinse out the loop before the disinfec-
tion rinse program is initiated.

Warning: Always test the AK 90S for chemical


residues after the rinse has been completed.

9. Appendix HCEN9315 Rev. 10. 00

Potrebbero piacerti anche