1000 A MCC BUSBAR SIZING CALCULATIO
Page 2 of 42
1000 A MCC BUSBAR SIZING CALCULATIO
Page 3 of 42
1000 A MCC BUSBAR SIZING CALCULATIO
Page 4 of 42
1000 A MCC BUSBAR SIZING CALCULATIO
Page 5 of 42
1000 A MCC BUSBAR SIZING CALCULATIO
=
a SK = Cantilever strength of insulator(Kg/cm²) =
b SF = Safety factor =
Length of Span of insulator in mm =
Adopted Span is
Conclusion:
4.4 Average span of 586.278 mm is required but span adopted is 500 mm, hence it is safe
envisaged.
Page 6 of 42
1000 A MCC BUSBAR SIZING CALCULATIO
Page 7 of 42
1000 A MCC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
Cubical Type
3PH ,3 Wire / 4 Wire
415V
50 Hz.
1000
50
50
85
70
IP: 52 & IP: 42 for ACB Incomer
1 x 1 x 125 x 10 MM
1 x 125 x 06 MM
1
1
125
10
750
1250
SMC support with ribbed construction
2.5KV RMS
Page 8 of 42
1000 A MCC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
25 mm
20 mm
IS: 8623 Construction
IS : 5082 Bus bar
IP: 54 for Indoor & IP: 55 for Outdoor
0.5mtr. (500mm)
Page 9 of 42
1000 A MCC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
50
1
85
200
1.0078517941
650.226
1250
section 650.226 Sq.mm is less than actual cross section 1250 Sq.mm of the bus bar
e bus bar size chosen is safe for the envisaged system.
for Continuous Current Rating :
As per Clause1.11
1850
1 x 1850
1850
150
5500 x 800 x 2400 mm
800 x 400 mm
50 Deg. C
35 Deg. C
Page 10 of 42
1000 A MCC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
MS Steel
Page 11 of 42
1000 A MCC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
g:
0.9
0.87
0.9
0.95
1
0.67
1850 x 0.67
1238.51025
1000
nt rating 1238.51 amp of Panel selected is more than the required current rating 1000
us bar. Hence, the bus bar size chosen is safe for the envisaged system.
Span Calculation During Short Circuit
K x 16 x Isc² x 10⁻⁴ / S
50
0.250
0.904
0.4 (Reffering to curve K is 0.9)
14400.000
1468.391
Fm (H+h)/4H
38
75
1091.6328126316
Page 12 of 42
1000 A MCC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
6.278 mm is required but span adopted is 500 mm, hence it is safe for the system
Page 13 of 42
1000 A MCC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
Calculation
1238.51025
1000
35
( I1 / I2 ) = ( T1 / T2)0.61
T1 / (I1 / I2 )1.64
24.64
OK
mperature rise of bus bar is 24.64 Deg. C, which is within the design Specified Temp. 35
e for the System envisaged.
Page 14 of 42
630 A MCC BUSBAR SIZING CALCULATION
1.16 Painting:
a. Enclosure Interior & Exterior :
b. Bus bar :
1.17 Minimum Clearance:
Page 15 of 42
630 A MCC BUSBAR SIZING CALCULATION
Page 16 of 42
630 A MCC BUSBAR SIZING CALCULATION
Page 17 of 42
630 A MCC BUSBAR SIZING CALCULATION
Page 18 of 42
630 A MCC BUSBAR SIZING CALCULATION
Page 19 of 42
630 A MCC BUSBAR SIZING CALCULATION
=
a SK = Cantilever strength of insulator(Kg/cm²) =
b SF = Safety factor =
Length of Span of insulator in mm =
Adopted Span is
Conclusion:
4.4 Average span of 586.278 mm is required but span adopted is 500 mm, hence it is safe
envisaged.
Page 20 of 42
630 A MCC BUSBAR SIZING CALCULATION
Page 21 of 42
630 A MCC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
Cubical Type
3PH ,3 Wire / 4 Wire
415V
50 Hz.
630
50
50
85
70
IP: 52 & IP: 42 for ACB Incomer
1 x 1 x 75 x 12 MM
1 x 75 x 06 MM
1
1
75
12
450
900
SMC support with ribbed construction
2.5KV RMS
Page 22 of 42
630 A MCC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
25 mm
20 mm
IS: 8623 Construction
IS : 5082 Bus bar
IP: 54 for Indoor & IP: 55 for Outdoor
0.5mtr. (500mm)
Page 23 of 42
630 A MCC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
50
1
85
200
1.0078517941
650.226
900
section 650.226 Sq.mm is less than actual cross section 900 Sq.mm of the bus bar
e bus bar size chosen is safe for the envisaged system.
for Continuous Current Rating :
As per Clause1.11
1350
1 x 1350
1350
150
7800 x 800 x 2400 mm
800 x 400 mm
50 Deg. C
35 Deg. C
Page 24 of 42
630 A MCC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
MS Steel
Page 25 of 42
630 A MCC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
g:
0.9
0.87
0.9
0.95
1
0.67
1350 x 0.67
903.77775
630
nt rating 903.78 amp of Panel selected is more than the required current rating 630 amp
r. Hence, the bus bar size chosen is safe for the envisaged system.
Span Calculation During Short Circuit
K x 16 x Isc² x 10⁻⁴ / S
50
0.250
0.904
0.4 (Reffering to curve K is 0.9)
14400.000
1468.391
Fm (H+h)/4H
38
75
1091.6328126316
Page 26 of 42
630 A MCC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
6.278 mm is required but span adopted is 500 mm, hence it is safe for the system
Page 27 of 42
630 A MCC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
Calculation
903.77775
630
35
( I1 / I2 ) = ( T1 / T2)0.61
T1 / (I1 / I2 )1.64
19.37
OK
mperature rise of bus bar is 19.37 Deg. C, which is within the design Specified Temp. 35
e for the System envisaged.
Page 28 of 42
800 A MCC BUSBAR SIZING CALCULATION
1.16 Painting:
a. Enclosure Interior & Exterior :
b. Bus bar :
1.17 Minimum Clearance:
Page 29 of 42
800 A MCC BUSBAR SIZING CALCULATION
Page 30 of 42
800 A MCC BUSBAR SIZING CALCULATION
Page 31 of 42
800 A MCC BUSBAR SIZING CALCULATION
Page 32 of 42
800 A MCC BUSBAR SIZING CALCULATION
Page 33 of 42
800 A MCC BUSBAR SIZING CALCULATION
=
a SK = Cantilever strength of insulator(Kg/cm²) =
b SF = Safety factor =
Length of Span of insulator in mm =
Adopted Span is
Conclusion:
4.4 Average span of 586.278 mm is required but span adopted is 500 mm, hence it is safe
envisaged.
Page 34 of 42
800 A MCC BUSBAR SIZING CALCULATION
Page 35 of 42
800 A MCC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
Cubical Type
3PH ,3 Wire / 4 Wire
415V
50 Hz.
800
50
50
85
70
IP: 52 & IP: 42 for ACB Incomer
1 x 1 x 100 x 10 MM
1 x 100 x 06 MM
1
1
100
10
600
1000
SMC support with ribbed construction
2.5KV RMS
Page 36 of 42
800 A MCC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
25 mm
20 mm
IS: 8623 Construction
IS : 5082 Bus bar
IP: 54 for Indoor & IP: 55 for Outdoor
0.5mtr. (500mm)
Page 37 of 42
800 A MCC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
50
1
85
200
1.0078517941
650.226
1000
section 650.226 Sq.mm is less than actual cross section 1000 Sq.mm of the bus bar
e bus bar size chosen is safe for the envisaged system.
for Continuous Current Rating :
As per Clause1.11
1500
1 x 1500
1500
150
4400 x 800 x 2400 mm
800 x 400 mm
50 Deg. C
35 Deg. C
Page 38 of 42
800 A MCC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
MS Steel
Page 39 of 42
800 A MCC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
g:
0.9
0.87
0.9
0.95
1
0.67
1500 x 0.67
1004.1975
800
nt rating 1004.19 amp of Panel selected is more than the required current rating 800 amp
r. Hence, the bus bar size chosen is safe for the envisaged system.
Span Calculation During Short Circuit
K x 16 x Isc² x 10⁻⁴ / S
50
0.250
0.904
0.4 (Reffering to curve K is 0.9)
14400.000
1468.391
Fm (H+h)/4H
38
75
1091.6328126316
Page 40 of 42
800 A MCC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
6.278 mm is required but span adopted is 500 mm, hence it is safe for the system
Page 41 of 42
800 A MCC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
Calculation
1004.1975
800
35
( I1 / I2 ) = ( T1 / T2)0.61
T1 / (I1 / I2 )1.64
24.11
OK
mperature rise of bus bar is 24.11 Deg. C, which is within the design Specified Temp. 35
e for the System envisaged.