Seismic Bracing Calculation

Project Contractor:
Address:

Calculations based on NFPA 13 2013 using FM approved product load limits

Brace Information Brace Components

PHD Component Fig. Number Adjusted Load


Max. Spacing: 40' Between Braces
Fig. 031 Clamping Pipe Attachment 816.4656 kg
Max. Brace Length: 7'-0" Fig. 030 C-Clamp Structural
Attachment
Bracing Material: Sch. 40 Pipe 1" 816.4656 kg
Fig. 045 Sway Brace Structural
Angle from Vertical: 45° to 59° Adapter

Least Rad. of Gyration: 0.421


*Calculations are Based on CONCENTRIC Loading
L/R Value: 200
*Please Note: These calculations are for PHD
Max Horizontal Load: 594.20552 kg components only. Use of any other components voids
these calculations and the listing of the assembly.

Fastener Information Assembly Detail

Structural Steel Member -


Structure Type:
Not Boltable

Structure Description: H Beam Structure

Fastener Orientation: NFPA Type B

Anchor Type: None Required

Orientation of Brace: Lateral

Brace ID on Plans: Machinery Zone 1 #6

Braced Pipe: 150 mm mm Sch. 40 Load Information Force Factor (Cp): 0.61
Size Type Total Length Weight Total Weight Wp (Weight +15%)

2" Sch. 40 1.524 m 7.6342810122 kg/m 11.793392 kg 13.154168 kg

6" Sch. 40 12.192 m 47.1599152586 kg/m 575.154656 kg 661.337136 kg

Total Adjusted Load of all pipe within Zone of Influence (Wp * Cp = Fpw): 411.861536 kg