Sei sulla pagina 1di 9

This article has been accepted for publication in a future issue of this journal, but has not been

fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TIA.2013.2297448, IEEE Transactions on Industry Applications

Reliable Detection of Induction Motor Rotor Faults


under the Rotor Axial Air Duct Influence
Chanseung Yang, Tae-June Kang, Doosoo Hyun, Sang Bin Lee* Jose Antonino-Daviu, and Joan Pons-Llinares
Department of Electrical Engineering, Department of Electrical Engineering,
Korea University, Seoul, Korea Universitat Politècnica de València, València, Spain
*Email: sangbinlee@korea.ac.kr

Abstract—Axial cooling air ducts in the rotor of large induction alternate path for the flux [4]-[6]. The difference in the flux
motors are known to produce magnetic asymmetry, and can path depending on the relative position between the magnetic
cause steady state current or vibration spectrum analysis based field and axial duct (spider) arms can be clearly seen in the
fault detection techniques to fail. If the number of axial air ducts results of the 2-dimensional finite element (FE) analysis in Fig.
and poles are identical, frequency components that overlap with 2(a)-(b) for a 4 pole motor with 4 axial ducts. The variation in
that of rotor faults can be produced for healthy motors. False the magnetic reluctance results in modulation of the
positive rotor fault indication due to axial ducts is a common magnetizing current, where the frequency of modulation
problem in the field that results in unnecessary maintenance cost. depends on the number of axial air ducts, Nd, and poles, Np. It
However, there is currently no known test method available for
was shown in [4]-[9] that the magnetic asymmetry can produce
distinguishing rotor faults and false indications due to axial ducts
other than off-line rotor inspection or testing. Considering that
components (fduct) in the steady state vibration or current
there is no magnetic asymmetry under high slip conditions due to spectrum that overlap with motor fault frequency components
limited flux penetration into the rotor yoke, detection of broken such as rotor cage damage or airgap eccentricity, if Nd is equal
bars under the startup transient is investigated in this paper. A to Np, as shown in (1). fe is the input electrical frequency, and k
wavelet-based detection method is proposed and verified on is a positive integer. If the number of air ducts, Nd, and poles,
custom-built lab motors and 6.6 kV motors misdiagnosed with Np, are the same, the air ducts can produce frequency
broken bars via steady state spectrum analysis. It is shown that components identical to that of rotor cage fault frequency (fbrb),
the proposed method provides reliable detection of broken bars as can be seen in (2). This can be misinterpreted as broken
under the startup transient independent of axial duct influence. rotor bars when steady state on-line FFT-based techniques are
applied, as reported in [4]-[9].
I. INTRODUCTION f duct ,vib  2ksf e , f duct ,cur  (1  2ks) f e (if N d  N p ) (1)
Most of the rotors of induction motors rated above 100kW f brb,vib  2ksf e , f brb,cur  (1  2ks) f e (2)
employ axial air ducts, as shown in Fig. 1, for effective cooling
of the rotor, reduction in rotor weight (inertia), and saving of Rotors for cases where the axial ducts caused false broken
material costs [1]-[3]. The most common axial air duct design bar indications on Nd = Np = 8 or 4, 6.6 kV induction motors
is to use shaft spiders, where 4, 6, or 8 radial arms are welded operating in power plants are shown in Fig. 1. The results of
to the shaft to support the rotor core, as shown in Fig. 1(b)-(c). motor current signature analysis (MCSA) of the three motor
Axial ducts can also be produced by punching holes in the rotor samples showed strong broken bar components (Fig. 3);
laminations prior to assembly, as shown in Fig. 1(a). Axial however, inspection of the rotor showed that the bars were in
ducts can cause the magnetic reluctance of the flux path to be good condition for all 3 motors. The cost of inspection for a
asymmetric since the spider arm and shaft can provide an motor with a false positive indication is typically tens of

(a) (b) (c)


Fig. 1. Rotors of 6.6 kV motors with false positive rotor fault MCSA indications due to axial ducts; (a) 2400 kW, 8 pole induced draft fan motor; (b) 280 kW, 4
pole, condensate pump motor; (c) 350 kW, 4 pole condensate pump motor (test samples A-C)

0093-9994 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TIA.2013.2297448, IEEE Transactions on Industry Applications

thousands of USD without including loss of production (if application, and figure number of the experimental results are
stand-by or spare motors are available). The cost is higher for summarized in Table I of the appendix. The MCSA results of
larger motors due to the difficulty of handling the heavy motors samples A, B, and C are shown in Fig. 3(a)-(c), respectively,
as it involves motor detachment, installation (spare motor), where the measurements were obtained from 2 or 3 units of
rental of crane/equipment, shipping to motor repair shop, and identical design that share the load. For the 2.4 MW induced
disassembly/inspection. The inspection cost alone for the 2.4 draft fan motor, both samples A1 and A2 showed very strong
MW motor of Fig. 1(a) exceeded 100,000 USD. Despite the f1-2s sidebands of -35.9 and -36.2 dB, respectively, in the
high cost of inspection, motors are inspected if fault indications current spectrum (Fig. 3(a)). Strong f2s components indicating
are given since the cost of forced outage can be orders of broken rotor bars were also observed with vibration analysis,
magnitude higher than that of inspection/repair.
False positive rotor fault indications due to axial duct
influence is a very common on-going problem in the field,
considering that a large portion (34.4%) of high voltage motors
are of Nd=Np design, according to the survey in [6]. In most
cases, it is unknown whether a motor is of Nd=Np design since
the number of axial ducts is unknown by the user after the
motor is assembled. Even if it is known that Nd=Np for a
particular motor, it is uncertain whether the air ducts would
produce the fduct component or not, since not all motors with
Nd=Np produce false indications. Whether fduct components are
produced depends on the rotor design and construction,
(a) (b)
material characteristics, and operating conditions [6]. An Fig. 2. FE analysis of flux distribution in 4 pole motor with 4 axial air ducts
attempt was made to separate the effect of broken bars and when magnetic poles and duct-/spider-arms are electrically (a) 90o
axial ducts on-line in [4], and guidelines for distinguishing the apart and (b) aligned (0o) under steady state operation
two problems were given in [5]-[8]; however, there are many
limitations in the field for applying what has been suggested.
In [6], a detailed analysis of the influence of axial ducts on
condition monitoring is presented. It is shown that broken bars
can be detected independent of axial ducts if tested under high
slip (standstill, off-line) conditions since there is no magnetic
asymmetry due to limited flux penetration in the rotor (cage
eddy current rejection). The downside of off-line test methods
is the requirement of motor disassembly or manual shaft
rotation for testing, which makes frequent, automated, and
remote motor testing difficult [10].
(a)
The arguments above show that false indications due to
axial ducts are common and the consequence can be serious;
however, there currently is no practical on-line test method
available for separating the influence of broken bars with axial
ducts. Based on the observation that broken bars can be
detected reliably independent the axial duct at high slip, testing
under the startup transient is investigated in this paper.
Although many papers have been published on startup
detection of rotor faults, this is the first time it is applied to the
axial duct problem. A wavelet transform based method is
proposed as an effective solution, and verified on a motor with (b)
a custom built rotor in the lab and on 6.6 kV motors in the field
with false broken bar MCSA indications. It is shown that the
proposed method is capable of providing reliable detection of
broken bars independent of the axial duct influence.

II. INFLUENCE OF ROTOR AXIAL AIR DUCTS ON MCSA

A. False Positive Broken Rotor Bar Indications


MCSA was performed for the healthy 6.6 kV motors of Fig.
1 with false positive broken rotor bar indications due to axial
ducts (Nd=Np). The three types of 6.6 kV motors of Fig. 1(a)- (c)
Fig. 3. Is spectrum (MCSA) of “healthy” 6.6 kV motors shown in Fig. 1
(c), which are fan or pump motors used in power plants, are
with false positive broken rotor bar indications; Samples (a) A1, A2
denoted as samples A, B, and C, respectively. The ratings, (Nd=Np=8); (b) B1, B2, B3 (Nd=Np=4); (c) C1, C2, C3 (Nd=Np=4)

0093-9994 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TIA.2013.2297448, IEEE Transactions on Industry Applications

but motor inspection did not reveal signs of rotor bar or end and the broken bar (fbrb) interact, and the amplitude can change
ring damage. with operating condition (e.g. voltage level) and due to the
characteristics or construction of individual motors.
For the 280 kW and 350 kW condensate pump motor
samples B and C, the MCSA measurements of the f12s The interaction between the broken bar and axial duct
component for three identical units were not consistent, as can influence has been investigated in [6], and it is shown that the
be seen in Fig. 3(b)-(c). The f1-2s component was -52.5 dB, fbrb and fduct components can add or cancel out depending on the
below -70 dB, and -69 dB for samples B1, B2, and B3, and - relative physical angle between the duct and broken bar,
45.1 dB, -59.5 dB, and -53.4 dB for samples C1, C2, and C3, represented as e in Fig. 4(b). The analysis is verified in the lab
respectively. Broken bars were strongly suspected for units B1 on two 4 pole, 380 V motors with custom-built Nd=Np rotors
and C1 considering that the f12s component of -55~-35 dB is shown in Fig. 5. The axial ducts of sample D were created by
the fault threshold used in commercial MCSA products, and drilling 20 holes in the yoke to produce 4 axial ducts in yoke of
because the f12s components were significantly higher than that an Al die-cast rotor, as shown in Fig 5(a). A fabricated Cu bar
of motors of identical design. Since the sample B1~B3 and rotor with 4 axial ducts, sample E, was designed and built to fit
C1~C3 motors were manufactured and commissioned at the the stator of sample D, as it is representative of large motors
same time and operated under similar load, it was natural to (Fig. 5(b)). Axial holes were laser cut in the rotor laminations
conclude that it is very unlikely for the motors to have larger of sample E, as shown in Fig. 5(c). The MCSA measurements
f12s components unless a rotor fault is present. However, the performed on samples D~E with 0, 1, 2 broken bars located at
results of off-line inspection and testing showed that the rotor e=45o and e=135o are shown in Figs. 6 and 7, respectively.
cages were in good condition. The single phase rotation test It can be observed that the f1-2s component increases if the
was performed on sample C1 with 380 V applied between two
bar is broken at the e=45o location shown in Fig. 4(b), and
terminals for pulsating field excitation [10]-[11]. The results of
the current measurements vs. rotor position shown in Fig. 4(a) decreases (and then increases) if e=135o. This is observed
imply that there is no asymmetry in the rotor cage (current because the fbrb and fduct components are in phase (add) when
varies with rotor position for faulty case). The FE simulation e=45o and out of phase (cancel out) when e=135o [6]. If the
under pulsating field excitation at motor standstill (s=1) in Fig. fault is located at e=135o, the f1-2s component initially
4(b) shows that flux penetration into the rotor yoke is limited. decreases, but starts to increase if the magnitude of the fbrb
The inconsistency in the amplitude of the f12s component for component exceeds that of the fduct component. It can be
samples B and C is suspected to be caused by part-to-part clearly seen in the results of Figs 6-7 that the f12s components
variation introduced due to component- and manufacturing- can remain constant or decrease with increase in broken bars
tolerances such as the variance in the Si-Fe lamination over time depending on the fault location, load, and the
magnetic characteristics, the non-ideal anisotropy in the rotor amplitude of individual fduct and fbrb components (counter-
laminations, etc [6]. It was concluded based on the inspection example of criterion 1). The f12s components can also decrease
and test results that the false positive indication for samples A,
B, and C is due to the axial air ducts for the Nd=Np motors.

B. Interaction between Rotor Magnetic Asymmetry and Faults


If the f12s components exceed a predetermined threshold
level with spectrum analysis, the criteria that knowledgeable
field maintenance engineers use to confirm broken bars and
screen out potential false positive indications are [5]-[8]:
1) observe the change in the f12s component over time: if
the amplitude of the f12s component increases with time (a) (b)
under similar load conditions, it is concluded that there is Fig. 4. (a) Single phase rotation test results (current vs. rotor position) on
rotor cage damage; if it is constant or decreases with time, sample C1 under 380 V pulsating field excitation at motor standstill;
a false positive indication is suspected (b) FE simulation of flux distribution under single phase rotation test

2) observe the change in the f12s component with load


variation: if the amplitude of the f12s component increases
with increase in load, it is concluded that there is rotor
cage damage; if it is constant or decreases with increase in
load, a false positive indication is suspected
3) compare the f12s component with motors of identical
design: if the amplitude of the f12s component is
considerably larger compared to that of motors of
identical design, rotor damage is suspected
However, it was shown in [6] that these are misconceptions and (a) (b) (c)
may lead to incorrect diagnosis for motors of Nd=Np design. Fig. 5. (a) Al die-cast rotor with 4 drilled axial holes (sample D); (b)
This is because the f12s components due to the axial duct (fduct) fabricated Cu rotor with 4 laser cut axial holes in rotor lamination
(sample E); (c) rotor lamination for sample E

0093-9994 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TIA.2013.2297448, IEEE Transactions on Industry Applications

with increase in load for a motor with broken bars depending The fault frequency associated with broken bars changes
on the fault location, load, and fault severity (counter-example during the direct on-line startup transient as the slip s decreases
of criterion 2). The MCSA results of samples B1~B3, and from 1 to a value close to 0 [12]. At the instant the motor
C1~C3 are counter-examples of the third criterion listed above. source switch is closed, |fbrb| is equal to fe (s=1), and decreases
The false rotor fault indication (B1, C1) is not necessarily to 0 (s=1/2), and increases back towards fe as s approaches 0.
present for all motors of the same design due to the variance in This leads to the characteristic -shaped evolution of |fbrb|
the characteristics of individual motors, as described previously illustrated in Fig. 9, which shows the variation in the slip and
in III.A. The results of Figs. 3, 6, 7 disprove the validity of the |fbrb| component measured for a 5.5 kW induction motor startup.
aforementioned criteria 1), 2), and 3) for confirming broken If the DWT is applied to the startup current of one phase of a
bars, and show that rotor faults in motors with Nd=Np design
cannot be reliably detected using spectrum analysis.

III. DETECTION OF ROTOR FAULTS INDEPENDENT OF AXIAL


DUCT INFLUENCE UNDER THE STARTUP TRANSIENT
Since steady state FFT based spectrum analysis cannot
provide reliable detection of broken bars for Np = Nd motors
with magnetic asymmetry, a new on-line detection method that
is not influenced by axial ducts is needed. Off-line standstill
tests such as the single phase rotation test provides reliable
detection of rotor faults since they are performed under high
slip conditions when flux penetration in the rotor is limited (Fig.
4). Fault detection under the startup transient, where the slip is
high and flux penetration into the rotor yoke is limited, is Fig. 6. MCSA measurements of the f1-2s component as a function of % rated
therefore considered under the expectation that magnetic slip with 0-2 broken bars (sample D) located at e = 45o (dotted line)
and e = 135o (real line)
asymmetry (and false positive indications) due to axial ducts
can be avoided. In this work, the discrete wavelet transform
(DWT), which has been successfully applied to motor fault
detection under transient conditions [12]-[17], is considered for
analyzing the startup current of Nd = Np motors for the first time.

A. Principles of DWT-based Rotor Fault Detection


The DWT performs decomposition of a signal into multiple
sub-signals that contain different frequency ranges of the
original signal according to predetermined frequency bands.
This makes DWT a powerful tool for analyzing non-stationary
signals with varying fault frequency components as in the case
of the f12s components of (1)-(2) under the startup transient.
Moreover, the implementation of the DWT based on the Mallat Fig. 7. MCSA measurements of the f1-2s component as a function of % rated
algorithm makes it a tool with low computational requirements slip with 0-2 broken bars (sample E) located at e = 45o (dotted line)
and e = 135o (real line)
in comparison to other time-frequency decomposition tools and
FFT [17]-[18].
The mathematical expression that characterizes the DWT
decomposition of a signal, e.g. i(t), is given by (3), where an
and dn…d1 represent the approximation and detail signals,
respectively. The details of the DWT is not described in this
paper, as it can be found in many resources [12]-[18]. Fig. 8. Decomposition process carried out by DWT for fs=10.24 kHz and n=9

i (t )  a n  d n  d n1  ...  d1 (3)


The most important underlying idea in the application of the
DWT is that each wavelet signal is associated with a certain
frequency band, i.e. the frequency components within the band
is extracted from the original signal into each wavelet signal.
The range of the band covered by each wavelet signal depends
on the sampling frequency fs and on the level n of the wavelet
signal, as illustrated in Fig. 8. In the figure, an example of the
frequency range for each wavelet signal is shown for fs=10.24
kHz and n=9 level decomposition (see guidelines for the Fig. 9. Evolution of slip and the -shaped broken rotor bar, |fbrb|, component
selection of DWT parameters in [13], [25]), which are the during a direct on-line startup transient measured for a 5.5 kW motor;
conditions used throughout this paper. concept of fault indicator, En, calculation is illustrated

0093-9994 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TIA.2013.2297448, IEEE Transactions on Industry Applications

machine with broken bars, the evolution of |fbrb| will be false broken bar indications (samples A~E), since magnetic
reflected in the wavelet signals covering the frequency band of asymmetry does not exist under startup. The oscillation at 6.5
0~fe Hz, enabling reliable detection of the fault. sec in Fig. 10 is due to incorrect timing in the closing of the
starting reactor bypass switch. Reactor startup is used in this
This is illustrated in Figs. 10(a)-(b), which show the startup application for limiting the high startup current (~2000 A) by
current, i, and high-level wavelet signals, a9, d9, and d8, reducing the voltage; however, it can be seen that the timing is
resulting from the DWT of the startup current of one phase for set incorrectly. If the switch is closed correctly after reaching
sample F with healthy (F1) and faulty (F2) rotor cages. Sample steady state, it does not interfere with DWT startup detection.
F is a 6.6 kV, 3800 kW water intake pump motor used at a
water supply facility. The wavelet signals, a9, d9, and d8, cover
the range of 0~40Hz (Fig. 8), for the specific case analyzed. B. Quantification of Fault Severity
The oscillations in certain wavelet sub-signals increase at a The -shaped pattern in the high level wavelet signals (a9,
particular interval of time, forming the -pattern as the |fbrb| d9, and d8) in the [0,40] Hz range resulting from the DWT is a
component changes with slip at startup, only if a broken bar is reliable qualitative indicator of the presence of rotor faults.
present. The magnitude of the oscillations in the DWT analysis The existence of the rotor cage faults in the machine can be
due to the rotor fault |fbrb| component is proportional to the identified since no other phenomenon or fault is likely to cause
magnitude of the f12s component in the MCSA results of a similar pattern. It is desirable to define a quantitative
samples F1 and F2 shown in Fig. 11. No oscillations are indicator capable of providing an 1) automated decision on
expected for healthy motors for which steady state FFT gave fault existence and 2) a measure of fault severity to
complement the qualitative information provided by the 
pattern. Although there could be numerous wavelet-based fault
indicators that can be defined for quantification of fault
severity, an energy-based parameter is proposed in this work
for simplicity of the algorithm.
The energy level of the high-level wavelet signals increase
due to the oscillations in the transient evolution of |fbrb|, as the
severity of the fault increases. Therefore, a quantification
parameter based on the energy level of the wavelet signals
influenced by |fbrb| (a9, d9, or d8) is introduced due to (2).
According to an extensive study on the startup transient current
data obtained from motor samples B~F, it was observed that
the oscillations in the falling part of  of the d8 signal provides
(a) the most sensitive indication of the fault existence and severity.
The energy in a predetermined time interval of d8 is normalized
with respect to the startup current within the same time interval
to make it independent of the operating conditions such as the
inertia, load level, etc. The proposed fault indicator En can be
calculated using

 j  N83 j  N83 
En (dB)  10  log  d 8 ( j ) 2 i 2 , (4)
 jN j 
 67 j  N 67 
where d8(j) and ij are the values of the jth sample of the d8 and
startup current signal, respectively.
(b) The time interval [N67, N83] used for calculating En
Fig. 10. Startup current and high-level wavelet signals, a9, d9, d8, resulting corresponds to the interval between 67% and 83% of the
from the DWT of the startup current for sample F: (a) healthy startup time, Tstart, shown in Fig. 9. The value of Tstart can be
motor (F1); (b) motor with rotor fault (F2)
calculated from the pattern of decrease in the startup current
magnitude. In this paper, the end of the startup transient period
Tstart was set to the time when the rate of decrease in current
falls below a predetermined limit. If it is assumed that slip
linearly decreases from 1 to 0 from the instant of startup (t=0s)
to Tstart, 67~83% of Tstart approximately corresponds to the
frequency range of 20~40 Hz, as shown in Fig. 9. This is the
range for which d8 shows rotor fault-related oscillations, which
is the reason En is calculated in this time interval. Since slip
does not decrease linearly with time, the [N67, N83] interval
does not exactly coincide with the oscillations, as can be seen
Fig. 11. Is spectrum (MCSA) of sample F (6.6 kV, 3400 kW, Nd=8, Np=12) in highlighted windows of Fig. 10. Although it does not
motor with healthy (F1) and faulty (F2) rotor cage

0093-9994 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TIA.2013.2297448, IEEE Transactions on Industry Applications

capture the oscillations precisely, it is shown in section IV that rotor used for the e=45o case in the opposite direction. This is
it is sufficient for detecting the fault and providing a measure equivalent to the broken bar being at e=135o. For samples B
of fault severity. and C, startup transient data was measured for the motors with
There are numerous techniques other than DWT such as the highest fbrb components for each sample (B1 and C1), and
Continuous Wavelet Transforms Hilbert-Huang transforms, for sample B2. It was not possible to damage the rotor bars of
Wigner-Ville and Choi-Williams Distributions, etc, that can be these samples since they are HV motors operating in the field.
applied to this problem [19]-[24]. The purpose of this paper is The startup current of one phase was sampled at 10.24 kHz,
to show that startup current analysis provides reliable detection and analyzed with daubechies wavelets. This sampling rate
of rotor faults independent of the axial duct influence. constricts the frequency range of d8 below 40 Hz to prevent
Therefore, the application of time-frequency decomposition interference with the mains frequency at 60 Hz [17], [25].
tools other than DWT or alternate fault indicators are not Since the oscillation in d8 in the falling end of  is used for
within the scope of this paper, and are left for future work.” calculating En, the influence of the electromagnetic transients at
the instant of startup (Fig. 10) can also be avoided.
IV. EXPERIMENTAL STUDY To produce the startup time typical of large motors, a steel
An experimental study was performed to verify the disc designed to increase the startup time to 1.0~1.5 secs was
effectiveness of the proposed DWT-based method for detecting attached to the shaft of the unloaded motor for samples D and E.
broken bars reliably independent of the axial duct influence. The motor was not loaded and nothing was connected to the
The startup current of samples B, C, D, and E (Np = Nd), which rotor shaft other than the inertia disc, to observe the fault
were diagnosed with false broken bars in steady state (MCSA), detectability under the worst case condition of no load.
were obtained and analyzed. The information, rotor photos,
test results for MCSA and DWT analysis for motor samples A. Experimental Results: Laboratory Test (Samples D and E)
B~E are summarized in Table I (appendix). For the custom The MCSA results for samples D and E with rotor faults
built motor samples D and E of Fig. 5, up to 2 Al or Cu bars located at e=45o and 135o in Figs. 6-7 clearly show that
were cut at the bar and end ring joint to simulate broken bars. MCSA cannot be used for detecting rotor faults for Nd=Np
To test under the condition where the fbrb and fduct components motors, since it is influenced by the location of the broken bar
are in phase (add), bars at the e=45o location shown in Fig. with respect to the axial duct. The waveforms of the startup
4(b) were cut. The case where fbrb and fduct components are out current, d9, and d8 wavelet signals for sample D are shown for 0,
of phase (cancel, e=135o) was also tested by rotating the same 1, and 2 broken bars at e = 45o and 135o in Figs. 12 and 13,

(a) (a)

(b) (b)

(c) (c)
Fig. 12. Stator current, d9, and d8 wavelet signals under startup transient for Fig. 13. Stator current, d9, and d8 wavelet signals under startup transient for
sample D with (a) 0, (b) 1, and (c) 2 broken bars at e=45o. sample D with (a) 0, (b) 1, and (c) 2 broken bars at e=135o.

0093-9994 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TIA.2013.2297448, IEEE Transactions on Industry Applications

(a) (a)

(b) (b)

(c)
(c)
Fig. 15. Stator current, d9, and d8 wavelet signals under startup transient for
Fig. 14. Stator current, d9, and d8 wavelet signals under startup transient for
samples B1, C1 (“healthy” motors with false positive MCSA
sample E with (a) 0, (b) 1, and (c) 2 broken bars at e=45o. indications), and B2
respectively. The time interval of d8 used for calculating En
described in III is highlighted in the figure, and the values of En
calculated for each condition are plotted in Fig. 16. For the
healthy cases (Figs. 12(a), 13(a)), where steady state MCSA
indicated faulty rotors (Fig. 6), the oscillations are negligible,
and the values of En are small. It can be observed in Figs. 12,
13, and 16 that the oscillations in d8 due to broken bars and the
values of En increase with the number of broken bars. For the
case of e = 135o, in which the fbrb components decrease with
broken bars (Fig. 6), the magnitude of the oscillations and
values of En are similar to that of the e = 45o case (Figs. 13, 16).
The fact that the increase in the d8 oscillations (Figs. 12-13)
and En (Fig. 16) are similar regardless of fault location, e, Fig. 16. Fault indicator: normalized energy level, En, for samples B1, B2, C1,
D, and E for 0, 1, and 2 broken bars
verifies that fault detection under the startup transient provides
fault indications only if broken bars are present, and that is not
B. Experimental Results: Field Test (Samples B1, B2, and C1)
influenced by axial ducts.
The waveforms of the startup current, wavelet signals d9,
The waveforms of the startup current, d9, and d8 signals,
and d8 for samples B1, B2, and C1 are shown in Fig. 15. The
and the time interval used for En calculation for sample E are
time interval used for En calculation is highlighted in Fig 15,
shown for 0, 1, and 2 broken bars at e = 45o in Fig. 14. The and the calculated values of En are shown in Fig. 16 along with
results for the e=135o case, which is not shown due to space that of samples D and E for comparison. The left sideband f1-2s
restrictions, are similar to that of Fig. 14. The values of En components measured for samples B1 and C1 were -52.5 and -
calculated for the e = 45o, 135o cases for sample E in Fig. 16 45.1 dB, which were considerably higher than motors of
show that the proposed fault indicator is a good measure of identical design, as shown in Figs. 3(b)-(c). The fbrb
broken bars, and that it is not influenced by axial ducts. The components were below -70 dB for sample B2, which is a 20
test results of samples D~E shown in Figs. 12-14, 16 clearly dB difference. For samples B1 and C1, oscillations cannot be
show that the proposed method provides reliable detection of clearly observed in the d8 wavelet signal shown in Fig. 15(a)
broken bars independent of the axial ducts, and that En is a and (c). The values of En for both samples were very low and
good indicator of rotor fault existence and severity. similar to that of sample B2 (Fig. 16), which was diagnosed as

0093-9994 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TIA.2013.2297448, IEEE Transactions on Industry Applications

a healthy motor with MCSA (f1-2s component below -70 dB). This work was supported by the Basic Science Research
Oscillations were not present in the d8 signal of sample B2, as Program through the National Research Foundation of Korea
expected (Fig. 15(b)). This indicates that the f1-2s components (NRF) funded by the Ministry of Education, Science and
in samples B1 and C1 are due to the magnetic asymmetry Technology (NRF-2013R1A1A2010370), and by the Human
caused by the axial ducts. The results of Fig. 15 show that it is Resources Development program (20134030200340) of the
possible to determine that the two cases of samples B1 and C1 Korea Institute of Energy Technology Evaluation and Planning
are false positive indications with the startup transient analysis. (KETEP) grant funded by the Korea government Ministry of
Trade, Industry, and Energy.
The results presented in Figs. 12-16 show that the proposed
DWT-based analysis of startup transient can detect rotor faults
independent of magnetic asymmetry caused by axial ducts. APPENDIX
This is because flux cannot penetrate deep into the rotor yoke Table I. Rotor axial air duct design and ratings for field and lab test motors
at high slip due to eddy current rejection, as shown in Fig. 4(b).
This verifies that startup transient analysis can provide reliable
assessment of rotor condition for Nd=Np motors, and help avoid
unnecessary maintenance costs due to false indications.

V. CONCLUSION
False positive rotor fault indications with steady state
spectrum analysis (e.g. MCSA) are a common problem in the
field for motors with magnetic asymmetry introduced by the
rotor axial ducts. However, there currently is no practical
solution for diagnosing rotor faults on-line for motors with
such magnetic asymmetry. In this paper, analysis of the stator REFERENCES
current under the startup transient is proposed as a solution for
[1] H.A. Toliyat, G.B. Kliman, Handbook of electric motors, 2nd edition,
diagnosing rotor faults independent of the axial duct influence. Marcel Dekker, 2004.
Startup transient analysis is considered since there is no [2] S. Williamson, and D. Gersh, “Representation of rotor spiders and axial
magnetic asymmetry due to limited flux penetration in the rotor ventilation ducts in reduced finite-element models for cage rotors,” IEE
yoke at high slip. An experimental study was performed on Proc. Elec. Power Appl., vol. 143, no. 6, pp. 423-428, Nov. 1996.
custom built rotors and on 6.6kV motors in the field that were [3] A.H. Bonnett, and T. Albers, “Squirrel–cage options for AC induction
motors,” IEEE Trans. on Ind. Appl., pp. 1197-1209, vol. 37, no. 4,
misdiagnosed with broken rotor bars (MCSA) due to axial July/Aug. 2001.
ducts. The experimental results show that broken bars can be [4] A. Bellini, et al., “On-field experience with on-line diagnosis of large
detected reliably independent of the axial duct influence under induction motors cage failures using MCSA,” IEEE Trans. on Ind. Appl.,
the startup transient with the proposed wavelet-based algorithm pp. 1045-1053, vol. 38, no. 4, July/Aug. 2002.
and energy level-based fault indicator. [5] W.T. Thomson, “On-line current monitoring – the influence of
mechanical loads or a unique rotor design on the diagnosis of broken
Startup transient analysis, which has been applied to this rotor bars in induction motors,” Proc. of ICEM, pp. 1236-1240, 1992.
problem for the first time in this work, is expected to help [6] S. Lee, J. Hong, S.B. Lee, E. Wiedenbrug, M. Teska, and H. Kim,
“Evaluation of the influence of rotor axial air duct design on condition
prevent unnecessary inspection and/or loss of production due to monitoring of induction motors,” IEEE Trans. on Ind. Appl., vol. 49, no.
false broken bar indications that frequently occur in the field. 5, pp. 2024-2033, Sept./Oct. 2013.
It also allows reliable diagnosis of motors with axial duct [7] I.M. Culbert, and W. Rhodes, "Using current signature analysis
induced magnetic asymmetry, which was only possible with technology to reliably detect cage winding defects in squirrel-cage
off-line test methods. The proposed algorithm is currently induction motors," IEEE Trans. on Ind. Appl., vol.43, no.2, pp.422-428,
being applied in the field for screening out false positive Mar./Apr. 2007.
indications when the broken bar frequency component of on- [8] W. Thomson, “Recent case histories on the application of motor current
signature analysis to detect broken rotor bars,” Proc. of IRMC, 2006.
line MCSA exceeds the alarm level. A limitation of startup
[9] B.D. Evans, “Induction motor case histories: a focus on electrically
transient analysis is the difficulty and cost involved with related phenomena,” Proc. of Vibration Institute Annual Meeting, 2009.
obtaining and analyzing the startup data; however, this is [10] Testing of squirrel cage rotors, Electrical Apparatus Service Association
usually not an issue in the field considering the high Inc., EASA Tech. Note 23, 2003.
maintenance cost associated with false positive indications. [11] D. Hyun, S. Lee, J. Hong, S.B. Lee, S. Nandi, "Detection of Airgap
Eccentricity for Induction Motors using the Single-Phase Rotation Test,"
IEEE Trans. on Ener. Conv., vol. 27, no. 3, pp. 689-696, Sept. 2012.
ACKNOWLEDGMENT [12] H. Douglas, P. Pillay, A.K. Ziarani, "Broken rotor bar detection in
The authors gratefully acknowledge Chaewoong Lim of induction machines with transient operating speeds," IEEE Trans. on
Ener. Conv., vol.20, no.1, pp.135-141, Mar. 2005.
Hansung Electrical Industrial Co., Dongwon Lee of GS EPS
Co., Ed Johnson of Progress Energy, Yoondal Park and [13] M. Riera-Guasp, J. Antonino-Daviu, M. Pineda-Sanchez, J. Perez-Cruz,
and R. Puche-Panadero. “A general approach for the transient detection
Joonghun (Charlie) Nam of GS Caltex, Sungbong Park of of slip-dependant fault components based on the Discrete Wavelet
MND Technology, for providing the photographs, MCSA field Transform” IEEE Trans. on Ind. Electr., vol. 55, no. 12, pp.4167-4180,
data, support with startup transient testing of high voltage Dec. 2008.
motors, and for sharing their experience with on-line MCSA [14] S. H. Kia, H. Henao, and G. A. Capolino, “Diagnosis of broken bar fault
testing of induction motors. in induction machines using discrete wavelet transform without slip

0093-9994 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TIA.2013.2297448, IEEE Transactions on Industry Applications

estimation,” IEEE Trans. on Ind. Appl., vol. 45, no. 4, pp. 1405-1415,
July/Aug. 2009.
[15] F. Briz, M.W. Degner, P. Garcia, and D. Bragado, “Broken rotor bar
detection in line-fed induction machines using complex wavelet analysis
of startup transients,” IEEE Trans. on Ind. Appl., vol. 44, no. 3, pp. 760-
768, May/June 2008.
[16] Y. Gritli, C. Rossi, L. Zarri, F. Filippetti, A. Chatti, D. Casadei, and A.
Stefani, "Advanced diagnosis of broken bar fault in induction machines
by using Discrete Wavelet Transform under time-varying condition,"
Proc. of IEMDC, pp. 424-429, May 2011.
[17] J. Antonino-Daviu, M. Riera-Guasp, J. Pons-Llinares, J. Park, S.B. Lee,
J. Yoo, and C. Kral, Detection of Broken Outer-Cage Bars for Double-
Cage Induction Motors under the Startup Transient,” IEEE Trans. on Ind.
Appl., vol. 48, no. 5, pp. 1539-1548, Sept./Oct. 2012.
[18] C.S. Burrus, R.A. Gopinath and H. Guo, Introduction to Wavelets and
Wavelet Transforms - A primer, Prentice Hall, 1998.
[19] Z. Zhang, Z. Ren, and W. Huang, “A novel detection method of motor
broken rotor bars based on wavelet ridge,” IEEE Trans. Ener. Conv., vol.
18, no. 3, pp. 417–423, Sept. 2003.
[20] J. Cusido, L. Romeral, J. A. Ortega, J. A. Rosero, and A. Garcia
Espinosa, “Fault detection in induction machines using power spectral
density in wavelet decomposition,” IEEE Trans. Ind. Elec., vol. 55, no. 2,
pp. 633–643, Feb. 2008.
[21] I.P. Tsoumas, G. Georgoulas, E.D. Mitronikas, and A.N. Safacas,
“Asynchronous machine rotor fault diagnosis technique using complex
wavelets,” IEEE Trans. on Ener. Conv., vol.23, no.2, pp. 444-459, June
2008.
[22] M. Blodt, D. Bonacci, J. Regnier, M. Chabert, and J. Faucher, “On-line
monitoring of mechanical faults in variable-speed induction motor drives
using the Wigner distribution,” IEEE Trans. Ind. Elec., vol. 55, pp. 522-
533, 2008.
[23] M. Pineda-Sanchez, M. Riera-Guasp, J.A. Antonino-Daviu, J. Roger-
Folch, J. Perez-Cruz, and R. Puche-Panadero, “Instantaneous frequency
of the left sideband harmonic during the start-up transient: a new method
for diagnosis of broken bars,” IEEE Trans. Ind. Elec., vol. 56, no. 11, pp.
4557–4570, Nov. 2009.
[24] Z.K. Peng, P.W. Tsey, and F.L. Chu, “A comparison study of improved
Hilbert-Huang transform and wavelet transform: application to fault
diagnosis for rolling bearing,” Mech. Sys. and Signal Proc., vol. 19, pp.
974-988, 2005.
[25] J. Antonino-Daviu, M. Riera-Guasp, J. Roger-Folch, F. Martínez-
Giménez, A. Peris, “Application and optimization of the discrete wavelet
transform for the detection of broken rotor bars in induction machines,”
Appl. and Comp. Harmonic Anal., vol. 21, no. 2, pp. 268-279, Sept.
2006.

0093-9994 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.

Potrebbero piacerti anche