DETAILS FOR 33 KV SUBSTATIONS

GROUND
HEIGHT OF EQUIP HEIGHT OF
SR NO. DESCRIPTION CLEARANCE (MM)
(MM).LIVE POINT STRUCTURE (MM)
FROM CL
1 Lightning Arrester 3700 620 3080
2 Current Transformer 3700 1100 2600
3 Potential Transformer 3700 1100 2600
4 Capacitive Voltage Transformer NA NA NA
5 Circuit Breaker (Higher Point) 4244 1372 2872
6 Wave Trap NA NA NA
7 Isolator 3700 636 3064
8 Pentograph Isolator NA NA NA
9 Bus Post Insulator 3700 508 3192
10 33/6.9kV Transformer, 6 MVA L= 4500, W = 3900 & H = 3800, OIL 4985L, Total Weight = 14570 kg.
11 33/6.9kV Transformer, 12.5 MVA L= 5700, W = 4450 & H = 4250, OIL 6980L, Total Weight = 25690 kg.
12 33/6.9kV Transformer, 20 MVA L= 5700, W = 4800 & H = 4450, OIL 9010L, Total Weight = 34820 kg.
13 33 kV Panels L= 800, W = 600 & H = 2200
14 11 kV VCB Panels L= 800, W = 1600 & H = 2330
15 11/0.415 kV Station Transformer, 500 KVA L= 2300, W =2550 & H = 2200, OIL 470L, Total Weight =2230 kg.
16 11/0.415 kV Station Transformer, 250 KVA L= 2000, W =2150 & H = 1900, OIL 380L, Total Weight =1610 kg.
17 11/0.433 kV Station Transformer, 2500 KVA L= 3500, W =2850 & H = 2900, OIL 2022L, Total Weight =6450 kg.
18 11/0.433 kV Station Transformer, 3000 KVA L= 2870, W =2985 & H = 2850, OIL 1600L, Total Weight =8000 kg.
SYSTEM PARAMETERS-STANDARD CONSIDERATION FOR 33 KV SUBSTATION

SR NO. DESCRIPTION 33 KV SS

1 Line conductor Single Panther/Dog


2 Line conductor height 7 Mtr
3 Bus Conductor -Main Bus Single Panther
4 Bus Conductor -Transfer Bus NA
5 Bus Conductor Flyover Single Panther
6 Bus height (Lower bus) 5.5 Mtr
7 Bus height (Upper bus Flyover) 9 Mtr/NA
8 Sub-Conductor spacing NA
9 Tension Insulator String Single 70 KN AF 4 nos.
10 Suspension Insulator String Single 70 KN AF 3 nos.
11 Earth wire 7 / 3.15 GI
12 Earth wire height 7 Mtr
13 Max. Span for Earth wire NA
14 Max. Span for Bus
15 Bus bar Scheme Single/ Two Main
16 Bay Width 4.7 Mtr.
17 Equipment Ground Clearance (considered from foundation plinth) 3.7 Mtr
18 DSLP LM / Shield Wire
19 Earth Mat IEEE-80
SYSTEM PARAMETERS-DESIGN PARAMETERS FOR 33 KV SYSTEM

SR NO. DESCRIPTION OF PARAMETERS 33 KV SYSTEMS

1 System Operating Voltage 33 kV


2 Max. Operating Voltage 36 kV
3 Rated Frequency 50 Hz
4 No. of Phase 3
5 Rated Insulation Levels
i) Full wave Impulse withstand voltage (1.2 / 50 micro sec.) 170 Kvp
ii) Switching Impulse withstand Voltage (250/2500 micro sec.) NA
iii) One Minute Power Ferequency Dry & Wet Wistand Voltage (rms) 70 Kvp
6 Corona Extinction Voltage NA
Max. Radio interference Voltaage for frequency between 0.5MHz & 2MHz at 320kV rms for 400kV system &
7 NA
156 Kv rms for 220kV & 92kV rms for 132kV system
8 Min. Creepage Distance 25mm/kV, 900mm
9 Min. Clearance
i) Phase to Phase 320mm
ii) Phase to Earth 320mm
iii) Safety Clearance 3000mm
iv) Ground Clearance 3700mm
10 Rated Short Circuit Current for 3 Sec. Duration 25kA/3 Sec
11 System Neutral Earthing Effectively Earthed
SYSTEM PARAMETERS-DESIGN PARAMETERS FOR 33 KV SYSTEM

SR NO. EQUIPMENT INTERCONNECTION DISTANCE IN METER

1 FENCE TO LA 5M
2 LA TO METERING CT 2M
3 METERING CT TO METERING PT 2M
4 METERING PT TO ISOLATOR WITH E/S 2.5 M
5 ISOLATOR WITH E/S TO PROTECTION CT 3M
6 PROTECTION CT TO CIRCUIT BREAKER 3M
7 CIRCUIT BREAKER TO ISOLATOR 3M
8 ISOLATOR TO COLUMN (AT STARTING OF BUS ) 1.5 M
9 ISOLATOR TO BPI (AT BUS LEVEL ) 1.5 M
10 LA TO POWER TRANSFORMER 5M
DETAILS FOR 66 KV SUBSTATIONS
GROUND
HEIGHT OF EQUIP HEIGHT OF
SR NO. DESCRIPTION CLEARANCE (MM)
(MM).LIVE POINT STRUCTURE (MM)
FROM CL
1 Lightning Arrester 4000 930 3070
2 Current Transformer 4000 1470 2530
3 Potential Transformer 4000 1455 2545
4 Capacitive Voltage Transformer 4000 2106 1894
5 Circuit Breaker (Higher Point) 4920 1615 3305
6 Wave Trap NA NA NA
7 Isolator 4000 1140 2860
8 Pentograph Isolator NA NA NA
9 Bus Post Insulator 4000 770 3230
10 66/11 kV Transformer, 5 MVA L= 4000, W = 2450 & H = 4300, OIL 5600L, Total Weight = 19060 kg.
11 66/11 kVTransformer, 7.5 MVA L= 4700, W = 4200 & H = 4400, OIL 6800L, Total Weight = 23900 kg.
11 66/11kV Transformer, 10MVA
12 66/11kV Transformer, 12.5MVA L= 5700, W = 4450 & H = 4250, OIL 6980L, Total Weight = 25690 kg.
13 66/11kV Transformer, 16/20MVA L= 6000, W = 5100 & H = 4900, OIL 10040L, Total Weight =38735 kg.
14 66 kV Panels L= 800, W = 600 & H = 2200
15 11 kV VCB Panels L= 800, W = 1600 & H = 2330
16 11/0.415 kV Station Transformer, 500 KVA L= 2300, W =2550 & H = 2200, OIL 470L, Total Weight =2230 kg.
17 11/0.415 kV Station Transformer, 250 KVA L= 2000, W =2150 & H = 1900, OIL 380L, Total Weight =1610 kg.
18 11/0.433 kV Station Transformer, 2500 KVA L= 3500, W =2850 & H = 2900, OIL 2022L, Total Weight =6450 kg.
19 11/0.433 kV Station Transformer, 3000 KVA L= 2870, W =2985 & H = 2850, OIL 1600L, Total Weight =8000 kg.
SYSTEM PARAMETERS-STANDARD CONSIDERATION FOR 66 KV SUBSTATION

SR NO. DESCRIPTION 66 KV (220/66 KV SS) 66/11 KV SS

1 Line conductor Single Panther/Dog Single Panther/Dog


2 Line conductor height 10 Mtr 7 Mtr
3 Bus Conductor -Main Bus Twin Moose ASCR Single Zebra
4 Bus Conductor -Transfer Bus NA NA
5 Bus Conductor Flyover Twin Zebra ASCR NA
6 Bus height (Lower bus) 7 Mtr 7 Mtr
7 Bus height (Upper bus Flyover) 10 Mtr NA
8 Sub-Conductor spacing 350 mm NA
9 Tension Insulator String Twin 90 KN AF 6 nos. Single 90 KN AF 6 nos.
10 Suspension Insulator String Single 90 KN AF 5 nos. Single 90 KN AF 5 nos.
11 Earth wire 7 / 3.15 GI 7 / 3.15 GI
12 Earth wire height 13 Mtr NA
13 Max. Span for Earth wire 23.8 Mtr NA
14 Max. Span for Bus 35 Mtr 50 Mtr
15 Bus bar Scheme 2 Main Bus 1 Main Bus
16 Bay Width 7.6 Mtr 7.6 Mtr
17 Equipment Ground Clearance (considered from foundation plinth) 4 Mtr 4 Mtr
18 DSLP Shield Wire LM
19 Earth Mat IEEE-80 IEEE-80
SYSTEM PARAMETERS-DESIGN PARAMETERS FOR 66 KV SYSTEM

SR NO. DESCRIPTION OF PARAMETERS 66 KV SYSTEMS

1 System Operating Voltage 66kV


2 Max. Operating Voltage 72.5kV
3 Rated Frequency 50 Hz
4 No. of Phase 3
5 Rated Insulation Levels
i) Full wave Impulse withstand voltage (1.2 / 50 micro sec.) 350kVP
ii) Switching Impulse withstand Voltage (250/2500 micro sec.) NA
iii) One Minute Power Ferequency Dry & Wet Wistand Voltage (rms) 160kV
6 Corona Extinction Voltage NA
Max. Radio interference Voltaage for frequency between 0.5MHz & 2MHz at 320kV rms for 400kV system &
7 NA
156 Kv rms for 220kV & 92kV rms for 132kV system
8 Min. Creepage Distance 25MM/kV (1810MM)
9 Min. Clearance
i) Phase to Phase 2000MM
ii) Phase to Earth 1800MM
iii) Safety Clearance 3100MM
iv) Ground Clearance 4000MM
10 Rated Short Circuit Current for 3 Sec. Duration 25KA
11 System Neutral Earthing Effectively Earthed
SYSTEM PARAMETERS-DESIGN PARAMETERS FOR 66KV SYSTEM

SR NO. EQUIPMENT INTERCONNECTION DISTANCE IN METER

1 FENCE TO LA 5M
2 LA TO METERING CT 2M
3 METERING CT TO METERING PT 2 M OR 2.5 M
4 METERING PT TO ISOLATOR WITH E/S 2.5 M
5 ISOLATOR WITH E/S TO PROTECTION CT 3M
6 PROTECTION CT TO CIRCUIT BREAKER 3M
7 CIRCUIT BREAKER TO ISOLATOR 3M
8 ISOLATOR TO COLUMN (AT STARTING OF BUS ) 1.5 M
9 ISOLATOR TO BPI (AT BUS LEVEL ) 2M
10 LA TO POWER TRANSFORMER 5M
DETAILS FOR 132 KV SUBSTATIONS
GROUND HEIGHT OF EQUIP HEIGHT OF
SR NO. DESCRIPTION
CLEARANCE (MM) (MM) STRUCTURE (MM)
1 Lightning Arrester 4600 1660 2940
2 Current Transformer 4600 2250 2350
3 Potential Transformer 4600 2400 2200
4 Capacitive Voltage Transformer 4600 2118 2482
5 Circuit Breaker (Higher Point) 6074 2689 3385
6 Wave Trap 9098 5098 4000
7 Isolator 4600 2033 2567
8 Pentograph Isolator NA NA NA
9 Bus Post Insulator 4600 1500 3100
10 132/11 kV Transformer, 10-12.5 MVA L= 5400, W = 5200 & H = 5900, OIL 12600L, Total Weight = 31500 kg.
11 132/33 kVTransformer, 31.5 MVA L= 7700, W = 5650 & H = 5700, OIL 12400L, Total Weight = 91600 kg.
12 132/33 kVTransformer, 60 MVA L= 8000, W = 5120 & H = 7440, OIL 20600L, Total Weight = 71500 kg.
13 132 kV Panels L= 800, W = 800 & H = 2000
14 11 kV VCB Panels L= 800, W = 1600 & H = 2330
15 11/0.415 kV Station Transformer, 500 KVA L= 2300, W =2550 & H = 2200, OIL 470L, Total Weight =2230 kg.
16 11/0.415 kV Station Transformer, 250 KVA L= 2000, W =2150 & H = 1900, OIL 380L, Total Weight =1610 kg.
17 11/0.433 kV Station Transformer, 2500 KVA L= 3500, W =2850 & H = 2900, OIL 2022L, Total Weight =6450 kg.
18 11/0.433 kV Station Transformer, 3000 KVA L= 2870, W =2985 & H = 2850, OIL 1600L, Total Weight =8000 kg.
SYSTEM PARAMETERS-STANDARD CONSIDERATION FOR 132 KV SUBSTATION

SR NO. DESCRIPTION 132 KV SS

Single Moose/Zebra/
1 Line conductor
Panther ACSR
2 Line conductor height 10 Mtr
3 Bus Conductor -Main Bus Twin Zebra ASCR
4 Bus Conductor -Transfer Bus NA
5 Bus Conductor Flyover Twin Zebra ASCR
6 Bus height (Lower bus) 7.25 Mtr
7 Bus height (Upper bus Flyover) 10 Mtr
8 Sub-Conductor spacing 350 mm

9 Tension Insulator String Twin 120 KN AF 10 nos.

10 Suspension Insulator String Single 120 KN AF 9 nos.

11 Earth wire 7 / 3.15 GI


12 Earth wire height 13 Mtr
13 Max. Span for Earth wire 50 Mtr
14 Max. Span for Bus 36 Mtr
15 Bus bar Scheme 1 Main Bus
16 Bay Width 12 Mtr
17 Equipment Ground Clearance (considered from foundation plinth) 4.6 Mtr
18 DSLP Shield Wire
19 Earth Mat IEEE-80
SYSTEM PARAMETERS-DESIGN PARAMETERS FOR 132 KV SYSTEM

SR NO. DESCRIPTION OF PARAMETERS 132 KV SYSTEMS

1 System Operating Voltage 132kV


2 Max. Operating Voltage 145kV
3 Rated Frequency 50 Hz
4 No. of Phase 3
5 Rated Insulation Levels
i) Full wave Impulse withstand voltage (1.2 / 50 micro sec.) 650kVP
ii) Switching Impulse withstand Voltage (250/2500 micro sec.) NA
iii) One Minute Power Ferequency Dry & Wet Wistand Voltage (rms) 275kV
6 Corona Extinction Voltage NA
Max. Radio interference Voltaage for frequency between 0.5MHz & 2MHz at 320kV rms for 400kV system &
7 NA
156 Kv rms for 220kV & 92kV rms for 132kV system
8 Min. Creepage Distance 25MM/Kv (3625MM)
9 Min. Clearance
i) Phase to Phase 3000MM
ii) Phase to Earth 3000MM
iii) Safety Clearance 3800MM
iv) Ground Clearance 4600MM
10 Rated Short Circuit Current for 3 Sec. Duration 31.5KA
11 System Neutral Earthing Effectively Earthed
SYSTEM PARAMETERS-DESIGN PARAMETERS FOR 132KV SYSTEM

SR NO. EQUIPMENT INTERCONNECTION DISTANCE IN METER

1 FENCE TO LA 5M
2 LA TO CVT 3M
3 CVT TO WAVETRAP 3M
4 WAVETRAP TO CT 3M
5 CT TO ISOLATOR WITH E/S 3.5 M
6 ISOLATOR WITH E/S TO PROTECTION CT 3.5 M
7 PROTECTION CT TO CIRCUIT BREAKER 3.5 M
8 CIRCUIT BREAKER TO ISOLATOR 3.5 M
9 ISOLATOR TO COLUMN (AT STARTING OF BUS ) 1.5 M
10 ISOLATOR TO BPI (AT BUS LEVEL ) 3M
11 LA TO POWER TRANSFORMER 6M
DETAILS FOR 220 KV SUBSTATIONS
GROUND HEIGHT OF EQUIP HEIGHT OF
SR NO. DESCRIPTION
CLEARANCE (MM) (MM) STRUCTURE (MM)
1 Lightning Arrester 5500 2790 2710
2 Current Transformer 5500 3300 2200
3 Potential Transformer 5500 2900 2600
4 Capacitive Voltage Transformer 5500 3520 1980
5 Circuit Breaker (Higher Point) 7482 4182 3300
6 Wave Trap NA NA NA
7 Isolator 5500 2725 2775
8 Pentograph Isolator NA NA NA
9 Bus Post Insulator 5500 2300 3200
10 220/33 kV Transformer, 50 MVA L= 9900, W = 7400 & H = 6800, OIL 25300L, Total Weight = 81500 kg.
11 220/90/33 kV Transformer, 75 MVA L= 9750, W = 8000 & H = 9000, OIL 47160L, Total Weight = 144500 kg.
12 220/33 KV,Transformer, 20 MVA L= 9500, W = 7180 & H = 8750, OIL 25568L, Total Weight = 65000 kg.
13 220 kV Panels L= 800, W = 800 & H = 2200
14 11 kV VCB Panels L= 800, W = 1600 & H = 2330
15 11/0.433 kV Station Transformer, 500 KVA L= 2300, W =2550 & H = 2200, OIL 470L, Total Weight =2230 kg.
16 11/0.433 kV Station Transformer, 250 KVA L= 2000, W =2150 & H = 1900, OIL 380L, Total Weight =1610 kg.
17 11/0.433 kV Station Transformer, 2500 KVA L= 3500, W =2850 & H = 2900, OIL 2022L, Total Weight =6450 kg.
18 11/0.433 kV Station Transformer, 3000 KVA L= 2870, W =2985 & H = 2850, OIL 1600L, Total Weight =8000 kg.
SYSTEM PARAMETERS-STANDARD CONSIDERATION FOR 220 KV SUBSTATION

SR NO. DESCRIPTION 220 KV SS

Single Moose ACSR /


1 Line conductor
AL-59
2 Line conductor height 18.5 Mtr

3 Bus Conductor -Main Bus Quad/Twin Moose ASCR

4 Bus Conductor -Transfer Bus Twin Moose ASCR


Twin Moose
5 Bus Conductor Flyover
ASCR/AL59
6 Bus height (Lower bus) 12.5 Mtr
7 Bus height (Upper bus Flyover) 18.5 Mtr
8 Sub-Conductor spacing 350 mm

9 Tension Insulator String Twin 120 KN AF 16 nos.


Single 120 KN AF 15
10 Suspension Insulator String
nos.
11 Earth wire 7 / 3.15 GI
12 Earth wire height 24 Mtr
13 Max. Span for Earth wire 76 Mtr
14 Max. Span for Bus 36 Mtr

Main & Main Cum


15 Bus bar Scheme Transfer / 2 Main &
Transfer

16 Bay Width 18 Mtr


17 Equipment Ground Clearance (considered from foundation plinth) 5.5 Mtr
18 DSLP Shield Wire
19 Earth Mat IEEE-80
SYSTEM PARAMETERS-DESIGN PARAMETERS FOR 220 KV SYSTEM

SR NO. DESCRIPTION OF PARAMETERS 220 KV SYSTEMS

1 System Operating Voltage 220kV


2 Max. Operating Voltage 245kV
3 Rated Frequency 50 Hz
4 No. of Phase 3
5 Rated Insulation Levels
i) Full wave Impulse withstand voltage (1.2 / 50 micro sec.) 1050kVP
ii) Switching Impulse withstand Voltage (250/2500 micro sec.) NA
iii) One Minute Power Ferequency Dry & Wet Wistand Voltage (rms) 460kV
6 Corona Extinction Voltage 208kV
Max. Radio interference Voltaage for frequency between 0.5MHz & 2MHz at 320kV rms for 400kV system &
7 1000 microV
156 Kv rms for 220kV & 92kV rms for 132kV system
8 Min. Creepage Distance 25MM/kV (6125MM)
9 Min. Clearance
i) Phase to Phase (Max.for Layout & Plan) 4500MM
ii) Phase to Earth (Max.for Layout & Plan) 4500MM
iii) Safety Clearance / Sectional Clearance 5000MM
iv) Ground Clearance 5500MM
10 Rated Short Circuit Current for 3 Sec. Duration 40kA
11 System Neutral Earthing Effectively Earthed
SYSTEM PARAMETERS-DESIGN PARAMETERS FOR 220 KV SYSTEM

SR NO. EQUIPMENT INTERCONNECTION DISTANCE IN METER

1 FENCE TO LA 5M
2 LA TO CVT 4M
3 CVT TO WAVETRAP 4.5 M
4 WAVETRAP TO PT 4.5 M
5 PT TO CT (IF APPLICABLE FOR METERING) 4.5 M
6 CT TO ISOLATOR WITH E/S 4.5 M
7 ISOLATOR WITH E/S TO PROTECTION CT 4.5 M
8 PROTECTION CT TO CIRCUIT BREAKER 4.5 M
9 CIRCUIT BREAKER TO ISOLATOR 5.5 M (Min.)
10 ISOLATOR TO COLUMN (AT STARTING OF BUS ) 2.5 M
11 ISOLATOR TO BPI (AT BUS LEVEL ) 4.5 M
12 LA TO POWER TRANSFORMER 6M
DETAILS FOR 400 KV SUBSTATIONS
GROUND HEIGHT OF EQUIP HEIGHT OF
SR NO. DESCRIPTION
CLEARANCE (MM) (MM) STRUCTURE (MM)
1 Lightning Arrester 8000 3990 4010
2 Current Transformer 8000 4375 3625
3 Potential Transformer 8000 4375 3625
4 Capacitive Voltage Transformer 8000 4632 3368
5 Circuit Breaker (Higher Point) 8488 4388 4100
6 Wave Trap 8300 3430 4870
7 Isolator 8300 4574 3726
8 Pentograph Isolator (Total Height) 13203 9285 NA
9 Bus Post Insulator 8000 3650 4350

10 400/132 kV,200 MVA ICT L= 16000, W = 7350 & H = 10000, OIL L=82000, Total Weight = 227900 kg.

11 400 kV Panels L= 800, W = 800 & H = 2200


12 11 kV VCB Panels L= 800, W = 1600 & H = 2330
13 11/0.433 kV Station Transformer, 500 KVA L= 2300, W =2550 & H = 2200, OIL 470L, Total Weight =2230 kg.
14 11/0.433 kV Station Transformer, 250 KVA L= 2000, W =2150 & H = 1900, OIL 380L, Total Weight =1610 kg.
15 11/0.433 kV Station Transformer, 2500 KVA L= 3500, W =2850 & H = 2900, OIL 2022L, Total Weight =6450 kg.
16 11/0.433 kV Station Transformer, 3000 KVA L= 2870, W =2985 & H = 2850, OIL 1600L, Total Weight =8000 kg.
SYSTEM PARAMETERS-STANDARD CONSIDERATION FOR 400 KV SUBSTATION

SR NO. DESCRIPTION 400 KV SS

Quad/Twin
1 Line conductor
Moose ACSR
2 Line conductor height 22 Mtr
3 Bus Conductor -Main Bus Quad Moose ASCR
Twin Moose ASCR /AL
4 Bus Conductor -Transfer Bus
59
Twin Moose ASCR /AL
5 Bus Conductor Flyover
59
6 Bus height (Lower bus) 15.6 Mtr
7 Bus height (Upper bus Flyover) 22 Mtr
8 Sub-Conductor spacing 450 mm

9 Tension Insulator String Twin 120 KN AF 25 nos.

Single 120 KN AF 24
10 Suspension Insulator String
nos.
11 Earth wire 7 / 3.66 GI
12 Earth wire height 29.5 Mtr
13 Max. Span for Earth wire 117 Mtr
14 Max. Span for Bus 56 Mtr
15 Bus bar Scheme 2 Main & Transfer
16 Bay Width 28 Mtr
17 Equipment Ground Clearance (considered from foundation plinth) 8 Mtr
18 DSLP Shield Wire
19 Earth Mat IEEE-80
SYSTEM PARAMETERS-DESIGN PARAMETERS FOR 400 KV SYSTEM

SR NO. DESCRIPTION OF PARAMETERS 400 KV SYSTEMS

1 System Operating Voltage 400kV


2 Max. Operating Voltage 420kV
3 Rated Frequency 50 Hz
4 No. of Phase 3
5 Rated Insulation Levels
i) Full wave Impulse withstand voltage (1.2 / 50 micro sec.) 1550kVP
ii) Switching Impulse withstand Voltage (250/2500 micro sec.) 1050kVp
iii) One Minute Power Ferequency Dry & Wet Wistand Voltage (rms) 630kV
6 Corona Extinction Voltage 320kV
Max. Radio interference Voltaage for frequency between 0.5MHz & 2MHz at 320kV rms for 400kV system &
7 1000 µV
156 Kv rms for 220kV & 92kV rms for 132kV system
8 Min. Creepage Distance 25MM/kV (10500MM)
9 Min. Clearance
i) Phase to Phase (Max.for Layout & Plan) 7000MM
ii) Phase to Earth (Max.for Layout & Plan) 7000MM
iii) Safety Clearance / Sectional Clearance 6500 mm
iv) Ground Clearance 8000MM
10 Rated Short Circuit Current for 3 Sec. Duration 40kA
11 System Neutral Earthing Effectively Earthed
SYSTEM PARAMETERS-DESIGN PARAMETERS FOR 400 KV SYSTEM

SR NO. EQUIPMENT INTERCONNECTION DISTANCE IN METER

1 FENCE TO LA 10 OR 15 M
2 LA TO CVT 4M
3 CVT TO WAVETRAP 5M
4 WAVETRAP TO PT 5M
5 PT TO CT (IF APPLICABLE FOR METERING) 5M
6 CT TO ISOLATOR WITH E/S 6M
7 ISOLATOR WITH E/S TO PROTECTION CT 6M
8 PROTECTION CT TO CIRCUIT BREAKER 8 OR 8.5 M
10 M (Min.) 14M
9 CIRCUIT BREAKER TO ISOLATOR
INCLUDING ROAD
10 ISOLATOR TO COLUMN (AT STARTING OF BUS ) 7M
11 ISOLATOR TO BPI (AT BUS LEVEL ) 7M
12 LA TO POWER TRANSFORMER 7 OR 8 M